Vapor absorption machine - Thermax - Presentation

16
VAPOUR ABSORPTION MACHINES Presented by - Cooling Division – C&H SBU - Thermax

description

The attached presentation would give you a general idea about the concept of Vapor Absorption Heat Pump,which would provide chilled water with heat energy as the driving source and requiring the least amount of power consumption.

Transcript of Vapor absorption machine - Thermax - Presentation

Page 1: Vapor absorption machine - Thermax - Presentation

VAPOUR ABSORPTION MACHINES

Presented by - Cool ing Divis ion – C&H SBU - Thermax

Page 2: Vapor absorption machine - Thermax - Presentation

Welcome to the home of Energy & Environment

We have tried to answer the following questions, so that, it would help you understand the product in a much easier way

• Who are you and what do you do?• What is Cooling and what are the conventional methods of cooling?• How does an Electrical Chiller work?• When should one go for an Absorption Chiller and how did a VAM

evolve in Thermax?• Why should one go for an Absorption Chiller?• What are the governing principles of a VAM?• How does an Absorption Machine work?• Can you explain the whole scheme?• What do we offer and where we can/have offered?• I have more queries, how can I get them cleared?• How can we reach you?

Page 3: Vapor absorption machine - Thermax - Presentation

Who are you and what do you do?

Vision – To be a globally respected high performance organization offering sustainable solution in energy and environment

Boilers & Heaters

Absorption Cooling

Water & Waste

Solutions

Air Pollution Control

Chemicals

Cogeneration

SolarHeating,Cooling

&Power

Solutions

Page 4: Vapor absorption machine - Thermax - Presentation

What is Cooling and what are the conventional methods of cooling?

Cooling – Removal/Transfer of heat from source to sink by performing an external work; even a body @ -272*C has one more degree of heat energy to be removed to achieve absolute zero (i.e.), 0*K (or) -273*C

1 TR = 3024KCal = 3.52KW = amount of energy absorbed by 1ton of ice, when it melts to water, at 0*C

CONVENTIONAL METHODS OF COOLING:Natural Refrigeration

E.g., Clay water pot, SweatingMechanical Refrigeration

Gas Refrigerators Vapour Refrigerators

Vapour Compression Vapour Absorption

Page 5: Vapor absorption machine - Thermax - Presentation

How does an Electrical Chiller work?

Parts & Process involved: Evaporator - Refrigerant Vapourization Compressor - Refrigerant (Vapour Phase)

Compression Condenser - Refrigerant ---> Vapour to

Liquid Expansion Valve - Pressure Reducer / Throttling

Valve – To help refrigerant achieve the required

Temperature

Page 6: Vapor absorption machine - Thermax - Presentation

Working CycleVapour Compression Machine

Reefer Cycle.swf

Page 7: Vapor absorption machine - Thermax - Presentation

When should one go for an Absorption Chiller and how did a VAM evolve in

Thermax?

We would go for an Absorption Chiller: When excess heat source is available, for e.g., availability of excess

steam in a boiler When Heat is ineffectively dissipated into the atmosphere, for e.g.,

exhaust from a D.G, steam from a turbine outlet When the operational expenditure of VAM is very much lesser than the

VCM, for e.g., when the industry is facing issues with power supply from the grid (high cost/frequent power cuts)

When the production cost of steam is almost negligible, for e.g., In sugar plants, they have a co-gen power plant by using the baggasse (a by-product of the process)

Evolution of VAM technology in Thermax: 1984-87 – Marketing tie-up with Sanyo, Japan 1988-94 – Technology collaboration with Sanyo, Japan 1991-96 - Direct Fired – Technology tie-up – Kawasaki Till Date – Installed over 3500 Machines in over 70 Countries

Page 8: Vapor absorption machine - Thermax - Presentation

Why should one go for an Absorption Chiller?

We should go for an Absorption Chiller, because: It is a simple Heat Exchanger operating at different pressures,

hence, we can assure that it has an unmatched Reliability It has a very less operating and maintenance cost, along with

an automatic and step-less modulation system It does not have any moving parts, hence, no noise, no

vibration and no dynamic load (Roof-top positioning is possible) Waste heat is utilized usefully and in-turn, avoids the need for

switching to a HT connection and also avoids a DG running especially for the chilling purpose (the load on EB power and DG is reduced to a huge extent)

It operates on an environment friendly refrigerant (i.e.), CFC free, ozone friendly machine

It is fully automated, hence, we require minimal amount of human intervention

Page 9: Vapor absorption machine - Thermax - Presentation

What are the governing principles of a VAM?

Working Materials – VAM Refrigerant – DM Water Salt – Lithium Bromide (LiBr)

Boiling Point of Water is directly proportional to the Vapour Pressure of the system @atm. Pressure (760mm of Hg) – Water boils @100*C In VAM, we maintain a shell pressure of 6mm of Hg, which

facilitates the water to boil @3.7*CHygroscopic nature of Salt

As we need to separate salt and water, it has to have a higher Vapour pressure difference, hence, we use LiBr as the salt

The operating concentration of LiBr lies between 57-64% in Water

Page 10: Vapor absorption machine - Thermax - Presentation

How does an Absorption Machine work?

Parts & Process involved: Evaporator – Refrigerant

Vapourization Absorber – Refrigerant (Vapour)

– Absorption by Absorbent

Generator – Regeneration of Refrigerant & Absorbent

Condenser – Liquefaction of Refrigerant

Totally we have 2 Shells: Lower Shell – Evaporator and

Absorber Upper Shell – Generator and

Condenser

Page 11: Vapor absorption machine - Thermax - Presentation
Page 12: Vapor absorption machine - Thermax - Presentation

Can you explain the whole scheme?

Page 13: Vapor absorption machine - Thermax - Presentation

What do we offer and where we can/have offered?

We offer, Steam Fired VAM – 50 to 3500TR Exhaust Fired VAM – 50 to 3500TR Direct Fired VAM – 50 to 3000TR Hot Water Fired VAM – 50 to 1150TR

We had offered to, Automotive Industry Breweries & Distilleries Chemical Industry Commercial Centers Dairy & Confectionary Educational Institutions Engineering & Electronic Industry Hotels & Hospital

Medical Centers Paper Plants Pharmaceuticals Power Plants Refineries & Petro-chemicals Steel Plants Super Markets & Malls Tyre Industry

Combination of two or three heat sources are possible:COGENIE or TRIGENIE

Page 14: Vapor absorption machine - Thermax - Presentation

I have more queries, how can I get them cleared?

Thank you for your patient viewing & hearingWe hope that we have answered the questions

which may rise, when you think of an absorption machine. If you have any of the feasible scenarios for an absorption machine, we are always on your search-list. We would be very much delighted to work in one- breath with you for a greener, energy efficient future

For anymore queries, please feel free to contact the respective regional sales engineer or visit www.thermaxindia.com and post your query

The contact details are given below

Page 15: Vapor absorption machine - Thermax - Presentation
Page 16: Vapor absorption machine - Thermax - Presentation