Variable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM Navigant Consulting, Inc.

Transcript of Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow...

Page 1: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

Variable Refrigerant Flow (VRF) Systems for Commercial

HVAC Bill Goetzler, CEM

Navigant Consulting, Inc.

Page 2: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

BackgroundWhat is VRF?

V R F

Variable Refrigerant Flow• In Japan, VRF is used in half of medium-sized commercial

buildings (<70,000 ft2) and ~ 1/3 of larger buildings• Very popular throughout Asia and Europe• Numerous suppliers worldwide:

– Daikin, Mitsubishi Electric, Hitachi, Sanyo, Fujitsu, Panasonic, Toshiba-Carrier, LG, MHI, Samsung

– At least 5 manufacturers selling in the U.S.

Page 3: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Technology OverviewVRF competes most naturally with a chillerOutdoor UnitOutdoor Unit Indoor UnitsIndoor Units

Key Attributes:-• Energy Efficient• Individual, tight temperature control• Very Quiet• Numerous zones• Large capacity but modular • Centralized plant with long refrigerant piping• Wide range of units• Advanced BAS control• Premium Price

Page 4: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Technology OverviewVRF Concept – System Design

• Single Outdoor Unit With Multiple Indoor Units

• Individual Control• Modular Build-up

• Energy Saving especially @ part-load

• Cost Effective• Low Noise

With proper engineering, code compliance with ASHRAE Standard 15 and Standard 62.1 is not a problem. Europe & Japan have analogous codes

Page 5: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Technology OverviewVRF Concept – Heat Transfer Media (8 ton example)

RefrigerantRefrigerant RR--410A410A

AirAir

WaterWater

Ø 7/8“ Ø 3/8“ Ø 2“ Ø 2“

�Ø25

½“ 49“

16“

24“

24“

or

Always twoducts needed

or

Page 6: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Technology OverviewVRF Concept – How does it operate?

Large SmallLoad

Non-inverter

Inverter

Inverter

Capacity Control100%

CompressorCapacityControl

14%

Page 7: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

BenefitsEnergy Efficiency

Partial Load Performance

0.0

2.0

4.06.0

8.0

10.0

12.014.0

16.0

18.0

10% 20% 30% 40% 50% 60% 70% 80% 90% 100%Load

EER75%

595

340

680

340

170

425510

255

85

Operation Hours of Main Machine

75%75% ofof total operationtotal operationhourshours-- less than less than 70%70% of of full loadfull load

And Virtually Eliminates duct losses

ARI Rating System in

Development

Page 8: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

BenefitsFlexible Configurations

On a single refrigerant piping network, up to 41 indoor units, including ducted and ductless, with varying capacities from ~0.5 – 4 ton per indoor unit.

Page 9: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

BenefitsHeat Recovery for Simultaneous Heating & Cooling

Same Operation modebut individual control

CoolingOnly

Individual Cool/Heat Changeover

Heat absorbed by indoor units in cooling mode is used in areas that require heating.

Page 10: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Technology OverviewEase of Installation:

Modularity, Size & Weight, fits in an elevator

Small footprint for rooftop, balcony, or machine room installation

Page 11: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

BenefitsComfort- Uses PID logic for tight control when room

to setpoint differential is +/- 3 °F

Set point temperature

Temp.

Time

Inverter power

control

Non Inverter type

Inverter Cools a room quickly

Inverter/VRF: Small temp. difference

Non-Inverter: Large Temp. Difference

Page 12: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

BenefitsExtremely Low Sound Levels

Indoor unitsIndoor units

3 ft3 ft

Indoor Unit Tonnage

1 2 3

Sound level db (A) at low speed

28 29 33

Page 13: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

BenefitsSophisticated Controls & Diagnostics

Fire alarm Security

LocalController

HRV

Ethernet

Power supply facility

BMS

~

~

System

Page 14: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

BenefitsFlexible, Advanced Controls & Diagnostics

Full color LCD Touch screen

Power Proportional Distribution (Hourly data)

Simple operation

Multi language

Max 64 groups

Max 10 Outdoor

Units

Web enabled

Self-Diagnostics: 66 malfunction

codes

Page 15: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Lille, France: Historic building- hotel built in 1460

Sample Installations

• 71 ducted indoor units installed• Provide heating and cooling to

guest rooms and central areas• All piping totally concealed • Outdoor units must not be seen

or heard• 9 VRF Heat Pump outdoor units

in sound proofed machine room • 75 Tons of fully modulating and

zoned air conditioning capacity

Page 16: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Dalian, China: 32 story, 500,000 ft2 office building• 212 Heat Pump outdoor units• 539 indoor units• 1,753 tons of cooling• Access panel behind each unit

so that service can be done from the inside of the building

Sample Installations

Page 17: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Types of VRF Types of VRF Systems Available• Air-Cooled (vs. small – large chillers)• Water-cooled (vs. medium – large chillers)• 208-230V/3-phase (renovation)• 460V/3-phase (new construction)• Heat Pump (vs. 2-pipe chiller)• Simultaneous heating & cooling (vs. 4-pipe

chiller)

Page 18: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Ongoing Challenges• Completion of ARI Rating Standard and

certification program• Incorporation into Energy Plus, EnergyPro,

E-Quest and DOE-2• Integration of outside air with VRF• Broadening the installer base

Page 19: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Conclusions• VRF is a viable alternative to chillers in many

cases, but many applications are better served by chillers or rooftop DX

• Energy savings and other benefits are application-specific and must be evaluated on case-by-case basis

• 25 year operating history throughout the world• Additional details: manufacturer websites and

ASHRAE Journal article April 2007: http://www.ashrae.org/doclib/20070327_goetzler.pdf

Page 20: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)

August 3-6, 2008

Bill Goetzler

Would you like to know more about this session?

• Bill Goetzler, Associate Director• Navigant Consulting, Inc.• 77 South Bedford Street, Suite 400

Burlington, MA 01803• [email protected]• Don’t forget to fill out and drop off your session

evaluations.

Page 21: Variable Refrigerant Flow (VRF) Systems for Commercial · PDF fileVariable Refrigerant Flow (VRF) Systems for Commercial HVAC Bill Goetzler, CEM ... • Heat Pump (vs. 2-pipe chiller)