Electronics Manual Valve terminals Field bus direct Field bus protocol: PROFIBUS−DP as per EN 50170 Type CPA−SC−DP Type CPV−SC−DP Valve terminals CPA−SC/CPV−SC PROFIBUS−DP Manual 548 726 en 0610NH [705 996]

Transcript of Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo...

Page 1: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Electronics Manual

Valve terminals Field bus direct

Field bus protocol:PROFIBUS−DPas per EN 50170

Type CPA−SC−DPType CPV−SC−DP

Valve terminals

CPA−SC/CPV−SC PROFIBUS−DP

Manual548 726en 0610NH[705 996]

Page 2: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade
Page 3: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

I

Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Edition en 0610NH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Designation P.BE−CPASC−CPVSC−DP−EN. . . . . . . . . . . . . . . .

Order no. 548 726. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

© (Festo SE�&�Co. KG, D�73726 Esslingen, Germany, 2006) Internet: http://www.festo.comE−Mail: [email protected]

The reproduction, distribution and utilization of this document as well as the communicaton of its contents to others without express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility module or design.

Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Page 4: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

PROFIBUS,PROFIBUS−DP�® are registered trade marks of PROFIBUS International (P.I.)

SIMATIC�® is a registered trade name of Siemens AG

TORX�® is a registered trade name of CAMCAR TEXTRON INC.,Rockford, Ill., USA

Page 5: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

IIIFesto P.BE−CPASC−CPVSC−DP−EN en 0610NH

Contents

Designated use of the valve terminals VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Notes on the use of this manual VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Important user instructions IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. Installation 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 General notes on installation 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Setting the rotary and DIL switches 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.1 Setting the station number 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.2 Deactivating the device−related diagnosis 1−7 . . . . . . . . . . . . . . . . . . . .

1.2.3 Setting the CP extension 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3 Connecting to the field bus 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.1 Field bus cable 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.2 Field bus baud rate and field bus length 1−10 . . . . . . . . . . . . . . . . . . . . .

1.3.3 Field bus interface 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.4 Connection possibilities 1−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4 Bus connection with terminating resistors 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Power supply 1−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.1 Calculating the current consumption 1−14 . . . . . . . . . . . . . . . . . . . . . . . .

1.5.2 Selecting the cable 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.3 Selecting the power unit� 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.4 Connect the power supply of the valve terminal 1−16 . . . . . . . . . . . . . . .

1.6 Extending the CP...−SC−DP on the CP extension connection 1−22 . . . . . . . . . . . . . .

1.6.1 Rules for extending the CPI system 1−24 . . . . . . . . . . . . . . . . . . . . . . . . .

Page 6: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

IV Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2. Commissioning 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 Preparing the valve terminal for commissioning 2−3 . . . . . . . . . . . . . . . . . . . . . .

2.1.1 Switching on the operating voltages 2−3 . . . . . . . . . . . . . . . . . . . . . . . .

2.1.2 Address assignment � CPA−SC−DP 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.3 Address assignment � CPV−SC−DP 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.4 Address assignment of CPI/CP modules 2−7 . . . . . . . . . . . . . . . . . . . . .

2.2 Commissioning on the PROFIBUS−DP 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Device master file (GSD) and icon files 2−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Configuration with a Siemens master 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.1 STEP 7 � HW Config (up to V 5.2) � preparations 2−12 . . . . . . . . . . . . . .

2.4.2 Station selection with STEP 7 2−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.3 Configuration with STEP 7 2−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.4 Tool change configuration 2−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5 Examples of configuration 2−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.1 Standard configuration 2−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.2 Tool change configuration 2−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3. Diagnosis 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Diagnosis via LEDs 3−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.1 Normal operating status 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.2 Fault displays 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.3 LEDs for status display of the valve solenoid coils 3−8 . . . . . . . . . . . . .

3.2 Reaction to faults in the control system 3−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Diagnosis via PROFIBUS−DP 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 Diagnosis steps� 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.2 Overview of the diagnostic bytes� 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.3 Details on standard diagnostic information 3−14 . . . . . . . . . . . . . . . . . . .

3.3.4 Details of the identification−related diagnosis 3−16 . . . . . . . . . . . . . . . . .

3.3.5 Channel−related diagnosis 3−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.6 Diagnosis with tool change configuration 3−19 . . . . . . . . . . . . . . . . . . . .

3.3.7 Siemens SIMATIC S5/S7 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Online diagnosis with STEP 7 3−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.1 Read out diagnostic buffer with STEP 7 (up to V 5.2) 3−23 . . . . . . . . . . .

3.4.2 Channel−related diagnosis with STEP 7 (up to V�5.3) 3−25 . . . . . . . . . . .

Page 7: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

VFesto P.BE−CPASC−CPVSC−DP−EN en 0610NH

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical specifications A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Accessories A−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B. General DP master B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1 PROFIBUS−DP: Commissioning with the general DP master B−3 . . . . . . . . . . . . .

B.1.1 Bus start B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.2 Send parametriziung data B−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.3 Check the configuration data� B−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.4 Transferring input and output data B−7 . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.5 Read diagnostic information B−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.6 Implemented functions and service access points (SAP) B−8 . . . . . . . .

B.1.7 Bus parameters/reaction times� B−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.8 Transmission times on the PROFIBUS−DP B−9 . . . . . . . . . . . . . . . . . . . .

C. Index C−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 8: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

VI Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Page 9: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

VIIFesto P.BE−CPASC−CPVSC−DP−EN en 0610NH

Designated use of the valve terminals

The valve terminals of types CPA−SC−DP and CPV−SC−DP with

field bus direct connection described in this manual are in�tended exclusively for use as slaves on the PROFIBUS−DP.

The valve terminals may only be used as follows:

� as designated in industrial applications.

� without any modifications by the user. Only the conver�sions or modifications described in the documentationsupplied with the product are permitted.

� in faultless technical condition.

The maximum values specified for pressures, temperatures,electrical data, torques etc. must be observed.

If additional commercially−available components such as sen�sors and actuators are connected, the specified limits forpressures, temperatures, electrical data, torques, etc. mustnot be exceeded.

Observe also the standards specified in the relevant chapters,

as well as national and local laws and technical regulations.

If implementing an emergency stop function, note themeasures listed in section 1.5.4.

Page 10: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

VIII Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Notes on the use of this manual

Areas of application and approval by authorities

Certain configurations of the product have been approved bythe Underwriters Laboratories Inc. (UL) as �UL�RecognizedComponent" for the USA and Canada. These configurationsare marked as follows:

Only for connection to a 24 V DC NEC Class 2 supply.Raccorder Uniquement a un circuit de Classe 2.

Please notePlease note the following if this product is intended for usein the USA and Canada:

� Rules for observing the UL approval can be found in theseparate UL−specific brief operating instructions. Therelevant technical specifications listed there also applyhere.

� The technical specifications in this documentation mayshow different values.

Target group�

This manual is intended exclusively for technicians trained incontrol and automation technology who have experience ininstalling, commissioning, programming and diagnosing

slaves on the field bus named.

Information on the pneumatics can be found in:1. CPA−SC: Pneumatics Manual P.BE−CPASC−..2. CPV−SC: Pneumatics Manual P.BE−CPVSC−..

Service

Please consult your local Festo repair service if you have anytechnical problems.

Page 11: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

IXFesto P.BE−CPASC−CPVSC−DP−EN en 0610NH

Important user instructions

Danger categories

This manual contains instructions on the possible dangerswhich may occur if the product is not used correctly. Theseinstructions are marked (Warning, Caution, etc.), printed on ashaded background and marked additionally with a picto�gram. A distinction is made between the following dangerwarnings:

WarningThis means that failure to observe this instruction mayresult in serious personal injury or damage to property.

CautionThis means that failure to observe this instruction mayresult in personal injury or damage to property.

Please noteThis means that failure to observe this instruction mayresult in damage to property.

The following pictogram marks passages in the text whichdescribe activities with electrostatically sensitive compo�nents.

Electrostatically sensitive components may be damaged ifthey are not handled correctly.

Page 12: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

X Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Marking special information

The following pictograms mark passages in the textcontaining special information.

Pictograms

Information:Recommendations, tips and references to other sources ofinformation.

Accessories:Information on necessary or sensible accessories for theFesto product.

Environment:Information on environment−friendly use of Festo products.

Text markings

· The bullet indicates activities which may be carried out inany order.

1. Figures denote activities which must be carried out in thenumerical order specified.

� Hyphens indicate general activities.

Page 13: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

XIFesto P.BE−CPASC−CPVSC−DP−EN en 0610NH

The following product−specific terms and abbreviations areused in this manual:

Term/abbreviation Meaning

CP Compact performance

CP connection Plug or socket on the CP modules which enable the modules to beconnected with the aid of the CP cable.

CP functions Supports the CP protocol without extended functions

CP string CPI or CP modules which are connected via a CPI/CP cable and to a CPImaster. For reasons of simplicity, only the term �CP string" is used, evenif it has CPI functions.

CP system Complete electrical installation system consisting of a CP master withone or more CP strings. The system consists of CP modules (withoutextended functions).

CPA−SC CPA Smart Cubic valve terminal, type 82

CPI/CP cable Special cable for connecting the different CPI/CP modules. CPI cablesare required for CPI modules with extended functions.

CPI/CP modules Collective term for the various modules that can be incorporated in aCPI/CP system.

CPI functions Supports the CPI protocol with extended functions

CPI master The CP...−SC−DP is a CPI master. CPI modules with extended functionscan be connected to the CP extension connection.

CPI system Complete electrical installation system consisting of a CP master withone or more CP strings. The system consists of CPI/CP modules withand without extended functions. The system need not consistexclusively of CPI modules.

CPV−SC CPV Smart Cubic valve terminal, type 80

I Digital input

I/O modules Common term for the CP modules which provide digital inputs andoutputs (CP input modules and CP output modules).

I/Os Digital inputs and outputs

Load voltage Power supply for valves

Page 14: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Contents and general instructions

XII Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Term/abbreviation Meaning

O Digital output

Operating voltage Power supply for the electronics

PLC/IPC Programmable logic controller/industrial PC

Tab.�0/1: Product−specific terms and abbreviations

Page 15: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Installation

1−1Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Chapter 1

Page 16: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−2 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Contents

1. Installation 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 General notes on installation 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Setting the rotary and DIL switches 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.1 Setting the station number 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.2 Deactivating the device−related diagnosis 1−7 . . . . . . . . . . . . . . . . . . . .

1.2.3 Setting the CP extension 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3 Connecting to the field bus 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.1 Field bus cable 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.2 Field bus baud rate and field bus length 1−10 . . . . . . . . . . . . . . . . . . . . .

1.3.3 Field bus interface 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.4 Connection possibilities 1−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4 Bus connection with terminating resistors 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Power supply 1−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.1 Calculating the current consumption 1−14 . . . . . . . . . . . . . . . . . . . . . . . .

1.5.2 Selecting the cable 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.3 Selecting the power unit� 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5.4 Connect the power supply of the valve terminal 1−16 . . . . . . . . . . . . . . .

1.6 Extending the CP...−SC−DP on the CP extension connection 1−22 . . . . . . . . . . . . . .

1.6.1 Rules for extending the CPI system 1−24 . . . . . . . . . . . . . . . . . . . . . . . . .

Page 17: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−3Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.1 General notes on installation

WarningSudden unexpected movements of the connected actua�tors and uncontrolled movements of loose tubing cancause injury to human beings and/or damage to property.

· Make sure that the higher−order controller has not sentcontrol signals to the valve solenoid coils.

· Switch off the following on the CP...−SC−DP beforecarrying out conversion work:

� the compressed air supply

� the power supply.

Please noteThe CP...−SC−DP valve terminal contains electrostaticallysensitive components.

� Do not therefore touch the electrical contacts of thecomponents.

� Observe the regulations for handling electrostaticallysensitive components.

You will then prevent the electronics from being damaged.

Please notePlease note the following if this product is intended for usein the USA and Canada:

� Rules for observing the UL approval can be found in theUL−specific brief operating instructions. The relevanttechnical specifications listed there also apply here.

� The technical specifications in this documentation mayshow different values.

Page 18: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−4 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Electrical connections and operating elements

You will find the following connections and operatingelements on the valve terminals type CP...−SC−DP:

1 2

56

1 2 4

564 7

3

7

3

CPA−SC−DP CPV−SC−DP

8 8

1 Rotary switch for station number

2 DIL switch for CP extension and fordeactivating the device−relateddiagnosis

3 LEDs (see section 3.1)

4 Earth connection

5 Connection for CP extension

6 Connection for power supply

7 Connection for field bus

8 Cover (for IP40)

Fig.�1/1: Electrical connections and operating elements

Page 19: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−5Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.2 Setting the rotary and DIL switches

1 2

Address

3

1 Setting the station number

2 Device−related diagnosis deactivated/activated

3 Setting/recognizing the CP extension

Fig.�1/2: Rotary and DIL switches on the CP...−SC−DP

Page 20: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−6 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.2.1 Setting the station number

Set the PROFIBUS address of the valve terminal by means of

the rotary switches.

Station numbers between 0 and 125 are permitted. Station

numbers may only be assigned once per field bus master.

If a non−permitted station number is set, the BF LED will flashfast (see section 3.1).

Station number set: 05 Station number set: 110

Tab.�1/1: Examples of set station numbers

Page 21: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−7Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.2.2 Deactivating the device−related diagnosis

You can deactivate the device−related diagnosis with DILswitch element 2 (see also section 3.3):

Device−related diagnosis Position ofDIL�switches

DIL switch element 2 = OFF:Device−related diagnosis activated(factory setting)

234 1

ON

OFF

DIL switch element 2 = ON:Device−related diagnosis deactivated

234 1

ON

OFF

Tab.�1/2: Deactivate the device−related diagnosis

Switch elements 3 and 4 are reserved (position: OFF).

Page 22: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−8 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.2.3 Setting the CP extension

Further CPI/CP modules can be connected to the CP connec�tion of the CP...−SC−DP (see section 1.6).

Recognition is controlled by DIL switch element 1:

Extending the valve terminal Position of theDIL�switches

If no CP extension is connected, switch element 1 must be set to OFF. 234 1

ON

OFF

Modifying the CP extension (adding or removing CPI/CP modules):1. Switch off all sources of energy (voltage, compressed air).2. Connect or remove CPI/CP modules3. Set DIL1 to ON.4. Switch on the operating voltage (electronics) again.

The CP...−SC now searches for connected CPI/CP modules.

234 1

ON

OFF

If modifications to the CP configuration are recognized, the SF LED willflash.

5. Set DIL1 to OFF again. Then set to ON again and leave it on.

The CP system is now configured and ready to run (LED SF is out).

234 1

ON

OFF

If modifications have been made to the CP extension:6. Start the recognition procedure again (steps 1 ... 5).

Tab.�1/3: Set the CP extension with DIL switch element 1

Please noteThe CP system will occupy a different number of input andoutput addresses depending on the extension recognized.The CP...−SC−DP supports CPI modules with extended func�tionality. Further information can be found in section 1.6.

Page 23: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−9Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.3 Connecting to the field bus

1.3.1 Field bus cable

Please noteIf installation has not been carried out correctly and if highbaud rates are used, data transmission errors may occuras a result of signal reflections and attenuations.Causes of the transmission faults may be:

� missing or incorrect terminating resistor

� incorrect screening/shield connection

� branches

� transmission over long distances

� unsuitable cables.

Observe the cable specifications. Refer to your controllermanual for information on the type of cable to be used.

Please noteIf the valve terminal is fitted into a moving part of amachine, the field bus cable on the moving part must beprovided with strain relief. Please observe also the relevantregulations in EN�60204 part 1.

Page 24: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−10 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Use a twisted screened 2−core cable for the field bus inaccordance with PROFIBUS specifications (EN 50170, cabletype A):

Surge impedance: 135 ... 165 � (3 ... 20 MHz)Capacitance per unit length: < 30 nF/kmLoop resistance: < 110 �/kmCore diameter: > 0.64 mmCore cross−sectional area: > 0.34 mm2

Bus length Exact specifications on the bus length can be found in thenext section and in the manuals for your control system.

1.3.2 Field bus baud rate and field bus length

Please noteThe maximum permitted field bus segment lengths dependon the baud rate used.

· Note the maximum permitted segment length (cablelength without repeater), if you connect the SFC−DC to afield bus segment.

· Avoid branch lines.

The valve terminal sets itself automatically to one of thefollowing baud rates:

Baud rate Maximum segment length

9.6; 19.2; 93.75 kBaud 1200 m

187.5 kBaud 1000 m

500 kBaud 400 m

1500 kBaud 200 m

3000 ... 12000 kBaud 100 m

Tab.�1/4: Maximum field bus segment lengthsforPROFIBUS−DP depending on the baud rate

Page 25: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−11Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.3.3 Field bus interface

There is a 9−pin sub−D socket on the valve terminal forconnecting it to the field bus.This connection serves for the incoming and continuing field

bus cable.

Pin PROFIBUS−DP Designation

123456789Housing

Screening/shieldn.c.RxD/TxD−PCNTR−P 2)

DGNDVPn.c.RxD/TxD−Nn.c.Screening

Connection to functional earthnot connectedReceive/transmit data PRepeater control signal (TTL)Data reference potential (M5V)Power supply positive (P5V)not connectedReceive/transmit data Nnot connectedConnection to functional earth

Socket on valve terminal

Tab.�1/5: Pin assignment of the field bus interface

Page 26: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−12 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.3.4 Connection possibilities

Field bus plug

Use the following for connecting the field bus plug forPROFIBUS: Possible plugs with protection class IP40 e.g.:

� Siemens 6ES7 972−0BA10−0XA0

� Siemens 6ES7 972−0BA20−0XA0

Connection with optical−fibre waveguide

The PROFIBUS−DP interface of the node complies with specifi�cation EN 50170−2 and supports the control of network com�ponents for optical fibre waveguides.

Use optical−fibre waveguides when transmission is affectedby heavy interference, as well as for extending the trans�mission range when high baud rates are used.

Example of optical−fibre waveguide network components:

� Siemens Optical Link Module (OLM) for PROFIBUS plus

� Siemens Optical Link Plug (OLP) for PROFIBUS (IP20)

� Harting Han−InduNet® Media converter IP65 in combina�tion with adapter cable for Festo products (optical datatransmission in DESINA installation concept).

Page 27: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−13Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.4 Bus connection with terminating resistors

Please noteIf the valve terminal is at the beginning or the end of thefield bus system, a bus termination will be required.

· Fit a bus termination to both ends of a bus segment.

RecommendationUse a ready−made field bus plug with a suitable resistancenetwork in the housing for the bus connection (see Fig.�1/3).This can be activated/deactivated by a switch.

Receive/send data P(data cable B)

Receive/send data N(data cable A)

390 �

390 �

220 �

Pin 6: Supply voltage

Pin 5: Data reference potential

Pin 3

Pin 8

120 nH

120 nH

Fig.�1/3: Circuit diagram for bus termination network forcable type A as per EN 50170

Page 28: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−14 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.5 Power supply

1.5.1 Calculating the current consumption

· Calculate the current consumption before selecting powerunits, cables and fuses:

Current consumption Sums

Electronics and sensors (pin 1)

CP...−SC−DP 200 mA

In the CP extension:

Valve terminal 1) or CP output module 1) ___________ mA

CPI/CP input module 1) ___________ mA

Sensors 1) on the CPI/CP input module ______ x ______ mA ___________ mA

Sum of pin 1 = _________ mA

Valves and outputs (pin 2)

CP...−SC−DP: all energized simultaneously Solenoid coils 2) 3) ______ x ______ mA __________ mA

In the CP extension:

All solenoid coils energized simultaneously 2) 3) ______ x ______ mA __________ mA

All digital outputs 1) 4) ______ x ______ mA __________ mA

Sum of pin 2 = _________ mA

Total = ________ mA

1) See technical specifications for the relevant product.2) The valves have one or two solenoid coils depending on the type.3) When switching on, with LEDs.4) If not with own load voltage supply.

Tab.�1/6: Calculating the current consumption

Page 29: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−15Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.5.2 Selecting the cable

· Calculate the necessary cross−sectional area and themaximum permitted cable length.

· Avoid long distances between the power unit and thevalve terminal. Long cables reduce the voltage supplied

by the power unit.

1.5.3 Selecting the power unit�

Warning· For the power supply use only PELV circuits as perIEC/DIN EN 60204−1 (Protective Extra−Low Voltage,PELV).Take into account also the general requirements forPELV circuits as per IEC/DIN EN 60204−1.

· Use only power packswhich guarantee reliable electricalisolation of the operating voltage as per IEC/DINEN�60204−1.

By the use of PELV power units, protection against electricshock (protection against direct and indirect contact) is guar�anteed in accordance with IEC/DIN EN 60204−1 (electricalequipment of machines, general requirements).

The current requirement of a CP system depends on thenumber of CP modules and valve coils. Recommendation:

· Use closed−loop controlled power units.

· When selecting the power unit, check that it provides

sufficient output. Calculate the total current requirementin accordance with section 1.5.1.

Page 30: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−16 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.5.4 Connect the power supply of the valve terminal

Please noteUse only a socket in accordance with appendix A.2 for thepower supply and connect this only to the connection forthe power supply (see Fig.�1/1).

Pin assignment of the power supply connection

Assignment Pin Plug on CP...−SC(A−coded)

24 V DC electronics and sensors24 V DC valves and outputs0 V electronics and sensors0 V valves and outputsFE

Pin 1Pin 2Pin 3Pin 4Pin 5

1

5

4 3

2

Tab.�1/7: Pin assignment of the power supply connection

Please noteIn order to extend CP valve terminals or output moduleswithout additional supply, you must insert a bridgebetween pins 3 and 4.

However, the electrical isolation will then no longer beeffective (see Fig.�1/6).

Page 31: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−17Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Fitting the connector socket

1 Cable

2 Strain relief

3 Housing

4 Connecting part

12

3

4

Fig.�1/4: Individual parts of plug and cable exit

Preparing When you have selected suitable cables, connect them asfollows (Fig.�1/4):

1. In order to open the plug, loosen the centre knurled nut.

2. Open the strain relief on the rear part of the housing.

Then pass the cable through.

3. Remove 5 mm of insulation from the end of the cable and

fit end sleeves on the strands.

4. Connect the ends of the conductors.

5. Replace the connector part on the housing of the socket.

Pull the cable back so that there are no loops inside thehousing.

6. Tighten the strain relief.

Page 32: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−18 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Observe the following when connecting the 24 V load voltage(pin�2):

· Observe the tolerance (20.4 ... 26.4 V DC). Check the 24 V load voltage of the valves while the

system is operating.

CautionExcessive voltages or short circuits can lead to functionaldamage to the CP...−SC−DP, whereby actuators can nolonger be controlled.

· Protect the load voltage of the valve coils with externalfuses.

In order to ascertain the size of the fuses, calculate firstthe maximum current consumption in accordance withsection 1.5.1.

Please noteCheck your emergency stop circuit, in order to ascertainthe measures necessary for switching your machine/sys�tem into a safe state in the event of an emergency stop.

� Switching off the load voltage for the valves and outputmodules in the secondary circuit of the power unit.

� Switching off the compressed air supply for the valveterminal.

Due to energy stored in the input circuitry of valve ter�minals, there may be a delayed reaction of the valves whenthe load voltage is switched off.

Take this into consideration, e.g. as follows:

� by using an input signal in the controller for checkingwhether the load voltage has been switched off.

� by blocking the control signal for the valves by lockingthe output signal with the input signal �Load voltage".

Page 33: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−19Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Potential equalization

Earth the valve terminal:

� at the power supply connection (pin 5)

� and at the earth connection of the housing (see Fig.�1/1).

Please note· By means of low−impedance connections, make surethat the housing of the valve terminal and the earthconnection at pin 5 have the same potential and thatthere are no equalizing currents.

In this way, you will avoid interference caused by electro�magnetic influences.

Page 34: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−20 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Connecting the voltage supply

1

45 232

1 Connection for voltage supply

2 Potential equalization

3 Earth connection at pin 5

4 Load voltage can be switched off separately andexternal fuses (design as per section 1.5.2)

5 Protective earth (PE)

Fig.�1/5: Example of connections for power supply with aPELV power unit

Page 35: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−21Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Connecting the power supply with electricalisolation of the electronics and the load voltage

1 Power unit forload voltage(valves andoutputs)

2 Device forisolationmonitoring

3 Load voltage canbe switched offseparately andexternal fuses(design as persection 1.5.2)

4 Power unit foroperating voltage(electronics andsensors)

1 2

3

4 2

Fig.�1/6: Example of connections for power supply with two PELV power units

Please noteElectrical isolation will not be possible if you loop thevoltage through to further I/O modules without electricalisolation.

Page 36: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−22 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.6 Extending the CP...−SC−DP on the CP extension connection

Further CPI/CP modules can be connected to the CP...−SC−DPvia the CP extension connection.

1

1 CP extension connection

Fig.�1/7: CP extension connection on the CPA−SC−DP

Proceed as follows

1. Connect the modules to the extension connection.

2. Start the automatic recognition process with DIL switchelement 1 (see section 1.2.3).

Please noteThe rules for CPI systems also apply for extending theCP...−SC−DP (see section 1.6.1).

You can connect the following CPI/CP modules to the CPextension connection:

� CP input and output modules

� CPI input and output modules (with extended functions)

Page 37: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−23Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

� CPV−SC with CPI connection

� CPV/CPA valve terminals with and without extendedfunctions.

CautionThe maximum cable length between rhe CP...−SC−DP andthe last CP module must not exceed 10 m.

The CP connecting cables must have special electricalproperties. Always use, therefore, Festo CP connectingcables.

Ready−to−use CP connecting cables are available from Festo.These are available in various lengths and designs.

RecommendationUse blanking plugs for sealing unusedconnections.

Page 38: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−24 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1.6.1 Rules for extending the CPI system

The CPI system supports a different number of modules perCP string, depending on the type of CP master and on theCPI/CP modules connected.

The CP...−SC−DP is a CPI master.

Modules can be placed in two different groups:

� CPI modules (with extended functions)

� CP modules (without extended functions).

CPI system 1)

Rules � Maximum 4 modules on the CP string� Max. 32 I and 32 O (per CP string)� The sequence of the modules within the

CP�string is optional

Master A mixture of CPI modules is possible on CPImasters:� Only one CP input module is possible at the

end of each CP string� Only one CP valve terminal�2) or one CP output

module�2) is possible per CP string.� �Unused" locations on the CP string can be

�filled" with CPI modules�1)

Input modules,output modules,valve terminalswith CPIconnection

There is an incoming and continuing interface onall CPI modules

1) with extended functions2) without extended functions

Tab.�1/8: Rules for extending the CPI system

Page 39: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−25Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Please noteIrrespective of the type of CPI/CP modules, not more than32 inputs and 32 outputs may be connected (sum of allmodules on a CP string).

X X I

CPI master

X X

X X I

X VI/O

X: any CPI module(with extended functions)

I: CP input module

VI/O: CP valve terminal orCP output module

X X

X

Fig.�1/8: Extension examples of a CPI system with CPI master and CPI/CP modules (grey: CPI modules with extended functions)

Page 40: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

1. Installation

1−26 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Page 41: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Commissioning

2−1Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Chapter 2

Page 42: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−2 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Contents

2. Commissioning 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 Preparing the valve terminal for commissioning 2−3 . . . . . . . . . . . . . . . . . . . . . .

2.1.1 Switching on the operating voltages 2−3 . . . . . . . . . . . . . . . . . . . . . . . .

2.1.2 Address assignment � CPA−SC−DP 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.3 Address assignment � CPV−SC−DP 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.4 Address assignment of CPI/CP modules 2−7 . . . . . . . . . . . . . . . . . . . . .

2.2 Commissioning on the PROFIBUS−DP 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Device master file (GSD) and icon files 2−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Configuration with a Siemens master 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.1 STEP 7 � HW Config (up to V 5.2) � preparations 2−12 . . . . . . . . . . . . . .

2.4.2 Station selection with STEP 7 2−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.3 Configuration with STEP 7 2−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.4 Tool change configuration 2−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5 Examples of configuration 2−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.1 Standard configuration 2−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.2 Tool change configuration 2−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 43: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−3Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.1 Preparing the valve terminal for commissioning

2.1.1 Switching on the operating voltages

Please notePlease observe the switching−on instructions in the manualfor your controller.

· Before switching on, make sure that the field bus hasbeen configured completely and correctly as specified.

Recommendation:Providing the safety concept of your machine/system permitsthis, commission the CP...−SC−DP at first with both supply volt�

ages (pins 1 and 2), but without compressed air. A suitabletest function is therefore available which does not triggerundesired reactions.

Please observe the following when switching on the powersupply:

Common supply Common power supply for the control system and all field

bus slaves via a central power unit or a central switch.

Separate supply If the control system and the field bus slaves have separate

power supplies, the devices must be switched on in thefollowing sequence:

1. the operating voltage supply for all field bus slaves

2. the operating voltage supply for the controller.

Page 44: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−4 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.1.2 Address assignment � CPA−SC−DP

The CPA−SC−DP valve terminal always occupies 32 outputaddresses, irrespective of the number of valve solenoid coils

fitted. This enables the valve terminal to be extended at alater date without the need to shift the addresses.

Please noteAs the CPA−SC−DP always occupies 32 addresses, the nextfree address in the CP extension is 32.

� Depending on the configuration (number of valve loca�tions and internal cabling), a valve location supports thecontrol of one or two solenoid coils. Accordingly, the valvelocations occupy one or two addresses, irrespective ofwhether the valve location is fitted with a valve plate or ablanking plate. The internal circuitry cannot be modifiedat a later stage.

The following diagram shows how many solenoid coils can becontrolled on the individual valve locations.

Pos = number of the valve locationCoils = total number of valve solenoid coilslight grey = 1 valve coildark grey = 2 valve coils

Fig.�2/1: Address assignment on the CPA−SC−DP

Page 45: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−5Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

� If a valve location for 2 addresses is actually equippedwith two solenoid coils, the following allocation applies:

� pilot solenoid coil 14 occupies the less significantaddress

� pilot solenoid coil 12 occupies the more significantaddress.

� If a valve location for two addresses is fitted with only onesolenoid coil, the more significant address will remainunused. However, the valve location still occupies twoaddresses.

� Address assignment of the valve coils on the CPA−SC−DP isfrom left to right and on the individual valve locationsfrom the front to the rear.

Example in the following diagram. The first 8 valve locationssupport control of two solenoid coils each.

0 7654321 8 1514131211109 181716

aB aD

aB Manual overrides and LEDs for the solenoid coils 12

aD Manual overrides and LEDs for the solenoid coils 14

Fig.�2/2: Addressing example on the CPA−SC−DP (with 24 valve locations)

Page 46: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−6 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.1.3 Address assignment � CPV−SC−DP

The valve terminal type CPV−SC−DP always occupies 16 out�put addresses, irrespective of the number of valve solenoidcoils fitted. This enables the valve terminal to be extended at

a later date without the need to shift the addresses.

Please noteAs the CPV−SC−DP always occupies 16 addresses, the nextfree address in the CP extension is 16.

0 7654321 8 1514131211109

1 2 1

1 Single−solenoid valves occupy one valve location

2 Double−solenoid valves occupy two valve locations

Fig.�2/3: Address assignment on the CPV−SC−DP

� If a valve location for 2 addresses is actually equippedwith two solenoid coils, the following allocation applies:

� pilot solenoid coil 14 occupies the less significantaddress

� pilot solenoid coil 12 occupies the more significantaddress.

Page 47: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−7Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.1.4 Address assignment of CPI/CP modules

Tab.�2/1 provides an overview of the assigned addresses forthe various CPI/CP modules (as at autumn 2006).

CPI/CP modules Assigned I/Os on ...

Design Type CPI−capable 1) CPI masters 1) CP masters 2)

I O I O

CPI/CP input modules CP−E08−M8−CLCP−E08−M12−CLCP−E16−KL−CLCP−E16−M8CP−E16N−M8CP−E16−M8−ZCP−E16−M12x2−5POLCP−E16N−M12x2CP−E16−KL−IP20−Z

YesYesYesNoNoNoNoNoNo

8 I8 I16 I16 I16 I16 I16 I16 I16 I

� 16 I16 I16 I16 I16 I16 I16 I16 I16 I

CPI/CP output modules CP−A04−M12−CLCP−A08−M12−5POLCP−A08N−M12

YesNoNo

� 8 O16 O16 O

� 16 O16 O16 O

CP valve terminals CPV...−CPICPV...−GE−FB−4CPV...−GE−FB−6CPV...−GE−FB−8CPA10/14−IFB−CP

YesNoNoNoNo

� 16 O16 O16 O16 O16 O

� 16 O16 O16 O16 O16 O

1) with extended functions2) without extended functionsFurther CPI modules and CPI−capable valve terminals in preparation.

Tab.�2/1: Assigned I/Os of the CPI/CP modules

Page 48: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−8 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.2 Commissioning on the PROFIBUS−DP

FREEZE and SYNC

The operating modes FREEZE and SYNC are supported inaccordance with EN 50170.

The method of accessing the commands FREEZE and SYNC

depends on the controller used. Please refer here to thedocumentation for your field bus module.

CautionThe operating mode FREEZE or SYNC will be reset auto�matically:

� after Power OFF/ON

� when the field bus module stops.

Only the operating mode FREEZE will be reset automati�cally:

� when the bus connection to the PROFIBUS is interrupted(response monitoring active).

FREEZE command

All the inputs of the DP slave will be �frozen". The CP...−SC−DP

now sends a constant image of all the inputs to the master.With each further FREEZE command, the input image is up�dated and sent again to the master.

Return to normal operation: UNFREEZE command

SYNC command

All the outputs of the DP slave will be �frozen". The CP...−SC−DPnow no longer reacts to modifications to the output image in

the master. With each further SYNC command, the outputimage will be updated and transferred.

Return to normal operation: UNSYNC command

Page 49: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−9Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Module consistency

The CP...−SC−DP supports the following variants in moduleconsistency:

� over the selected format (word).

Please noteMake sure that extensions connected at the CP connectionare recognized by the DIL switch setting (see section 1.2.3).

Page 50: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−10 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

The following table provides an overview of the possible DPidentifiers for the CP system:

CP...−SC and extension DP identifier Comment

Siemens EN 50170

CPA−SC−DP (without extension) ID: 32DO ID: 23h/35d 32 digital outputs/valvecoils of the CPA−SC

CPV−SC−DP (without extension) ID: 16DO ID: 21h/33d 16 digital outputs/valvecoils of the CPV−SC

Extension 8 digital inputs ID: 8DI ID: 10h/16d e.g. CPI/CP inputmodules

Extension 16 digital inputs ID: 16DI ID: 11h/17dmodules

Extension 24 digital inputs ID: 24DI ID: 12h/18d

Extension 32 digital inputs ID: 32DI ID: 13h/19d

Extension 8 digital outputs ID: 8DO ID: 20h/32d e.g. CPI/CP outputmodules CP valve

Extension 16 digital outputs ID: 16DO ID: 21h/33dmodules, CP valveterminals

Extension 24 digital outputs ID: 24DO ID: 22h/34d

Extension 32 digital outputs ID: 32DO ID: 23h/35d

Extension �tool change mode"configuration (32 digital inputs andoutputs)

ID: 32DX ID: 33h/51d see section 2.4.4

Tab.�2/2: Overview of DP identifiers for various extensions to the CPV Direct

Please noteEnter the identifiers corresponding to the physicalsequence of the modules on the CP extension string,starting with the CP...−SC−DP.

Page 51: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−11Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.3 Device master file (GSD) and icon files

In order to configure the CP...−SC−DP with a programmer/PC,you will require the appropriate GSD file. In addition to theslave−typical entries (Ident. number, Revision, etc.), the de�vice master file (GSD) also contains a selection of identifiers.

Reference sources Current GSD files can be found on the Festo Internet pages

under:

� www.festo.com/fieldbus

GSD files For the CP...−SC−DP you will require one of the following files:

� SC_0A44.GSD (German version) or

� SC_0A44.GSE (international version)

Icon files You will find icon files to represent the valve terminal in yourconfiguration software under the above−mentioned Internetaddress.

Normal operatingstatus

Diagnostic case Special operatingstatus

File: SC_0A44_N.dib File: SC_0A44_D.dib File: SC_0A44_S.dib

Tab.�2/3: Icon files for configuration software

Page 52: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−12 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.4 Configuration with a Siemens master

Please noteVarious configuration programs are available for use inconjunction with a Siemens master. Please observe therelevant procedure for your configuration program.

The following sections describe as an example the main con�figuration steps with the STEP�7 software. It is assumed thatthe reader is already familiar with the information in the man�ual for the STEP�7 software.Information on operation with general DP masters can befound in appendix B.1.

2.4.1 STEP 7 � HW Config (up to V 5.2) � preparations

GSD 1. Copy the GSD of the valve terminal into the directory...\STEP7\S7DATA\GSD on your PC/programmer.File: SC_0A44.GS*(Reference sources for the GSD see section 2.3)

The GSDs can either be:

� copied manually into the above mentioned directory(e.�g. with Windows Explorer) or

� loaded via the menu [Options] � [Install new GSD].

Please noteUpdate the hardware catalogue if you copy the GSD duringwork with STEP 7.Menu in HW Config�: [Options] [Update Catalog]

Page 53: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−13Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Please noteAs from STEP 7 V4.02, GSDs are stored within the STEP� 7project (station GSD). This can cause the updating/readingof new GSD files to appear as if incorrect. Please informyourself about handling the station GSD files in the STEP� 7help.

2. Process the dialogue window �Properties � PROFIBUSinterface"� Baud rate� Profile

Icons 3. Copy the icon files (see section 2.3) for the CP...−SC intodirectory ...\STEP7\S7DATA\NSBMP on your PC orprogrammer.

The icon files can either be:

� copied manually into the above named directory or

� loaded via the menu [Options] [Install new GSD] � filetype �Bitmap files" in HW Config.

4. Insert a DP master system:� Right−hand mouse click on �DP" under �CPU" in the

rack.� Click on [Insert master system] in the context menu.

The line of the DP master system will be displayed.

Page 54: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−14 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.4.2 Station selection with STEP 7

1 2

3

Fig.�2/4: Station selection with STEP 7 � HW Config (The windows displayed are not all visible at the same time, see text)

1. If the hardware catalogue is not open: click on thecatalogue icon (see Fig.�2/4 1�).The hardware catalogue will be displayed.

2. Open the following folder in the hardware catalogue:�\PROFIBUS−DP\Additional Field Devices\Valves".The folder �Valves" is displayed when you copy the GSD(see step 1 of the preparations).

Page 55: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−15Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Pull the station type �Festo CP−SC" onto the line of the DPmaster system 2.The dialogue window �Properties � PROFIBUS interface"will be displayed 3.

3. Select the PROFIBUS address identical to the setting onthe rotary switches (see section 1.2.1) and close with OK.

2.4.3 Configuration with STEP 7

12 3

4 5

Fig.�2/5: Configuration with STEP 7 V � HW Config (example for adding one CP input

module with 16 inputs, explanations see text)

Page 56: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−16 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

1. Click on the icon of the valve terminal to be configured inthe HW Config 1. The configuration table will be dis�played under the rack 2.

2. Open the module �Festo CP−SC" (folder\PROFIBUS−DP\Additional Field Devices\Valves\...) in the hardware cata�logue 3.

Basic configuration The valve terminals type CPV−SC−DP always occupy 16 out�put addresses; valve terminals type CPA−SC−DP alwaysoccupy 32 output addresses (see section 2.1.3). Thereforecarry out first of all a configuration of the basic device asfollows.

3. Depending on your valve terminal pull the appropriateentry out of the hardware catalogue onto the 1st. line ofthe configuration table 4�:

� �CPV−SC (O 16)"

� �CPA−SC (O 32)"

Configuring the extension If you have connected modules to the CP extension connec�tion of the CP...−SC−DP, assign the configuration table furtheras follows:

4. Pull the entries out of the hardware catalogue onto the nextfree line of the configuration table, according to the physi�cal sequence of the modules on the CP extension string.

�tool change mode"configuration

Alternatively you can use the �tool change mode" configur�ation (see�section 2.4.4).

Modifying the address The addresses are assigned automatically.

· Double click on the appropriate line in the configurationtable and modify the starting address of the inputs oroutputs in the window �Properties � DP slave" 5.

Please noteWith S7−400 controllers, up to 4 bytes of addresses arereserved for each DP identifier, depending on the versionstatus.

Page 57: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−17Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.4.4 Tool change configuration

With the �tool change mode" configuration you can commissionmodules without new configuration on the CP extension con�nection. The �tool change mode" configuration is useful if variousextensions are connected in turn to the CP...−SC−DP duringoperation.

1 2

Fig.�2/6: Tool change configuration

Page 58: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−18 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Procedure:

1. Carry out the basic configuration 1.

2. Pull the entry �tool change mode I/O 32/32" out of thehardware catalogue onto the 2nd. line of the configur�ation table 2.

Addressing and function With the �tool change mode" configuration the maximumpossible 32 inputs and 32 outputs will be assigned, irre�spective of whether these are used or not. The addressesare assigned without gaps, module after module in ascend�ing sequence. Please take this into account when program�ming the controller.

CautionCommunication via the PROFIBUS−DP will start in any case,even if the addresses are used incorrectly.

Incorrect addressing can cause functional damage with the�tool change mode" configuration.

With the �tool change mode" configuration make sure thatthe input and output signals are used correctly in yourcontrol sequence (see example in Tab.�2/7).

Configuration Advantages Disadvantages

Standardconfiguration

� Good diagnostic possibilities� Protection against confusion of the

modules on the CP string.

� Modifications to the CP extensionstring must be configured again.

�tool changemode"configuration

� Modifications to the CP extensionstring are possible without newconfiguration.

� Can be configured

� Limited diagnostic possibilities(see section 3.3.6)

� Address assignment of the changeconfigurations must be carried outvery carefully.

Tab.�2/4: Advantages and disadvantages of the �tool change mode" configuration

Page 59: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−19Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.5 Examples of configuration

2.5.1 Standard configuration

The following table shows three examples of configurationand addressing extensions on the CPI extension connection ofa CPV−SC−DP.

No. Standard configuration DP identifiers Addressing

1 16DO 1) O20.0 ... O21.7

CPV−SC−DP + CP−E08−M12−CL8DI I20.0 ... I20.7

2 16DO 1) O20.0 ... O21.7

8DO O22.0 ... O22.7

CPV−SC−DP + CP−A04−M12−CL + CP−E08−M12−CL 8DI I20.0 ... I20.7

3 16 DO 1) O20.0 ... O21.7

8DI I20.0 ... I20.7

CPV SC DP CP E08 M 2 CL

8DI I21.0 ... I21.7

CPV−SC−DP + 4x CP−E08−M12−CL8DI I22.0 ... I22.7

8DI I23.0 ... I23.7

1) CPV−SC−DP basic device

Tab.�2/5: Examples of standard configuration and addressing a CPV−SC−DP withdifferent CPI extensions

Page 60: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−20 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

2.5.2 Tool change configuration

The following table shows the same CPI extensions asTab.�2/5, but this time with the �tool change mode"configuration. Inthis way you can connect the extensions 1�,2 or 3 without a new configuration.

�Tool change mode" configuration DPidentifiers

Assignedaddresses

16DO 1) O20.0 ... O21.7

I20 0 I20 71

32DX I20.0 ... I23.7

I20.0...I20.71

O22.0 ... O25.7

O22 0 O22 3 I20 0 I20 72

O22.0...O22.3 I20.0...I20.7O20.0...O21.7

2

I20.0...I20.7 I21.0...I21.73I20.0...I20.7 I21.0...I21.7

I22.0...I22.7 I23.0...I23.7

Addresses used

1 CPV−SC−DP + CP−E08−M12−CL2 CPV−SC−DP + CP−A04−M12−CL + CP−E08−M12−CL3 CPV−SC−DP + 4x CP−E08−M12−CL1) CPV−SC−DP basic device

Tab.�2/6: Different extensions with �tool change mode" configuration (compare with example in Tab.�2/5)

Page 61: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−21Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Please noteThe following example makes clear that with the toolchange configuration you must be very careful, especiallyin using the input and output addresses.

Explanation of theexample

In configuration 1 in Tab.�2/7 a lamp is connected to the2nd. output module as a signal generator. In configuration2 an actuator is connected to the 2nd. output module. Inboth cases address O23.7 is used. Take into account in the controller that the lamp now lies ataddress O25.7 and an actuator at O23.7.

�Tool change mode" configuration DPidentifiers

Assignedaddresses

O22.0...O22.3 O23.0...O23.7 16DO 1) O20.0 ... O21.7

132DX I20.0 ... I23.7

1O23.7 O22.0 ... O25.7

O22 0 O22 7 O23 0 O23 7O22.0...O22.7 O23.0...O23.7O24.0...O24.7 O25.0...O25.7O20.0...O21.7O20.0...O21.7

2O23 7 O25 7

2

Addresses usedO23.7 O25.7

1 CPV−SC−DP + 2x CP−A08−M12−CL2 CPV−SC−DP + 4x CP−A08−M12−CL1) CPV−SC−DP basic device

Tab.�2/7: Example of a �tool change mode" configuration which requires specialattention with the addressing (see text above)

Page 62: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

2. Commissioning

2−22 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Page 63: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Diagnosis

3−1Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Chapter 3

Page 64: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−2 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Contents

3. Diagnosis 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Diagnosis via LEDs 3−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.1 Normal operating status 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.2 Fault displays 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.3 LEDs for status display of the valve solenoid coils 3−8 . . . . . . . . . . . . .

3.2 Reaction to faults in the control system 3−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Diagnosis via PROFIBUS−DP 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 Diagnosis steps� 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.2 Overview of the diagnostic bytes� 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.3 Details on standard diagnostic information 3−14 . . . . . . . . . . . . . . . . . . .

3.3.4 Details of the identification−related diagnosis 3−16 . . . . . . . . . . . . . . . . .

3.3.5 Channel−related diagnosis 3−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.6 Diagnosis with tool change configuration 3−19 . . . . . . . . . . . . . . . . . . . .

3.3.7 Siemens SIMATIC S5/S7 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Online diagnosis with STEP 7 3−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.1 Read out diagnostic buffer with STEP 7 (up to V 5.2) 3−23 . . . . . . . . . . .

3.4.2 Channel−related diagnosis with STEP 7 (up to V�5.3) 3−25 . . . . . . . . . . .

Page 65: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−3Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.1 Diagnosis via LEDs

The LEDs indicate the operating status of the valve terminals:

13 4

2

CPV−SC−DP CPA−SC−DP

12 12 12

14 14 14

1 LEDs of the valve solenoid coils (12 or 14)

2 PS �Power System": Operating voltage supply for the electronics (and sensors in a CP input module)

PL �Power Load": Load voltage supply for the valves (and valves/outputs in the CP extension string)

SF CP system faultsBF Bus fault/status

3 LEDs of valve solenoid coils 12

4 LEDs of valve solenoid coils 14

Fig.�3/1: LEDs of the CP...−SC−DP

Page 66: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−4 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.1.1 Normal operating status

In the normal operating status two LEDs light up green. TheLEDs SF and BF are out.

� lights up; flashes; out

LED Sequence Reaction Operating status Fault treatment

PSON

OFF

lights up green Power supply for the electronicsOK

none

PLON

OFF

lights up green Power supply for the valves OK none

SF ON

OFF

off No system fault none

BF ON

OFF

off No bus fault none

Tab.�3/1: LEDs: normal operating status

Page 67: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−5Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.1.2 Fault displays

Fault diagnosis with the LED PS

The PS LED (Power status) indicates faults in the operatingvoltage supply.

LED Sequence Reaction Operating status Fault treatment

PSON

OFF

off Power supply for the electronics(and sensors) not applied.

· Check power supply(pin�1).

PSON

OFF

flashesgreen

Power supply for the electronics(and sensors) outside thetolerance (see appendix withtechnical data)

· Check power supply(pin�1).

Tab.�3/2: LED PS

Fault diagnosis with the LED PL

The PL LED (Power load) indicates faults in the load voltagesupply.

LED Sequence Reaction Operating status Fault treatment

PLON

OFF

off Power supply for the valves (andCP outputs) not applied.

· Check power supply(pin�2).

PLON

OFF

flashesgreen

Power supply for the valves (andCP outputs) outside the tolerance(see appendix with technical data)

· Check power supply(pin�2).

Tab.�3/3: LED PL

Page 68: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−6 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

Fault diagnosis with the LED SF

The SF LED indicates CP system faults and special CP systemstates.

LED Sequence Reaction Operating status Fault treatment

SFON

OFF

off � Normal operating status · None

SF ON

OFF

flashes redfast

CP string faults:� Deviation nominal status

<−> actual status of the CPconfiguration

� CP configuration notpermitted

· Check the CP configur�ation and, if necessary,carry out new recognition(see section 1.2.3)

· Alternative: use the toolchange configuration

SF ON

OFF

flashes redslowly

Periphery fault in theCP�string:� The module has a diag�

nostic fault (short circuit,overload, ...)

· Check the modules in theCP string for diagnosis(see section 3.3)

SF ON

OFF

lights upred

Module failure in theCP�string:� Cable interrupted� Module defective

· Check CPI/CP cables· Servicing required

Tab.�3/4: LED SF

Page 69: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−7Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

Fault diagnosis with the LED BF

The BF LED indicates the bus fault or bus status.

LED Sequence Reaction Operating status Fault treatment

BFON

OFF

off No fault (if the green PS LEDlights up)

· None

BF ON

OFF

flashes redfast

Field bus connection not OK.Possible causes:� station number not

correct (e.g. addressassigned twice)

� defective field bus module� Interrupted, short−cir�

cuited or faulty field busconnection

� faulty configuration

Check the ...· address setting of the

rotary switches in thefield bus node

· field bus module/master· field bus connection

· configuration of themaster

Tab.�3/5: LED BF

Page 70: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−8 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.1.3 LEDs for status display of the valve solenoid coils

There is a yellow LED for every valve solenoid coil. This LEDshows the switching status of the valve solenoid coil.

LED Colour Solenoid coil Meaning

off � Basic position� Switch position

There is no signal (logical �0")There is a signal (logical �1") but:� the load voltage of the valves lies below the

permitted tolerance range <�20.4 V DC)

yellowlights up

� Switch position� Basic position

There is a signal (logical �1")There is a signal (logical �1") but:� compressed air supply not OK

or� pilot exhaust blocked

or� servicing required

Tab.�3/6: LEDs for solenoid coils

Page 71: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−9Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.2 Reaction to faults in the control system

The reaction of the outputs to control or communicationfaults can be set by means of the parameters

� �Fault mode" and �Fault state"

� �Idle value" and �Idle action"

The standard setting is �Reset output".

Further information on parametrizing can be found insection�B.1.

Please notePlease note the following if the outputs are reset after PLCstop, field bus interruption or fault:

� Single−solenoid valves move to the basic position.

� Double−solenoid valves remain in the current position.

� Mid−position valves move to the mid−position (depend�ing on valve type: pressurized, exhausted or blocked).

Page 72: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−10 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.3 Diagnosis via PROFIBUS−DP

The CP...−SC−DP supports the following diagnostic possibilityvia PROFIBUS as per EN 50170:

� identification−related diagnosis (see section 3.3.4)� identification number.

� channel−related diagnosis (section 3.3.5)� module number and type � type of diagnosis (fault number).

Please noteIf you are operating the CP...−SC−DP with the tool changeconfiguration, only one diagnostic information will beoutput for the CP extension (see section 3.3.6).

Please noteThe diagnostic information is only sent to the mastersystem if the device−related diagnosis is activated in theswitch module. In order to do this, set switch element 2 ofthe DIL switch to �OFF".

Page 73: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−11Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.3.1 Diagnosis steps�

The diagram below shows you the steps required fordiagnosing the CP...−SC−DP.

123 04567

1

Bit

Station status 1

1. Step (evaluation of bits 0and 2):CP...−SC−DP without voltage,bus plug is not inserted,�...(Diag.Station_Non_Existent)

1

The planned configuration ofthe CP...−SC−DP is not the sameas the actual configuration(Diag.Cfg_Fault)

1

2. Step: Additionaldevice−specific diagnosis(Diag.Ext_Diag see section3.3.4)

Fig.�3/2: Diagnosis steps

In order to commission your system, it may be useful in somecases to switch off the device−related diagnosis. If your con�troller does not start, try with the DIL switch setting �Device−

related diagnosis inactive" (see section 1.2.2).

Page 74: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−12 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.3.2 Overview of the diagnostic bytes�

In the following the diagnostic bytes are represented in fourtables.

Standard diagnostic information

Byte Contents Explanation

1 Station status 1 see Tab.�3/9

2 Station status 2 see Tab.�3/10

3 Station status 3 see Tab.�3/11

4 Diag.Master_add Master address: The address of the master, whichparametrized the CP...−SC−DP, is entered in thisbyte.

5 Ident_number high byte Manufacturer identifier high byte (05h)

6 Ident_number low byte Manufacturer identifier low byte (9Eh)

7 ... External diagnostic data Data block of the identification and channel−relateddiagnosis

Tab.�3/7: Overview of diagnostic bytes: standard diagnostic information

Identification−related diagnosis (variable length)

Byte Contents Explanation

1 Header Fixed for CP...−SC−DP

2 Identification−related diagnosis Specifies the identification with diagnosis.

Tab.�3/8: Overview of diagnostic bytes: identification−related diagnosis (details in section 3.3.4)

Page 75: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−13Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

The following applies to entries in the diagnostic bytes of theidentification−related diagnosis:

� entries according to identification must be in ascendingorder without gaps. The entries must always be in thesame sequence as the configured identifications, irre�spective of the time sequence of the diagnostic messages(if necessary, the entries with large module numbers willbe shifted).

Page 76: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−14 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.3.3 Details on standard diagnostic information

The following diagnostic information can be requested by theDP master via the function Slave_Diag �from the CP...−SC−DP.

The procedure for reading out this diagnostic informationwith a SIMATIC S5/S7 system is described in section 3.3.7.

Station status_1

Bit Meaning Explanation

0 Diag.Station_Non_Existent CP...−SC−DP no longer/not yet addressable. Possible causes:� Operating voltage not applied� Data cable interrupted� Fault in data cable

1 Diag.Station_Not_Ready CP...−SC−DP not yet ready for data exchange

2 Diag.Cfg_Fault The configuration data received from the master are notthe same as those ascertained by the CP...−SC−DP.

3 Diag.Ext_Diag There is a diagnosis. Possible causes:� Cable fracture on input/output module� Short circuit/overload at electrical outputs, ...

4 Diag.Not_Supported 1 = CP...−SC−DP does not support the function requested

5 Diag.Invalid_Slave_Response Always 0 (set by the CP...−SC−DP)

6 Diag.Prm_Fault Last parametrizing telegram faulty

7 Diag.Master_Lock Always 0 (set by the CP...−SC−DP)

bold = CP...−SC−DP related bits

Tab.�3/9: Diagnostic bits Station status_1

Page 77: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−15Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

Station status_2

Bit Meaning Explanation

0 Diag.Prm_Req 1 = Master must configure the CP...−SC−DP again

1 Diag.Stat_Diag 1 = The master must request diagnostic data until thisbit is set to 0

2 � Always 1 (set by the CP...−SC−DP)

3 Diag.WD_On 1 = response monitoring/watchdog activated

4 Diag.Freeze_Mode 1 = Freeze activated

5 Diag.Sync_Mode 1 = Sync activated

6 � Reserved

7 Diag.Deactivated Always 0 (set by the CP...−SC−DP)

bold = CP...−SC−DP related bits

Tab.�3/10: Diagnostic bits station status_2

Station status_3

Bit Meaning Explanation

0 ... 6 � Reserved

7 Diag.Ext_Diag_Overflow 1 = The CP...−SC−DP has more diagnostic messages thancan be buffered orthe master receives more diagnostic messages thanit can buffer.

Tab.�3/11: Diagnostic bits station status_3

Page 78: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−16 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.3.4 Details of the identification−related diagnosis

One bit is reserved for every module (identifier byte) assignedduring configuration. A set bit means that there is a diagnos�tic message in this I/O range.

5 123 0467 Bit Header byte of the identification−relateddiagnosis

Length of the diagnostic block in bytesincluding the header byte (fixed at 2h)

1

fixed at 0, 1

0 0100 0 0

Fig.�3/3: Header byte of the identification−related diagnosis

5 123 0467 BitIdentification−related diagnosis

1. Identification byte has diagnosis (Basis CP...−SC−DP)

Identification byte 1 has diagnosis

Reserved

Identification byte 2 has diagnosis

Identification byte 3 has diagnosis

Identification byte 4 has diagnosis

0 0 0

Fig.�3/4: Identification−related diagnosis

Page 79: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−17Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.3.5 Channel−related diagnosis

On the CP...−SC−DP detailed diagnostic information is given notchannel−by−channel but module−by−module via the channel−related diagnosis. 3 bytes of diagnostic data are available:

Bit 7, 6 fixed at 10

5 123 0467 Bit Module number

Module number 0 ... 5 (0: Basis CP...−SC−DP,1�...�4: Modules in the CP extension string)

01

Fig.�3/5: Channel−related diagnostic byte 1: Module number

5 123 0467 Bit Module type

Bit 0 ... 5 fixed at 0

Input/output00 = reserved 10 = output01 = input 11 = input/output

0 0 0 0 0 0

Fig.�3/6: Channel−related diagnostic byte 2: Module type

5 123 0467 Bit Type of diagnosis

Fault type (see Tab.�3/12)

Data format of the channel:000 = reserved 100 = byte001 = bit 101 = word010 = 2 bits 110 = 2 words011 = 4 bits 111 = reserved

Fig.�3/7: Channel−related diagnostic byte 3: Type of diagnosis

Page 80: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−18 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

Value Fault type (standard) Value Fault type (CP...−SC−DP)

0 Reserved 16 Incorrect valve setting

1 Short circuit 17 Valve: Switching counter, limit value exceeded

2 Undervoltage 18 Periphery fault tool change configuration

3 Overvoltage 19 Reserved

4 Overload 20 Parameterizing fault (signal range)

5 Overtemperature 21 Parametrizing fault (data format)

6 Cable fracture 22 Parametrizing fault (linear scaling)

7 Upper limit value exceeded 23 Parametrizing fault (digital filter)

8 Lower limit value exceeded 24 Parametrzing fault (lower limit value)

9 Reserved 25 Parametrzing fault (upper limit value)

10 Reserved 26 Faulty actuator supply

11 Reserved 27 CPI/CP module failed/faulty

12 Reserved 28 CPI/CP configuration faulty

13 Reserved 29 Short circuit in the CP string (CP line)

14 Reserved 30 Periphery fault in CPI/CP module (slave does not have bus connection)

15 Reserved 31 Channel failed

Tab.�3/12: Fault types (byte 3 of the channel−related diagnosis)

Page 81: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−19Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.3.6 Diagnosis with tool change configuration

In the tool change configuration only a simple diagnosticmessage is output for the CP string via the channel−relateddiagnosis. (Information on the tool change configuration seesection 2.4.4.)

Please noteIn the tool change configuration the diagnostic informationfor all modules in the CP string is entered in the 2nd. diag�nostic byte. No information is given as to which moduleregisters the fault. Note the module LEDs in the CP stringfor ascertaining the exact location of the fault.

Value Fault type (standard) Value Fault type (Festo)

... ... ... ...

... ... 18 Periphery fault in the tool change configuration

... ... ... ...

Tab.�3/13: Diagnosis with tool change configuration

The diagnostic information of the CP...−SC−DP basic device isnormally entered in the 1st. diagnostic byte in the tool changeconfiguration.

Page 82: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−20 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.3.7 Siemens SIMATIC S5/S7

With these controllers you have the possibility of specifyingthe reaction of the CP...−SC−DP to the faults named (detailssee controller manual).

Almost all configuration programs contain the function

�Response monitoring". For the operating modes named, thespecified time corresponds to the drop−out time of the valvesand electrical outputs.

Further details on response monitoring can be found in therelevant controller manuals.

Page 83: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−21Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

You can set two types of fault reactions of the control system:

� hard fault reaction: the controller switches to the operat�ing mode �STOP" when a fault occurs.

� soft fault reaction: the controller remains in the operatingmode �RUN" when a fault occurs.

Control system Module Meaning STOP RUN

SIMATIC S5 withIM 308C

OB23 Reaction to QVZ with directaccess to peripherals

default OB is programmed

OB24 Reaction to QVZ with access toperipherals via process image

default OB is programmed

OB35 Reaction to PEU(periphery not clear)

default OB is programmed

SIMATIC S7/M7 OB82 Reaction to a device−relateddiagnosis

default OB is programmed

OB86 Reaction to failure of a DP slave default OB is programmed

QVZ: quitting delayOB: organisation modulePEU: periphery not clear

Tab.�3/14: Fault reactions STOP and RUN with S5/S7

Page 84: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−22 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

Possibilities for downloading the diagnosis forS5/S7

The diagnosis for PROFIBUS−DP is supported in the different

control systems by means of function modules. These down�load the slave diagnosis and write it into a data range of theuser program.

Control system Function module See ... Manufact.

SIMATIC S5 withIM 308C

FB192 �IM 308C" �ET 200 Decentral Periphery System"manual

Siemens

SIMATIC S5 withS5−95U/DP master

FB230 �S_DIAG" �ET 200 Decentral Periphery System"manual

Siemens

SIMATIC S5 withSF 50/DP master

FB230 �S_DIAG" �Programmable valve terminal withSB/SF 50" manual

Festo

SIMATIC S7/M7 SFC13 �DP NRM_DG" �System and Standard Functions"reference manual

Siemens

SIMATIC S7/M7 FB125 Siemens download in Internet Siemens

Tab.�3/15: Possibilities for downloading the diagnosis for S5/S7

Example for a STEP 7 user program

STL ExplanationCALL SFC 13REQ:=TRUE Read requestLADDR:=W#16#03FE Pointer at diagnostic address, e.g. 1022d = 03FEh

(see mask �Properties � DP slave" in the HW Config)RET_VAL:=MW100 When faults occur, output fault codeRECORD:=P#M110.0 BYTE 20 Pointer at start of data range for diagnosis

and maximum length of the diagnostic dataBUSY:=M10.0 Read procedure finished

Fig.�3/8: Programming example in STL

Page 85: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−23Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.4 Online diagnosis with STEP 7

Direct diagnostic events in conjunction with the CP...−SC−DPcan be:

� Decentral periphery station failure

� communication between slave and master interrupted

� Module faulty (see identification−related diagnosis in

Fig.�3/4)

� Change of operating status from START to RUN (nominal/actual difference exists)� configuration data of the CP...−SC−DP are not the same as the periphery.

3.4.1 Read out diagnostic buffer with STEP 7 (up to V 5.2)

Prerequisites:

� HW Config must be accessed.

Proceed as follows (Fig.�3/9):

1. Switch from offline to online 1.

2. Click with the right−hand mouse button on the CPU inrack�2.

3. Click on [Module information...] in the context menushown. The window �Module information" will thenappeart 3.

4. Click on the register �Diagnostic buffer" 4.

5. Click on the event and read the details 5. Here you willfind more detailed information on proceding further, de�pending on the S7 controller used.

Page 86: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−24 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

1 2 3 4

56

Fig.�3/9: Online diagnosis via the diagnostic buffer

(explanation see text, screenshot only in German)

Page 87: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−25Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

3.4.2 Channel−related diagnosis with STEP 7 (up to V�5.3)

You can display fault messages of the channel−related diag�nosis with STEP 7 HW Config V5.1 if you mark the icon of theCP...−SC−DP instead of the CPU. Proceed as follows (see Fig.�3/10):

Prerequisite:� HW Config has been accessed

1. Switch from offline to online.

2. Click with the right−hand mouse key on the icon of theCP...−SC−DP 1. Click on �Module information" in the contextmenu which now appears.The dialogue window �Module information" now appears.

3. Select the register �DP slave diagnosis".

4. Read the diagnostic information 2.

Page 88: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

3. Diagnosis

3−26 Festo P.BE−CPASC−CPVSC−DP−E N en 0610NH

1 2

Fig.�3/10: Channel−related diagnosis with STEP 7 (explanation see text, screenshot only in German)

Page 89: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Technical appendix

A−1Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Appendix A

Page 90: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

A. Technical appendix

A−2 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Contents

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical specifications A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Accessories A−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 91: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

A. Technical appendix

A−3Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

A.1 Technical specifications

General

Temperature range� operation� storage/transport

−5 ... +50 °C−10 ... +50 °C

Relative air humidity 90�% at 50 °C, non−condensing

Free of paint wetting impairment substances yes

Vibration resistance(seealso pneumatics manual)

EN 60068−2−6: Wall mounting severity class 2Hat rail fastening: Severity level 1

Shock resistance(seealso pneumatics manual)

EN 60068−2−27: Wall mounting severity class 2Hat rail fastening: Severity level 1EN 60068−2−29:Wall mounting severity class 1Hat rail fastening: Severity level 1

IP protection class as per EN 60529 IP40 (with cover as per Fig.�1/1 and in the case ofCPV−SC−DP only for wall fitting)

Protection against electric shock(protection against direct and indirect contact asper EN 60204−1/IEC 204)

by means of PELV power supply unit(Protected Extra Low Voltage)

Valves see Pneumatics manual type P.BE−CPASC−.. / P.BE−CPVSC−..

Page 92: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

A. Technical appendix

A−4 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Power supply for electronics (and CP sensors)

Pin 1:Connection protected against incorrect polarity, fusedinternally, automatic switching on again, electricallyisolated from the power supply for the valves� Nominal value� Tolerance

24 V DC21.6 ... 26.4 V

Current consumption� Nominal value max. 200 mA + current consumption of

the sensors

Residual ripple 4 Vpp (within tolerance)

Power supply for valves (and CPI outputs)

Pin 2:Connection protected against incorrect polarity, fusedinternally, automatic switching on again, electricallyisolated from the power supply for the electronics� Nominal value� Tolerance

24 V DC21.6 ... 26.4 V

Current consumption� Nominal value� Tolerance

Sum of all switched−on CP solenoidvalves; see manual type P.BE−CPASC−../P.BE−CPVSC−..

Residual ripple 4 Vpp (within tolerance)

Field bus

PROFIBUS chip SPC 3 with DPV1

Design RS485, floating

Type of transmission serial asynchronous, half duplex

Protocol PROFIBUS−DP

Baud rate 9.6�...�12000�kBaud, automatic baud rate recognition

Cable type depnds on the cable length and on the set field bus baud rate: see the manual for your controller

Page 93: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

A. Technical appendix

A−5Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Field bus

Electrical isolation bus interface opto−decoupled

CPI system CP...−SC−DP valve terminal is a CPI master on the Festo CPI/CP system

Electromagnetic compatibility

� Interference emission� Interference immunity

tested as per EN 61000−6−4 (industry)tested as per EN 61000−6−2 (industry)

Technical specifications of the pneumatics can be found in thePneumatics manual P.BE−CPASC−.. / P.BE−CPVSC−..

Page 94: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

A. Technical appendix

A−6 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

A.2 Accessories

This chapter provides an overview of necessary and usefulFesto accessories.

Connection of power supply

Plug connectors Type

Mains connector socket for PROFIBUS M12,5−pin socket (A−coded)

FBSD−GD−9−5POL

Connection for field bus

Plug connectors Type

Sub−D connection 9−pin � Siemens type 6ES7 972−0BA10−0XA0� Siemens type 6ES7 972−0BA20−0XA0

Page 95: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

A. Technical appendix

A−7Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Overview of CP connecting cables

The following CP connecting cables are available for extendingthe CPA/CPV−SC−DP:

Valve terminal connection Type Part no.

angled plug � angled socket 0.25 m suitable as drag chain KVI−CP−3−WS−WD−0,25 540 327

angled plug � angled socket 0.5 m suitable as drag chain KVI−CP−3−WS−WD−0,5 540 328

angled plug � angled socket 2 m suitable as drag chain KVI−CP−3−WS−WD−2 540 329

angled plug � angled socket 5 m suitable as drag chain KVI−CP−3−WS−WD−5 540 330

angled plug � angled socket 8 m suitable as drag chain KVI−CP−3−WS−WD−8 540 331

angled plug � angled socket 2 m suitable as drag chain KVI−CP−3−WS−WD−2 540 332

angled plug � angled socket 5 m suitable as drag chain KVI−CP−3−WS−WD−5 540 333

angled plug � angled socket 8 m suitable as drag chain KVI−CP−3−WS−WD−8 540 334

angled plug � angled socket 0.5 m KVI−CP−3−WS−WD−0,5 178 564

angled plug � angled socket 2 m KVI−CP−1−WS−WD−2 163 139

angled plug � angled socket 5 m KVI−CP−1−WS−WD−5 161 138

straight plug � angled socket 5 m KVI−CP−1−GS−WD−5 163 137

straight plug � angled socket 8 m KVI−CP−1−GS−WD−8 163 136

straight plug � straight socket 2 m can be used as drag chain KVI−CP−2−GS−GD−2 170 234

straight plug � straight socket 5 m can be used as drag chain KVI−CP−2−GS−GD−5 170 235

straight plug � straight socket 8 m can be used as drag chain KVI−CP−2−GS−GD−8 165 616

Page 96: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

A. Technical appendix

A−8 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Plug for input and output modules

Plug Type Part no.

Sensor plug straight, M12, PG7 SEA−GS−7 18 666

Sensor plug straight, M12, 5−pin, PG7 SEA−M12−5GS−7 175 487

DUO plug M12, (2 cable openings) SEA−GS−11−DUO 18 779

DUO plug M12, (2 cable openings), 5 pin SEA−5GS−11−DUO 192 010

Sensor plug straight, M8, 3−pin, (can be soldered) SEA−GS−M8 18 696

Sensor plug straight, M8, 3−pin, (can be screwed) SEA−3GS−M8−S 192 009

Plug for output module with its own additionalpower supply

Plug Type Part no.

Mains connector plug straight, PG9 NTSD−GD−9 18 493

Mains connector plug straight, PG13.5 NTSD−GD−13,5 18 526

Mains connector plug angled PG9 NTSD−WD−9 18 527

Sensor plug straight, M12, PG7 SEA−GS−7 18 666

Page 97: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

A. Technical appendix

A−9Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Page 98: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

General DP master

B−1Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Appendix B

Page 99: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−2 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Contents

B. General DP master B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1 PROFIBUS−DP: Commissioning with the general DP master B−3 . . . . . . . . . . . . .

B.1.1 Bus start B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.2 Send parametriziung data B−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.3 Check the configuration data� B−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.4 Transferring input and output data B−7 . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.5 Read diagnostic information B−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.6 Implemented functions and service access points (SAP) B−8 . . . . . . . .

B.1.7 Bus parameters/reaction times� B−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1.8 Transmission times on the PROFIBUS−DP B−9 . . . . . . . . . . . . . . . . . . . .

Page 100: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−3Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

B.1 PROFIBUS−DP: Commissioning with the general DP master

The CP...−SC can be controlled by any PLC, PC or industrial PCwith a PROFIBUS−DP module as per EN 50170.

Further information Read the information on the following themes in theappropriate sections:

� Module consistency, FREEZE and SYNC, identifiers:section 2.2.

� GSD: section 2.3

B.1.1 Bus start

In order to commission the CP...−SC correctly, the DP mastermust carry out the following functions in the sequence

specified:

1. request diagnosis

2. send parametrizing data (Set_Prm)

3. check configuration data (Chk_Cfg)

4. transfer input and output data (cyclic data exchange,Data_Exchange)

5. read diagnostic information (Slave_Diag).

The composition and contents of the individual telegrams aredescribed in the following sections.

Page 101: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−4 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

B.1.2 Send parametriziung data

Set_Prm The parametrizing data are transferred from the DP masterto the valve terminal with the function Set_Prm

Octet 1: Station status

Bit Meaning Explanation

0 � Reserved

1 �

2 �

3 WD_On Response monitoring of the CP...−SC on/off:0 = off1 = on

4 Freeze_Req 0 = FREEZE mode not requested by the master1 = FREEZE mode set by the master

5 Sync_Req 0 = SYNC mode not requested by the master1 = SYNC mode set by the master

6 Unlock_Req Bit 7 Bit 6 Explanation

7 Lock_Req 0 0 min TSDR + slave parameters may be overwritten

0 1 CP...−SC enabled for other masters

1 0 CP...−SC blocked for other masters

1 1 CP...−SC enabled for other masters

Tab.�B/1: Octet 1: Station status

Page 102: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−5Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Further octets

Octet Designation Explanation

2 and 3 WD_Fact_1WD_Fact_2

Range 1 ... 255: The response monitoring time ofthe CP...−SC is transferred with these two octets:TWD [s] = 10 ms x WD_Fact_1 x WD_Fact_2

4 Minimum station DelayResponder (min TSDR)

The minimum time the CP...−SC must wait, beforethe reply telegram may be sent to the DP master.

5 and 6 Ident_number Transmission of the manufacturer identifier of theCP...−SC (= 009Ch); parametrizing telegrams to theCP...−SC are only accepted if the transmitted and theprogrammed manufacturer identifiers are the same.

7 Group_Ident Not supported by the CP...−SC

8 ... 10 DPV1 status Not supported by the CP...−SC

11 ... User_Prm_Data Slave−specific parameters

Tab.�B/2: Octets 2 ... 32

Page 103: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−6 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

B.1.3 Check the configuration data�

Chk_Cfg The configuration data are transferred from the DP masterto the CP...−SC with the function Chk_Cfg.

Overview of parameters (Chk_Cfg):

Octet 1−n: DP identifierPermitted identifiers for the CP...−SC (see also Tab.�2/2):

CP...−SC and extensions DP identifier Comment

decimal hex

CPA−SC (without extension = 32 DO) Octet 1: 35 Octet 1: 23h 32 digital outputs/valvecoils of the CPA−SC

CPV−SC (without extension = 16 DO) Octet 1: 33 Octet 1: 21h 16 digital outputs/valvecoils of the CPV−SC

Extension 8 digital inputs Octet 16 Octet 1: 10h e.�g. CPI/CP inputmodules

Extension 16 digital inputs Octet 17 Octet 11hmodules

Extension 24 digital inputs Octet 18 Octet 12h

Extension 32 digital inputs Octet 19 Octet 13h

Extension 8 digital outputs Octet 32 Octet 20h e.�g. CPI/CP outputmodules CP valve

Extension 16 digital outputs Octet 33 Octet 21hmodules, CP valveterminals

Extension 24 digital outputs Octet 34 Octet 22h

Extension 32 digital outputs Octet 35 Octet 23h

Tab.�B/3: Overview of DP identifiers for various extensions of the CP...−SC

Configuration examples can be found in section 2.5.

Page 104: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−7Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

B.1.4 Transferring input and output data

Data_Exchange The cyclic exchange of data is accomplished with thefunction Data_Exchange.

With this function the output data for the CP...−SC is trans�

mitted as an octet string of length x. The octet string lengthdepends on the number of identifier bytes.

Please noteWith the function Data_Exchange, the CP...−SC expects theoutput data for the valves and electric outputs.

The input data are sent to the master as a reply telegram.

B.1.5 Read diagnostic information

Slave_Diag The diagnostic data are requested by the CP...−SC via thefunction Slave_Diag (see section 3.3, Diagnosis viaPROFIBUS−DP).

Set_Prm With the function Set_Prm you can determine the watchdogtime (WD_Fact_1, Octet 2, WD_Fact_2, Octet 3). In the eventof a fault, the CP...−SC will switch off all the valves and elec�tric outputs after the parametrized time (e.�g. if there is abus failure).

Page 105: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−8 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

B.1.6 Implemented functions and service access points (SAP)

Function Available Destination SAP(DSAP)

Data_Exchange Yes NIL

RD_Inp Yes 56

RD_Outp Yes 57

Slave_Diag Yes 60

Set_Prm Yes 61

Chk_Cfg Yes 62

Get_Cfg Yes 59

Global_Control Yes 58

Set_Slave_Add No 55

Tab.�B/4: Overview of implemented functions and serviceaccess points

Page 106: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−9Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

B.1.7 Bus parameters/reaction times�

Baud rate (kBaud) max TSDR (TBit) min TSDR (TBit)

... 187.5 60

500 100

1500 150 11

3000 250

11

6000 450

12000 800

Tab.�B/5: Bus parameters and reaction times

B.1.8 Transmission times on the PROFIBUS−DP

Please noteObserve here the cycle time of your PLC and the updatetime of the PROFIBUS−DP.

The time delay within the CP...−SC depends on the amount of

data and therefore on the extension of the CP...−SC. It amounts to: < 2 ms.

Please refer to the manual for your controller for ascertainingthe total time required for transmission.

Page 107: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

B. General DP master

B−10 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Page 108: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

Index

C−1Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Appendix C

Page 109: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

C. Index

C−2 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

Contents

C. Index C−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 110: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

C. Index

C−3Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

A

AbbreviationsProduct−specific XI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accessories A−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Address assignmentCPA−SC−DP 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPI/CP modules 2−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPV−SC−DP 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B

Baud rate 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Bus termination 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C

CableAccessories A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field bus 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power supply 1−14, 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cable length 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ConnectingField bus 1−9, 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power supply 1−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Connection for optical−fibre waveguide 1−12 . . . . . . . . . . . . .

ConnectionsElectrical 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CP extensionSetting 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CP extension connection 1−22 . . . . . . . . . . . . . . . . . . . . . . . . .

CPI systemRules 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CPI/CP modulesAddress assignment 2−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 111: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

C. Index

C−4 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

D

Designated use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Diagnosis via PROFIBUS−DP 3−10 . . . . . . . . . . . . . . . . . . . . . .

Diagnosis bytes 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Diagnosis steps 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DIL switches 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E

Electrical isolation 1−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Examples of configuration 2−19 . . . . . . . . . . . . . . . . . . . . . . . .

Extending the CP...−SC−DP 1−22 . . . . . . . . . . . . . . . . . . . . . . . .

F

FaultReaction to faults 3−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Field bus baud rate 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Field bus cable 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Field bus length 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Field bus plug 1−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

I

Important user instructions IX . . . . . . . . . . . . . . . . . . . . . . . . . .

L

LEDBF 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PL 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PS 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SF 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

N

Notes on the use of this manual VIII . . . . . . . . . . . . . . . . . . . .

Page 112: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

C. Index

C−5Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

O

Operating elements 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating voltageSwitching on 2−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Operating voltage cable 1−14, 1−15 . . . . . . . . . . . . . . . . . . . . .

PPELV (Protected Extra−Low Voltage) 1−15 . . . . . . . . . . . . . . . .

Pictograms X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pin allocationField bus interface 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power supply connection 1−16 . . . . . . . . . . . . . . . . . . . . . . .

Potential equalization 1−19 . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power supply 1−14, 1−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical isolation 1−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power unit 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PreparationInstallation 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PreparingCommissioning 2−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PROFIBUS−DPConfiguration 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Check the configuration data B−6 . . . . . . . . . . . . . . . . . . . . . Cyclic exchange of data B−7 . . . . . . . . . . . . . . . . . . . . . . . . . Device master file (GSD) 2−11 . . . . . . . . . . . . . . . . . . . . . . . DP identifier 2−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FREEZE 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General DP master B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Icon files 2−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Implemented functions B−8 . . . . . . . . . . . . . . . . . . . . . . . . . Module consistency 2−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reaction times B−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Send parametrizing data B−4 . . . . . . . . . . . . . . . . . . . . . . . . Service access points (SAP) B−8 . . . . . . . . . . . . . . . . . . . . . . SYNC 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RRotary switches 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 113: Valve terminals CPA−SC/CPV−SC PROFIBUS−DP · Contents and general instructions II Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH PROFIBUS, PROFIBUS−DP® are registered trade

C. Index

C−6 Festo P.BE−CPASC−CPVSC−DP−EN en 0610NH

S

Safety concept 1−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Segment length 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SettingCP extension 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Station number 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Station numberSetting 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Station status 3−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

STEP 7Commissioning 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Online diagnosis 3−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strain relief 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

T

Target group VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Technical specifications A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . .

Text markings X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

�Tool change mode" configuration 2−17, 2−20 . . . . . . . . . . . . .

V

Valve solenoid coilsStatus display 3−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .