VIP-9511 Line protection measurement and control device
LCD:UAB UBC UCA IA IC P Q COSΦ f io ia ib icChannel display:Ia Ic;Uab Ucb io ia ib ic
explain:UAB、UBC、UCA:Bus line voltage; IA、IC:Measured current value;
P 、Q:Active power, reactive power once value;COSΦ、f:Power factor, frequency;
io:Zero sequence current twice value; ia、ib、ic:Protection current twice value
Ia、Ic:Measuring current twice value;Uab、Ucb:Two line of the line voltage twice value.
1、major function:(a)Protection function:
01. current instantaneous trip (tripping operation)02 Time limit current instantaneous trip (tripping operation)03. Over current (tripping operation) 04. current instantaneous trip nverse time limit (General / very /
extreme; three kinds of anti time limit can choose one or not.)05. Over load (Alarm / trip)06.Zero sequence current instantaneous trip (tripping operation)07.Zero sequence current instantaneous trip I (tripping operation)08. Zero sequence current instantaneous trip II (tripping operation)09. Zero current period III (General / very / extreme; three kinds of anti
time limit can choose one or not.)10. Zero sequence over current (Alarm / trip)11.Over voltage (tripping operation)12.low voltage (tripping operation)13.Low frequency load shedding (tripping operation)14. Coincidence gate (Don't check)15. System loss of power (tripping operation)16.PT line break line (Alarm)17. PT Pressure loss (Alarm)18. Control circuit break (give an alarm)Description: in the conditions, the protection function can be
increased to meet the needs of the field.(b)Remote control function:
01. Measuring current : IA 、 IC ( Primary value ) ; Ia 、 Ic ( Two times value);
02. Protection current:ia、ib、ic(Two times value);03. Bus voltage:UAB、UBC、UCA(Primary value),Uab、Ucb(Two times
value);04. Zero sequence current:i0(Twice value);05. Frequency:f;06.Power:P、Q(Primary value);07. Power factor:cosФ;(c) control function:01. the opening, closing of Circuit breaker02.the remote opening, closing of Circuit breaker
(d)Auxiliary function:01. Operation indication : When the device is running normally, "run"
indicator light has a regular flashing;02. Power indication:When the device is operating normally, the "power"
indicator light is always on;03. Abnormal device:Self checking error, blocking relay will output;04.Device alarm:Current, the voltage reaches the set value and remains
to the set time;05. Device trip : Current, the voltage reaches the set trip value and
remains to the set time;06. The indiction of switch07. Event record : To record 32 events, 32 remote events, 8 self test
events;08. Online modification : “ Protection and retreat”and“Protection fixed
value”Modify can be directly modified by computer communications and saved;
09. Online print : Any interface in the protection menu can be printed directly after computer communication;
10. Communication function:With 485 communication mode.
2、Function menu:VIP-9511 Protection fixed value menu
Fixed
number
Code Fixed value name
Setting menu
Integer value
specification
remarks
00 Copy protection
setting
Copy protection setting
1~3 1 Usually set 1
01 Kv1 Primary PT
ratio/10
0.01~300.00 Set according to the
voltage level
If 10kV setting 10
02 Ki1 Primary CT
Ratio/10
0.01~300.00 Transformer ratio/10 If 100/5 is set to 2
03 Idz0 Current quick
set value
0.1~100A Twice rated 4-8 times Less than the total load value
04 Idz1 Limit quick
determined
value
0.1~100A Twice rated 3-4 times
05 Tzd1 Time delay 0~100s 0.20-0.40S The time delay is less
than the previous
stage
06 Idz2 Current setting
value
0.1~100A Twice rated 1.5-3 times
Usually 2 times the
setting
07 Tzd2 Over current
delay
0~100s 0.30-0.50S The time delay is less
than the previous
stage
08 Idz3 Over load value 0.1~100A Twice rated 1-1.2
times
09 Tzd3 Overload delay 0~100s Usually the delay is
not more than 10S
Can be set according
to the requirements
10 I0dz1 Zero sequence
current
instantaneous
trip value
0.1~100A 10A/The zero
sequence transformer
ratio
Protection sampling
does not exceed 7A
11 TI0zd1 Zero sequence
current
instantaneous
trip segment
delay
0~100s 0.00-0.10S Shorter time
12 I0dz2 Zero sequence
current
instantaneous
trip I value
0.1~100A 9-10A/Transformer
ratio
Protection sampling
does not exceed 7A
13 TI0zd2 Zero sequence
current
instantaneous
trip I delay
0~100s 0.10-0.30S Longer time
14 I0dz3 Zero sequence
current
instantaneous
trip II fixed
value
0.1~100A 8-9A/Transformer
ratio
Protection sampling
does not exceed7A
15 TI0zd3 Zero sequence
current
instantaneous
trip II delay
0~100s 0.30-0.50S Long time
16 I0dz4 Zero sequence
over current
fixed value
0.01~100A 6-8A/Transformer
ratio
17 TI0zd4 Zero sequence
over current
delay
0~100s greater than 0.50S Can be set according
to the requirements
18 Udz1 Over-voltage
fixed value
50~200V
19 TUzd1 Over-voltage
delay
0~100s 0.01-0.50Better Can be set according
to the requirements
20 Udz2 Low voltage
setting
30~100V 70V setting value
according to the state
21 TUzd2 Low voltage
delay
0~100s 0.50-1.00Better Can be set according
to the requirements
22 Dpjz Low frequency
load shedding
fixed value
35.00-50.00Hz 48.00-49.80 usually49.50
23 Tdp Low frequency
load shedding
0~100s 0.10-0.50Better Can be set according
to the requirements
24 Idz4 Non current
fixed value of
the coincidence
gate
0~5A 0.05-0.20 Greater than zero drift
value
25 Tzd4 Coincidence
gate delay
0~100s 0.05-1.00 0.20-0.50Better
26 Upt1 Mixed value
ofPT line break
set value
10-90V 70V Line voltage value
27 Upt2 Mixed value of
PT Loss of
pressure
1-30V 30V Line voltage value
28 TKZDX Control loop
delay
0~100s 10-20S Higher than the
closing time of the
switch contact
VIP-9511menu of Protection and retreatProtect
serial
number
Code
Protect name
Setting mode remarks
01 RLP01current instantaneous trip in/out tripping operation
02 RLP02Time limit current instantaneous trip in/out tripping operation
03 RLP03 Over current in/out tripping operation
04RLP04
current instantaneous trip
nverse time limit
General / very /
extreme / backThree ways to choose
05RLP05 Over load
Alarm / trip /
returnAlarm / trip optional
06RLP06
Zero sequence current
instantaneous trip segmentin/out tripping operation
07RLP07
Zero sequence current
instantaneous trip I segmentin/out tripping operation
08
RLP08
Zero sequence current
instantaneous trip II Zero
sequence over current
in/out tripping operation
09RLP09
Zero current period III
inverse time limit
General / very /
extreme / backThree ways to choose
10RLP10 Zero sequence over current
Alarm / trip /
returnAlarm / trip optional
11 RLP11 Over voltage in/out tripping operation
12 RLP12 low voltage in/out tripping operation
13RLP13
Low frequency load
sheddingin/out tripping operation
14 RLP14 Coincidence gate in/out Don't check
15 RLP15 System loss of power in/out tripping operation
16 RLP16 PT Break in/out give an alarm
17 RLP17 PT Pressure loss in/out give an alarm
18 RLP18 control circuit device break in/out give an alarm
Protect output:4J-B12/B13terminal; Coincidence gate:3J-B10/B11terminalAccident signal:5J-B14/B15terminal; Alarm signal:6J-B14/B16terminal
3、Protective action principleQuick break1).RLP01 Quick break-“in”;2).Protection currentia、ib、icAny one phase≧ Current quick break fixed value(Idz0);
Meet the above conditions, protect the immediate exit B12/B13 , Simultaneous drive accident signal relay B14/B15(Until the manual, before returning to the relay ), indicator of Panel accident light.
Limit speed break1).RLP02 Limit speed break-“in”;2).Protection current ia、ib、ic Any one phase≧ Limit quick break fixed value(Idz1);3).Add current time≧ delay the limit quick break Tzd1;
Meet the above conditions ,Protect immediate exitB12/B13,Simultaneous drive accident signal relayB14/B15 ( Until the manual, before returning to the relay ) , indicator of Panel accident light.
Over current1).RLP03 Over current-“in”;2).Protection current ia、ib、ic Any one phase≧Current setting value(Idz2);3).Add current time Over current delay Tzd2≧ ;
Meet the above conditions,Protect immediate exit B12/B13,Simultaneous drive accident signal relay B14/B15 ( Until the manual, before returning to the relay ) , indicator of Panel accident light.
current instantaneous trip nverse time limitThe device provides three inverse time characteristics(According to IEC225-4
standard):1)General inverse time limit:
0.02 1
0.14I Ip
t Tp
2)Inverse time limit:
1
13.5I Ipt Tp
3)Extreme inverse time limit:
2 1
80I Ip
t Tp
above, Ip represents inverse time limit Current fixed value,Tp represents Current inverse time limit Time setting.Note: over current protection and over current anti time limit protection shared values and time limits, both at the same time, the inverse time limit protection is invalid.Coincidence gate1).RLP14 Coincidence gate-“in”;2).When the switch is closed ,No blocking reclosing signal ,Coincidence gate charge,After
charging for 15 seconds, battery charging full symbol displayed on the upper right corner of the liquid crystal
3).Quick break、limit break and over current,After any of the three paragraph of the protection work, detect the value of the residual current is less than that of the non flow fixed value,After the time of the coincidence gate delay, the coincidence gate is coincident.
Description: the coincidence gate only under following situation : fast break, limit speed off, after the current action to coincide.Over load1).RLP05 Over load-“Alarm / trip”;2).Protection current ia、ib、ic Any one phase ≧ Over load fixed value(Idz3);3).Add current time Overload delay Tzd3≧ ;
Meet the above conditions , If the "trip" to protection immediate exit B12/B13,Simultaneous drive accident signal relayB14/B15(Until the manual, before returning to the relay)indicator of Panel accident light.
If the "alarm" protection drive the alarm signal relay B14/B16(Until the manual, before the relay return),indicator of Panel accident light
Zero sequence current instantaneous trip segment1).RLP06 Zero sequence current instantaneous trip segment-“in”;2) . Zero sequence current i0Sample value≧ Zero sequence current instantaneous trip
segment(I0dz1);3).Add current time Zero sequence ≧ current instantaneous trip segment delay TI0zd1;
Meet the above conditions , Protection immediate exit B12/B13 , Simultaneous drive accident signal relay B14/B15(Until the manual, before returning to the relay ), indicator of Panel accident lightZero sequence current instantaneous trip I segment1).RLP07 Zero sequence time delay current instantaneous trip segment-“in”;2).Zero sequence currenti0Sample value≧ Zero sequence time delay current instantaneous trip
segment(I0dz2);3).Add current time Zero sequence over≧ current Ⅱsegment delayed TI0zd2;
Meet the above conditions , Protection immediate exitB12/B13 , Simultaneous drive accident signal relay B14/B15(Until the manual, relay to return) , indicator of Panel accident light
Zero sequence over current Ⅲsegment1).RLP08Zero sequence current instantaneous trip segment-“in”;2) . Zero sequence currenti0Sample value≧ Zero sequence current instantaneous trip II
segment(I0dz3);3).Add current time Zero sequence ≧ current instantaneous trip II segment TI0zd3;
Meet the above conditions, protection the immediate exit B12/B13 , Simultaneous drive accident signal relay B14/B15(Until the manual, before returning to the relay ), indicator of Panel accident light
Zero current Ⅲsegment Inverse time limitThe characteristic of Zero current Ⅲ segment is the same as verse time limit
Note:Zero sequence over current Ⅲsegment and Zero current Ⅲsegment
Inverse time limit.Shared numeric value and time limit,Both at the same time,
the anti time limit protection is invalid.
Zero sequence over currentSystem for large current or small resistance grounding , The device is provided with zero sequence over current protection, and can choose alarm or trip.1).RLP10 Zero sequence over current-“Alarm / trip”;2).Zero sequence current i0 Sample value≧Zero sequence over current(Iodz);3).Add current time Zero sequence over≧ current delay TIozd;indicator of Panel accident lightMeet the above conditions,if the“trip”Protect immediate exit B12/B13 , Simultaneous drive accident signal relay B14/B15 ( Until the manual, before returning to the relay ) , if“alarm”Protection for immediately driving alarm signal relay B14/B16 ( Until the manual, relay to return),indicator of Panel accident light
Over voltage1).RLP11 Over voltage-“in”; 2) . Three-phase line voltage Uab 、 Ubc 、 Uca choose Sampling median value,Maximum line voltage≧ Over voltage fixed value(Udz1);3).Over voltage sampling delay time Over≧ voltage delay(TUzd1);Meet the above conditions,Protect immediate exit B12/B13,Simultaneous drive accident signal relay B14/B15(Until the manual, before returning to the relay ), indicator of Panel accident light
low voltage1).RLP12 low voltage-“in”; 2).Three-phase line voltage Uab、Ubc、Uca Sampling values are all the same≦ Low voltage setting(Udz2);3).Low voltage sampling delay time Low voltage delay≧ (TUzd2);4).Three phase line voltage≧30V; Meet the above conditions,Protection immediate exitB12/B13 ,Simultaneous drive accident signal relayB14/B15 ( Until the manual, before returning to the relay ) , indicator of Panel
accident light
Low frequency load shedding1).RLP13 Low frequency load shedding-“in”;2).Measuring current C Phase sampling current value is not less than0.3A;3).Sample value f Sample value≦ Low frequency load shedding(Dpjz);4).Add current time Low frequency load shedding Tdp≧ ;Meet the above conditions,Protect immediate exit B12/B13,Simultaneous drive accident signal relay B14/B15(Until the manual, before returning to the relay ), indicator of Panel accident light
System loss of power1).RLP15 System loss of power-“in”;2).Sampling voltage (line voltage) is less than 30V;3).Sampling current ia、ib、ic both <0.1A;4).Switch is closed;5 ) . Pressure sign system =1 ( When the system voltage is greater than30V,Set pressure sign=1,monitoring the break signal and then cancel it);
Meet the above conditions , Protection immediate exitB12/B13 , Simultaneous drive accident signal relay B14/B15(Until the manual, before returning to the relay ), indicator of Panel alarm light
PT Break1).RLP16PT line break-“in service”;2).A phase voltage sampling value ≧PT line breaking voltage value(Upt1),The rest of the two phase voltages in at least one phase sampling value< PT Breaking voltage value(Upt1);
Meet the above conditions,Device delay 10S occur PT Disconnection protection , Drive alarm signal relay B14/B16 ( Until the manual, before returning to the relay),indicator of Panel alarm light
PT Pressure loss1).RLP17 PT Pressure loss-“in service”;2).Three phase line voltage is less than PT Loss of pressure(Upt2);3).Protection current ia、ib、ic Anyone phase 0.3A≧ ;
Meet the above conditions,Device delay 10Soccur PT Pressure loss protection , Drive alarm signal relay B14/B16 ( Until the manual, before returning to the relay),indicator of Panel alarm light
control circuit Break1).RLP18 control circuit Break-“in service”;
2).At the same time, the signal is collected.,Or at the same time the close and break signal can not be collected ,Duration time control ≧ circuit Break delayed(TKZDX);
Meet the above conditions,the control circuit disconnection Device alarmed , and drive alarm signal relay B14/B16 ( Until the manual, before returning to the relay),indicator of Panel alarm light
4、Device function drawing
VIP-9511 Device terminal diagram explain:
AC circuit control circuit Communication circuitterminal
definition
explain
terminal
explain terminal
explain
A1 Ua*Generatrix
voltage
B1 Positive power supply
C1 485A
A2 Ub* B2 Negative power supply
C2 485B
A3 Uc* B3 Positive indicator
C3 Communication grounding
A4 Empty
B4 Trip coil TQ C4 Closing signal
A5 io* zero sequenceelectric
current
B5 The closing coil HQ
C5 breaking signal
A6 io B6
Remote Trip exit
C6 Spare capacity 3
A7 ia*
protection
current
B7 C7 Standby opening4
A8 ia B8Remote control switch
exit
C8 Spare capacity 5
A9 ib* B9 C9
Manual trip signal(Coincidence lock
A10 ib B10 Coincidence gate Relay outlet
C10 Spare capacity7A11 ic* B11 C11 Spare capacity8
A12 ic B12 Protection tripRelay outlet
C12 Input of common port
A13 Ia* measu B13
rement
current
A14 Ia B14 Signal common
A15 Ic* B15 Accident signal terminal
A16 Ic B16 Alarm signal terminal
Device wiring instructions
1.The above connection is the standard wiring way.2.Voltage using the V-V connection,and Ua*connect A1、Ub*connect A2、Uc*connect A33 . If the current is two mutual inductor,and B Phase current position does not wiring , and A9/A10can be empty。4.If there is no zero sequence current transformer,and the io No connection,and A5/A6can be empty5.If the protection device uses AC power supply,and B1Connecting earth wire,B2 connecting live wire.6.Relay exports have been defined,Special requirements will be according to the manufacturers are defined.7.input of switch for passive contact,input of swith C4/C5 Has been defined.
Input of switch C9 is Manual tripping signal , when needed to reclosure t,Must access to it, Other input quantities are not defined.
8 . This figure does not take the jump,If the protection needs to take the anti jump circuit,Please refer to our company's drawings with anti jump.
VIP-9511 Schematic diagram of the device:
1
1
2
1
YY1A- 2
DZ47 3A/2PLW12- 16Z/ 5858. 3
VI P-9511KKXL
1- 2LPZK
90-
45-
0
90
45
LW12-16Z/5858.3
1- 23- 4
7- 85- 6
9- 1011- 12
0°90°- 90°+45°- 45°+
B5
3
42
1
B9
B1
posit ive power control
B2
VI P-9511XL
B13B12
B3B4
B7
B8
B6
C5C4
12V(wi thi n suppl y- )
+12V(wi thi n suppl y)
XLVI P-9511
QF
C6C7C8C9
485B485A
584
C2C1
B14
B16
B15
A630
B630
C630
A1
A2
A3
A6
L4313LH A5
A131LH
1LH A15
A411
C411
A14
A16
A8A10
A12
C421B421
A421
A11A9
2LH2LH
2LH
I C*
A7I A*
I B*
C10C11C12
I A
I C
I B
I c*
I a*
I a
I c
3I o
3I o*
UC
UB
UA
1LP
1 22LPB10 B11
ZK
posi ti ve swi tchcont rol
posi tive power protecti on
recl osure
reclosuremanual cl osing
remotecontrolswi tch
remotepowercontrol
remotepowercontrol
remotepowercontr ol
remote tri p
manual tri p
protect i on tri p
pr ot ect ion power
negati ve powercont rol
negati ve swi tchcont rolnegati ve swi tchcont rol
cl osing coi l
cl osing coi l
tri p coi lprotecti on of openi ng posi t i on i ndi cator
pr ot ect ive tri pping
volt age
loop
busbar
vol tage
busbar
vol t age
protection
ci rcuit
cur rent
loop
curr ent
measuri ng
ci rcuit
swi tchi ng si gnal
openi ng posi t i on si gnals Di gi t al I nput
Di gi t al I nput
Di gi tal I nputmanual tri p si gnal
Di gi tal I nput Di gi tal I nput
Di gi t al I nput
passi ve nul l correspondi ng contact
communi cati ons
si gnal commom
acci dent si gnal
al arm si gnal
si gnaloutput
l ocationaft er t rip
sel f reset sel f resetaft er swi t chi ng
manual cl osingmanual tri pcontactnumber
remar k: the refer to termi nal on the devi ce
refer to the upper termi nal
outlet pressure pl atecontr ol swi tchpower swi tch
protecti on devi cecomponent nameCode namesequence No.
markdesi gndesi gndesi gn
audit or
several part change thefi l e number si gn
technical
fi gure number
approval
date
model speci fi cati on uni t quanti ty
Changj i ang electr i c
Hangzhou Ji Bao Nanr uiremarks
name of drawi ngVI P-9501 comprehensi ve andprotecti on control devi ce
schematic diagram
phrase mark quantit ypr oport ion
total 2 page
VIP-9000substation compreh ensive automatic system
VIP-9511F instruction of device terminal diagram:
AC circuit control circuit communication circuitterminal
definition
explain
terminal
explain terminal
explain
A1 Ua*
generatrixvoltage
B1 Positive power supply
C1 485A
A2 Ub* B2 Negative power supply
C2 485B
A3 Uc* B3 Positive indicator
C3 Communication grounding
A4 Empty
B4 Trip coil TQ C4 Close signal
A5 io* zero sequence
current
B5 Closing coil HQ C5 Break signalA6 io B6
Anti-trip negative power supply
C6 Spare Open volume3
A7 ia*
protect
protect
current
B7Remote Trip exit
Remote control public end
Remote control on export
C7 spare Open volume4
A8 ia B8 C8 spare Open volume5
A9 ib* B9 C9
Manual trip signal
(coincidence gate lock)
A10 ib B10 Coincidence gate
Relay outlet
C10 spare Open volume7
A11 ic* B11 C11 spare Open volume8
A12 ic B12 Protection trip
Relay outlet
C12 Open volume Common end
A13 Ia* measure
amount
current
B13A14 Ia B14 Signal Common
endA15 Ic* B15 Accident signalA16 Ic B16 Alarm signal
Device wiring instructions1The above wiring is the standard wiring.
2.Voltage using V-V Wiring,and then Ua*connect A1、Ub*connect A2、Uc*connect A3.3 . If the current is two mutual inductor,and B Phase current position does not wiring,A9/A10 is empty 4.If there is no zero sequence current transformer,the io is not connection.that is empty A5/A65.If the protection device uses AC power supply,则 B1 connect earth line,B2 Connected to the zero line.6.Relay exports have been defined,Special requirements will be according to the manufacturers are defined.7.Input of switch access for passive contact,input of switch C4/C5 has been defined.
Open volume C9 Manual tripping signal,when needed reclosing,Must access to it,Other input quantities are not defined.
8.This drawing with anti jump circuit.
VIP-9511FSchematic diagram of the device:
HQTQ
C6C7
C4C5
C2C3
C1
C9C8
C12C11C10
485 eart h
B15B16
B14
B10B11
B13B12
B8B9
~B1 +220
B3B2 - 220
B5B4
B7B6
485B485A
VI P-9511 l i ne prot ect ion cont rol devi ce
AC sampl i ng operati ng output operati ng output
busbar
vol tage
empty
sequence
zero
pr otect ion curr ent
loop
measurment
pos i ti veindi catortri p coi lclosing coi l
work power
controlloop
rel ay
protect i on
si gnoutput
remotecontroltri p
remot e c ontrolcl osi ng
aut o- r eclosur eout put
protecti on tri p
common portacci dent si gnal
al arm si gnal
communicati on
entr y
di gi t al i nput
di gi t al i nput spare( )
di gi t al i nput spare( )
di git al input 3
di git a l input 4
di git a l input 5
di gi t al i nputaut o recl osur e at resi a)
di git al input 6
di git al input 7
i nput of common port
mark sever alrevise par t change the
fi le number si gn datedesign
chec keraudi t or
technical
fi gur e No
rat if y
date
name of drawi ng name of proj ect
mark the phrase quant it ypr oport ion
VI P-9000 substati oni on comprehensive auto-system
to ta l 2 page total 2 page
termi nal wi ri ng di agram