VES Fire Detection Systems: Product Guide

16
Product Guide FIRE DETECTION SYSTEMS

description

VES Fire Detection Systems was founded with one mission: to give dealers a comprehensive, cost-effective means of providing fire detection networks for corporate, educational, government and retail campuses of any size using 21st century technologies.

Transcript of VES Fire Detection Systems: Product Guide

Page 1: VES Fire Detection Systems: Product Guide

Product Guide

FIREDETECTIONSYSTEMS

Page 2: VES Fire Detection Systems: Product Guide

Available with one or two detection loops capable of hosting up to 252 devices. Elite RS uses leading edge microprocessor based electronics to provide a flexible control system with high reliability and integrity.

Suitable for all small to medium sized fire detection systems, Elite RS control panels can be expanded and networked to become part of much larger systems if the need arises, therefore providing a future proof solution for any installation.

With its large graphical display and ergonomic button and indicator layout, the Elite RS control panel is simple and straightforward to understand for installers, commissioning engineers and end users alike.

Available in Red or Gray 2 programmable NAC circuits 3 programmable relays 5.25A power supply Large 320 Character graphic display Up to 512 additional programmable I/O via I/O modules Powerful, network wide cause and effects Sensitivity adjustment and Drift Compensation Can be networked with other Elite control panels Compatible with eVIEW Annunciator Stores the last 1000 events Compact, stylish enclosure Multi language option available 4 - Internal NAC synchronization protocols

Also available:VF1054 1 loop expansion board VF1071 Trim ring VF1170 Network Card

Elite RSAnalog Addressable Fire Control Panels(1 or 2 Loops)

VES was founded with one mission: to give dealers a comprehensive, cost-effective means of providing fire detection networks for corporate, educational, government and retail campuses of any size using 21st century technologies.

Building on our success in the Engineered Systems Market we are introducing our new Elite range of fire detection products including the all new Elite RS control panel. With Elite, VES enables Dealers to compete in the small systems market, without compromising on features or expandability. Rest easy, knowing that our systems will grow with you, from a simple 32 point system to a 32,000 point system. No matter what the scope of your installation, all of the VES panels program the same way, with easy-to-use software.

Our state-of-the-art line of sensors and modules are easy to install, requiring no special programming tool. Sensor heads assume the address of the base, for easy swap-outs and all other modules use simple DIP switch programming for address and feature selection.

Whether you need a single product line to satisfy small installations or the ability to offer larger system solutions including multi-panel networking, VES has the product range. Remember all VES panels program the same way, with easy-to-use, easy-to-learn configuration software.

About VES Elite

APPROVED

All VES controls are UL 9th Edition listed

and FM approved

1 Loop VF0850-10 Red

2 LoopsVF0860-10 Red

Page 3: VES Fire Detection Systems: Product Guide

Available with two or four detection loops capable of hosting up to 504 devices. Elite uses leading edge microprocessor based electronics to provide a flexible control system with high reliability and integrity.

Suitable for all medium sized fire detection systems, Elite control panels can be expanded and networked to become part of much larger systems if the need arises, therefore providing a future proof solution for any installation.

With its large graphical display and ergonomic button and indicator layout, the Elite control panel is simple and straightforward to understand for installers, commissioning engineers

and end users alike.

Available in Red or Gray 4 programmable NAC circuits 5 programmable relays 5.25A power supply Large 320 Character graphic display Up to 512 additional programmable I/O via I/O modules Powerful, network wide cause and effects Sensitivity adjustment and Drift Compensation Can be networked with other Elite control panels Compatible with eVIEW Annunciator Stored 500 last events in event log Compact, stylish enclosure Multi language option available

Elite Analog Addressable Fire Control Panels (2 or 4 Loops)

4 LoopsVF1480-10 Red

Also available:VF1053 2 loop expansion board VF1070 Trim ring VF1170 Network Card

Up to 64 nodes High integrity protocol Fully secure against short or open circuit faults Simple 2-wire loop connection Network wide test and disablement functions Network wide cause and effect logic Flexible configuration options Panels configurable to act on network events or not, as required

VF1170 - Network Card

2 LoopsVF1460-10 Red

Page 4: VES Fire Detection Systems: Product Guide

The eVIEW fire alarm annunciator provides a simple and convenient method of extending the controls and indications of the Elite fire alarm control panel to other locations.

The large, graphic LCD display and high brightness LED indicators duplicate the indications on the Elite fire alarm control panel at up to 15 additional locations via a simple, two-wire serial data connection.

Available in Red or Gray Up to 15 annunciators can be connected to each Elite RS fire control panel Large 320 Character graphic display High brightness LED indications Internal Sounder Replicates all panel controls Simple, two-wire serial connection plus 24VDC Low power consumption Multi language options Connection supervised by Elite fire control panel Flush Mounting Kit available (VF1173)

The eMATRIX system uses flexible, optic light guides to illuminate areas on a floor plan, laid over a high resolution grid. This unique system dispenses completely with wiring and enables indicators to be moved, removed or added on site without the need for any wiring.

All indicators can be configured to operate upon any event type and at point, zone or group level via the powerful and intuitive Loop Explorer configuration.

Available in Red or Gray Up to 504 LED’s can be controlled from any Elite panel Select up to 12 printed colors (not including background and building outline) Available in a range of standard enclosures to suit any applications Custom sized units can be made upon request Choice of Red, Green or Yellow LED’s eMATRIX can easily be re-configured or upgraded on site with minimal cost and effort Special Order Item

eVIEWSerial LCD Annunciator

eMATRIXConfigurable Floor Plan Mimic Annunciator

Enclosure sizes: AM2: 14.5” Wide x 12.2” High x 3.5” Deep, Max. number of LED’s = 40AM3: 14.5” Wide x 18.9” High x 4.25” Deep, Max. number of LED’s = 72AM4: 14.5” Wide x 24” High x 5” Deep, Max. number of LED’s = 88

VF1172-10 Red

Page 5: VES Fire Detection Systems: Product Guide

VF1171 16 Channel Input/Output Board

To add more I/O capablity to the extensive options already offered by the Elite control panel, up to thirty two, sixteen channel I/O boards may be connected.

When using a simple two wire RS485 communications protocol, these boards may be mounted locally to the control panel or distibuted on a bus up to 3,900 feet long by using a suitable cable.

The flexibility of these boards is further enhanced by the fact that each of the channels is configurable as either an input or and output.

16 channels Each channel configurable as input or output Inputs opto-isolated Outputs open collector transistor Simple 2 wire connection to control panel Up to 32 boards supported per panel (512 Input/Output Channels) Inputs and outputs configurable as per field devices Full cause and effects on all inputs and outputs Multi drop RS485 communications Can be used with other Elite I/O modules on the same panel

The VF3033 and VF3034 series pull stations are operated by pulling the handle marked “PULL” on the front of the station as far down as it will go. At that point, the station will lock in place and is easily visible from up to 50 feet. The activation handle is reset by opening the station with the key, placing the handle in the normal upright position and relocking the station.

On the dual action, the push bar rotates inward allowing the “PULL” handle to be grasped and operated by a single hand. A VF5608 Mini Switch Monitor is an integrated component of this assembly allowing user flexibility in assigning its own unique Signaling Line Circuit (SLC) loop address.

Single or Dual Action Gold Plated Alarm Contacts Surface or Weatherproof back boxes available. Status LED to indicate device operational state SLC wiring easily attached with screw compression plates

VF3033/ VF3034Single Action and Dual ActionAddressable Pull Station

Page 6: VES Fire Detection Systems: Product Guide

VF5601Photoelectric Smoke Sensor Head 5 programmable response modes Drift compensation Two Status LEDs for 360° visibility of alarm status Address is set by X-Pert card and is stored in base

VF5600Ionization Smoke Sensor Head 5 programmable response modes Drift compensation Address is set by X-Pert card and is stored in base Two Status LEDs for 360° visibility of alarm status

VF5603Multisensor Detector Head 5 programmable response modes Combines photo smoke and heat value for enhanced detection performance and false alarm reduction Address is set by X-Pert addressing and is stored in the sensor base Rate of rise heat option Drift compensation Two Status LEDs for 360° visibility of alarm status

VF5602Heat Detector Head 5 programmable response modes Address is set by X-Pert card and is stored in base Fixed point or rate of rise function Two Status LEDs for 360° visibility of alarm status Programmable Range 135° - 190° (F)

Page 7: VES Fire Detection Systems: Product Guide

VF5632E-Z Fit Base The E-Z fit base is a low profile 6” mounting base for detectors High degree of protection against unauthorized removal

VF4990

Aux Powered Sounder Base Compatible panel silence functions Sync network “self tests” to ensure synchronized output if “upstream” sync signal is lost Sounders will operate in “failsafe” mode if the sync network is compromised Continuous or Temporal output with Sync module available to sync multiple temporal units

VF5635 Low Power Relay BaseThe VF5635 Low Power Relay Base incorporates a low power relay to control field equipment such as automatic door closers

Gives a set of voltage free contacts controlled by the remote output of a detector Draws negligible current

VF5633 Isolating BaseThe VF5633 Isolating Base sense and detects short circuit faults on SLC loops

Up to 20 devices may be installed between isolating bases XPERT addressing Accommodates a sensor head.

VF5640Blank XPERT CardA Universal address card supplied with all bases. Using a coding guide, pips are removed to set the address of the inserted detector.

Simplifies and speed up installation and commissioning Used patented, proven technology Address remains the same, no matter how often detectors are replaced

Page 8: VES Fire Detection Systems: Product Guide

VF5664 Dual Input Module Three input states per input - “normal”, “fault” and “alarm” Two visible LEDs Fast response time Mounts on 2-gang or 4x4 box 2 Individual inputs on one module Class A or Class B input configuration

VF5665 Input/ Output Module Provides a single-pole output, supervised input and a non-supervised input Visible LED Fast response time Mounts on 2-gang or 4x4 box Class A or Class B input configuration

VF5666

Supervised Output Module Allows sounders to be operated continuously or be pulsed, 1 second on, 1 second off Can also be used for public address speakers Visible LED Can be used for remote NAC circuits or boosters.

VF5667 Relay Output Module The Relay Output Module provides a single 2-pole changeover relay Can be placed anywhere on loop Visible LED

VF5663 Input Module Three input states - “normal”, “fault” and “alarm” One visible LED Fast response time Mounts on 2-gang or 4x4 box Class A or Class B input configuration

Page 9: VES Fire Detection Systems: Product Guide

VF5608

Mini Input Module Designed for use where space is limited LED status indication (Yellow - Fault, Green - Polling, Red - Alarm) DIN Rail Mountable

VF5660 Pigtail Input Module Three input states - “normal”, “fault” and “alarm” LED depicting module status condition Designed to fit into equipment with limited space Monitors equipment where a fast response is required Class A or Class B input capability

VF5605 IsolatorThe VF5605 Isolator is placed at intervals on the loop and ensures that, in the case of a short circuit, only the section between the isolators will be affected. When the short circuit is removed, the isolators automatically restore power and data to the isolated section.

Detects wiring short circuits using patented technology Minimizes disruption from short circuits Automatic de-isolation on short circuit removal Up to 20 devices may be installed between isolators

VF4992Duct Smoke Detector Patent pending “Test Port Valve” allows for aerosol smoke testing without cover removal Clear cover fitted with four captive “No-Tools Required” thumbscrews In-line terminal block for easier wiring More wiring space than competitive models Built in alarm relay test switch Unit includes green pilot and red alarm visual indicators External mounting tabs do not require cover removal to install One set of 15A form “C” alarm contacts

VF5634 Isolator BaseThe VF5634 Isolator Base is unique and designed to only accept the Isolator

Only accepts Isolators

Page 10: VES Fire Detection Systems: Product Guide

VF071x

Fire Document Enclosure Matches design and color scheme for standard Elite control panels Standard enclosure holds 50 sheets of paper, deep version holds 100 sheets Key lockable, Tamper included Designed for versatility Choice of small or large capacity enclosure in Red or Gray The “Doc Box” also doubles up as a Key Box, providing 7 easily accessible formed key hooks

VF0710-xx* StandardVF0711-xx* DeepVF0712-xx* Standard w/TamperVF0713-xx* Deep w/Tamper*xx = 10 (Red) or 40 (Gray)

VF073x

Ancillary Enclosure The Ancillary Enclosure is designed to provide an organized and secure mounting enclosure for I/O cards and SLC devices. The Ancillary Enclosure is manufactured in three different sizes, two different colours and with a tamper option. The Ancillary Enclosure is customized with mounting requirements and multiple conduit entries to fit module configurations depicted in the table below. A combination of SLC devices, I/O boards, din rail and PSU can be achieved. Available in Red (-10) or Gray (-40).

VF0730-xx* 14.5”W x 12.2”H x 3.4”DVF0731-xx* 14.5”W x 18.9”H x 4.25”DVF0732-xx* 14.5”W x 24”H x 5”D* xx = 10 (Red) or 40 (Gray)

Chassis plate part number: VF0752-00 Auxiliary Enclosure Device Plate, Large Enclosure VF0751-00 Auxiliary Enclosure Device Plate, Medium Enclosure VF0750-00 Auxiliary Enclosure Device Plate, Small Enclosure

Horns and StrobesThe VES series of notification appliances feature a sleek modern design that will please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction.

Sleek modern aesthetics Finger slide switches Voltage test points Multiple voltages 3 audible settings 90, 95, 99 dB 8 Candela settings: Wall - 15 / 1575 / 30 / 75 / 95 / 110 / 135 / 185 Ceiling - 15 / 30 / 60 / 75 / 95 / 115 / 150 / 177 Universal mounting base - Ceiling and wall mounts to 5 backbox types Environmentally friendly - Low current draw Compatible with UL “Regulated Voltage” using filtered DC or unfiltered VRMS input voltage

VF4672-30

VF4670-10

VF4674-10

VF4675-30

VF4670-10 Horn Strobe - Square - RedVF4670-30 Horn Strobe - Square - WhiteVF4671-10 Horn Strobe - Round - RedVF4671-30 Horn Strobe - Round - WhiteVF4672-10 Strobe - Square - RedVF4672-30 Strobe - Square - WhiteVF4673-10 Strobe - Round - RedVF4673-30 Strobe - Round - WhiteVF4674-10 Horn - Square - RedVF4674-30 Horn - Square - WhiteVF4675-10 Horn - Round - RedVF4675-30 Horn - Round - White

Page 11: VES Fire Detection Systems: Product Guide

Elite - Network System Schematic

Ether/DACT

Virtual Panel®

RS232

Loop 1 Loop 2 Loop 3 Loop 4

Loop 1

i

HighIntegrity

ConfigurableNetwork

RS485 I/O BUS

Up to 64 Panelscan be added to thenetwork.

RS232

RS2

32

RS4

85 24V DC

HighIntegrity

ConfigurableNetwork

EliteControl

Panel

Elite RSControl

Panel

Elite RSControl

Panel

(if fitted)

(if fitted)

iEach loop is capableof hosting up to 126devices.

iEach loop is capableof hosting up to 126devices.

iA mixture of up to 32devices (includingeVIEW & eMATRIX boards)can be fitted to each panelon the RS485 serialinterface. The maximumnumber of eVIEW panelson a single RS485 serialinterface is 15.

iControlpanels aresupplied with1, 2 or 4 detectionloops .

24V DC

Loop 2

eVIEWAnnunciator

eVIEWAnnunciator

24V DC

I/OBoard

RS232

RS485

eMATRIX

Network CardRequired

Network CardRequired

Network CardRequired Network Card

Required

EliteControl

Panel

Page 12: VES Fire Detection Systems: Product Guide

Maximum System Configuration Up to 256 Distributed Panels (VF9755) Up to 2028 monitor and control points

The VES VoiceAlert High Rise Evacuation System operates in conjunction with the Elite Fire Alarm Control Panel (FACP) in a building to provide automatic response to life safety emergencies. The VoiceAlert system includes all necessary features to provide an effective voice evacuation system. The VoiceAlert can be custom configured to satisfy the needs of any high rise application.

True Multiplex 6 Channel Distributed Audio Integrated Fire Phone, Area of Rescue and Fan & Damper Control capability Modular System - components added as needed Integrated 2 Channel Digital Message Repeater Live Microphone Page to any zone Fast RS-485 Communication Protocol Easy Installation and Operation Natural Sound Voice Recordings Built in Alarm and Alert Signals Up to 4 Minute Message Capacity Works with 12VDC or 24VDC Fire Alarm Panel Listed with for use with the Elite FACP 3 Minute Message Restart on Microphone Key Fully Supervised

Operation - Basic System includes

Master Panel (VF9700) Master Mic Control 16 switch control points Dual Channel DMR High speed communication loop

Optional Integrated Fire Phone Area-of-Rescue

VoiceAlert Voice Evacuation System

VF9700 Master Panel

VF9775 Distributed Panel

Distributed Panel (VF9755)* 4 Output Zones (may be configured for 8) Dual Channel Audio Interface Dual Channel Amplification

Master Panels

VF9720 16 Zones VF9740 16 Zones with Fire PhoneVF9722 32 ZonesVF9742 32 Zones with Fire PhoneVF9724 48 Zones VF9744 48 Zones with Fire PhoneVF9726 64 Zones VF9746 64 Zones with Fire PhoneVF9728 80 Zones VF9748 80 Zones with Fire PhoneVF9730 96 Zones VF9750 96 Zones with Fire PhoneVF9751 112 ZonesVF9752 128 Zones

Distributed Panels - Single Channel

VF9760 25WattVF9778 25Watt with Fire PhoneVF9762 50WattVF9768 50Watt with Fire PhoneVF9764 100WattVF9770 100Watt with Fire PhoneVF9788 100Watt, 16 Audio Channels with Fire Phone

Distributed Panels - Dual Channel

VF9774 50Watt VF9780 50Watt with Fire PhoneVF9776 100WattVF9782 100Watt with Fire PhoneVF9798 200Watt , 4 Audio Channels with Fire Phone VF9793 200Watt, 16 Audio Channels with Fire Phone

*Number of distributed panels to be determined by building specifications

Page 13: VES Fire Detection Systems: Product Guide

VF9511Portable Handset Color - Red 6 mount in VF9510 cabinet Can be used with telephone jack plate (VF9512)

VF9510Telephone Cabinet Holds 6 VF9511 Available in Red or Gray Size: Surface / Semi-Flush Mount / Key Lock 27 x 14-1/2 x 4” h-w-d

VF9514Fire Phone Station Coil cord / Thumb Turn Latch Available in Red or Gray Size: Surface / Semi-Flush Mount 12-3/4 x 7-1/4 x 3-3/4” h-w-d

VF9517Warden Station Armored cable / Thumb Turn Latch Available in Red or Gray Size: Surface / Semi-Flush Mount 12-3/4 x 7-1/4 x 3-3/4” h-w-d

VF9512Telephone Jack Brushed Stainless Steel Single Gang Plate

Fire Phone accessories give the VMX system two-way communication capability. Fire Phone jacks are mounted on a single gang plate. Fixedtelephone and warden stations are available in surface/ semi-flush mount cabinet with a thumb-turn-latch.

VoiceAlert Fire Phone Equipment

VF4405-10 Wall Speaker 2 Watt RedVF4405-30 Wall Speaker 2 Watt WhiteVF4409-10 Ceiling Mount Speaker 2 Watt RedVF4409-30 Ceiling Mount Speaker 2 Watt WhiteVF4412-10 Vandal-Proof Speaker 8 Watt Surface RedVF4412-30 Vandal-Proof Speaker 8 Watt Surface WhiteVF4414-10 Vandal-Proof Speaker 8 Watt Flush RedVF4414-30 Vandal-Proof Speaker 8 Watt Flush White

For a full list of units please see individual data sheets

VES offer a comprehensive range of speakers and speaker strobes including wall mounted, ceiling mounted and vandal resistant versions. All models feature high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. They are designed to provide a sleek, aesthetic appearance for emergency voice/alarm communications systems. VES speakers and speaker strobes mount to standard electrical boxes for ease of installation, they are also available as a surface mounted option.

Speakers and Speaker/Strobes

Approvals: UL, FM, MEA, CSFM, BFP ADA/NFPA/ANSI compliant Field selectable candela settings Field selectable taps for 25 or 70 VRMS operation from 1/8 - 2 watts High efficiency design for maximum output at minimum wattage Fast IN/OUT screw terminals Available in Red or Off White

Page 14: VES Fire Detection Systems: Product Guide

The VF922x and VF924x range in the Voice Evacuation System provides 50Watts and 100Watts of speaker power respectively.

The VF922x and VF924x range includes all necessary features to provide an effective voice evacuation system. With the addition of zone splitters, remote microphone panels and expander modules, both ranges can be custom configured to satisfy the needs of most applications.

Clean Dead-front Construction Digitally Recorded Automatic Evacuation Message (Up to 4 Minutes of Message Capacity) 50/ 100 Watt High Efficiency Digital Amplifier (VF922x/ VF924x) 25 or 70 VRMS Field Selectable 120 VAC Power Supply and Battery Charger Live Microphone Override of Message and Tone Analog Addressable Compatible High Reliability, No Maintenance Fully Supervised Easy Installation and Operation Natural Sound Recordings Built in Alarm and Alert Signals Works with 12VDC or 24VDC Fire Alarm Panels Works with Analog/Addressable and Microprocessor based Fire Alarm Panels 3 Minute Message Restart on Microphone Key 24 Hour Backup with two 12V 7AHr Batteries

VF922x*/ VF924x*

The VF926x and VF928x range of panels provide 150Watts and 200Watts of speaker power respectively. Speaker zones can be configured for general alarm or alarm by zone operation as required.

Dead-front Construction Digitally Recorded Automatic Evacuation Message (Up to 4 Minutes of Message Capacity) 150/ 200 Watt Bullet-Proof Amplifier (VF926x/ VF928x) 25 or 70 VRMS Field Selectable 120 VAC Power Supply and Battery Charger Live Microphone Override of Message and Tone Analog Addressable Compatible High Reliability, No Maintenance, Fully Supervised Easy Installation and Operation Natural Sound Recordings Built in Alarm and Alert Signals Works with 12VDC or 24VDC Fire Alarm Panel Works with Analog/Addressable and Microprocessor based Fire Alarm Panels.

VF926x*/ VF928x*

* for full product listings please see our price guide

VoiceAlert Voice Evacuation System

Page 15: VES Fire Detection Systems: Product Guide

VoiceAlert- Voice Evacuation System Schematic

Voice EvacuationSpeaker Circuits

Fire Phone

Master Panel

Master Panel - Internal

Distributed Panel

Voice EvacuationSpeaker Circuits

#18 AWG

Fire Phone

#22 AWG Twisted Pair

Distributed Panel

PAGING CONTROL

SYSTEMRESET

PAGEALL-CALL

FAULTSILENCE

LAMPTEST

ALARMFAULT

POWER

THIS

DE

VIC

E C

OM

PLIE

S W

ITH P

AR

T 15 OF TH

E FC

C R

ULE

S.

PN

: HW

-000

007

REV

E

OP

ER

ATIO

N IS

SU

BJE

CT TO

THE

FOLLO

WIN

G TW

O C

ON

DITIO

NS

:

TES

TED

TO C

OM

PLY

WITH

FCC

STA

ND

AR

DS

Unshielded Twisted Pair (Low cap.) 4,000 Feet max. between panels Data and 6 Audio Channels simultaneously High Speed RS-485 Communications

Switch plates can be added or removed in banks of 16 Giving up to 128 switches (or 96, if telephone is used) Telephone can be added or removed. This takes up two plate areas

Page 16: VES Fire Detection Systems: Product Guide

FIREDETECTIONSYSTEMS

VES LLC, 620 Allendale Road, King of Prussia, PA. 19406 Tel: 610.992.3378 (US) or +44 (0)1322 222121 (Non US)

Fax: 610.992.3380 (US) or +44 (0)1322 291794 (Non US)

E-mail: [email protected] Web: www.ves-network.com