VENTILATION SYSTEMS - Master Group · VENTILATION SYSTEMS Canadian Model Numbers ... 5.2 Exhaust...
Transcript of VENTILATION SYSTEMS - Master Group · VENTILATION SYSTEMS Canadian Model Numbers ... 5.2 Exhaust...
03119-00/11/15
Installer Manual
VENTILATION SYSTEMS
Canadian Model Numbers
1001 ERV
1001 HRV
2001 ERV
2001 HRV
U.S. Model Numbers
HRV100H
HRV200H
ERV100HC
ERV200HC
VB0038
2
Table of Contents
1.0 SERVICE ..............................................................................................41.1 3-D Drawing ................................................................................41.2 Parts Ordering Chart ..................................................................51.3 Technical Support ......................................................................5
2.0 SIZING ................................................................................................6
3.0 UNIT TYPE & DEFROST SETTING VS GEOGRAPHICAL LOCATION ..7
4.0 TECHNICAL DATA ..............................................................................84.1 Air Distribution (Normal Operation) ........................................84.2 Air Distribution (Defrost Mode) ................................................84.3 Performance Charts ..............................................................9-124.4 Dimensions ..............................................................................134.5 Controls and Furnace Link Option..........................................134.6 Specifications ..........................................................................13
5.0 TYPICAL INSTALLATIONS ..................................................................145.1 Fully Ducted System ................................................................145.2 Exhaust Ducted System (Source Point Ventilation) ..............145.3 Simplified (Volume Ventilation) ..............................................14
6.0 INSTALLATION ..................................................................................156.1 Adsjusting the Damper Rod (for ERVs installed in warm regions) 156.2 Locating and Mounting the Unit ............................................156.3 Planning of the Ductwork ........................................................166.4 Calculating the Duct Size ........................................................16
6.4.1 Example Calculation ......................................................166.4.2 Example of a Design for a Fully Ducted System ........17
6.5 Installing the Ductwork and Registers....................................176.5.1 Fully Ducted System......................................................176.5.2 Exhaust Ducted System (Source Point Ventilation) ..186.5.3 Simplified Installation (Volume Ventilation)................18
6.6 Connecting Duct to the Unit....................................................196.7 Installing the Exterior Hoods ..................................................206.8 Connecting the Drain ..............................................................21
7.0 CONTROL DEVICES ..........................................................................227.1 Main Controls ..........................................................................227.2 Optional Control ......................................................................237.3 Other Features ..........................................................................237.4 Main and Optional Controls Available for your Unit ............237.5 Special Cold Weather TBI Mode for ERVs ............................23
3
Table of Contents (cont’d)
About this Manual
8.0 INSTALLATION OF THE CONTROLS ..................................................248.1 Dimensions and Specifications ............................................248.2 Installation of the Main Control ......................................24-258.3 Electrical Connection to Optional Controls ..........................268.4 Electrical Connection to the Furnace....................................26
9.0 WIRING DIAGRAMS ....................................................................27-28
10.0 AIR FLOW BALANCING ..............................................................29-30
11.0 OVERALL VERIFICATION ..................................................................3111.1 Main Controls....................................................................31-3211.2 Optional Control ....................................................................32
12.0 MAINTENANCE / INSTRUCTIONS FOR USER ..................................33
13.0 REFERENCES ....................................................................................33
14.0 TROUBLESHOOTING ....................................................................34-36
This manual uses the following symbols to emphasize particular information:
NOTE: Indicates supplementary information needed to fully complete an instruction.
WARNINGIdentifies an instruction which, if not followed, might cause serious personal injuriesincluding possibility of death.
!
CAUTIONDenotes an instruction which, if not followed, may severely damage the unit and/or its components.
4
1.1 3-D DRAWING
1.0 Service
6
21
1
23
4
5
7
8
910
11
12 13
14
15
16
17
18
19
20
22
23324
24
25
26
27
VL0
009
5
Canada: tel: 1-888-908-2633 (for distributors only)
U.S.A.: tel: 1-800-637-1453
No Description 1001 1001 2001 2001 HRV ERV HRV ERVHRV ERV HRV ERV 100H 100HC 200H 200HC
1 Double collar port #2 00866 00866 00866 00866 00866 00866 00866 008662 Wing nut #10-32 00874 00874 00874 00874 00874 00874 00874 008743 Balancing double collar port 02256 02256 02256 02256 02256 02256 02256 022564 Inlet ring 12913 12913 12913 12913 12913 12913 12913 129135 Top wheel 14307 03093 14308 03093 14307 03093 14308 030936 Electronic board V99 13507 13507 13507 13507 13508 13507 13508 135077 Motor assembly 13504 13555 13556 13506 13504 13555 13505 135068 Bottom wheel 02015 02015 03093 03093 02015 02015 03093 030939 Square balancing damper 12645 12645 12645 12645 12645 12645 12645 1264510 Door latches (latch) 00886 00886 00886 00886 00886 00886 00886 0088611 Drain connector 02418 02418 02418 02418 02418 02418 02418 0241812 Drain gasket 0,625”D 02419 02419 02419 02419 02419 02419 02419 0241913 Washer 5/8” ID x 1” OD 03117 03117 03117 03117 03117 03117 03117 0311714 Nut 5/8-18 02420 02420 02420 02420 02420 02420 02420 0242015 Recovery core 03132 03136 03133 03137 03134 03136 03135 0313716 Door assembly 12644 12644 12644 12644 12648 12648 12648 1264817 Door latches (keeper) 00887 00887 00887 00887 00887 00887 00887 0088718 Hinge assembly 00672 00672 00672 00672 00672 00672 00672 0067219 Filter 03096 03096 03097 03097 03096 03096 03097 0309720 Switch E69 10A 01825 01825 01825 01825 01825 01825 01825 0182521 Electronic board and cover 12647 12647 12647 12647 12646 12647 12646 1264722 Damper assembly #2 12643 12643 12649 12649 12643 12643 12649 1264923 Plastic balancing damper 02253 02253 02253 02253 02253 02253 02253 0225324 Damper rod 12620 12620 12620 12620 12620 12620 12620 1262025 Double collar port #5 02021 02021 02021 02021 02021 02021 02021 0202126 Damper #1 12459 12459 12459 12459 12459 12459 12459 1245927 Damper actuator assembly 03124 03124 03124 03124 03124 03124 03124 03124
1.2 PARTS ORDERING CHART
1.0 Service (cont’d)
1.3 Technical Support (for assistance)
For assistance, call on week days, 8:30 AM to 5:00 PM (Eastern Standard Time).
NOTE: Do not call these numbers for ordering parts.
Technical Support Department
Please take note that parts not listed are not available; those parts require assembly knowledge that only manufacturer can guarantee.
TO ORDER PARTS: Contact your local distributor
6
2.0 SizingThese are the two most common methods used to evaluate the ventilation needs of a house:
CSA F326 and Canadian Building Code:• High speed: 10 cfm per room
20 cfm for the master bedroom and the basement
• Low speed: 40-60% of high speed
ASHRAE Standard 62-1989:• 0.35 air change per hour
Refer to ventilation code of your area to determine which method to use.
Example:
Masterbedroom
Bedroom #1
Kitchen
Basement
Bedroom #2
Bedroom #3
Living room Bath
room
#3
Dining room
VH0021A
Family room
Bath
room
#1
Bath
room
#2 Laundry
room
1320 ft21320 ft2
CSA F326
Kitchen (10 cfm)Dining room (10 cfm)Living room (10 cfm)Family room (10 cfm)Master bedroom (20 cfm)Bedroom #1 (10 cfm)Bedroom #2 (10 cfm)Bedroom #3 (10 cfm)Bathroom #1 (10 cfm)Bathroom #2 (10 cfm)Bathroom #3 (10 cfm)Laundry room (10 cfm)Basement (20 cfm)
Total 150 cfm(high speed)
ASHRAE Standard 62-1989
Volume of basement 10560 ft3
Volume of main floor 10560 ft3
Volume of second floor 10560 ft3
Total volume 31680 ft3
x .35/h
11090 ft3/h÷ 60 (min/h)
Total 185 cfm (high speed)
1320 ft2
Second floor Main floor
Basement
7
3.0 Unit Type and Defrost Setting vs Geographical Location
AN
CH
ORA
GE
WH
ITEH
ORSE
JUN
EA
U
HA
Y R
IVER
YELLO
WKN
IFE
Prince
Rupert
GRA
ND
E P
RA
IRIE
FORT M
CM
URRA
Y
ZO
NE
A
FORT S
MIT
H
ED
MO
NTO
NPRIN
CE A
LBERT
SA
SKA
TO
ON
JASPER
KA
MLO
OPS
CA
LG
ARY
PEN
TIC
TO
NREG
INA
LETH
BRID
GE
HELEN
A
VIC
TO
RIA
OLYM
PIA
WIN
NIP
EG
SA
LEM
BO
ISE
BIS
MA
RCK
SA
LT L
AKE C
ITY
SA
ULT S
TE M
ARIE
ST. PA
UL
DES M
OIN
ES
MA
DIS
ON
TIM
MIN
S
HA
RRIS
BU
RG
SA
CRA
MEN
TO
DEN
VER
TO
PEKA
SU
DBU
RY
TO
RO
NTO
DETRO
IT
IND
IAN
APO
LIS
SA
NTA
FE
SPRIN
GFI
ELD
OKLA
HO
MA
CIT
Y
PH
OEN
IX
CO
LU
MBU
S
NA
SH
VIL
LE
ATLA
NTA
BA
TO
N R
OU
GE
AU
STIN
CO
LU
MBIA
RA
LEIG
H
WA
SH
ING
TO
N
OTTA
WA
NO
RTH
BA
Y
VA
L-D
ORCH
ICO
UTIM
I
HA
RTFO
RD
CH
IBO
UG
AM
AU
MO
NTRÉA
LQU
EBEC
BO
STO
N
GO
OSE B
AY
LA
BRA
DO
R C
ITY
SEPT-ILES
MA
TA
NE
GA
SPÉ
BA
TH
URST
ST-J
OH
NH
ALIF
AX
CH
ARLO
TTETO
WN
ST J
OH
N'S
ZO
NE
C
ZO
NE
B
ZO
NE
D1
ZO
NE
D2
REN
O
VN
00
02
ZONE
A(H
RVs
only)
•Set
Ext
ende
d De
frost
acc
ordi
ng to
sec
tion
8.2,
poi
nt 1
0.•M
ODE
LS: 1
001
HRV,
200
1 HR
V, H
RV 1
00H,
HRV
200
H.
ZONE
B (
HRVs
onl
y)
• Ext
ende
d De
frost
set
ting
not r
equi
red
(fact
ory
defro
st
stra
tegy
pre
-set
).•M
ODE
LS: 1
001
HRV,
200
1 HR
V, H
RV 1
00H,
HRV
200
H.
ZONE
C (
HRV
or E
RV a
ccor
ding
to y
our c
lient
’s pa
rticu
lar
prob
lem
s)
see
ZONE
C S
ELEC
TIO
N CH
ART
besi
de
• HRV
MO
DELS
: 100
1 HR
V, 2
001
HRV,
HRV
100
H, H
RV 2
00H.
•ERV
MO
DELS
: 100
1 ER
V, 2
001
ERV,
ERV
100
HC, E
RV 2
00HC
.
ZONE
D1
(ERV
s re
com
men
ded)
•ER
V M
ODE
LS: 1
001
ERV,
200
1 ER
V, E
RV 1
00H,
ERV
200
H.•
ERVs
: Se
t Def
rost
mod
e #1
acc
ordi
ng to
sec
tion
6.1.
ZONE
D2
(HRV
s re
com
men
ded)
•HR
V M
ODE
LS: 1
001
HRV,
200
1 HR
V, H
RV 1
00H,
HRV
200
H.•
If ER
V : S
et D
efro
st m
ode
#1 a
ccor
ding
to s
ectio
n 6.
1.
SYM
PTOM
SOLU
TION
(con
dens
atio
n)
Indo
or a
ir qu
ality
pro
blem
ERV
and
/ or
Exce
ss m
oist
ure
prob
lem
ERV
and
/ or
Impo
rtant
exc
ess
moi
stur
e pr
oble
mHR
V
ZONE
C S
ELEC
TION
CHA
RT
8
Applicable to all model numbers.
Defrost Mode 1Applicable to model numbers: • 1001 HRV• 2001 HRV• HRV100H• HRV200H
Defrost Mode 2Applicable to model numbers: • 1001 ERV• 2001 ERV• ERV100HC• ERV200HC
Model numbers ERV100HC and ERV200HC should be set to defrost mode 1 when installed in warm regions (Zone D, as defined in Section 3.0). Refer to Section 6.1 for setting instructions.
4.1 AIR DISTRIBUTION (NORMAL OPERATION)
4.2 AIR DISTRIBUTION (DEFROST MODE)
4.0 Technical Data
VF0013
FRESH AIRFROM
OUTSIDE
STALE AIRFROM
BUILDING
STALE AIRTO OUTSIDE
FRESH AIR TOBUILDING
VF0012
STALE AIRFROM
BUILDING
STALE AIRTO OUTSIDE
FRESH AIR TOBUILDING
VF0020
STALE AIRFROM
BUILDING
FRESH AIR TOBUILDING
For defrost cycles tables, refer to Section 9.0, Wiring Diagrams.
9
MODEL NUMBER: 1001 ERVElectrical requirements: 120 volts, 1.3 AmpsExhaust Air Transfer Ratio: 0.06
4.3 PERFORMANCE CHARTS
4.0 Technical Data (cont’d)
VENTILATION PERFORMANCE
External Static Net Supply Gross Air FlowPressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 81 173 87 184 93 19750 0.2 78 165 83 175 86 18275 0.3 72 152 76 162 80 169100 0.4 67 142 71 151 77 163125 0.5 55 117 59 124 67 143150 0.6 46 98 49 104 56 118175 0.7 36 77 39 82 41 87200 0.8 30 63 32 67 24 51Note: Unit operating at maximum speed.
ENERGY PERFORMANCESupply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Airflow Power Efficiency Effectiveness Moisture Transfer°C °F L/s cfm Watts % %0 32 29 60 56 71 79 0.530 32 47 100 80 64 73 0.410 32 65 137 126 60 68 0.36
-15 5 31 65 64 56 81 0.41Total Recovery Efficiency
35 95 28 59 52 45
HEATING
COOLING
ENERGY PERFORMANCESupply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Airflow Power Efficiency Effectiveness Moisture Transfer°C °F L/s cfm Watts % %0 32 52 110 93 69 76 0.450 32 74 157 130 64 71 0.380 32 96 203 193 60 68 0.30
-15 5 52 110 122 55 76 0.26Total Recovery Efficiency
35 95 50 106 89 41
HEATING
COOLING
MODEL NUMBER: 2001 ERVElectrical requirements: 120 volts, 1.9 AmpsExhaust Air Transfer Ratio: 0.06
VENTILATION PERFORMANCE
External Static Net Supply Gross Air FlowPressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 109 231 116 245 128 27150 0.2 107 228 114 241 123 26075 0.3 101 214 107 227 118 249100 0.4 95 201 101 213 110 233125 0.5 86 182 91 193 103 217150 0.6 79 167 83 177 92 195175 0.7 62 132 66 140 81 172200 0.8 40 85 43 90 55 116Note: Unit operating at maximum speed.
Ext
ern
al S
tati
c P
ress
ure
- P
asca
ls(2
50 P
asca
ls =
1”
of
wat
er)
Gross Airflow - L/s (0.47 L/s = 1 cfm)
225
175
200
150
125
100
75
50
25
00 5025 100 12575 150VG0041
Ext
ern
al S
tati
c P
ress
ure
- P
asca
ls(2
50 P
asca
ls =
1”
of
wat
er)
Gross Airflow - L/s (0.47 L/s = 1 cfm)
225
175
200
150
125
100
75
50
25
00 5025 100 12575 150VG0042
Supply(l/s)Exhaust(l/s)
Supply(l/s)Exhaust(l/s)
ENERGY PERFORMANCESupply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Airflow Power Efficiency Effectiveness Moisture Transfer°C °F L/s cfm Watts % %0 32 51 109 92 70 77 -0.010 32 73 155 128 65 72 -0.020 32 102 215 191 62 70 -0.01
-25 -13 52 110 104 60 94 0.05Total Recovery Efficiency
35 95 Not tested
ENERGY PERFORMANCESupply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Airflow Power Efficiency Effectiveness Moisture Transfer°C °F L/s cfm Watts % %0 32 30 64 54 75 83 -0.030 32 46 97 78 67 74 0.010 32 65 138 124 64 72 -0.02
-25 -13 26 55 62 67 89 0.05Total Recovery Efficiency
35 95 Not tested
10
MODEL NUMBER: 1001 HRVElectrical requirements: 120 volts, 1.3 AmpsExhaust Air Transfer Ratio: 0.05
4.3 PERFORMANCE CHARTS (CONT’D)
4.0 Technical Data (cont’d)
VENTILATION PERFORMANCE
External Static Net Supply Gross Air FlowPressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 84 177 88 186 90 19050 0.2 80 169 84 178 86 18275 0.3 77 163 81 171 81 171100 0.4 69 146 72 153 76 161125 0.5 61 130 65 137 66 139150 0.6 46 98 49 103 52 110175 0.7 38 81 40 85 31 67
Note: Unit operating at maximum speed.
MODEL NUMBER: 2001 HRVElectrical requirements: 120 volts, 1.9 AmpsExhaust Air Transfer Ratio: 0.042
VENTILATION PERFORMANCE
External Static Net Supply Gross Air FlowPressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
50 0.2 120 253 124 264 126 26875 0.3 118 250 123 262 119 251100 0.4 111 235 116 245 114 241125 0.5 102 216 106 224 107 226150 0.6 87 185 91 193 96 204175 0.7 75 160 78 167 81 172200 0.8 57 120 59 124 57 121
Note: Unit operating at maximum speed.
Ext
ern
al S
tati
c P
ress
ure
- P
asca
ls(2
50 P
asca
ls =
1”
of
wat
er)
Gross Airflow - L/s (0.47 L/s = 1 cfm)
225
175
200
150
125
100
75
50
25
00 5025 100 12575 150VG0039
Ext
ern
al S
tati
c P
ress
ure
- P
asca
ls(2
50 P
asca
ls =
1”
of
wat
er)
Gross Airflow - L/s (0.47 L/s = 1 cfm)
225
175
200
150
125
100
75
50
25
00 5025 100 12575 150
VG0040
HEATING
COOLING
HEATING
COOLING
Supply(l/s)Exhaust(l/s)
Supply(l/s)Exhaust(l/s)
ENERGY PERFORMANCESupply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Airflow Power Efficiency Effectiveness Moisture Transfer°C °F L/s cfm Watts % %0 32 51 109 92 69 76 -0.010 32 73 155 128 65 72 -0.020 32 102 215 191 62 70 -0.01
-25 -13 52 110 104 60 94 0.05Total Recovery Efficiency
35 95 Not tested
11
MODEL NUMBER: HRV100HElectrical requirements: 120 volts, 1.3 AmpsExhaust Air Transfer Ratio: 0.05
4.3 PERFORMANCE CHARTS (CONT’D)
4.0 Technical Data (cont’d)
VENTILATION PERFORMANCE
External Static Net Supply Gross Air FlowPressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 78 164 81 172 83 17650 0.2 74 156 78 165 80 16875 0.3 71 151 75 158 75 158100 0.4 64 135 67 142 70 149125 0.5 56 120 60 127 61 129150 0.6 43 91 45 95 48 102175 0.7 35 75 37 79 29 62
Note: Unit operating at maximum speed.
MODEL NUMBER: HRV200HElectrical requirements: 120 volts, 1.9 AmpsExhaust Air Transfer Ratio: 0.04
VENTILATION PERFORMANCE
External Static Net Supply Gross Air FlowPressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
50 0.2 107 226 111 236 113 24075 0.3 106 224 110 234 107 225100 0.4 99 210 104 219 102 216125 0.5 91 193 95 200 96 202150 0.6 78 166 81 173 86 183175 0.7 67 143 70 149 72 154200 0.8 51 107 53 111 51 108
Note: Unit operating at maximum speed.
Ext
ern
al S
tati
c P
ress
ure
- P
asca
ls(2
50 P
asca
ls =
1”
of
wat
er)
Gross Airflow - L/s (0.47 L/s = 1 cfm)
225
175
200
150
125
100
75
50
25
00 5025 100 12575 150VG0043
Ext
ern
al S
tati
c P
ress
ure
- P
asca
ls(2
50 P
asca
ls =
1”
of
wat
er)
Gross Airflow - L/s (0.47 L/s = 1 cfm)
225
175
200
150
125
100
75
50
25
00 5025 100 12575 150VG0044
ENERGY PERFORMANCESupply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Airflow Power Efficiency Effectiveness Moisture Transfer°C °F L/s cfm Watts % %0 32 30 64 54 72 80 -0.030 32 46 97 78 65 72 0.010 32 65 138 124 62 70 -0.02
-25 -13 26 55 62 65 87 0.05Total Recovery Efficiency
35 95 Not tested
HEATING
COOLING
HEATING
COOLING
Supply(l/s)Exhaust(l/s)
Supply(l/s)Exhaust(l/s)
12
MODEL NUMBER: ERV100HCElectrical requirements: 120 volts, 1.3 AmpsExhaust Air Transfer Ratio: 0.06
4.3 PERFORMANCE CHARTS (CONT’D)
4.0 Technical Data (cont’d)
VENTILATION PERFORMANCE
External Static Net Supply Gross Air FlowPressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 74 158 80 169 85 18050 0.2 71 151 76 160 79 16775 0.3 66 139 70 148 73 155100 0.4 61 130 65 138 71 149125 0.5 50 107 54 114 61 131150 0.6 42 90 45 95 51 108175 0.7 33 71 36 75 38 80200 0.8 27 58 29 61 22 47Note: Unit operating at maximum speed.
MODEL NUMBER: ERV200HCElectrical requirements: 120 volts, 1.9 AmpsExhaust Air Transfer Ratio: 0.06
VENTILATION PERFORMANCE
External Static Net Supply Gross Air FlowPressure Air Flow Supply Exhaust
Pa in. w.g. L/s cfm L/s cfm L/s cfm
25 0.1 109 231 116 245 128 27150 0.2 107 228 114 241 123 26075 0.3 101 214 107 227 118 249100 0.4 95 201 101 213 110 233125 0.5 86 182 91 193 103 217150 0.6 79 167 83 177 92 195175 0.7 62 132 66 140 81 172200 0.8 40 85 43 90 55 116Note: Unit operating at maximum speed.
Ext
ern
al S
tati
c P
ress
ure
- P
asca
ls(2
50 P
asca
ls =
1”
of
wat
er)
Gross Airflow - L/s (0.47 L/s = 1 cfm)
225
175
200
150
125
100
75
50
25
00 5025 100 12575 150VG0045
Ext
ern
al S
tati
c P
ress
ure
- P
asca
ls(2
50 P
asca
ls =
1”
of
wat
er)
Gross Airflow - L/s (0.47 L/s = 1 cfm)
225
175
200
150
125
100
75
50
25
00 5025 100 12575 150VG0042
ENERGY PERFORMANCESupply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Airflow Power Efficiency Effectiveness Moisture Transfer°C °F L/s cfm Watts % %0 32 29 60 56 71 79 0.520 32 47 100 80 64 73 0.410 32 65 137 126 60 68 0.36
-15 5 31 65 64 56 81 0.41Total Recovery Efficiency
35 95 28 59 52 45
HEATING
COOLING
ENERGY PERFORMANCESupply Net Average Sensible Recovery Apparent Sensible Latent Recovery
Temperature Airflow Power Efficiency Effectiveness Moisture Transfer°C °F L/s cfm Watts % %0 32 52 110 93 69 79 0.450 32 74 157 130 64 71 0.380 32 96 203 193 60 68 0.30
-15 5 52 110 122 55 76 0.26Total Recovery Efficiency
35 95 50 106 89 41
HEATING
COOLING
Supply(l/s)Exhaust(l/s)
Supply(l/s)Exhaust(l/s)
13
Model numbers:
• 1001 ERV• 1001 HRV• HRV100H• ERV100HC
Model numbers:
• 2001 ERV• 2001 HRV• HRV200H• ERV200HC
13-3/4" (349mm)
20" (508mm)500" (
6" (152mm)
2.5" (63mm)
30-1/4" (768mm)
VK0040
4.4 DIMENSIONS
4.0 Technical Data (cont’d)
19" (483mm)
20" (508mm)8m50
6" (152mm) 30-1/4" (768mm)
2.5" (63mm)VK0039
Main controls:• Basic (Can.) / VT1W (U.S)• Electro (Can.) / VT2W (U.S.)• Detector (Can.) / VT3W (U.S.)
Optional controls:• 20-minute push button• 60-minute crank timer• Humidity Control
Link option:• Furnace interlock (use with
forced air systems)
4.5 CONTROLS AND FURNACE LINK OPTION
4.6 SPECIFICATIONS
Model numbersWeight
Port DiameterDrain Diameter
1001 ERV, 1001 HRV, HRV100H, ERV100HC
65 lb (30 kg)6” (152 mm)1/2” (12 mm)
2001 ERV, 2001 HRV, HRV200H, ERV200HC
73 lb (33 kg)6” (152 mm)1/2” (12 mm)
Installation Chains, springs and hooks (provided with the unit).Motor Speed High and low speeds factory set (optional increased low speed - BLUE wire).Electrical supply 120 V, 60 Hz 120 V, 60 HzPower Consumption 150 Watts 225 Watts
14
5.0 Typical Installation
(Primarily for homes with radiant hotwater or electric baseboard heating. See figure 1.)
Moist, stale air is exhausted from the highhumidity areas in the home, such as bathrooms,kitchen and laundry room. Fresh air is suppliedto bedrooms and principal living areas.
The use of bathroom fans and a range hood issuggested to better exhaust stale air.
Homes with more than one level require atleast one exhaust register at the highest level.
5.1 FULLY DUCTED SYSTEM
There are three (3) common installation methods.
VH0024 figure 1See 6.5.1 for details
5.2 EXHAUST DUCTED SYSTEM (SOURCE POINT VENTILATION)(For homes with forced air heating. See figure 2.)
Moist, stale air is exhausted from the highhumidity areas in the home, such as bathrooms,kitchen and laundry room. Fresh air is supplied tothe cold air return or the supply duct of the furnace.
The use of bathroom fans and a range hood issuggested to better exhaust stale air.
Homes with more than one level require at leastone exhaust register at the highest level.NOTE: For this type of installation, it is not essential
that the furnace blower runs when the unitis in operation, but we recommend it.
VH0025See 6.5.2 for detailsfigure 2
5.3 SIMPLIFIED (VOLUME VENTILATION)(For homes with forced air heating. See figure 3 or 4.)
Fresh air and exhaust air flow through the furnace ducts wich simplifies the installation.
The use of bathroom fans and a range hood is suggested to better exhaust stale air.NOTE: For the installation type shown in figure 4, furnace blower should be running when the
unit is in operation.
VH0027
figure 3See 6.5.3 for details
VH0026
figure 4See 6.5.3 for details
OR
15
6.0 Installation
6.1 ADJUSTING THE DAMPER ROD (FOR ERVS INSTALLED IN WARM REGIONS)Refer to Section 4.2 and observe the difference in the damperposition at the right in diagrams Defrost Mode 1 and Defrost Mode 2:for Defrost Mode 1 the damper is completely closed, whereas for Defrost Mode 2 the damper is half closed. At the factory, all ERVsare assembled for defrost Mode 2. Therefore, if your installation is for an ERV in a warm region (zone D as defined in Section 3),the rod must be moved to position 1 (see figure 5).
NOTE: Before attempting to change the position of the damperrod, place the unit on a table for easy access and removethe recovery core.
6.2 LOCATING AND MOUNTING THE UNIT
Choose an appropriate location for the unit:
• Within an area of the house where the temperature is above10°C / 50°F (basement, attic, furnace room, laundry room, etc.).
• Away from living areas (dining room, living room, bedroom), ifpossible.
• So as to provide easy access to the interior cabinet andto the control panel on the right hand side of the unit.
• Close to an exterior wall, so as to limit the length of the insulated flexible duct to and from the unit.
• Close to a drain. If no drain is close by, use a pail to collectrun-off.
• Away from hot chimneys, electrical panel and other firehazards.
• Allow for a power source (110 V standard outlet).
Hang the unit to ceiling joists with the 4 chains andsprings provided (see figures 6 and 7).
VD0064
VD0038
figure 6
figure 7
CAUTIONMake sure the unit is level.
CAUTIONThis is a delicate operation: to avoid injury proceed carefully and use the appropriatetools (the clip is easier to remove by turning it rather than pulling it).
VO0015
1
2
Clip
figure 5
INSPECT THE CONTENTS OF THE BOX
• Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to thedoor, door latches, door hinges, dampers, duct collars, cabinet, etc.
• Inspect the interior of the unit for damage. Ensure that the fan motor assembly, recoverycore, insulation, dampers, damper actuator and drain pan are all intact.
• If the unit was damaged during shipping, contact your local distributor. (Claim must be madewithin 24 hours after delivery.)
• Use checklist included with the unit to ensure that no parts are missing.
16
6.0 Installation (cont’d)
a) Follow the instructions in Section 6.4 below to determine the appropriate duct diameters foryour system.
b) Keep it simple. Plan for a minimum number of bends and joints. Keep the length of insulatedduct to a minimum.
c) Do not use wall cavities as ducts. Do not use branch lines smaller than 4” (102 mm) Ø.d) Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a
dryer or a range hood. This would cause clogging of the recovery module. Use sheet metal forthe kitchen exhaust duct.
e) Be sure to plan for at least one exhaust register on the highest lived-in level of the house if ithas 2 floors or more.
Use the table below to ensure that the ducts you intend to install will be carrying airflows at or under the recommended values. Avoid installing ducts that will have to carryair flows near the maximum values and never install a duct if its air flow exceeds themaximum value.
NOTE: Examples 6.4.1 and 6.4.2 use imperial measures. The same calculation applies to metric measures.
6.4.1 Example of calculation:
Problem: My installation requires two exhaust registers (one for the kitchen, one for thebathroom). I will connect these registers to a main duct which will connect to the unit (highspeed performance value of 140 cfm). What size of duct should I use for the main exhaustduct and for the two end branches leading to the registers? (See figure 8.)
Solution: Simplified method. (For a more detailed method of calculating duct size refer tothe ASHRAE or HRAI HANDBOOK).
Main duct: Table above indicates a 6” Ø duct: recommended air flow: 120 cfm; maximumair flow: 180 cfm. The high speed air flow of 140 cfm is close enough to the recommendedvalue (120) and far enough away from the maximum value (180). Therefore a 6”Ø duct orlarger is an appropriate choice for the main exhaust duct.
End branches: Each end branch will have to transport an air flow of 70 cfm (140 divided by 2).Table above indicates a 5ӯ duct: recommended air flow: 75 cfm; maximum air flow: 110 cfm.The high speed air flow of 70 cfm is close enough to the recommended value (75) and farenough away from the maximum value (110). Therefore a 5ӯ duct or larger is an appropriatechoice for the 2 end branches.
N.B.: A 4ӯ duct would have been too small because the maximum acceptable value for a4ӯ duct is 60 cfm.
6.3 PLANNING OF THE DUCTWORK
6.4 CALCULATING THE DUCT SIZE
VI0003
end branches
main branch6”ø 140 cfm
5”ø70 cfm
4”(102 mm) 40 cfm 19 l/s 68 m3/h 60 cfm 28 l/s 102 m3/h5”(127 mm) 75 cfm 35 l/s 127 m3/h 110 cfm 52 l/s 187 m3/h6”(152 mm) 120 cfm 57 l/s 204 m3/h 180 cfm 85 l/s 306 m3/h7”(178 mm) 185 cfm 87 l/s 314 m3/h 270 cfm 127 l/s 459 m3/h8”(203 mm) 260 cfm 123 l/s 442 m3/h 380 cfm 179 l/s 645 m3/h
Duct Recommended MaximumDiameter Air Flow Air Flow
figure 8
140 cfm
17
6.0 Installation (cont’d)
6.4.2 Example of a design for a fully ducted system for a unit having a high speed performance of 222 cfm (See figure 9).
VI0004
4” Ø42 cfm
6” Ø 129 cfm
5” Ø65 cfm
5” Ø 64 cfm
6” Ø 93 cfm
5”
6”
7” 7”6”
6”6”
4”
4”
4”4”
7” Ø 222 cfm
7” Ø 222 cfm
4” Ø 42 cfm
6” Ø 84 cfm6” Ø 96 cfm
6” Ø 138 cfm
6.5.1 Fully Ducted System (as illustrated in Section 5.1)
Stale air exhaust ductwork:
• Install registers in areas where contaminants are produced: kitchen, bathrooms, laundry room, etc.
• Install registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall ORinstall them in the ceiling.
• Install the kitchen register at least 4 feet (1.2 m) from the range top.• If possible, measure the velocity of the air flowing through the registers. If the velocity
is higher than 400 ft/min. (122 m/min), then the register type is too small. Replace witha larger one.
Fresh air distribution ductwork:
• Install registers in bedrooms, dining room, living room and basement.• Install registers either in the ceiling or high on the walls with air flow directed
towards the ceiling. (The cooler air will then cross the upper part of the room, andmix with room air before descending to occupant level.)
• If a register must be floor installed, direct the air flow up the wall.
6.5 INSTALLING THE DUCTWORK AND REGISTERS
WARNINGNever install a stale air exhaust register in a room where a combustion device is, suchas a gas furnace, a gas water heater or a fireplace.
!
figure 9
6.4 CALCULATING THE DUCT SIZE (CONT’D)
18
6.0 Installation (cont’d)
6.5.2 Exhaust Ducted System (Source Point Ventilation) (as illustrated in Section 5.2)
Stale air exhaust ductwork: (same as for Fully Ducted System, described on page 17)
Fresh air distribution:There are two methods for connecting the unit to the furnace:
Method 1: supply side connection• Cut an opening into the furnace supply duct at least
18 inches (0.5 m) from the furnace.• Connect this opening to the fresh air distribution port
of the HRV/ERV (use steel duct, see figure 10).• Make sure that the HRV/ERV duct forms an elbow
inside the furnace ductwork.• If desired, interlock (synchronize) the furnace blower
operation with the HRV/ERV operation. (See Section 8.4).
Method 2: return side connection• Cut an opening into the furnace return duct
at least 6 feet (1.8 m) from the furnace or at a minimum distance of 10 linear feet upstream(from furnace drop).
• Connect this opening to the fresh air distributionport of the HRV/ERV (see figure 11).
NOTE: For Method 2, it is not essential that the furnaceblower runs when the HRV/ERV is in operation,but we recommend it. If desired, synchronize the furnace blower operation (see Section 8.4).
6.5 Installing the Ductwork and Registers (cont’d)
VD0040
VD0041
minimum 18”(0.5 m)
Steel duct
minimum 6’ (1.8 m)or 10’ (3.1 m)
upstream
6.5.3 Simplified installation (Volume Ventilation) (as illustrated in Section 5.3)
There are two methods (figures 12 and 13) for connecting the unit to the furnace:
Method 1: return-supply Method 2: return-return
Stale air intake:• Cut an opening into the furnace return duct (at least 6 feet (1.8 m) from the furnace).• Connect this opening to the stale air intake port on the HRV/ERV as shown .
Fresh air distribution: (same instructions as for Method 1 or Method 2, Section 6.5.2).For method 2 (return-return) make sure there is a distance of at least 3 feet (0.9 m) betweenthe 2 connections to the furnace.
NOTE: For Method 1, it is not essential to synchronize the furnace blower operation with theHRV/ERV operation, but we recommend it.
VD0042 VD0043
minimum 3’(0.9 m)minimum 6’ (1.8 m)
Steel ductminimum 18”
(0.5 m)
figure 10
figure 11
figure 12figure 13
minimum 6’ (1.8 m)or 10’ (3.1 m)
upstream
CAUTIONIf using Method 2, make sure the furnace blower operation is synchronized with theHRV/ERV operation! See Section 8.4.
19
6.0 Installation (cont’d)
Insulated flexible duct
Use the following procedure for connecting the insulated flexible duct to the ports on the unit(exhaust to outside and fresh air from outside).
a) Pull back the insulation to expose the flexible duct.b) Connect the interior flexible duct to the port using a duct tie.c) Carefully seal the connection with duct tape.d) Pull the insulation over the joint and tuck it between the inner and outer rings of the double collar.e) Pull the vapor barrier over the insulation and over the outer ring of the double collar.f) Apply duct tape to the joint making an airtight seal. Avoid compressing the insulation when you
pull the tape tightly around the joint. Compressed insulation loses its R value and causes waterdripping due to condensation on the exterior surface of the duct.
a) b) c) d), e) f)
Rigid duct:Use duct tape to connect the rigid ducts to the ports.
Make sure that the 2 balancing dampers are left in a fully open position before connecting the ductsto these ports (fresh air distribution port and stale air exhaust port as shown on figure 14).
VJ0001 VJ0002 VJ0003 VJ0004 VJ0005
6.6 CONNECTING DUCT TO THE UNIT
VJ0009
CAUTIONMake sure that the vapor barrier on the insulated ducts does not tear during installationto avoid condensation within the duct.
CAUTIONDo not use screws to connect rigid ducts to the ports.
figure 14
20
VD0028
6.7 INSTALLING THE EXTERIOR HOODS
6.0 Installation (cont’d)
Exhausthood
Optional duct location
Tape and duct tie
Caulking
Intakehood
6ӯ(152 mm)
18” (457 mm)
18” (457 mm)
6’ (1.8 m)
6’ (1.8 m)
Choose an appropriate location for installing the exterior hoods:• a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination• a minimum distance of 18 inches (457 mm) from the ground
Make sure the intake hood is at least 6 feet (1.8 m) away from any of the following:• dryer exhaust, high efficiency furnace vent, central vacuum vent• gas meter exhaust, gas barbecue-grill• any exhaust from a combustion source• garbage bin and any other source of contamination
Refer to figure 15 for connecting the insulated duct to the hoods. Place the “FRESH AIR INTAKE”sticker, provided in the installation kit, on corresponding hood. An “Anti-Gust Intake Hood” shouldbe installed in regions where a lot of snow is expected to fall.
18” (457 mm)
figure 15
21
6.8 CONNECTING THE DRAIN
12"(305 mm)
VO0004
VO0003
VO0011VO0005To drain
6.0 Installation (cont’d)
Attach the 2 plastic drain fittings tothe unit using the gaskets, washersand nuts as shown.
Cut 2 sections of plastic tubing, about12” (305 mm) long and attach themto each drain fitting.
Join the 2 short sections to the “T”junction and main tube as shown.
Make a water trap loop in the tube toprevent the unit from drawingunpleasant odors from the drainsource. Make sure this loop is situated BELOW the “T” as shown.This will prevent water from beingdrawn back up into the unit in case ofnegative pressure. Run the tube tothe floor drain or to an alternativedrain pipe or pail. Be sure there is aslight slope for the run-off.
Tie-wrap
1 2
3 4
22
1 DETECTED POLLUTANTS- Carbon monoxide - Phenols - Aldehydes - Acetone- Aromatics - Alcohols - Hydrocarbons - Etc.- Esters - Cigarette smoke
Pollutants detection sensitivity: Less than 10 ppm
(U.S) VT1W model(Can) Basic model
7.1 Main Controls
7.0 Control Devices
CONDENSATI0N CONTROL
AIR SUPPLY CONTROLY CONTROL L
MIN.
MAX.
OFF
AAIRRIRIEXCHANGECHHA
-20 C-4°
41°F
CO F NE
SUMM
ER
VC0027
(U.S.) VT2W model(Can) Electro model
°C-4°F
-5C
41°F
CONDENSATI0N CONTROL
AIR SUPPLY CONTROLY CONTROL L
CONDENSATION CONTROLMAXIMUM SPEED
AIR EXCHANGE IN PROGRESS
MIN. MAX.
CONTINUOUSCONTINUOUS INTERMITTENTTINTERMITTENT
20 MIM N.N.NONON
40 MIN.MOFFOF
CO M Z O E
SUMM
ER
VC0028
(U.S.) VT3W model(Can) Detector model
POLLUTANT CONTROL
AIR SUPPLY CONTROLY CONTROL L
POLLUTANT CONTROLTANT CONTROLTMAXIMUM SPEED
AIR EXCHANGE IN PROGRESS
MIN. MAX.
CONTINUOUSCONTINUOUS INTERMITTENTTINTERMITTENT
20 MIM N.N.NONON
40 MIN.MOFFOF
Pollutantstst+
S
E
S
IITIVIITY
VC0029
U.S. models VT1W VT2W VT3W DH100WCanadian models Basic Electro Detector Humidity controlOFF Position X X X XIntermittent exchange (TBI) 20 ON - 40 OFF X XLow speed continuous exchange X X XHigh speed continuous exchange X X XHumidity control (Relative humidity scale %) XCondensation control (Temperature scale) X XPollutant control (detector) 1 XMode indicator X XAir exchange indicator X XCondensation/Pollutant control max speed indicator X XMaintenance indicator with flashing intermittent X XSliding button XPush button X XSw
itche
sIn
dica
tors
Mod
es
Dete
ctor
type
s
Humidity Control
Designed primarily for use with our low price HRV (HeatRecovery Ventilator) units, the Humidity Control helpscontrol indoor maximum humidity level during fall, winterand spring. This control should not be installed in ahouse already equipped with other main controls (exceptthe 3-position switch). You will find a relative humidity %scale instead of a temperature scale meant to reduce thewindow condensation problems.
3-position switch
Some model may come with a 3-position mounted switchon the electical box on the exterior lower right front side.It is basically an airflow control that gives the customerthe choice between the low and high speed or the OFF(REMOTE) position. This OFF (REMOTE) position doesnot deactivate the optional controls.
WARNINGThe pollutant detecting control is not a warning device and must not be used in placeof a smoke detector or carbon monoxide detector.
!
23
7.0 Control Devices (cont’d)
7.4 MAIN AND OPTIONAL CONTROLS AVAILABLE FOR YOUR UNIT
MAIN CONTROLS OPTIONAL CONTROLS
Model number Humidity VT1W (U.S.) VT2W (U.S) VT3W (U.S.) 20-min. 60-min. Furnace
Control Basic (CAN.) Electro (CAN.) Detector (CAN.) push-button crank timer Interlocktimer
1001 ERV / ERV100HC X X X X X Integrated1001 HRV X X X X X Integrated
2001 ERV / ERV200HC X X X X X Integrated2001 HRV X X X X X Integrated
HRV100H / HRV200H X X X X Optional kitPart # 12658
7.5 SPECIAL COLD WEATHER TBI MODE FOR ERVS
The enthalpic core installed in ERVs requires extra protection when the outside temperature dropsbelow -15°C (5°F). A special operating mode called TBI (Time-Based Intermittent) is activated under these conditions.
Characteristics of cold weather TBI mode• activated when the outside temperature drops below -15°C (5°F).• 20/40 cycle (20 minutes LOW speed followed by 40 minutes OFF).• usual control of air supply via the main wall control is suspended (except for the OFF position).• optional control (20-minute push button) retain its temporary high speed activation capability.• deactivated when the outside temperature warms up higher than -15°C (5°F).
7.3 OTHER FEATURES
FURNACE INTERLOCK (for forced air heating system)
The furnace fan can be interlocked so that it will run simultaneously with the ERV or HRV to ensureproper distribution of fresh air throughout the house (see table section 7.4, to see if it’s available onyour unit).
PERMANENT MEMORY
Our electronic controls have a default memory feature in the event of a power outage. Even the dateof the last service reminder is maintained as a convenience to the homeowner.
CONTROL UPGRADES
All controls can be used on any ERV, so a Basic (or VT1W) control can be upgraded to the Electro (or VT2W)or the Detector (or VT3W) in the future (see table, section 7.4, for control availability on HRVs).
LIGHTED PUSH-BUTTON REMOTE 20-MINUTE SWITCH:This remote illuminated switch is typically installed in bathrooms, kitchen and laundry room to provide 20 minutes of high speed ventilation at the push of a button. The switch is supplied andmounted on a white single gang wall plate.
MECHANICAL TIMER
This timer allows up to 60 minutes of high speed operation to be selected from a remote location.
7.2 OPTIONAL CONTROL
24
8.0 Installation of the Controls
Voltage: 12 volts DCDimensions: 5” x 5” x 1 3/8”
(127 mm x 127 mm x 35 mm)
INSTRUCTIONS:
1- Determine the location of the control. The wall control must be installed in a central location onthe main floor. Typical locations for these controls are kitchen, main hallways and family room.
Note: When installing the DETECTOR (VT3W) control, the following should be avoided:
• Do not install close to a heating source (wood stove, baseboard, fireplace, etc.); this couldaffect the functioning of the control.
• Do not install close to a bathroom. The many humidity changes could affect the functioningof the control.
• Do not install on an exterior wall. • Do not install close to a door or a window.• Do not install in an area where there is no (or not much) air circulation.• Do not install in an area where there are no (or not many) pollutants.
2- Remove the button(s) and the cover plate of the control.
8.1 DIMENSIONS AND SPECIFICATIONS (MAIN CONTROLS)
8.2 INSTALLATION OF THE MAIN CONTROL(HUMIDITY CONTROL, BASIC (VT1W), ELECTRO (VT2W) AND DETECTOR (VT3W))
13/8"(35 mm)
5" (127 mm)
VC0016
5" (127 mm
)
FRONT VIEW SIDE VIEW
VC0026
Humidity ControlELECTRO (VT2W)
OR DETECTOR (VT3W)
BASIC (VT1W)
CAUTIONNever install more than one main control per unit.
25
8.0 Installation of the Controls (cont’d)
3- Install the wall control 60 inches (1.5 m) from the floorand leave a free space of at least 2 inches (5 cm) to theright of the control to allow user to slide out the controlinstructions.
Use the template provided in the control box to positionthe wire hole and the screw holes. Use the screws and theplastic anchors provided in the installation kit to securethe control. (See figure 16)
4- Connect the wires to the main control. (See figure 17 or 18.) NOTE: For HRV 100 and HRV 200H only:
to install VT1W, only connect GREENand BLACK wires to main control.
5- Make sure the instruction pull-out is in the occupant’s language. If not, turn it to the other side.(See figure 19.)
6- Re-install the cover plate and the button(s).
7- Connect the wires to theircorresponding position insidethe electrical compartment.Make sure the connectionsof the unit and of the wallcontrol correspond exactly.(See figure 20.)
8- Connect the optional control(if applicable) by referring toSection 8.3.
9- Do the appropriate connection to the furnace (if applicable) by referring to Section 8.4.
10-NOTE: If you are in a cold region (Zone A, as defined in Section 3.0), set up “extended defrost”by removing jumper JU1F on the main circuit board inside the electrical compartment (seeSection 9.0).
11-Plug in the unit and do the “overall verification” of the system as described in Section 11.0.
Y R GB
VD
0026
F I OCOL Y R G B F F I OCOL Y R G B
Y R G B G B
VE0038A
F F I OCOL Y R G B
G B
SWITCH
VENTILATION
Proper switchPosition
REMOTEARRÊT
LOW SPEEDBASSE VITESSE
HIGH SPEEDHAUTE VITESSE
60" (1.5 m)
2" (5 cm)
VD0025
BASIC/ELECTRO/DETECTOR(VT2W / VT3W)
VD0044
8.2 INSTALLATION OF THE MAIN CONTROL (cont’d)
figure 16
figure 18figure 17
figure 19
figure 20
(VT1W)
VD0070
HUMIDITYCONTROL
BASIC/ELECTRO/DETECTOR(VT1W / VT2W / VT3W)
HUMIDITYCONTROL
26
8.0 Installation of the Controls (con’d)
W R G Y
W
R
G
C
Y
987654321
HR V CONTROL CONNECTOR
THERMOSTATTERMINALS
FOURWIRES
I OC OL Y R G BF F
J3TWO WIRESheating only
FURNACE24-VOLT
TERMINAL BLOCKTWO WIRES
COOLING SYSTEMVE0010A
Standard furnace interlock wiring
8.3 ELECTRICAL CONNECTION TO OPTIONAL CONTROLS
9
8
7
6
5
4
3
2
1
OL
OC
I
1 4 7
2 5 8
3 6 9
J3
MAIN PC BOARD
PUSH-BUTTON SWITCHES
(5 switches maximum)
J1
0L I
VE0036A
REAR VIEW
8.4 ELECTRICAL CONNECTION TO THE FURNACE
W R G Y
W
R
Y
R
G
Y
C
J 11
2
4
5
6
8
93
* F U R N A C E I N T E R L O C KR E L A Y
N C N O
7
C O M
7
T H E R M O S T A TT E R M I N A L
U n i t C o n t r o l M o d u l e
4 W I R E S
2 W I R E S
h e a t i n g o n l yw i r i n g n u t s
F U R N A C E2 4 - V O L T
T E R M I N A L B L O C K2 W I R E S
C O O L I N G S Y S T E M
G R A Y B R O W NR E D
G R E E N
B L U E
9 - P I N A M P P L U G
* F U R N A C E I N T E R L O C K R E L A Y , P A R T # 1 2 6 5 8
VE0009A
Alternate furnace interlock wiring
For a furnace connected to cooling system:On some older thermostats, energizing the “R” and “G” terminals at the furnace has the effect of energizing “Y” atthe thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you must use the“alternate furnace interlock wiring”. An additional control relay will then have to be installed.
WARNINGNever connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Onlyuse the low voltage class 2 circuit of the furnace blower control.
!
27
9.0 Wiring Diagrams
A1M
1
M2
K1R
ELAY
K2R
ELAY
K5R
ELAY
FAN
MO
TOR
DAM
PER
MO
TOR
NEU
TRAL
MED
NC
HIG
H
LOW
J1
6J1
3
J1
4
J1
9
K4R
ELAY
J3
1
J3
2
FUR
NAC
E BL
OW
ER IN
TER
LOC
KC
LASS
2 C
IRC
UIT
ON
LY
ELEC
TRO
NIC
ASS
EMBL
Y
S1
120V
60H
z
FRO
M M
AIN
J1
2
J1
1
J1
8
VE00
18A
BK G R Y R BK Y
NO
TE 4
WAL
L C
ON
TRO
LW
ALL
CO
NTR
OL
WAL
L C
ON
TRO
LW
ALL
CO
NTR
OL
OVE
RR
IDE
SWIT
CH
OVE
RR
IDE
SWIT
CH
OVE
RR
IDE
LED
FUR
NAC
E BL
OW
ERIN
TER
LOC
K
NO
TES
1, 5
NO
TE 5
OPT
ION
AL
NO
TES
5, 6
OPT
ION
AL
M1
X2M
2
1
21
123
1 2
4
7
6
9
3
456789
2 3
1 2
NEU
TRAL
MED
IUM
HIG
H LOW
FAN
MO
TOR
X1G
YO G BL R
GY
O GN
CR
(NO
TE 2
)
BN BNC
1
BL BL
DAM
PER
MO
TOR
MAI
N E
ARTH
ING
POIN
T
R
O
GY
W
T1
R1
A1
DEF
RO
STTE
MPE
RAT
UR
ESE
NSO
R
JU1J4 J1
J3
ABCDEFG
FFIOCOLYRGB
ELEC
TRO
NIC
ASS
EMBL
Y
Y BL
BLY
CO
M
120V
60
Hz
W1
G
BK
W
NEM
A-15
P5-
15 P
LUG
BK
DO
OR
INTE
RLO
CK
SWIT
CH
S1
NO
NEU
TRAL
LIN
EBK
VE00
37A
-t°Mod
els:
100
1 ER
V, 1
001
HRV
, 200
1 ER
V,20
01 H
RV, E
RV10
0HC,
ERV
200H
C
NOTE
S
1-C
ontro
ls av
aila
ble.
See
Sec
tion
8.0
(Low
vol
tage
onl
y, 12
VDC
)
2-Th
e fa
ctor
y se
t w
iring
for
blo
wer
spe
ed s
elec
tion
is h
igh
and
low.
Med
ium
spe
ed c
an b
e se
lect
ed in
stea
d of
low
spe
ed. D
isco
nnec
t the
RED
wire
from
the
mot
or R
ED ta
p an
d co
nnec
t it to
the
mot
or B
LUE
tap.
3-If
any
of th
e or
igin
al w
ire, a
s su
pplie
d, m
ust b
e re
plac
ed, u
se th
esa
me
or e
quiva
lent
wire
.
4-U
se th
e fa
ctor
y su
pplie
d pr
otec
tive
tubi
ng.
5-Th
e fie
ld w
iring
mus
t com
ply
with
app
licab
le c
odes
, ord
onna
nces
and
regu
latio
ns.
6-Th
e fu
rnac
e fa
n cir
cuit
mus
t be
class
2cir
cuit
only.
LINE
VO
LTAG
E
LOW
VO
LTAG
E AN
DFI
ELD
WIR
E
COLO
R CO
DEBK
BLAC
KNC
NO C
ONN
ECTI
ON
BLBL
UEO
ORA
NGE
BNBR
OW
NR
RED
GG
REEN
WW
HITE
GY
GRE
YY
YELL
OW
DEF
RO
STTI
ME
JUM
PER
S TA
BLE
MO
DEL
MO
DEL
DEF
RO
ST/V
ENTI
LATI
ON
TYPE
S
M
INU
TES
23°F
5°F
-22°
FJU
1AJU
1BJU
1CJU
1DJU
1EJU
1FJU
1G-5
°C-1
5°C
-30°
C
OU
TO
UT
ININ
OU
TIN
OU
T10
01 H
RV
6/32
6/32
6/20
2001
HR
V
OU
TIN
OU
TIN
OU
TIN
OU
T10
01 E
RV,
200
1 ER
V6/
32N
OTE
NO
TEER
V 10
0HC
, ER
V 20
0HC
NO
NO
NO
NO
NO
OU
TN
OEX
TEN
DED
DEF
RO
ST10
/30
10/2
010
/15
CHAN
GECH
ANGE
CHAN
GECH
ANGE
CHAN
GECH
ANGE
HR
V O
NLY
Co
nn
ecti
on
Logic
WARNINGRisk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
!
AB
C D
E F
G
2 1
JU 1
. .
. .
. .
. .
. .
. .
. .
FUN
CTI
ON
TAB
LE
R
ELAY
MO
DE
K
1
K2
K4
K5
Inte
rmitt
ent
0
0
0
0
Exch
ange
Low
1
0
1
1
Exch
ange
Hig
h
1
1
1
1
Circ
ulat
ion
Low
1
0
1
0
Circ
ulat
ion
Hig
h
1
1
1
0
Def
rost
Cyc
le
1
1
1
0
Off
0
0
0
0
0 =
Rel
ay c
oil i
s de
-ene
rgiz
ed
1 =
Rel
ay c
oil i
s en
ergi
zed
SP
EC
IAL
DE
FRO
ST
CY
CLE
: T
he
mo
de
is t
he
sam
e w
hic
hev
er t
he
exch
ang
e sp
eed
sel
ecte
d b
y th
e w
all
con
tro
l.6
min
. def
rost
34 m
in. O
FF
20
min
. exc
han
ge
low
sp
eed
BE
LOW
-15°
C
- A
cha
nge
of a
ir ex
chan
ge s
peed
on
the
wal
lcon
trol
(-5°
F)
d
urin
g th
e sp
ecia
l def
rost
cyc
le w
ill r
eset
the
spec
ial
def
rost
cyc
le t
o t
he
beg
inn
ing
(6
min
. def
rost
).-
Th
e o
verr
ide
circ
uit
will
rem
ain
act
ive
du
rin
g t
he
spec
ial d
efro
st c
ycle
. An
over
ride
call
will
be
answ
ered
.-
If th
e ou
tsid
e te
mpe
ratu
re r
ever
t abo
ve -1
5°C
(5°F
),it
is o
nly
du
rin
g t
he
last
par
t o
f th
e cy
cle
(20
min
. ex
chan
ge)
th
at t
he
con
tro
ller
will
sto
p t
he
spec
ial
def
rost
cyc
le.
NO
TE
28
9.0 Wiring Diagram (cont’d)
A1M
1
M2
K1R
ELAY
K2R
ELAY
K5R
ELAY
FAN
MO
TOR
DAM
PER
MO
TOR
NEU
TRAL
MED
NC
HIG
H
LOW
J1
6J1
3
J1
4
J1
9
ELEC
TRO
NIC
ASS
EMBL
Y
S1
120V
60H
z
FRO
M M
AIN
J1
2
J1
1
J1
8
VE00
40A
BK G R
NO
TE 4
BK T
O R
= L
OW
SPE
ED E
XCH
ANG
EBK
TO
G =
HIG
H S
PEED
EXC
HAN
GE
NO
CO
NN
ECTI
ON
= O
FF
OVE
RR
IDE
SWIT
CH
OVE
RR
IDE
SWIT
CH
OVE
RR
IDE
LED
NO
TES
1
NO
TES
1, 6
OPT
ION
AL
M1
X2M
2
1
21
123
1 2
4
7
6
9
3
45789
2 3
1 2
NEU
TRAL
MED
IUM
HIG
H LOW
FAN
MO
TOR
X1G
YO G BL R
GY
O GN
CR
(NO
TE 2
)
BN BNC
1
BL BL
DAM
PER
MO
TOR
MAI
N E
ARTH
ING
POIN
T
R
O
GY
W
T1
R1
A1
DEF
RO
STTE
MPE
RAT
UR
ESE
NSO
R
JU1J4 J1
J3
ABCDEFG
FFICOCOLYRGB
ELEC
TRO
NIC
ASS
EMBL
Y
Y BL
BLY
CO
M
120V
60
Hz
W1
G
BK
W
NEM
A-18
P5-
15 P
LUG
BK
DO
OR
INTE
RLO
CK
SWIT
CH
S1
NO
NEU
TRAL
LIN
EBK
VE00
39A
-t°
S2SP
DT
SWIT
CH
(ON
-OFF
-ON
) FAN
FU
RN
ACE
INTE
RLO
CK
KIT
NO
TES
5, 6
GY
BN
Mod
els:
HRV
100H
, HRV
200H
NOTE
S
1-C
ontro
ls ca
nnot
be
conn
ecte
d to
J3.
2-Th
e fa
ctor
y se
t w
iring
for
blo
wer
spe
ed s
elec
tion
is h
igh
and
low.
Med
ium
spe
ed c
an b
e se
lect
ed in
stea
d of
low
spe
ed. D
isco
nnec
t the
RED
wire
from
the
mot
or R
ED ta
p an
d co
nnec
t it to
the
mot
or B
LUE
tap.
3-If
any
of th
e or
igin
al w
ire, a
s su
pplie
d, m
ust b
e re
plac
ed, u
se th
esa
me
or e
quiva
lent
wire
.
4-U
se th
e fa
ctor
y su
pplie
d pr
otec
tive
tubi
ng.
5Fi
eld
inst
alle
d op
tion:
use
onl
y fa
ctor
y su
pplie
d kit
.
6-Th
e fie
ld w
iring
mus
t com
ply
with
app
licab
le c
odes
, ord
onna
nces
and
regu
latio
ns.
LINE
VO
LTAG
E
LOW
VO
LTAG
E AN
DFI
ELD
WIR
E
COLO
R CO
DEBK
BLAC
KNC
NO C
ONN
ECTI
ON
BLBL
UEO
ORA
NGE
BNBR
OW
NR
RED
GG
REEN
WW
HITE
GY
GRE
YY
YELL
OW
DEF
RO
STTI
ME
JUM
PER
S TA
BLE
MO
DEL
MO
DEL
DEF
RO
ST/V
ENTI
LATI
ON
TYPE
S
M
INU
TES
23°F
5°F
-22°
FJU
1AJU
1BJU
1CJU
1DJU
1EJU
1FJU
1G-5
°C-1
5°C
-30°
C
OU
TO
UT
OU
TO
UT
OU
TIN
INH
RV1
00H
6/32
6/32
6/20
HR
V200
H
OU
TO
UT
OU
TO
UT
OU
TO
UT
INEX
TEN
DED
DEF
RO
ST10
/30
10/2
010
/15
ALL
TYPE
S
FUN
CTI
ON
TAB
LE
REL
AY
MO
DE
K1K2
K5
Inte
rmitt
ent
00
0
Exch
ange
Low
10
1
Exch
ange
Hig
h1
11
Circ
ulat
ion
Low
10
0
Circ
ulat
ion
Hig
h1
10
Def
rost
Cyc
le1
10
Off
00
0
0 =
Rel
ay c
oil i
s de
-ene
rgiz
ed
1 =
Rel
ay c
oil i
s en
ergi
zed
Co
nn
ecti
on
Logic
WARNINGRisk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
!
AB
C D
E F
G
2 1
JU 1
. .
. .
. .
. .
. .
. .
. .
29
WHAT YOU NEED TO BALANCE THE UNIT• A magnehelic gauge capable of measuring 0 to
0.25 inch of water (0 to 62.5 Pa) and 2 plastic tubes.
• Two ”Flow Measuring Stations” or two flow collars(the size will vary depending on the duct diameter).
PRELIMINARY STAGES TO BALANCE THE UNIT• Seal all the unit ductwork with tape. Close all windows and doors. • Turn off all exhaust devices such as range hood, dryer and bathroom fans.• Make sure all filters are clean (if it is not the first time you balance the unit).• Make sure the balancing dampers are fully open (F and G in figure 21).
Choose appropriate locations for the 2 flow collars (or flow measuring stations), according to figure 21:• On the exhaust air duct (first measuring location, A)• On the fresh air distribution duct (second measuring location, B• At least 36” away from the unit; at least 12” before or after a 90° elbow; at least 12” away from a register.
INSTALLATION OF FLOW COLLARS OR “FLOW MEASURING STATIONS”• If you are using Flow Collars:
Insert the flow collars in the duct at each location. Make sure their arrows are pointing in the direction of the airflow. Tape collars in place temporarily.
• If you are using “Flow Measuring Stations”:Cut a 1” (25.4mm) diameter hole in the duct at each location. Insert the “Flow Measuring Stations”. Make suretheir arrows are pointing in the direction of the airflow. Tape the “Flow Measuring Stations” in place temporarily.
BALANCING PROCEDURE1. Set the unit to high speed.
Make sure that the furnace blower is ON if the installation is in any way connected to the ductwork of the coldair return. If not, leave furnace blower OFF. If the outside temperature is below 0°C / 32°F, make sure the unit isnot running in defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured thatthe unit is not in a defrost cycle.)
2. Place the magnehelic gauge on a level surface and adjust it to zero.
3. Connect tubing from gauge to flow collar (or “Flow Measuring Station”) in exhaustair stream at location A. Be sure to connect the tubes to their appropriate high/lowfittings. If the gauge drops below zero, reverse the tubing connections. NOTE: It is suggested to start with the exhaust air flow reading because the exhausthas typically more restriction than the fresh air, especially in cases of fully ducted installations and exhaust ducted installation. Place the magnehelic gauge uprightand level. Record the readings
10.0 Air Flow Balancing
Flow collar Flow measuring station
Figure 21
LOW HIGHFLOW
HIGH LOW FLOW
VP0006
12¨(304mm)
12¨(30 mm)04m
36¨(914mm)36¨(914mm)
ORB A
GF
VP0012
LOW HIGHFLOW
VP0003
30
4. Move tubing to FRESH air flow on the other side of the unit (location B) and note readings.Adjust the fresh air balancing damper F until the reading at B is approximately thesame as the reading at A. If the reading at B is less than the reading at A, then go backand adjust the exhaust balancing damper G to equal the fresh air flow.
5. Secure both dampers in place withtape or with a fastening screw.
6. If you are using flow collars, remove them, reconnect the duct and seal with duct tape. If you are using “FlowMeasuring Stations”, remove them and seal the holes with duct tape. Write the required air flow information ona label and stick it near the unit for future reference (date, maximum speed air flows, your name, phone numberand business address).
NOTES: Most flow collar kits provide a conversion chart located on the collar which enables you to convert magnehelicgauge readings to equivalent cfm values.The unit is considered balanced even if there is a difference of +/- 10 cfm (+/- 0.015 inch w.g.) between the twoair flow readings.If you are only using one flow collar or one “Flow Measuring Station”, then, after completing the first reading,transfer this measuring device to the other side of the unit and take the second reading.
VD0052VD0069
10.0 Air Flow Balancing (cont’d)
LOW HIGHFLOW
VP0004
F G
31
BASIC (Can.) / VT1W (U.S.) (6 different control scenarios to be tested)
11.1 MAIN CONTROLSThis procedure allows the installer to verify that all modes of operation are fully functional. During the verification of a main control, make sure that all optional remote controls are inactive.
A precise test of the pollution sensor is only possible in a controlled laboratory environment. The chart belowincludes DETECTOR settings for references purposes only. Test only for scenario #6 as described on next page.
11.0 Overall Verification
POLLUTANT CONTROL
AIR SUPPLY CONTROLY CONTROL L
POLLUTANT CONTROLTANT CONTROLTMAXIMUM SPEED
AIR EXCHANGE IN PROGRESS
MIN. MAX.
CONTINUOUSCONTINUOUS INTERMITTENTTINTERMITTENT
20 MIM N.N.NONON
40 MIN.MOFFOF
Pollutantstst+
S
E
S
IITIVIITY
VC0029
Set the slider Set condensation control Results expectedswitch to dial to fan speed
1 Off maximum counterclockwise motor off2 Off maximum clockwise motor off3 Min. maximum counterclockwise low speed4 Min. maximum clockwise high speed5 Max. maximum counterclockwise high speed6 Max. maximum clockwise high speed
CONDENSATI0N CONTROL
AIR SUPPLY CONTROLY CONTROL L
MIN.
MAX.
OFF
AAIRRIRIEXCHANGECHHA
-20 C-4°
41°F
CO F NE
SUMM
ER
VC0027
Set air supply Set condensation controlResults expected
control to dial toFan Exchange Max speed
speed indicator indicator(A) (B)
1 Off maximum counterclockwise off off off2 Off maximum clockwise off off off3 Min. maximum counterclockwise low on off4 Min. maximum clockwise high on on5 Max. maximum counterclockwise high on off6 Max. maximum clockwise high on on
7 Intermittent maximum counterclockwise off 40 min off 40 min offlow 20 min on 20 min off
8 Intermittent maximum clockwise high on on
ELECTRO (Can.) / VT2W (U.S.) (8 different control scenarios to be tested)
°C-4°F
-5C
41°F
CONDENSATI0N CONTROL
AIR SUPPLY CONTROLY CONTROL L
CONDENSATION CONTROLMAXIMUM SPEED
AIR EXCHANGE IN PROGRESS
MIN. MAX.
CONTINUOUSCONTINUOUS INTERMITTENTTINTERMITTENT
20 MIM N.N.NONON
40 MIN.MOFFOF
CO M Z O E
SUMM
ER
VC0028
DETECTOR (Can.) / VT3W (U.S.) (12 different control scenarios to be tested)
Set air supply PollutantResults expected
control to level:Fan Pollutant Exchange Max speed
speed indicator indicator indicator(C) (A) (B)
1 Off none off off off off2 Off low off on off off3 Off high off on off off4 Min. none low off on off5 Min. low low on on off*6 Min. high high on on on7 Max. none high off on off8 Max. low high on on off9 Max. high high on on on
10 Intermittent none off / 40 min. off off / 40 min. offlow / 20 min. off on / 20 min. off
11 Intermittent low low on on off12 Intermittent high high on on on
B A
CB A
32
Turn dial to maximum clockwise position.Results expected: Motor speed changes to high.NOTE: Appearance may vary.
Humidity Main Control
COT Z NE
F
RELL TIV HU IDI
70%
60%
50%40%
30%
25%
20%
HUMIDITYCONTROL
VC0031
11.2 OPTIONAL CONTROLS
First, turn OFF the main control device (Basic (VT1W), Electro (VT2W), Detector (VT3W) or 3-PositionSwitch before checking the remote optional controls.
20-MINUTE PUSH BUTTON:Activate the push button.
Results expected:1. Motor speed: high for 20 minutes.2. Indicator light goes “ON”.3. Air exchange indicator light goes “ON” (Electro (VT2W) and Detector (VT3W)
wall controls only).
11.0 Overall Verification (cont’d)
ON
VC003060-MINUTE CRANK TIMER:Activate the timer.
Results expected:1. Motor speed: high for either 20, 40, 60 or 80 minutes.2. Indicator light goes “ON”.3. Air exchange indicator light goes “ON” (Electro (VT2W) and Detector (VT3W)
wall controls only).
High speed activation time Position of dial20 minutes 1 to 1940 minutes 20 to 3960 minutes 40 to 5980 minutes 60
OFF
10
20
30
40
50
60
TURNPAST
20
VC0017
*Method for testing the Detector wall control at start-up time (scenario 6).
1. Set the sensitivity knob at the maximum position.2. Plug in the unit and set the AIR SUPPLY CONTROL to MIN.3. Wat 5 minutes.4. Put pollution source (cigarette smoke, perfume or other strong vapors) near the control. Wait for 1 minute. The
unit should switch to high speed.5. Reset the unit (unplug, wait 10 seconds and plug back in) and reset the knob to medium sensitivity before leaving
the house. Warn the occupants that they should wait up to 48 hours before attempting any adjustments to theirwall control. (This waiting period will allow the control te restabilise after the test.)
NOTE: If the pollution level of the surrounding air is very high when you do the test, the test pollutants (see above)might not be strong enough to provoke high speed operation. If this case occurs, then allow the polluted airto clear by operating the unit at MAX. for several hours. Then reset the unit and retry performing the test.
11.1 MAIN CONTROLS (CONT’D)
33
• Review with the user the steps required for the regular maintenance of her/his ventilation system. These steps are described in details in the user manual:
• Warn the user of the necessity to rebalance the system following a major house renovation orfollowing the installation of any extra registers.
• Make sure the user understands how to use the main control as described in the user manual.
• If the unit being installed is an ERV, then make sure the user understands the characteristics ofthe special cold weather TBI mode. The user should understand that his unit will not obey thesettings on the main wall control when the temperature drops below -15°C (5°F). See section 7.5.
12.0 Maintenance / Instructions for User
FOUR TIMES A YEAR:
• Inspect the intake hood, and clean if needed.• Clean the filters.• Clean the interior of the cabinet and clean the door.• Clean the condensation tray and inspect the drain tubing.
ONCE A YEAR:
• Clean the recovery core.• Clean the blades of the blower wheels if needed.
13.0 References
R 2000CLISTED
CLISTED
USMember of Home
Ventilating Institute,AMCA division
• HVI, “Installation Manual for Heat Recovery Ventilators”, 1987 edition.
• ASHRAE 1984 Systems Handbook, chapter 11, “Air Distribution Design for Small Heating andCooling Systems”.
WARNINGRisk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
!
CAUTIONDo not oil the motor. It is already permanently lubricated.
34
Problems Possible causes You should try this
1. Unit doesn't work. • The breaker in the electrical • Reset breaker. If it trips again, unplug the unit and panel may be tripped. call an electrician.
• Erratic operation of the • Unplug the unit. Wait 30 seconds. Plug it back in.electronic circuit.
• The door switch may • Using a multimeter, check for power across the switch.be defective. (The door switch must be pushed in for this test.) If
there is no power, replace the switch.
• The circuit board may • Using a multimeter, check for 12 V DC between thebe defective. YELLOW and BLACK terminals of the circuit board,
or jump BLACK and GREEN terminals. If the motorruns on high speed and the damper opens, circuit board is not defective. (The door switch must bepushed in during this test.) Replace the board if novoltage is detected.
• The 9-pin connector may • Unplug the unit and check to make sure all the crimphave a loose connection. connections are secured. Check the fan motor and
the damper actuator connections as well.
• The fan motor may be • Unplug the unit and disconnect the fan motor (4 wires).defective. Supply 120 V directlyto the GRAY and ORANGE wires
of the fan motor. Replace the motor if it is not working.To remove fan motor assembly, first remove theheat recovery core and the filters. Then, remove thewing nut located on the left side of the unit and slide out the fan motor assembly from its track.
2. The damper actuator • The 9-pin connector may • Unplug the unit and check to make sure all the crimpdoesn't work. have a loose connection. connections are secured. Check the damper actuator
connections as well.
• The damper actuator may be • Feed 120 V directly to the damper actuator. If the defective. problem persists, replace the damper actuator.
• The circuit board may be • Replace the circuit board if the problem is not solveddefective. by the above.
3. The wall control does • TBI mode is activated. • If the outside temperature is below -15°C (5°F) and thenot work OR unit has an enthalpic recovery core (energy recoverythe indicators flashes core), then the TBI mode is probably activated. every 8 seconds. (See Section 7.5.)
• The wires may be in reverse • Ensure that the color coded wires have been connectedposition. to their appropriate places.
• Erratic operation of the • Unplug the unit. Wait 30 seconds. Plug it back in.control every 8 seconds.
• The wires may be broken. • Inspect every wire and replace any that are damaged.
• There may be a short-circuit. • With the help of a multimeter, check for continuity.
• The wire in the wall OR the • Remove the wall control and test it right beside the unitwall control may using another shorter wirer. If the wall control works there,be defective. change the wire. If it doesn’t, change the wall control.
• The circuit board may • If the second wall control does not solve the problem,be defective. then replace the circuit board.
Start-up troubleshooting:Note: Be sure to unplug and inspect the unit before proceeding with these steps.
14.0 Troubleshooting
35
Problems Possible causes You should try this
4. The indicators flash • Erratic operation of the • Unplug the unit. Wait 30 seconds. Plug it back in.every second. electronic board.
• The wall control may be • Replace the wall control if the above test does not defective. settle the problem.
5. The dehumidistat • The dehumidistat • Jump the dehumidistat wires. If the unit switches to high doesn't work. may be defective. speed, replace the dehumidistat.
• The wiring may be defective. • If the problem is not solved by the above test thencheck the wiring (as in point 3 on page 34).
6. The 20-minute push-button • The wires may not be • Ensure that the color coded wires have been switch doesn’t work OR connected properly. connected to their appropriate places.its indicator lightdoesn’t stay on.
• The switch may be • Jump the OL and OC terminals. If the unit switchesdefective. to high speed then the wires are not the problem.
Replace the switch.
7. The defrost cycle • Ice deposits may be hindering • Remove the ice.doesn't work the damper operation.(the fresh air duct is frozen OR the fresh air •The damper rod or the port • Inspect these parts and replace if necessary.distributed is very cold damper itself may be broken.OR the “AIR EXCHANGE”light flashes). • The damper actuator may • Plug in the unit and select “MIN” or “MAX”. Press
be defective. the door switch and see if the port damper opens.If it doesn’t open, feed 120V directly to the damperactuator. If the port damper still doesn’t open, replace the damper actuator.
• The circuit board may • Unplug the unit. Unplug the defrost sensor wire (seebe defective. J4 on electrical diagrams, Section 9.0). Plug the unit
back in. Select “MIN” and make sure the unit isadjusted for low speed operation (turn all dehumidistats maximum counterclockwise). Wait 3 minutes. Theunit should switch to high speed and the damper at the fresh air intake port should close (defrost mode). If this doesn’t happen, then replace the circuit board.
• The thermistor may be • If the defrost mode works well after having disconnecteddefective. the thermistor wire (above test), this means the
thermistor is probably defective. You should replace it.
14.0 Troubleshooting (cont’d)
36
Long term troubleshooting:
Problems Possible causes You should try this
8. Cold air at registers. • The registers are poorly located. • Relocate the registers according to instructions in Section 6.5.
• The temperature outside is • Suggest adding a “duct heater” in the system. Considerextremely cold. connecting the “extended defrost” option (see wiring
diagrams, Section 9.0).
• The system needs rebalancing. • Rebalance the system (see Section 10.0).
• The defrost is not working. • See point 7 on page 35.
9. Persistent condensation • Refer to user manual, page17, • Refer to user manual, page 17 and pages 11 to 15.on windows. point 4.
• Dehumidistat defective. • See point 5 on page 35.
• Occupants might need more • Suggest installing additional timers or dehumidistats.controls.
• Hot tubs or pools present. • Cover these sources of humidity.
• Firewood in the house. • Store wood in a closed room with a dehumidifier or have the room well ventilated with outside air orstore the wood outside.
• Unheated crawl space. • Prevent circulation of air from the crawl space to thehouse. If the crawl space has an earth floor, cover itwith a vapor barrier and 2 to 3 inches (5 to 8 cm) of gravel.
10. Noisy unit. • Fan wheel is out of adjustment. • Remove the fan assembly and tighten the loose parts.
• Blower wheel dirty. • Remove, clean and review with user the maintenancerequirements in his manual.
• Damaged fan assembly. • Replace.
• Unbalanced wheel. • Replace.
11. Noisy registers • The air ducts are too short. • Install a silencer.at MAX. speed.
• The register is too small. • Replace with a larger register.
12. Very little or no air flow. • Dirty filters, exterior hoods • Clean filters and/or hoods and review with user theclogged up. maintenance instructions in his manual.
• The system may need • Rebalance (see Section 10.0). rebalancing.
13. Snow in the unit. • The exterior intake hood is • Clear snow away from hoods and warn user he/shepoorly located. should regularly remove snow from near the
exterior hoods.
• Install the “anti-gust intake hood”, part number 12570.• Turn the unit off during snowstorms.
14. Condensation, frost or ice •The duct insulation is defective • Make sure there are no tie ducts or duct tapeinside the insulated ducts. and /or the vapor barrier is torn. compressing the insulation. Check the insulated
ducts for any damaged or weak spots.
14.0 Troubleshooting (cont’d)