VF Series M9000 Electrically and D-3000 Pneumatically … · 2013-08-06 · VF Series M9000...
Transcript of VF Series M9000 Electrically and D-3000 Pneumatically … · 2013-08-06 · VF Series M9000...
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesProduct Bulletin Code No. LIT-977202
Issued May 7, 2007Supersedes January 26, 2005
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves are designed specifically for a wide range of Heating, Ventilating, and Air Conditioning (HVAC) applications including two-position and modulating control of hot, chilled, or condenser water, and 50/50 glycol solutions. These valves are also bidirectional, allowing positive shutoff with the flow in either direction.
Two-way configurations are available in sizes from 2 through 6 in. for M9000 Electrically Actuated, and 2 through 10 in. for D-3000 Pneumatically Actuated assemblies. Three-way assemblies have two valves that are linked together and mounted on a flanged, cast-iron tee. Three-way configurations are available in sizes from 2 through 6 in. for M9000 Electrically Actuated and 2 through 8 in. for D-3000 Pneumatically Actuated assemblies.
M9000 Electrically Actuated models are available with or without a rugged, factory-installed weather shield. M9000 Electrically Actuated non-spring return, non-weather shield models feature an integral handle for manual positioning of the valve, independent of a power supply.
Figure 1: VF Series M9000 Electrically and D-3000 Pneumatically Actuated
Standard-Pressure, Standard-Temperature Butterfly Valves
Table 1: Features and BenefitsFeatures BenefitsLow Seating/Unseating Torques Reduce actuator torque and size requirements, particularly with lower
pressure rated valves.
Bubble-Tight Shutoff Provides positive closure when needed.
PreAssembled Actuators Reduce assembly costs.
Compatible with All Types of ANSI 125/150 Slip-On and Weld-Neck Flanges
Allows configuration in the field, with readily available standard fittings.
M9000 Electric Actuators Available with or without a Rugged, Factory-Installed Weather Shield
Provide protection from the elements in outside applications.
M9000 Electric Actuators Available with or without End Switches
Provide adjustable switch points for positive indication or operation of auxiliary equipment.
D-3000 Pneumatic Actuators Available with or without a Pneumatic Positioner
Provide precise valve positioning.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
1
Application OverviewAll VF Series Standard-Pressure, Standard-Temperature Valves are available with a factory-assembled M9000 Series Electric Actuator or D-3000 Series Pneumatic Actuator, to provide years of trouble-free operation. The valve and actuator can be provided in Normally Open (N.O.) or Normally Closed (N.C.) combinations for two-way operation. Three-way valves are available in four mounting styles to meet all possible piping layouts. These butterfly valves have an inherent modified equal percentage relationship between disk rotation and flow at a constant pressure drop (as illustrated in Figure 2).
The valve body is cast iron and meets the temperature and pressure requirements for ANSI Class 125 B16.1 Class B pipe flanges. The valve neck is extended to allow for 2 in. (51 mm) of insulation as well as easy access to the actuator. All valve sizes are fully lugged.
The resilient seat of VF Series M9000 Electrically Actuated or D-3000 Series Pneumatically Actuated Standard-Pressure, Standard-Temperature Valves is molded from Ethylene Propylene Diene Monomer (EPDM). The disk is constructed of aluminum bronze, and the stem is 416 stainless steel.
The flow characteristics of VF Series M9000 Electrically Actuated or D-3000 Series Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves are illustrated in Figure 2. Inherent flow characteristics are modified equal percentage.
Figure 2: Modified Equal Percentage Valve Flow Characteristics
100
90
80
70
60
50
40
30
20
10
00 10 20 30 40 50 60 70 80 90 100
Percent of Valve Opening
Per
cent
of F
low
Actual Flow Curve(Modified Equal
Percentage)
EqualPercentageFlow Curve
FIG
:MEP
VFC
Table 2: Valve Flow Coefficients, Cv (kv)Valve Size, in.
Disk Position, Degrees Open1
90° Maximum Stroke for Valves with M9000 Electric Actuators
80° 70°Maximum Stroke for Valves with D-3000 Pneumatic Actuators
60° 50° 40° 30° 20°
2 159 135 105 70.6 44.5 26.3 14.2 4.06
2-1/2 266 215 156 140 65.3 38.6 20.9 6.17
3 457 342 240 156 98.0 57.9 31.4 13.6
4 860 625 423 274 173 102 55.1 23.9
5 1,320 970 656 426 268 158 85.6 37.2
6 2,020 1,420 941 610 384 227 123 53.3
8 3,540 2,500 1,660 1,080 679 401 217 94.3
10 5,580 3,830 2,560 1,660 1,040 617 334 145
1. Recommended disk rotation is between 30° and 70° open for proportional control; preferred disk rotation for control valve sizing is 50° to 70° open.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
2
Product GuidelinesPlease be sure to read the following information carefully before installing a VF Series M9000 Electrically Actuated or D-3000 Series Pneumatically-Actuated Standard-Pressure, Standard-Temperature Butterfly Valve Assembly.
• Be sure that the pipeline and flange faces are clean. Pipe scale, metal chips, weld slag, and weld rods can obstruct disk movement and damage the disk and seat.
• The resilient seat of the valve is equipped with molded O-rings on the face of the seat; do not use gaskets.
• The valves should be handled by the extended valve neck only. Heavier valves may require a nylon sling to be used as a hoist around the valve neck and/or cast-iron tee (on three-way assemblies). Never pick up a valve by the actuator, mounting bracket, or interconnecting linkage.
• Most VF Series M9000 Electrically Actuated or D-3000 Series Pneumatically-Actuated Standard-Pressure, Standard-Temperature Butterfly Valve Assemblies are shipped with the disk in the near-closed position (approximately 10 degrees open).
For proper actuator wiring and commissioning, refer to the following documents:
• M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions (Part No. 34-636-399)
• M9220-AGx-3 Floating Electric Spring Return Actuators Installation Instructions (Part No. 34-636-1689)
• M9220-Bxx-3 On/Off Electric Spring Return Actuators Installation Instructions (Part No. 34-636-1239)
• M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions (Part No. 34-636-1697)
Table 3: Cv Correction Factor - Two-Way and Three-Way – 90° Fully OpenValve Size, in.
Pipe Size, in.2 2-1/2 3 4 5 6 8 10 12 14
2 159 140 123 --- --- --- --- --- --- ---
2-1/2 --- 266 231 --- --- --- --- --- --- ---
3 --- --- 457 336 --- --- --- --- --- ---
4 --- --- --- 860 679 551 --- --- --- ---
5 --- --- --- --- 1,320 1086 776 --- --- ---
6 --- --- --- --- --- 2,020 1,484 1,202 --- ---
8 --- --- --- --- --- --- 3,540 2,811 2,287 ---
10 --- --- --- --- --- --- --- 5,580 4,612 3,768
Table 4: Cv Correction Factor - Two-Way and Three-Way – 70° (Modulating Applications)Valve Size, in.
Pipe Size, in.2 2-1/2 3 4 5 6 8 10 12 14
2 105 100 95 --- --- --- --- --- --- ---
2-1/2 --- 156 148 --- --- --- --- --- --- ---
3 --- --- 240 212 --- --- --- --- --- ---
4 --- --- --- 423 385 345 --- --- --- ---
5 --- --- --- --- 656 611 518 --- --- ---
6 --- --- --- --- --- 941 838 754 --- ---
8 --- --- --- --- --- --- 1,660 1,525 1,384 ---
10 --- --- --- --- --- --- --- 2,560 2,401 2,202
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
3
• D-3153 Pneumatic Actuator Product Bulletin (LIT-2681054P)
• D-3240 Series Pneumatic Piston Actuators Product Bulletin (LIT-2681055P)
SelectionUse Table 5 and Table 6 as a quick-reference for ordering a butterfly valve assembly and factory-mounted actuator. For more detailed information on standard valve and actuator assemblies (including flow coefficients), see Table 7 through Table 30.
Table 5: Ordering Data1
V F Butterfly
1 2 Valve
4 Disk Type/ 4 = Standard Disk Without Weather Shield
3 Actuator 5 = Standard Disk With Weather Shield
Enclosure 6 = Undercut Disk without Weather Shield
2 Body Type 2 = Two-Way, Normally Open (N.O.)
4 4 = Two-Way, Normally Closed (N.C.)
8 = Three-Way
3 Flange 3 = ANSI Class 125/150, Fully Lugged
5
1 Flow Characteristics
1 = Modified Equal Percentage
6
C Valve Size A = 2 in. (With Four Mounting Lugs)
7 B = 2-1/2 in. (With Four Mounting Lugs)
C = 3 in. (With Four Mounting Lugs)
D = 4 in. (With Eight Mounting Lugs)
E = 5 in. (With Eight Mounting Lugs)
F = 6 in. (With Eight Mounting Lugs)
G = 8 in. (With Eight Mounting Lugs)
H = 10 in. (With Twelve Mounting Lugs)
A Valve Style A = Two-Way
8 D = Three-Way, Style D2
E = Three-Way, Style E2
F = Three-Way, Style F2
G = Three-Way, Style G2
+ + = Factory-Mounted Actuator
9
Example: Two-way 3 in. ANSI Class 125/150 Valve1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 = Field
V F 4 2 3 1 C A +
Butterfly Valve Assembly
1. For a replacement valve body, configure the appropriate code number from the first eight fields in Table 5; the existing actuator-to-valve linkage will need to be reused.
2. See Figure 6 for three-way valve body styles.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
4
Table 6: Ordering Data – Adding a Factory Mounted Actuator1
V F 4 2 3 1 C A + + = Factory-Mounted Actuator
1 2 3 4 5 6 7 8 9 2 = Tandem Actuators
9 1 6 Factory Mounted Electric Actuator
916 = M9116 Non-Spring Return
10 11 12 924 = M9124 Non-Spring Return
92N = M9220 Spring Return Open
94N = M9220 Spring Return Closed
G Control A = Floating
13 B = On/Off
G = Proportional with 0-10 VDC Feedback
G Voltage G = 24 VAC
14
C Auxiliary Switches
A = None
15 C = Two Auxiliary Switches
3 1 5 3 Factory Mounted Pneumatic Actuator
3153 = D-3153
10 11 12 13 3244 = D-3244
3246 = D-3246
P Accessories P= D-9502 Pneumatic Positioner
14 Blank = None
Example: Two-way normally open valve without weather shield, 3 in., with proportional, non-spring return electric actuator, 0 to 10 VDC feedback and two auxiliary switches
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 = Field
V F 4 2 3 1 C A + 9 1 6 G G C
Butterfly Valve Assembly
1. For a replacement valve body, configure the appropriate code number from the first eight fields in Table 5; the existing actuator-to-valve linkage will need to be reused. Refer to the appropriate actuator product bulletin for additional actuator details.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
5
Two-Way Valve with M9000 Series Electric Actuator (Less Weather Shield)
Table 7: On/Off (Floating) Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.
M91xx-AGA-2 without End Switches
M91xx-AGC-2 with Two End Switches
2 159 105 200 VF4231AA+916AGA VF4231AA+916AGC
2-1/2 266 156 200 VF4231BA+916AGA VF4231BA+916AGC
3 457 240 200 VF4231CA+916AGA VF4231CA+916AGC
4 860 423 200 VF4231DA+924AGA VF4231DA+924AGC
5 1320 656 50 VF4231EA+924AGA VF4231EA+924AGC
5 1320 656 200 VF4231EA2924AGA2
2. Valve assemblies have two actuators mounted in tandem.
VF4231EA2924AGC2
6 2020 941 100 VF4231FA2924AGA2 VF4231FA2924AGC2
Figure 3: Two-Way Valve with M9000 Series Non-Spring Return Electric Actuator
(Less Weather Shield)
Figure 4: Two-Way Valve with M9000 Series Spring Return Electric Actuator
(Less Weather Shield)
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
6
Table 8: 0 to 10 VDC Proportional Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M91xx-GGA-2 without End Switches
M91xx-GGC-2 with Two End Switches
2 159 105 200 VF4231AA+916GGA VF4231AA+916GGC
2-1/2 266 156 200 VF4231BA+916GGA VF4231BA+916GGC
3 457 240 200 VF4231CA+916GGA VF4231CA+916GGC
4 860 423 200 VF4231DA+924GGA VF4231DA+924GGC
5 1320 656 50 VF4231EA+924GGA VF4231EA+924GGC
5 1320 656 200 VF4231EA2924GGA2 VF4231EA2924GGC2
6 2020 941 100 VF4231FA2924GGA2 VF4231FA2924GGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
Table 9: Floating Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M9220-AGA-3 without End Switches
M9220-AGC-3 with Two End Switches
Spring Open Spring Closed Spring Open Spring Closed2 159 105 200 VF4231AA+92NAGA VF4431AA+94NAGA VF4231AA+92NAGC VF4431AA+94NAGC
2-1/2 266 156 200 VF4231BA+92NAGA VF4431BA+94NAGA VF4231BA+92NAGC VF4431BA+94NAGC
3 457 240 200 VF4231CA+92NAGA VF4431CA+94NAGA VF4231CA+92NAGC VF4431CA+94NAGC
4 860 423 50 VF4231DA+92NAGA VF4431DA+94NAGA VF4231DA+92NAGC VF4431DA+94NAGC
4 860 423 200 VF4231DA292NAGA2 VF4431DA294NAGA2 VF4231DA292NAGC2 VF4431DA294NAGC2
5 1320 650 100 VF4231EA292NAGA2 VF4431EA294NAGA2 VF4231EA292NAGC2 VF4431EA294NAGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
Table 10: On/Off Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M9220-BGA-3 without End Switches
M9220-BGC-3 with Two End Switches
Spring Open Spring Closed Spring Open Spring Closed2 159 105 200 VF4231AA+92NBGA VF4431AA+94NBGA VF4231AA+92NBGC VF4431AA+94NBGC
2-1/2 266 156 200 VF4231BA+92NBGA VF4431BA+94NBGA VF4231BA+92NBGC VF4431BA+94NBGC
3 457 240 200 VF4231CA+92NBGA VF4431CA+94NBGA VF4231CA+92NBGC VF4431CA+94NBGC
4 860 423 50 VF4231DA+92NBGA VF4431DA+94NBGA VF4231DA+92NBGC VF4431DA+94NBGC
4 860 423 200 VF4231DA292NBGA2 VF4431DA294NBGA2 VF4231DA292NBGC2 VF4431DA294NBGC2
5 1320 656 100 VF4231EA292NBGA2 VF4431EA294NBGA2 VF4231EA292NBGC2 VF4431EA294NBGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
7
Table 11: 0 to 10 VDC Proportional Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M9220-GGA-3 without End Switches
M9220-GGC-3 with Two End Switches
Spring Open Spring Closed Spring Open Spring Closed2 159 105 200 VF4231AA+92NGGA VF4431AA+94NGGA VF4231AA+92NGGC VF4431AA+94NGGC
2-1/2 266 156 200 VF4231BA+92NGGA VF4431BA+94NGGA VF4231BA+92NGGC VF4431BA+94NGGC
3 457 240 200 VF4231CA+92NGGA VF4431CA+94NGGA VF4231CA+92NGGC VF4431CA+94NGGC
4 860 423 50 VF4231DA+92NGGA VF4431DA+94NGGA VF4231DA+92NGGC VF4431DA+94NGGC
4 860 423 200 VF4231DA292NGGA2 VF4431DA294NGGA2 VF4231DA292NGGC2 VF4431DA294NGGC2
5 1320 656 100 VF4231EA292NGGA2 VF4431EA294NGGA2 VF4231EA292NGGC2 VF4431EA294NGGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
8
Three-Way Valves with M9000 Series Electric Actuators (Less Weather Shield)
Table 12: On/Off (Floating) Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
1. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
M91xx-AGA-2 without End Switches
M91xx-AGC-2 with Two End Switches
2 159 105 200 VF4831AD+916AGA VF4831AD+916AGC
2-1/2 266 156 200 VF4831BD+916AGA VF4831BD+916AGC
3 457 240 200 VF4831CD+916AGA VF4831CD+916AGC
4 860 423 50 VF4831DD+924AGA VF4831DD+924AGC
5 1320 656 100 VF4831ED2924AGA2
2. Valve assemblies have two actuators mounted in tandem.
VF4831ED2924AGC2
6 2020 941 100 VF4831FD2924AGA2 VF4831FD2924AGC2
Table 13: 0 to 10 VDC Proportional Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (Less Weather Shield) (Part 1 of 2)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M91xx-GGA-2 without End Switches
M91xx-GGC-2 with Two End Switches
2 159 105 200 VF4831AD+916GGA VF4831AD+916GGC
2-1/2 266 156 200 VF4831BD+916GGA VF4831BD+916GGC
3 457 240 200 VF4831CD+916GGA VF4831CD+916GGC
4 860 423 50 VF4831DD+924GGA VF4831DD+924GGC
Figure 5: Three-Way Valve with M9000 Series Electric Actuator (Less Weather Shield)
N.O.
Style F
N.O.
N.C.
Style G
N.C. FIG
:3w
ay_v
bs
N.C.
Style D
N.O.
Style E
N.C.
N.O.
Figure 6: Three-Way Valve Body Styles
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
9
5 1320 656 100 VF4831ED2924GGA2 VF4831ED2924GGC2
6 2020 941 100 VF4831FD2924GGA2 VF4831FD2924GGC2
1. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
2. Valve assemblies have two actuators mounted in tandem.
Table 14: On/Off Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)2
M9220-BGA-3 without End Switches
M9220-BGC-3 with Two End Switches
2 159 105 200 VF4831AD+92NBGA VF4831AD+92NBGC
2-1/2 266 156 200 VF4831BD+92NBGA VF4831BD+92NBGC
3 457 240 150 VF4831CD+92NBGA VF4831CD+92NBGC
4 860 423 175 VF4831DD292NBGA3 VF4831DD292NBGC3
1. Code numbers listed are three-way valves in Style D. See Figure 6. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.
2. All valves are rated for dead-end service. Valves rated at for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
3. Valve assemblies have two actuators mounted in tandem.
Table 15: Proportional Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)2
M9220-GGA-3 without End Switches
M9220-GGC-3 with Two End Switches
2 159 105 200 VF4831AD+92NGGA VF4831AD+92NGGC
2-1/2 266 156 200 VF4831BD+92NGGA VF4831BD+92NGGC
3 457 240 150 VF4831CD+92NGGA VF4831CD+92NGGC
4 860 423 175 VF4831DD292NGGA3 VF4831DD292NGGC3
1. Code numbers listed are three-way valves in Style D. See Figure 6. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.
2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
3. Valve assemblies have two actuators mounted in tandem.
Table 13: 0 to 10 VDC Proportional Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (Less Weather Shield) (Part 2 of 2)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M91xx-GGA-2 without End Switches
M91xx-GGC-2 with Two End Switches
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
10
Two-Way Valves with M9000 Series Spring Return and Non-Spring Return Electric Actuator (With Weather Shield)
Table 16: Floating Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (Less Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)2
M9220-AGA-3 without End Switches
M9220-AGC-3 with Two End Switches
2 159 105 200 VF4831AD+92NAGA VF4831AD+92NAGC
2-1/2 266 156 200 VF4831BD+92NAGA VF4831BD+92NAGC
3 457 240 150 VF4831CD+92NAGA VF4831CD+92NAGC
4 860 423 175 VF4831DD292NAGA3 VF4831DD292NAGC3
1. Code numbers listed are three-way valves in Style D. See Figure 6. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.
2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
3. Valve assemblies have two actuators mounted in tandem.
Table 17: On/Off (Floating) Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (With Weather Shield) (Part 1 of 2)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M91xx-AGA-2 without End Switches
M91xx-AGC-2 with Two End Switches
2 159 105 200 VF5231AA+916AGA VF5231AA+916AGC
2-1/2 266 156 200 VF5231BA+916AGA VF5231BA+916AGC
3 457 240 200 VF5231CA+916AGA VF5231CA+916AGC
4 860 423 200 VF5231DA+924AGA VF5231DA+924AGC
Figure 7: Two-Way Valve with M9000 Series Electric Actuator (With Weather Shield)
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
11
5 1320 656 50 VF5231EA+924AGA VF5231EA+924AGC
5 1320 656 200 VF5231EA2924AGA2 VF5231EA2924AGC2
6 2020 941 100 VF5231FA2924AGA2 VF5231FA2924AGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
Table 18: 0 to 10 VDC Proportional Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (With Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M91xx-GGA-2 without End Switches
M91xx-GGC-2 with Two End Switches
2 159 105 200 VF5231AA+916GGA VF5231AA+916GGC
2-1/2 266 156 200 VF5231BA+916GGA VF5231BA+916GGC
3 457 240 200 VF5231CA+916GGA VF5231CA+916GGC
4 860 423 200 VF5231DA+924GGA VF5231DA+924GGC
5 1320 656 50 VF5231EA+924GGA VF5231EA+924GGC
5 1320 656 200 VF5231EA2924GGA2 VF5231EA2924GGC2
6 2020 941 100 VF5231FA2924GGA2 VF5231FA2924GGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
Table 19: Floating Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (With Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M9220-AGA-3 without End Switches M9220-AGC-3 with Two End SwitchesSpring Open Spring Closed Spring Open Spring Closed
2 159 105 200 VF5231AA+92NAGA VF5431AA+94NAGA VF5231AA+92NAGC VF5431AA+94NAGC
2-1/2 266 156 200 VF5231BA+92NAGA VF5431BA+94NAGA VF5231BA+92NAGC VF5431BA+94NAGC
3 457 240 200 VF5231CA+92NAGA VF5431CA+94NAGA VF5231CA+92NAGC VF5431CA+94NAGC
4 860 423 50 VF5231DA+92NAGA VF5431DA+94NAGA VF5231DA+92NAGC VF5431DA+94NAGC
4 860 423 200 VF5231DA292NAGA2 VF5431DA294NAGA2 VF5231DA292NAGC2 VF5431DA294NAGC2
5 1320 656 100 VF5231EA292NAGA2 VF5431EA294NAGA2 VF5231EA292NAGC2 VF5431EA294NAGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
Table 17: On/Off (Floating) Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (With Weather Shield) (Part 2 of 2)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M91xx-AGA-2 without End Switches
M91xx-AGC-2 with Two End Switches
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
12
Table 20: On/Off Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (With Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M9220-BGA-3 without End Switches M9220-BGC-3 with Two End SwitchesSpring Open Spring Closed Spring Open Spring Closed
2 159 105 200 VF5231AA+92NBGA
VF5431AA+94NBGA
VF5231AA+92NBGC
VF5431AA+94NBGC
2-1/2 266 156 200 VF5231BA+92NBGA
VF5431BA+94NBGA
VF5231BA+92NBGC
VF5431BA+94NBGC
3 457 240 200 VF5231CA+92NBGA
VF5431CA+94NBGA
VF5231CA+92NBGC
VF5431CA+94NBGC
4 860 423 50 VF5231DA+92NBGA
VF5431DA+946BGA
VF5231DA+92NBGC
VF5431DA+94NBGC
4 860 423 200 VF5231DA292NBGA2
VF5431DA294NBGA2
VF5231DA292NBGC2
VF5431DA294NBGC2
5 1320
656 100 VF5231EA292NBGA2
VF5431EA294NBGA2
VF5231EA292NBGC2
VF5431EA294NBGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
Table 21: 0 to 10 VDC Proportional Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (With Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
M9220-GGA-3 without End Switches M9220-GGC-3 with Two End Switches
Spring Open Spring Closed Spring Open Spring Closed
2 159 105 200 VF5231AA+92NGGA VF5431AA+94NGGA VF5231AA+92NGGC VF5431AA+94NGGC
2-1/2 266 156 200 VF5231BA+92NGGA VF5431BA+94NGGA VF5231BA+92NGGC VF5431BA+94NGGC
3 457 240 200 VF5231CA+92NGGA VF5431CA+94NGGA VF5231CA+92NGGC VF5431CA+94NGGC
4 860 423 50 VF5231DA+92NGGA VF5431DA+94NGGA VF5231DA+92NGGC VF5431DA+94NGGC
4 860 423 200 VF5231DA292NGGA2 VF5431DA294NGGA2 VF5231DA292NGGC2 VF5431DA294NGGC2
5 1320 656 100 VF5231EA292NGGA2 VF5431EA294NGGA2 VF5231EA292NGGC2 VF5431EA294NGGC2
1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
13
Three-Way Valve with M9000 Series Spring Return and Non-Spring Return Electric Actuator (With Weather Shield)
Table 22: On/Off (Floating) Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (With Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
1. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
M91xx-AGA-2 without End Switches
M91xx-AGC-2 with Two End Switches
2 159 105 200 VF5831AD+916AGA VF5831AD+916AGC
2-1/2 266 156 200 VF5831BD+916AGA VF5831BD+916AGC
3 457 240 150 VF5831CD+916AGA VF5831CD+916AGC
4 860 423 100 VF5831DD+924AGA VF5831DD+924AGC
5 1320 656 100 VF5831ED2924AGA2
2. Valve assemblies have two actuators mounted in tandem.
VF5831ED2924AGC2
6 2020 941 100 VF5831FD2924AGA2 VF5831FD2924AGC2
Figure 8: Three-Way Valve with M9000 Series Spring Return and Non-Spring Return
Electric Actuator (With Weather Shield)
N.O.
Style F
N.O.
N.C.
Style G
N.C. FIG
:3w
ay_v
bs
N.C.
Style D
N.O.
Style E
N.C.
N.O.
Figure 9: Three-Way Valve Body Styles
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
14
Table 23: 0 to 10 VDC Proportional Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (With Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)1
1. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
M91xx-GGA-2 without End Switches
M91xx-GGC-2 with Two End Switches
2 159 105 200 VF5831AD+916GGA VF5831AD+916GGC
2-1/2 266 156 200 VF5831BD+916GGA VF5831BD+916GGC
3 457 240 150 VF5831CD+916GGA VF5831CD+916GGC
4 860 423 100 VF5831DD+924GGA VF5831DD+924GGC
5 1320 656 100 VF5831ED2924GGA2
2. Valve assemblies have two actuators mounted in tandem.
VF5831ED2924GGC2
6 2020 941 100 VF5831FD2924GGA2 VF5831FD2924GGC2
Table 24: Floating Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (With Weather Shield)
1. Code numbers listed are three-way valves in Style D. See Figure 9. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)2
2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
M9220-AGA-3 without End Switches
M9220-AGC-3 with Two End Switches
2 159 105 200 VF5831AD+92NAGA VF5831AD+92NAGC
2-1/2 266 156 200 VF5831BD+92NAGA VF5831BD+92NAGC
3 457 240 150 VF5831CD+92NAGA VF5831CD+92NAGC
4 860 423 175 VF5831DD292NAGA3
3. Valve assemblies have two actuators mounted in tandem.
VF5831DD292NAGC3
Table 25: On/Off Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (With Weather Shield)
1. Code numbers listed are three-way valves in Style D. See Figure 9. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)2
2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
M9220-BGA-3 without End Switches
M9220-BGC-3 with Two End Switches
2 159 105 200 VF5831AD+92NBGA VF5831AD+92NBGC
2-1/2 266 156 200 VF5831BD+92NBGA VF5831BD+92NBGC
3 457 240 150 VF5831CD+92NBGA VF5831CD+92NBGC
4 860 423 175 VF5831DD292NBGA3
3. Valve assemblies have two actuators mounted in tandem.
VF5831DD292NBGC3
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
15
Two-Way Valves with D-3000 Series Spring Return Pneumatic Actuators
Table 26: Proportional Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (With Weather Shield)
Size, in.
Cv at 90°
Cv at 70°
Closeoff Pressure (psig)2
M9220-GGA-3 without End Switches
M9220-GGC-3 with Two End Switches
2 159 105 200 VF5831AD+92NGGA VF5831AD+92NGGC
2-1/2 266 156 200 VF5831BD+92NGGA VF5831BD+92NGGC
3 457 240 150 VF5831CD+92NGGA VF5831CD+92NGGC
4 860 423 175 VF5831DD292NGGA3 VF5831DD292NGGC3
1. Code numbers listed are three-way valves in Style D. See Figure 9. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.
2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.
3. Valve assemblies have two actuators mounted in tandem.
Table 27: Two-Way Butterfly Valve Assemblies with 175 psig Closeoff PressureSize, in.
Cv at 70°
Closeoff Pressure (psig)1
1. All valves are rated for dead-end service. Valves rated at 175 psig closeoff have 150 psig maximum dead-end service rating.
On/Off (Proportional Control) Proportional Control (With Postioner)Spring Open Spring Closed Spring Open Spring Closed
2 105 175 VF4231AA+3153 VF4431AA+3153 VF4231AA+3153P VF4431AA+3153P
2-1/2 156 175 VF4231BA+3153 VF4431BA+3153 VF4231BA+3153P VF4431BA+3153P
3 240 175 VF4231CA+3153 VF4431CA+3153 VF4231CA+3153P VF4431CA+3153P
4 423 175 VF4231DA+3244 VF4431DA+3244 VF4231DA+3244P VF4431DA+3244P
5 656 175 VF4231EA+3246 VF4431EA+3246 VF4231EA+3246P VF4431EA+3246P
6 941 175 VF4231FA+3246 VF4431FA+3246 VF4231FA+3246P VF4431FA+3246P
8 1,660 175 VF4231GA232462
2. Valve assemblies have two actuators mounted in tandem.
VF4431GA232462 VF4231GA23246P2 VF4431GA23246P2
Figure 10: Two-Way Valves with D-3000 Series Spring Return Pneumatic Actuators
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
16
Three-Way Valves with D-3000 Series Spring Return Pneumatic Actuators
Table 28: Two-Way Butterfly Valve Assemblies with 50 psig Closeoff PressureSize, in.
Cv at 70°
Closeoff Pressure (psig)1
On/Off (Proportional Control) Proportional Control (With Postioner)Spring Open Spring Closed Spring Open Spring Closed
4 423 50 VF6231DA+3153 VF6431DA+3153 VF6231DA+3153P VF6431DA+3153P
5 656 50 VF6231EA+3244 VF6431EA+3244 VF6231EA+3244P VF6431EA+3244P
6 941 50 VF6231FA+3246 VF6431FA+3246 VF6231FA+3246P VF6431FA+3246P
8 1,660 50 VF6231GA+3246 VF6431GA+3246 VF6231GA+3246P VF6431GA+3246P
10 2560 50 VF6231HA232462 VF6431HA232462 VF6231HA23246P2 VF6431HA23246P2
1. All valves are rated for dead-end service. Valves rated at 50 psig closeoff have 50 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.
Table 29: Three-Way Butterfly Valve Assemblies with 175 psig Closeoff PressureSize, in.
Cv at 70°
Closeoff Pressure (psig)1
1. All valves are rated for dead-end service. Valves rated at 175 psig closeoff have 150 psig maximum dead-end service rating.
On/Off Control2
2. Code numbers listed are three-way valves in Style D. See Figure 12. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.
Proportional Control (With Postioner)2
2 105 175 VF4831AD+3153 VF4831AD+3153P
2-1/2 156 175 VF4831BD+3244 VF4831BD+3244P
3 240 175 VF4831CD+3244 VF4831CD+3244P
4 423 175 VF4831DD+3246 VF4831DD+3246P
5 656 175 VF4831ED+3246 VF4831ED+3246P
6 941 175 VF4831FD232463
3. Valve assemblies have two actuators mounted in tandem.
VF4831FD23246P3
Figure 11: Three-Way Valves with D-3000 Series Spring Return Pneumatic Actuators
N.O.
Style F
N.O.
N.C.
Style G
N.C. FIG
:3w
ay_v
bs
N.C.
Style D
N.O.
Style E
N.C.
N.O.
Figure 12: Three-Way Valve Body Styles
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
17
DimensionsTwo-Way VF Series M9000 Electrically Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesValve sizes 2 through 3 in. feature four mounting lugs with a different orientation than what is illustrated in Figure 13 and Figure 14. Valve sizes 4 through 6 in. feature eight mounting lugs with an orientation similar to what is illustrated in Figure 13 and Figure 14. Always bolt the side of valve marked INLET first to the pipe flange.
For dead-end service, the side of the valve marked INLET should be installed facing pressure when downstream piping will be removed. Placement of a downstream flange is recommended when the valve will be dead-ended for extended periods, in the presence of elevated temperatures, dangerous or expansive fluids, or any combination thereof.
Table 30: Three-Way Butterfly Valve Assemblies with 50 psig Closeoff PressureSize, in.
Cv at 70°
Closeoff Pressure (psig)1
On/Off (Proportional Control)2 Proportional Control (With Postioner)2
4 423 50 VF6831DD+3244 VF6831DD+3244P
5 656 50 VF6831ED+3246 VF6831ED+3246P
6 941 50 VF6831FD+3246 VF6831FD+3246P
8 1,660 50 VF6831GD232463 VF6831GD23246P3
1. All valves are rated for dead-end service. Valves rated at 50 psig closeoff have 50 psig maximum dead-end service rating.2. Code numbers listed are three-way valves in Style D. See Figure 12. For Styles E, F, or G, change the D in the eighth digit
of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.3. Valve assemblies have two actuators mounted in tandem.
Figure 13: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116, M9124 Non-Spring Return and M9220 Spring Return Electric Actuators (Less Weather Shield)
EH
F
C D
A Sleeve
SingleDesign
G
EH
C D
B Chord
TandemDesign
FIG
:2w
ay_e
lec_
ns
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
18
ce d for r l
for
Table 31: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116 and M9124 Series Non-Spring Return Electric Actuators (Less Weather Shield) Dimensions, in. (mm)
Valve Size, in.
A B C D E F G H J Lug Data ClearanRequireActuatoRemova
Bolt Circle
No. of Holes
Threads UNC-2B
2 1.81 (46)
1.49 (38)
13.1 (333)
16.2 (411)
5.75 (146)
12-1/2 (318)
4.5 (114)
7.14 (181)
4(102)
4.75 (121)
4 5/8–11 5(127)
2-1/2 1.94 (49)
2.01 (51)
13.6 (345)
17 (432)
5.75 (146)
12-1/2 (318)
4.5 (114)
7.14 (181)
4(102)
5.5 (140)
4 5/8–11 5(127)
3 2.19 (56)
2.64 (67)
13.8 (351)
17.6 (447)
5.75 (146)
12-1/2 (318)
4.5 (114)
7.14 (181)
4(102)
6(152)
4 5/8–11 5(127)
4 2.19 (56)
3.67 (93)
14.6 (371)
18.9 (480)
5.75 (146)
12-1/2 (318)
4.5 (114)
7.14 (181)
4(102)
7.5(191)
8 5/8–11 5(127)
5 2.31 (59)
4.71 (120)
15.1 (384)
20.0 (508)
5.75 (146)
12-1/2 (318)
4.5 (114)
7.14 (181)
4(102)
8.5(216)
8 3/4–10 5(127)
61 2.31 (59)
5.66 (144)
18.9 (480)
24.3 (617)
8.31 (211)
15(381)
8.75 (222)
9.7 (246)
4(102)
9.5(241)
8 3/4–10 5(127)
1. Valve assemblies have two actuators mounted in tandem.
Table 32: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9220 Series Spring Return Electric Actuators (Less Weather Shield) Dimensions, in. (mm)
Valve Size, in.
A B C D E F G H J Lug Data ClearanceRequired Actuator Removal
Bolt Circle
No. of Holes
Threads UNC-2B
2 1.81 (46)
1.49 (38)
13.1 (333)
16.2 (411)
7.81 (198)
--- 4.5 (114)
10 (254)
4.91 (125)
4.75 (121)
4 5/8–11 6(152)
2-1/2 1.94 (49)
2.01 (51)
13.6 (345)
17.0 (432)
7.81 (198)
--- 4.5 (114)
10 (254)
4.91 (125)
5.5(140)
4 5/8–11 6(152)
3 2.19 (56)
2.64 (67)
13.8 (351)
17.6 (447)
7.81 (198)
--- 4.5 (114)
10 (254)
4.91 (125)
6(152)
4 5/8–11 6(152)
4 2.19 (56)
3.67 (93)
14.6 (371)
18.9 (480)
7.81 (198)
--- 4.5 (114)
10 (254)
4.91 (125)
7.5(191)
8 5/8–11 6(152)
51 2.31 (59)
4.71 (120)
19.2 (488)
24.1 (612)
8.31 (211)
--- 8.75 (222)
10.44 (265)
4.91 (125)
8.5(216)
8 3/4–10 6(152)
1. Valve assemblies have two actuators mounted in tandem.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
19
Table 33: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116 and M9124 Series Non-Spring Return, and M9220 Series Spring Return Electric Actuators with Weather Shield Dimensions, in. (mm)
Valve Size, in.
A B C D E F G H J Lug Data Clearance Required for Actuator Removal
Bolt Circle
No. of Holes
Threads UNC-2B
2 1.81 (46)
1.49 (38)
17.8 (452)
20.9 (531)
11.9 (302)
--- 9 (229)
15.5 (394)
8.25 (210)
4.75(121)
4 5/8–11 6(152)
2-1/2 1.94 (49)
2.01 (51)
18.3 (465)
21.5 (546)
11.9 (302)
--- 9 (229)
15.5 (394)
8.25 (210)
5.5(140)
4 5/8–11 6(152)
3 1.94 (49)
2.64 (67)
18.5 (470)
22.3 (566)
11.9 (302)
--- 9 (229)
15.5 (394)
8.25 (210)
6(152)
4 5/8–11 6(152)
4 2.19 (56)
3.67 (93)
19.3 (490)
23.5 (597)
11.9 (302)
--- 9 (229)
15.5 (394)
8.25 (210)
7.5(191)
8 5/8–11 6(152)
5 2.31 (59)
4.71 (120)
19.8 (503)
24.5 (622)
11.9 (302)
--- 9 (229)
15.5 (394)
8.25 (210)
8.5(216)
8 3/4–10 6(152)
61
1. Valve assemblies have two actuators mounted in tandem.
2.31 (59)
5.66 (144)
20.3 (516)
25.5 (648)
11.9 (302)
--- 9 (229)
15.5 (394)
8.25 (210)
9.5(241)
8 3/4–10 6(152)
Figure 14: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116, M9124 Non-Spring Return and M9220 Spring Return Electric Actuators (With Weather Shield)
FE
H
CD
G
FIG
:2w
ay_e
lec_
ws
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
20
Three-Way VF Series M9000 Electrically Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesValve sizes 2 through 3 in. feature four mounting lugs with a different orientation than what is illustrated in Figure 15 and Figure 16. Valve sizes 4 through 6 in. feature eight mounting lugs with an orientation similar to what is illustrated in Figure 15 and Figure 16.
Three-way valve assemblies are supplied with the INLET side of the valves bolted to the pipe tee. If it is necessary to make changes, always bolt the side of valve marked INLET first to the pipe flange.
For dead-end service, the side of the valve marked INLET should be installed facing pressure when downstream piping will be removed. Placement of a downstream flange is recommended when the valve will be dead-ended for extended periods, in the presence of elevated temperatures, dangerous or expansive fluids, or any combination thereof.
Table 34: Three-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116 and M9124 Series Non-Spring Return Electric Actuators (Less Weather Shield) Dimensions, in. (mm)
Valve Size, in.
A B C D E F G H J K L Lug Data Clearance Required forActuator Removal
Bolt Circle
No. of Holes
Threads UNC-2B
2 1.75 (44.5)
1.5 (38)
13.1 (333)
16.2 (411)
5.75 (146)
12.5 (318)
4.5 (114)
7.14 (181)
4.5 (114)
6.25 (159)
--- 4.75 (121)
4 5/8–11 5(127)
2-1/2 1.88 (47.8)
2.01 (51)
13.6 (345)
17.3 (439)
5.75 (146)
12.5 (318)
4.5 (114)
7.14 (181)
5 (127)
6.88 (175)
--- 5.5 (140)
4 5/8–11 5(127)
3 1.88 (47.8)
2.64 (67)
13.8 (351)
17.6 (447)
5.75 (146)
12.5 (318)
4.5 (114)
7.14 (181)
5.5 (140)
7.39 (188)
--- 6(152)
4 5/8–11 5(127)
4 2.13 (54.0)
3.67 (93)
14.6 (371)
19.2 (488)
5.75 (146)
12.5 (318)
4.5 (114)
7.14 (181)
6.5 (165)
8.63 (219)
--- 7.5 (191)
8 5/8–11 5(127)
5 2.25 (57.2)
4.71 (120)
15.1 (383)
20.3 (516)
5.75 (146)
12.5 (318)
4.5 (114)
7.14 (181)
7.5 (191)
9.75 (248)
--- 8.5 (216)
8 3/4-10 5(127)
6 2.25 (57.2)
5.66 (144)
18.9 (480)
24.6 (625)
8.31 (211)
--- 8.75 (222)
9.7 (246)
8 (203)
10.25 (260)
--- 9.5 (241)
8 3/4-10 5(127)
Figure 15: Three-Way Assemblies: M9116, M9124 Non-Spring Return and M9220 Spring Return Electric Actuators (Less Weather Shield)
JKEH
EH
F
A
G
BChord
SingleDesign
TandemDesign
FIG
:3w
ay_e
lec_
ns
GC D
C D
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
21
Table 35: Three-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9220 Series Spring Return Electric Actuators (Less Weather Shield) Dimensions, in. (mm)
Valve Size, in.
A B C D E F G H J K L Lug Data Clearance Required for Actuator Removal
Bolt Circle
No. of Holes
Threads UNC-2B
2 1.75 (44.5)
1.5 (38)
13.1 (333)
16.2 (411)
7.81 (198)
---
4.5 (114)
10 (254)
4.5 (114)
6.25 (159)
--- 4.75 (121)
4 5/8–11 6(152)
2-1/2 1.88 (47.8)
2.01 (51)
13.6 (345)
17.3 (439)
7.81 (198)
---
4.5 (114)
10 (254)
5 (127)
6.88 (175)
--- 5.5 (140)
4 5/8–11 6(152)
3 1.88 (47.8)
2.64 (67)
13.8 (351)
17.6 (447)
7.81 (198)
---
4.5 (114)
10 (254)
5.5 (140)
7.39 (188)
--- 6(152)
4 5/8–11 6(152)
4 2.13 (54.0)
3.67 (93)
14.6 (371)
19.2 (488)
7.81 (198)
---
4.5 (114)
10 (254)
6.5 (165)
8.63 (219)
--- 7.5 (191)
8 5/8–11 6(152)
5 2.25 (57.2)
4.71 (120)
15.1 (383)
24.3 (617)
8.31 (211)
---
8.75 (222)
10.44 (265)
7.5 (191)
9.75 (248)
--- 8.5 (216)
8 3/4-10 6(152)
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
22
Table 36: Three-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116 and M9124 Series Non-Spring Return, and M9220 Series Spring Return Electric Actuators with Weather Shield Dimensions, in. (mm)
Valve Size, in.
A B C D E F G H J K L Lug Data Clearance Required for Actuator Removal
Bolt Circle
No. of Holes
Threads UNC-2B
2 1.75 (44.5)
1.5 (38)
17.8 (452)
20.9 (531)
11.9 (302)
--- 9(229)
15.5 (394)
--- 6.25 (159)
8.25 (210)
4.75 (121)
4 5/8–11 6(152)
2-1/2 1.88 (47.8)
2.01 (51)
18.3 (465)
21.8 (554)
11.9 (302)
--- 9(229)
15.5 (394)
--- 6.88 (175)
8.25 (210)
5.5 (140)
4 5/8–11 6(152)
3 1.88 (47.8)
2.64 (67)
18.5 (470)
22.3 (566)
11.9 (302)
--- 9(229)
15.5 (394)
--- 7.39 (188)
8.25 (210)
6(152)
4 5/8–11 6(152)
4 2.13 (54.0)
3.67 (93)
19.3 (490)
23.8 (605)
11.9 (302)
--- 9(229)
15.5 (394)
--- 8.63 (219)
8.25 (210)
7.5 (191)
8 5/8–11 6(152)
5 2.25 (57.2)
4.71 (120)
19.8 (503)
24.8 (630)
11.9 (302)
--- 9(229)
15.5 (394)
--- 9.75 (248)
8.25 (210)
8.5 (216)
8 3/4-10 6(152)
6 2.25 (57.2)
5.66 (144)
20.3 (516)
25.8 (655)
11.9 (302)
--- 9(229)
15.5 (394)
--- 10.25 (260)
8.25 (210)
9.5 (241)
8 3/4-10 6(152)
Figure 16: Three-Way Assemblies: M9116, M9124 Non-Spring Return and M9220 Spring Return Electric Actuators (With Weather Shield)
LE
H
CD
G
FIG
:3w
ay_e
lec
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
23
Two-Way Pneumatically-Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesValve sizes 2 through 3 in. feature four mounting lugs. Valve sizes 4 through 8 in. feature eight mounting lugs. Valves 10 in. in size have 12 mounting lugs. Always bolt the side of valve marked INLET first to the pipe flange.
For dead-end service, the side of the valve marked INLET should be installed facing pressure when downstream piping will be removed. Placement of a downstream flange is recommended when the valve will be dead-ended for extended periods, in the presence of elevated temperatures, dangerous or expansive fluids, or any combination thereof.
Figure 17: Single Pneumatic Piston Actuator Assembled on a Two-Way Butterfly Valve
(See Table 37.)
C
D
FIG
:sing
_pne
u_2w
ay
ASleeve
F
H G
BChord
Figure 18: Dual Tandem Pneumatic Piston Actuators Assembled on a Two-Way Butterfly
Valve (See Table 37.)
ASleeve
FIG
:dua
l_Pn
eu_2
way
D
C
F Typical
H
G Typical
BChord
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
24
Table 37: Overall Dimensions of D-3153, D-3244, and D-3246 Series Pneumatic Piston Actuators Assembled on Two-Way VF4000 and VF6000 Series Butterfly Valves, in. (mm)
Valve Size, in.
Actuator A B C D E F G H
2 D-3153 1.81(46)
1.49(38)
3.14 (79.8)
12.84 (326.0)
10.33 (262.4)
14.06 (357)
5.68 (144)
9.06 (230)
2-1/2 1.94(49)
2.01(51)
3.40 (86.4)
13.34 (339)
10.83 (275.0)
14.06 (357)
5.68 (144)
9.06 (230)
3 1.94(49)
2.64(67)
3.77 (95.6)
13.59 (345.0)
11.08 (281)
14.06 (357)
5.68 (144)
9.06 (230)
4 2.19 (55.6)
3.67(93)
4.26 (108.2)
14.37 (364)
11.83 (300)
14.06 (357)
5.68 (144)
9.06 (230)
D-3244 2.19 (55.6)
3.67(93)
4.26 (108.2)
15.41 (391)
12.88 (327)
17.75 (451)
6.70 (170)
11.20 (285)
5 2.31 (58.6)
4.71 (119.6)
4.89 (124.2)
15.91 (404)
13.38 (340)
17.75 (451)
6.70 (170)
11.20 (285)
D-3246 2.31 (58.6)
4.71(119.6)
4.89 (124.2)
15.72 (399)
13.56 (344.5)
22.80 (579)
8.22 (209)
13.67 (347)
6 2.31 (58.6)
5.66 (143.7)
5.41 (137.4)
16.22 (410)
14.06 (357)
22.80 (579)
8.22 (209)
13.67 (347)
8 2.53 (64.3)
7.72 (196)
6.54 (166.0)
16.72 (425)
14.56 (370)
22.80 (579)
8.22 (209)
13.67 (347)
Tandem D-3246
2.53 (64.3)
7.72 (196)
6.54 (166.0)
17.60 (447)
15.44 (392)
22.80 (579)
8.22 (209)
16.44 (418)
10 2.85 (72.4)
9.70 (246.2)
7.83 (198.9)
18.78 (477)
16.62 (422)
22.80 (579)
8.22 (209)
16.44 (418)
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
25
Three-Way Pneumatically-Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesValve sizes 2 through 3 in. feature four mounting lugs. Valve sizes 4 through 8 in. feature eight mounting lugs. Valves 10 in. in size have 12 mounting lugs. Always bolt the side of valve marked INLET first to the pipe flange.
Three-way valve assemblies are supplied with the INLET side of the valves bolted to the pipe tee. If it is necessary to make changes, always bolt the side of valve marked INLET first to the pipe flange.
For dead-end service, the side of the valve marked INLET should be installed facing pressure when downstream piping will be removed. Placement of a downstream flange is recommended when the valve will be dead-ended for extended periods, in the presence of elevated temperatures, dangerous or expansive fluids, or any combination thereof.
Figure 19: Single Pneumatic Piston Actuator Assembled on a Three-Way Butterfly Valve
D
CChord
A
B FIG
:sing
_pne
u_3w
ay
J
H
G
Figure 20: Dual Tandem Pneumatic Piston Actuators Assembled on a Three-Way Butterfly
ValveFI
G:d
ual_
pneu
_3w
ay
FE
D
A
B
CChord
J
H
G Typical
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
26
Table 38: Overall Dimensions of D-3153, D-3244, and D-3246 Series Pneumatic Piston Actuators Assembled on Three-Way VF4000 and VF6000 Series Butterfly Valves, in. (mm)
Valve Size, in.
Actuator A B C D E F G H J
2 D-3153 6.25 (159)
10.75 (273)
1.49 (38) 3.00 (76) 12.84 (326)
10.33 (262)
14.06 (357)
5.68 (144)
11.93 (303)
2-1/2 D-3244 6.88 (175)
11.88 (302)
2.01 (51) 3.50 (89) 14.41 (366)
11.88 (302)
17.75 (451)
6.70 (170)
13.58 (345)
3 7.38 (185)
12.88 (327)
2.64 (67) 3.75 (950
14.66 (372)
12.13 (308)
17.75 (451)
6.70 (170)
14.08 (358)
4 8.36 (219)
15.13 (384)
3.67 (93) 4.50 (114)
15.41 (391)
12.88 (327)
17.75 (451)
6.70 (170)
15.33 (389)
D-3246 8.36 (219)
15.13 (384)
3.67 (93) 4.50 (114)
15.22 (386)
13.06 (332)
22.80 (579)
8.22 (209)
16.58 (421)
5 9.75 (248)
17.25 (438)
4.71 (119.6)
5.00 (127)
15.72 (399)
13.56 (344)
22.80 (579)
8.22 (209)
17.97 (456)
6 10.25 (261)
18.25 (463)
5.66 (143.7)
5.50 (140)
16.22 (410)
14.06 (357)
22.80 (579)
8.22 (209)
18.47 (496)
Tandem D-3246
10.25 (261)
18.25 (463)
5.66 (143.7)
5.50 (140)
16.22 (412)
14.06 (357)
22.80 (579)
8.22 (209)
18.47 (469)
8 11.44 (291)
20.44 (519)
7.72 (196.2)
6.75 (171)
17.60 (447)
15.44 (392)
22.80 (579)
8.22 (209)
19.66 (499)
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
27
Shipping Weights Table 39: Representative Maximum Shipping Weights for VF4000, VF5000, and VF6000 Series Two-Way
Butterfly Valve and Actuator Assemblies1
Valve Size, in.
M9000 Electrically Actuated
Shipping Weight, lb (kg) D-3000 Pneumatically Actuated
Shipping Weight,lb (kg)Without
Weather Shield
With Weather Shield
2 M9116-GGx-2 (+916GGx) 22 (10) 26 (11.8) One D-3153 (+3153) 26 (11.8)
M9220-GGx-3 (+92NGGx)2 24 (10.9) 31 (14.1)
2-1/2 M9116-GGx-2 (+916GGx) 23.5 (10.7) 27.5 (12.5) One D-3153 (+3153) 27 (12.2)
M9220-GGx-3 (+92NGGx)2 25.5 (9.1) 32.5 (14.7)
3 M9116-GGx-2 (+916GGx) 24.5 (11.1) 28.5 (12.9) One D-3153 (+3153) 30 (13.6)
M9220-GGx-3 (+92NGGx)2 26.5 (12) 33.5 (15.2)
4 M9124-GGA-2 (+924GGA) 30 (13.6) 35 (15.9) One D-3244 (+3244) 54 (24.5)
M9220-GGx-3 (+92NGGx)2 35 (15.9) 39 (17.7) One D-3153 (+3153) 44 (20)
Two M9220-GGx-3 (+92NGGx)2 44 (20) 48 (21.8) --- ---
5 M9124-GGA-2 (+924GGA) 34 (15.4) 56 (25.4) One D-3246 (+3246) 89 (40.4)
Two M9124-GGA-2 (2924GGA) 40 (18.1) 60 (27.2) One D-3244 (+3244) 77 (34.9)
Two M9220-GGx-32 (+92NGGx) 48 (21.8) 66 (29.9) --- ---
6 Two M9124-GGA-2 (2924GGA) 46 (20.9) 62 (28.1) One D-3246 (+3246) 129 (58.5)
8 --- --- --- Two D-3246s (23246) 206 (93.4)
One D-3246 (+3246) 138 (62.6)
10 --- --- --- Two D-3246s (23246) 227 (103)
1. The above shipping weights are only approximate, and are based on the heaviest valve, actuator, and accessory combination available for each size.
2. The weights given for M9220 actuated assemblies are for M9220-AGx and M9220-GGx models. For Assemblies with M9220-Bxx On/Off actuators, add 1.2 lbs. (0.55 kg) for single actuator assemblies and 2.4 lbs. (1.1 kg) for tandem actuated assemblies to the weights listed.
Table 40: Representative Maximum Shipping Weights for VF4000, VF5000, and VF6000 Series Three-Way Butterfly Valve and Actuator Assemblies1 (Part 1 of 2)
Valve Size, in.
M9000 Electrically Actuated
Shipping Weight, lb (kg) D-3000 Pneumatically Actuated
Shipping Weight,lb (kg)Without
Weather Shield
With Weather Shield
2 M9116-GGA-2 (+916GGA) 60 (27.2) 63 (28.6) One D-3153 (+3153) 62 (28.1)
M9220-GGx-3 (+92NGGx)2 63 (28.6) 70 (31.8)
2-1/2 M9116-GGA-2 (+916GGA) 69 (31.3) 73 (33.1) One D-3244 (+3244) 82 (37.2)
M9220-GGx-3 (+92NGGx)2 73 (33.1) 80 (36.3)
3 M9116-GGA-2 (+916GGA) 80 (36.3) 84 (38.1) One D-3244 (+3244) 92 (41.7)
M9220-GGx-3 (+92NGGx)2 84 (38.1) 91 (41.3)
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
28
Repair Information .
4 M9124-GGA-2 (+924GGA) 120 (54.4) 124 (56.2) One D-3246 (+3246) 151 (68.5)
Two M9220-GGx-3 (+92NGGx)2 132 (59.9) 136 (61.7) One D-3244 (+3244) 142 (64.4)
5 Two M9124-GGA-2 (2924GGA) 148 (67.1) 151 (68.5) One D-3246 (+3246) 186 (84.3)
6 Two M9124-GGA-2 (2924GGA) 183 (83) 186 (84.4) Two D-3246s (23246) 370 (168)
One D-3246 (+3246) 311 (141)
8 --- --- --- Two D-3246s (23246) 397 (180)
1. The above shipping weights are only approximate, and are based on the heaviest valve, actuator, and accessory combination available for each size.
2. The weights given for M9220 actuated assemblies are for M9220-AGx and M9220-GGx models. For Assemblies with M9220-Bxx On/Off actuators, add 1.2 lbs. (0.55 kg) for single actuator assemblies and 2.4 lbs. (1.1 kg) for tandem actuated assemblies to the weights listed.
Table 40: Representative Maximum Shipping Weights for VF4000, VF5000, and VF6000 Series Three-Way Butterfly Valve and Actuator Assemblies1 (Part 2 of 2)
Valve Size, in.
M9000 Electrically Actuated
Shipping Weight, lb (kg) D-3000 Pneumatically Actuated
Shipping Weight,lb (kg)Without
Weather Shield
With Weather Shield
Table 41: Replacement Electric Spring and Non-Spring Return ActuatorsCode Number DescriptionM9116-AGA-2 Electric Motor Actuator, Non-Spring Return, 140 lb⋅in, Floating Control, 24 VAC/VDC Input, No End
Switches (Cannot be Used in Tandem Configurations)
M9116-AGC-2 Electric Motor Actuator, Non-Spring Return, 140 lb⋅in, Floating Control, 24 VAC/VDC Input, Two End Switches (Cannot be Used in Tandem Configurations)
M9116-GGA-2 Electric Motor Actuator, Non-Spring Return, 140 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, No End Switches
M9116-GGC-2 Electric Motor Actuator, Non-Spring Return, 140 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, Two End Switches
M9124-AGA-2 Electric Motor Actuator, Non-Spring Return, 210 lb⋅in, Floating Control, 24 VAC/VDC Input, No End Switches
M9124-AGC-2 Electric Motor Actuator, Non-Spring Return, 210 lb⋅in, Floating Control, 24 VAC/VDC Input, Two End Switches
M9124-GGA-2 Electric Motor Actuator, Non-Spring Return, 210 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, No End Switches
M9124-GGC-2 Electric Motor Actuator, Non-Spring Return, 210 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, Two End Switches
M9220-AGA-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, Floating Control, 24 VAC/VDC Input, No End Switches
M9220-AGC-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, Floating Control, 24 VAC/VDC Input, Two End Switches
M9220-BGA-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, On/Off Control, 24 VAC/VDC Input, No End Switches
M9220-BGC-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, On/Off Control, 24 VAC/VDC Input, Two End Switches
M9220-GGA-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, No End Switches
M9220-GGC-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, Two End Switches
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
29
Table 42: Replacement Pneumatic Spring Return ActuatorsCode Number DescriptionD-3153-5120 Pneumatic Piston Actuator with Positioner, for Use with 2, 2-1/2, or 3 in. 175 or 150 psig Valves or
4 in. 50 psig Valves
D-3153-5130 Pneumatic Piston Actuator without Positioner, for Use with 2, 2-1/2, or 3 in. 175 or 150 psig Valves or 4 in. 50 psig Valves
D-3244-5100 Pneumatic Piston Actuator with Positioner, for Use with 4 in. 175 or 150 psig Valves or 5 in. 50 psig Valves
D-3244-5110 Pneumatic Piston Actuator without Positioner, for Use with 4 in. 175 or 150 psig Valves or 5 in. 50 psig Valves
D-3246-5100 Pneumatic Piston Actuator with Positioner, for Use with 5 or 6 in. 175 or 150 psig Valves or 6, 8, or 10 in. 50 psig Valves
D-3246-5110 Pneumatic Piston Actuator without Positioner, for Use with 5 or 6 in. 175 or 150 psig Valves or 6, 8, or 10 in. (Requires Two Actuators) 50 psig Valves
Table 43: Mounting Kits 1 for Field Mounting D-3000 Series, Pneumatic Piston Actuators on Two-Way VF4000 and VF6000 Series Butterfly Valves
Code Number DescriptionVF4-D3000-201 D-3153-51x0 Actuator Mounting Kit for 2, 2-1/2, or 3 in. 175 psig Valves
VF4-D3000-202 D-3513-51x0 Actuator Mounting Kit for 4 in. 50 psig Valves
VF4-D3000-203 D-3244-51x0 Actuator Mounting Kit for 4 in. 175 psig and 5 in. 50 psig Valves
VF4-D3000-204 D-3246-51x0 Actuator Mounting Kit for 5 in. for 175 psig Valves
VF4-D3000-205 D-3246-51x0 Actuator Mounting Kit for 6 in. 50 or 175 psig Valves
VF4-D3000-206 D-3246-51x0 Actuator Mounting Kit for 8 in. 50 psig Valves
VF4-D3000-207 D-3246-51x0 Actuator Mounting Kit for 8 in. 175 psig Valves (Includes Parts for Mounting Two Actuators)
VF4-D3000-208 D-3246-51x0 Actuator Mounting Kit for 10 in. 50 psig Valves (Includes Parts for Mounting Two Actuators)
1. The mounting kits contain a mounting bracket, crankarm, sleeve adaptor, a clevis kit, and all necessary hardware for completing actuator field mounting D-3000 Series Actuator to bare stem VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).
Table 44: Conversion Kits for Changing the Configuration of VF4000 and VF6000 Series Three-Way Valve Assemblies with D-3000 Series Pneumatic Piston Actuators (Part 1 of 4)
Valve Size Existing Assembly Desired Assembly Conversion Kit1
2 in. VF4831AD VF4831AE or VF4831AF VF4-D3000-301
VF4831AG VF4-D3000-302
VF4831AE VF4831AD VF4-D3000-303
VF4831AF 2
VF4831AG VF4-D3000-304
VF4831AF VF4831AD VF4-D3000-303
VF4831AE 2
VF4831AG VF4-D3000-304
VF4831AG VF4831AD VF4-D3000-305
VF4831AE or VF4831AF VF4-D3000-301
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
30
2-1/2 in. VF4831BD VF4831BE or VF4831BF VF4-D3000-301
VF4831BG VF4-D3000-302
VF4831BE VF4831BD VF4-D3000-303
VF4831BF 2
VF4831BG VF4-D3000-304
VF4831BF VF4831BD VF4-D3000-303
VF4831BE 2
VF4831BG VF4-D3000-304
VF4831BG VF4831BD VF4-D3000-305
VF4831BE or VF4831BF VF4-D3000-301
3 in. VF4831CD VF4831CE or VF4831CF VF4-D3000-306
VF4831CG VF4-D3000-307
VF4831CE VF4831CD VF4-D3000-308
VF4831CF 2
VF4831CG VF4-D3000-309
VF4831CF VF4831CD VF4-D3000-308
VF4831CE 2
VF4831CG VF4-D3000-309
VF4831CG VF4831CD VF4-D3000-310
VF4831CE or VF4831CF VF4-D3000-306
Table 44: Conversion Kits for Changing the Configuration of VF4000 and VF6000 Series Three-Way Valve Assemblies with D-3000 Series Pneumatic Piston Actuators (Part 2 of 4)
Valve Size Existing Assembly Desired Assembly Conversion Kit1
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
31
4 in. VF4831DD VF4831DE or VF4831DF VF4-D3000-306
VF4831DG VF4-D3000-307
VF4831DE VF4831DD VF4-D3000-308
VF4831DF 2
VF4831DG VF4-D3000-309
VF4831DF VF4831DD VF4-D3000-308
VF4831DE 2
VF4831DG VF4-D3000-309
VF4831DG VF4831DD VF4-D3000-310
VF4831DE or VF4831DF VF4-D3000-306
VF6831DD VF6831DE or VF6831DF VF4-D3000-306
VF6831DG VF4-D3000-307
VF6831DE VF6831DD VF4-D3000-308
VF6831DF 2
VF6831DG VF4-D3000-309
VF6831DF VF6831DD VF4-D3000-308
VF6831DE See Note
VF6831DG VF4-D3000-309
VF6831DG VF6831DD VF4-D3000-310
VF6831DE or VF6831DF VF4-D3000-306
5 in. VF4831ED VF4831EE or VF4831EF VF4-D3000-311
VF4831EG VF4-D3000-312
VF4831EE VF4831ED VF4-D3000-313
VF4831EF 2
VF4831EG VF4-D3000-314
VF4831EF VF4831ED VF4-D3000-313
VF4831EE 2
VF4831EG VF4-D3000-314
VF4831EG VF4831ED VF4-D3000-315
VF4831EE or VF4831EF VF4-D3000-311
VF6831ED VF6831EE or VF6831EF VF4-D3000-311
VF6831EG VF4-D3000-312
VF6831EE VF6831ED VF4-D3000-313
VF6831EF 2
VF6831EG VF4-D3000-314
VF6831EF VF6831ED VF4-D3000-313
VF6831EE 2
VF6831EG VF4-D3000-314
VF6831EG VF6831ED VF4-D3000-315
VF6831EE or VF6831EF VF4-D3000-311
Table 44: Conversion Kits for Changing the Configuration of VF4000 and VF6000 Series Three-Way Valve Assemblies with D-3000 Series Pneumatic Piston Actuators (Part 3 of 4)
Valve Size Existing Assembly Desired Assembly Conversion Kit1
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
32
6 in. VF4831FD VF4831FE or VF4831FF VF4-D3000-311
VF4831FG VF4-D3000-312
VF4831FE VF4831FD VF4-D3000-313
VF4831FF 2
VF4831FG VF4-D3000-314
VF4831FF VF4831FD VF4-D3000-313
VF4831FE 2
VF4831FG VF4-D3000-314
VF4831FG VF4831FD VF4-D3000-315
VF4831FE or VF4831FF VF4-D3000-311
VF6831FD VF6831FE or VF6831FF VF4-D3000-311
VF6831FG VF4-D3000-312
VF6831FE VF6831FD VF4-D3000-313
VF6831FF 2
VF6831FG VF4-D3000-314
VF6831FF VF6831FD VF4-D3000-313
VF6831FE 2
VF6831FG VF4-D3000-314
VF6831FG VF6831FD VF4-D3000-315
VF6831FE or VF6831FF VF4-D3000-311
8 in. VF6831GD VF6831GE or VF6831GF VF4-D3000-316
VF6831GG VF4-D3000-317
VF6831GE VF6831GD VF4-D3000-318
VF6831GF 2
VF6831GG VF4-D3000-319
VF6831GF VF6831GD VF4-D3000-318
VF6831GE 2
VF6831GG VF4-D3000-319
VF6831GG VF6831GD VF4-D3000-320
VF6831GE or VF6831GF VF4-D3000-316
1. The conversion kit includes the necessary levers and threaded rod. These kits are designed for VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).
2. A conversion kit is not required when converting between Styles E and F; simply switch the valve with the actuator and bracket to the opposite flange, and adjust the valves to the desired normally open and normally closed positions
Table 44: Conversion Kits for Changing the Configuration of VF4000 and VF6000 Series Three-Way Valve Assemblies with D-3000 Series Pneumatic Piston Actuators (Part 4 of 4)
Valve Size Existing Assembly Desired Assembly Conversion Kit1
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
33
Table 45: D-3000 Replacement BracketsPneumatic Actuator
Bracket Kit1
D-3153 VF4-D3000-601
D-3244 VF4-D3000-602
D-3246 VF4-D3000-603
Two D-3246 VF4-D3000-604
1. For VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).
Table 46: D-3000 Replacement CrankarmsPneumatic Actuator Crankarm
Kit1
Master Lever, Three-Way, Styles D and G and Normally Open Two-Way with Tandem D-3246
VF4-D3000-610
Master Lever, Three-Way, Styles E and F and Normally Closed Two-Way with Tandem D-3246
VF4-D3000-611
Slave Lever, Three-Way Style D VF4-D3000-612
Slave Lever, Three-Way Style E and F
VF4-D3000-613
Slave Lever, Three-Way Style G VF4-D3000-614
Two-Way with One D-3000 Series Actuator
VF4-D3000-615
1. For VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).
Table 47: D-3000 Replacement Sleeve AdaptorsValve Size Sleeve Adaptor
Kit1
2, 2-1/2, and 3 in. VF4-D3000-620
4 and 5 in. VF4-D3000-621
6 in. VF4-D3000-622
8 in. VF4-D3000-623
1. For VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).
Table 48: Clevis Kits for Field Repair of D-3153, D-3244, and D-3246 Series Pneumatic Actuators
Pneumatic Actuator Clevis Kit1
D-3153 VF4-D3000-630
D-3244 VF4-D3000-631
D-3246 VF4-D3000-632
Three-Way Tandem Actuators VF4-D3000-633
1. Clevis kit includes clevis, clevis pin, and clevis hair pin. These kits are designed for VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).
Table 49: Mounting Kits for Field Mounting M9000 Series Electric Actuators on Two-Way VF4000 Series Butterfly Valves
Mounting Kit Code Number1
Valve Size Actuator
VF4-M9000-120 2, 2-1/2, and 3 in. M9116
VF4-M9000-121 4 and 5 in. M9124
VF4-M9000-122 6 in. Tandem M9124
VF4-M9000-123 2, 2-1/2, and 3 in. M9220
VF4-M9000-124 4 in. M9220
VF4-M9000-125 5 in. Tandem M9220
1. Mounting kit includes all brackets and hardware to mount M9000 Series Actuators to a bare stem VF4000 Series Valve date coded 0501 or later (manufactured 2005 or later).
Table 50: Mounting Kits for Field Mounting M9000 Series Electric Actuators on Three-Way VF4000 Series Butterfly Valves
Mounting Kit Code Number1
Valve Size Actuator
VF4-M9000-130 2, 2-1/2 and 3 in. M9116
VF4-M9000-131 4 in. M9124
VF4-M9000-132 5 in. Tandem M9124
VF4-M9000-133 6 in. Tandem M9124
VF4-M9000-134 2, 2-1/2, and 3 in. M9220
VF4-M9000-135 4 in. Tandem M9220
1. Mounting kit includes all brackets and hardware to mount M9000 Series Actuators to a bare stem VF4000 Series Valve date coded 0501 or later (manufactured 2005 or later).
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
34
Table 51: Weather Shield Kits for Field Installation on Two-Way VF4000 Series Valves with M9000 Series Electric Actuators
Mounting Kit Code Number1
1. Weather shield kit includes weather shield and all necessary hardware for installation on an existing VF4000 Series Valve and M9000 Series Actuator assembly date coded 0501 or later (manufactured 2005 or later).
Valve Size Actuator
VF4-M9000-140 2, 2-1/2, and 3 in. M9116
VF4-M9000-141 4 and 5 in. M9124
VF4-M9000-142 6 in Tandem M9124
VF4-M9000-143 2, 2-1/2, and 3 in. M9220
VF4-M9000-144 4 in. M9220
VF4-M9000-145 5 in. Tandem M9220
Table 52: Weather Shield Kits for Field Installation on Three-Way VF4000 Series Valves with M9000 Series Electric Actuators
Mounting Kit Code Number1
1. Weather shield kit includes weather shield and all necessary hardware for installation on an existing VF4000 Series Valve and M9000 Series Actuator assembly date coded 0501 or later (manufactured 2005 or later).
Valve Size Actuator
VF4-M9000-150 2, 2-1/2, and 3 in. M9116
VF4-M9000-151 4 in. M9124
VF4-M9000-152 5 in. Tandem M9124
VF4-M9000-153 6 in. Tandem M9124
VF4-M9000-154 2, 2-1/2, and 3 in. M9220
VF4-M9000-155 4 in. Tandem M9220
Table 53: M9000 Replacement BracketsActuator Code Number1
M9116 or M9124 VF4-M9000-640
Tandem M9124 (Also Requires VF4-M9000-640)
VF4-M9000-641
M9220 VF4-M9000-642
Tandem M9220 (Also Requires VF4-M9000-642)
VF4-M9000-643
M9116 or M9124 with Weather Shield
VF4-M9000-644
M9220 with Weather Shield VF4-M9000-645
1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).
Table 54: Replacement Levers for Three-Way Valve Assemblies with M9000 Series Actuators
Valve Size Code Number1
2, 2-1/2, and 3 in. VF4-M9000-650
4 and 5 in. VF4-M9000-651
6 in. VF4-M9000-652
1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).
Table 55: Replacement Couplers for Two-Way Valve Assemblies with M9000 Series Actuators
Valve Size
Actuator Code Number1
2, 2-1/2, and 3 in.
M9116 or M9220 VF4-M9000-660
4 and 5 in. M9124 VF4-M9000-661
4 in. M9220
6 in. Tandem M9124 VF4-M9000-662
5 in. Tandem M9220 VF4-M9000-663
1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
35
Technical Specifications
Table 56: Replacement Couplers for Three-Way Valve Assemblies with M9000 Series Actuators
Valve Size
Actuator Code Number1
2, 2-1/2, and 3 in.
M9116 or M9220 VF4-M9000-670
4 in. M9124 VF4-M9000-671
5 in. Tandem M9124 VF4-M9000-672
4 in. Tandem M9220
6 in. Tandem M9124 VF4-M9000-673
1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).
Table 57: Rod End Kit for Three-Way Valve Assemblies with M9000 Series Actuators
Valve Size Code Number1
Three-Way, All Sizes VF4-M9000-680
1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves1 (Part 1 of 2)Service Hot, Chilled, or Condenser Water, and 50/50 Glycol Solutions
(Not Designed for Use in Steam Applications)
Models and Ordering Data See Table 5 through Table 30.
Body Styles and Sizes Two-Way and Three-Way, 2 through 10 in., Fully Lugged
Fluid Temperature Limits -30 to 250°F (-34 to 121°C)
Maximum Closeoff Pressure
See Table 9 through Table 30. (All Valves are Rated for Dead-End Service; Maximum Dead-End Pressure Rating is 150 psig)
Maximum Fluid Velocity 30 ft/Second (9 m/Second)
Rangeability 80:1 Minimum
Leakage Bubble Tight, Bidirectional Shutoff Rated for Dead-End Service (Uni-Directional); Inlet Must Face Pressure
Flow Characteristics Modified Equal Percentage (See Figure 2.)
Flow Coefficients (Cv) See Table 2 through Table 4.
Materials Body Cast Iron, ASTM A126 CL B
Tee (Three-Way Valves Only)
Cast Iron
Disk Aluminum Bronze, ASTM B148
Seal and Liner Ethylene Propylene Diene Monomer (EPDM)
Stem 416 Stainless Steel
Bearings Reinforced Polytetrafluoroethylene (RPTFE)
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
36
Ambient Temperature Limits
Storage -20 to 150°F (-29 to 66°C); Preferably 40 to 85°F (4 to 29°C)
Operating Spring Return Actuator (M9220 Series): -40 to 131°F (-40 to 55°C)
Non-Spring Return Actuator (M91xx Series): -4 to 122°F (-20 to 50°C)
Weather Shield Rating NEMA 4
Valve and Actuator Assembly Shipping Weights
See Table 39 and Table 40.
Repair Parts Valve None available; for a Replacement Valve Body, configure the appropriate code number from the first eight fields in Table 5.
Actuators and Brackets
See Table 41 through Table 57.
1. Refer to the appropriate actuator product bulletin for actuator specifications. All information included in this product bulletin is for valves date coded 0501 or later (manufactured 2005 or later).
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves1 (Part 2 of 2)
Published in U.S.A. www.johnsoncontrols.com
VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin
37
Controls Group507 E. Michigan StreetMilwaukee, WI 53202
Metasys® is a registered trademark of Johnson Controls, Inc.All other marks herein are the marks of their respective owners.
© 2007 Johnson Controls, Inc.