Visual Inspection - Interactive Guide

download Visual Inspection - Interactive Guide

of 26

Transcript of Visual Inspection - Interactive Guide

  • 8/3/2019 Visual Inspection - Interactive Guide

    1/26

    CLICK SELV

    CLICK PELV

    CLICK Double or Reinforced Insulation

    CLICK Insulation of live parts

    CLICK Barriers or enclosures

    CLICK Obstacles **

    CLICK Placing out of reach **

    CLICK Presence of Earthing conductor

    CLICK Presence of circuit protective conductors

    CLICK Presence of main protective bonding conductors

    CLICK

    CLICK

    CLICK FELV

    CLICK

    Basic Protection

    Fault protection

    Choice and setting of protective and monitoring devices (for

    fault and/or over-current protection)

    Protective measure(s) against electric shock. Basic fault

    protection

    Presence of adequate arrangements for alternative sources,

    where applicable

    Presence of earthing arrangement for combined protective

    and functional purpose

    Visual inspection - learning aid. To discover more about an it

    taken to a note file or read the comme

  • 8/3/2019 Visual Inspection - Interactive Guide

    2/26

    CLICK Absence of protective conductors

    CLICK Presence of Earth free equipotential bonding

    CLICK For one item of current using equipment

    CLICK For more than one item of current using equipment

    CLICK Presence of Residual Current device(s)

    CLICK Presence of supplementary bonding conductors

    For further reading please refer to: Ins

    periodic reporting) NICEI

    Additional protection

    CLICK TO GO TO

    Electrical separation

    Non conducting location **

    Earth free equipotential bonding **

  • 8/3/2019 Visual Inspection - Interactive Guide

    3/26

    CLICK Proximity of non-electrical services & other influences

    CLICK

    CLICK Segregation of safety circuits

    CLICK

    CLICK Presence of danger notices and other warning notices

    CLICK Labelling of protective devices, switches and terminals

    CLICK Identification of conductors

    CLICK

    CLICK Erection methods

    CLICK Routing of cables in prescribed zones

    CLICK

    CLICK

    CLICK Connection of conductors

    CLICK

    Cables incorporating earthed armour or sheath, or run in an

    earthed wiring system, or otherwise protected against nails,

    screws and the like

    Additional protection provided by 30mA RCD for cables

    concealed in walls (where required in premises not underthe supervision of skilled or instructed person)

    Presence of fire barriers, suitable seals and protection

    Identification

    Cables & conductors

    Selection of conductors for current carrying capacity and

    voltage drop

    Prevention of mutual detrimental influence

    Presence of diagrams, instructions, circuit charts and similar

    information

    Segregation of Band I & Band II circuits or Band II Insulation

    used

  • 8/3/2019 Visual Inspection - Interactive Guide

    4/26

    CLICK

    CLICK Adequacy of access to switchgear and other equipment

    CLICK

    CLICK

    CLICK Correct connection of accessories and equipment

    CLICK Presence of under-voltage protective devices

    CLICK

    CLICK Selection of appropriate functional switching devices

    Selection of equipment and protective measures

    appropriate to external influences

    Particular protective measures for special installations or

    locations

    Connection of single pole devices for protection or

    switching in line conductors only

    against thermal effects

    General

    Presence and correct location of appropriate devices for

    isolation and switching

  • 8/3/2019 Visual Inspection - Interactive Guide

    5/26

    RETURN SELV

    RETURN PELV

    RETURN Double or reinforced Insulation

    RETURN Insulation of live parts

    RETURN Barriers or enclosures

    Protective measure(s) against

    Pictures!B31

    Double or rein

    Basic protectiis provided by

    fault protecti

    accessible par

    Separated ext

    recognised by

    important thi

    SELV side sho

    Pictures!D7

    Pictures!B19

    Visual inspection - Definitions table

    An understan

    for the inspec

    Barriers or en

    at least IP2X oor enclosure

    Protected ext

    side is generalwill not be sui

    special install

    Basic

    Inspection of t

    covered with i

    with the relev

    intended to p

    generally not

    normal servic

  • 8/3/2019 Visual Inspection - Interactive Guide

    6/26

    RETURN Presence of CPC

    RETURN

    RETURN

    RETURN

    RETURN FELV

    RETURN

    RETURN Absence of protective conductors

    A visual inspe

    where require

    have determi

    application of

    cables, or be f

    may also be u

    Note. Metallic enclosures used for CPC

    purposes must satisfy the requirements of

    section 543 of BS7671, in terms of continuity,

    CSA and reliability

    Main protecti

    earthing termi

    include: Steel

    1, Water insta

    installation pi

    installation piThe installatio

    conductors to

    should confir

    area and are c

    BS7671 the co

    purposes only

    Where a suppl

    inspection sh

    safety are pre

    automatic swi

    generators, in

    BS7671.

    Presence of main protective

    bonding conductors

    A functional e

    measures req

    used for both

    applied. 1) Ba

    barriers/encloprotective con

    This section c

    current monit

    current, Type,

    verify confor

    Choice and setting of protective and

    monitoring devices (for fault and/or over

    current protection)

    Presence of earthing arrangement

    for combined protective and

    functional purpose

    E.g. IT SUITES

    Presence of adequate

    arrangements for alternative

    sources, where applicable

    Non conducting location **

    None of the in

    may be marke

  • 8/3/2019 Visual Inspection - Interactive Guide

    7/26

    RETURN

    RETURN

    RETURN

    RETURN

    RETURN Segregation of safety circuits Fire alarm and

    other circuits

    importance of

    breakdown of

    caused by a fa

    Electromagne

    another circui

    resulting from

    conduit, ducts

    Iden

    P f di i i Th

    Addition

    Addition prot

    points or circu

    are intended f

    current ratinginstallations a

    Some of the l

    in section 7 of

    bonding may

    411.3.1.2 of B

    Presence of residual current

    device(s)

    RCD's should have the operating characteristics as

    given in section 415 of BS7671.i.e. operating current not exceeding 30mA and

    operating time not exceeding 40ms.

    Presence of supplementary

    bonding conductors

    It should be v

    occurred, are

    any part of th

    Segregation o

    Where every c

    separate cont

    separate com

    separation.

    The requirement for supplementary equipotential

    bonding is generally applicable only to installationsand locations where there is an increased risk of

    electric shock.

    Prevention of mutu

    Proximity of non-electrical services

    & other influences

    Segregation of Band I & Band II

    circuits or Band II Insulation usedBand I = Voltage too low to cause serious electric shocks e.g.

    ELV including telecommunications, bell wire, control and

    alarm circuits.

    Band II = All voltages used in electrical installations not

    included in Band I. So all 230/400v supplies are included.

  • 8/3/2019 Visual Inspection - Interactive Guide

    8/26

    RETURN

    RETURN Identification of conductors

    RETURN

    RETURN Erection Methods

    RETURN

    RETURN

    protective con

    supply (Regul

    Labelling of protective devices,

    switches and terminals

    The inspector

    protective de

    necessary). Lacircuit breake

    1) It is arrange

    recognised, a

    rated current i

    The correct idconductors, in

    This is in addit

    connection re

    exceptions* (

    identified by c

    must be identi

    Cables concea

    50mm or less

    appropriate st

    they are cable

    zones.

    If a cable cann

    conduit or SW

    The sizes and

    trunking syste

    information t

    the designer. I

    available to th

    Cables a

    Selection of conductors for current

    carrying capacity and voltage drop

    Note: Particular attention should be given to

    cables in contact with thermally insulating

    material.

    Adequate inspinstallation is

    Compliance w

    considered at

    all equipment

    equivalent, ar

    defective so aRouting of cables in prescribed

    zones

    Cables incorporating earthed

    armour or sheath or run in an

  • 8/3/2019 Visual Inspection - Interactive Guide

    9/26

    RETURN

    RETURN

    RETURN

    RETURN

    RETURN

    RETURN

    G

    Presence and correct location of

    appropriate devices for isolationand switching

    Correct connection of accessories

    and equipment

    The inspector

    equipment ar

    well made bot

    where possibl

    Presence of under-voltageprotective devices

    The inspectordevices which

    of a significan

    They are foun

    motors. They

    automatic con

    inspector sho

    design require

    Particular protective measures for

    special installations and locations

    The special in

    the risks assoc

    or minimal clo

    other risks, su

    and installatio

    measures ass

    shower etc.Connection of single pole devices

    for protection or switching in line

    conductors only

    This is a visual

    are connected

    breaker, fuse,

    the like shoul

    made in additi

    conducted lat

    Adequacy of access to switchgear

    and other equipment

    It must be con

    have been aff

    inspection, te

    Isolation and

    namely isolatiand functional

    purposes of in

    however, that

    provided that

    requirements

  • 8/3/2019 Visual Inspection - Interactive Guide

    10/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    11/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    12/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    13/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    14/26

    eneral

  • 8/3/2019 Visual Inspection - Interactive Guide

    15/26

    RETURN

    RETURN

    RETURN

    RETURN

    PELV

    Visual inspection - Definitions table - CLICK HE

    SELV

    Double or Reinforced Insulation

    Insulation of live parts

  • 8/3/2019 Visual Inspection - Interactive Guide

    16/26

    RETURN

    RETURN Placing out of reach **

    Obstacles **

  • 8/3/2019 Visual Inspection - Interactive Guide

    17/26

    RETURN

    RETURN

    RETURN

    For the periodic inspection of an existing installation, the inspector

    will need to make an assessment based on all the relevant

    circumstances. The electrical safety council technical manual and

    IEE Guidance note 5: Protection against electric shock and Guidance

    note 8: Earthing and bonding which give advice to help determine

    whether or not a conductive part is an extraneous-conductive-part.

    Other examples of extraneous conductive parts include:

    1, Central heating and air conditioning systems2, Exposed metallic structural parts of a buildings

    3, Connection to a lightning protection system to the protective

    equipotential bonding (made in accordance with BSEN 62305)

    Presence of main protective bonding conductors

    FELV

    Choice of setting of protective and monitoring devices (for fault

  • 8/3/2019 Visual Inspection - Interactive Guide

    18/26

    RETURN

    RETURN

    RETURN

    RETURN

    Segregation of Band I and Band II circuits or band II insulation us

    Identification of conductors

    Presence of danger notices and other warning notices - EXAMPL

    Labelling of protective devices, switches and terminals - EXAMP

  • 8/3/2019 Visual Inspection - Interactive Guide

    19/26

    RETURN

    RETURN

    RETURN

    Erection Methods

    Routing of cables in prescribed zones

  • 8/3/2019 Visual Inspection - Interactive Guide

    20/26

    RETURN Routing of cables in prescribed zones

  • 8/3/2019 Visual Inspection - Interactive Guide

    21/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    22/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    23/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    24/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    25/26

  • 8/3/2019 Visual Inspection - Interactive Guide

    26/26