Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle...

143
9604 Valve terminal type 03/05 Electronics Manual Field bus connection FB7 Only valid in agreement with the printed documentation accompanying the product! Compare this edition code. Field bus protocols: Beckhoff II/O-Bus, Eberle EDP-L System or compatibles

Transcript of Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle...

Page 1: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

9604

Valve terminal type 03/05Electronics Manual

Field bus connection FB7

Only valid in agreement with the printed documentationaccompanying the product! Compare this edition code.

Field bus protocols:Beckhoff II/O-Bus, Eberle EDP-L System

or compatibles

Page 2: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Author: Eberhard Klotz

Editors H.J. Drung, M.Holder

Translation: Douglas Smith

Layout: Festo KG, Dept. PV-IDM

Type setting: TP

3nd. edition 9604

1994 Festo KG, D-73726 Esslingen Federal Republic of Germany

All rights reserved, including translation rights.No part of this publication may be reproduced ortransmitted in any form or by any means, elec-tronic, mechanical photocopying or other-wise,without the prior written permission of Festo KG.

prin

ted

on 1

00%

rec

yclin

g pa

pier

VIFB7 - 03/05

9604 I

Page 3: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Part no.: 152 767

Title: MANUAL

Designation: P.BE-VIFB7-03/05-GB

VIFB7 - 03/05

II 9604

Page 4: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Contents

GENERAL SAFETY INSTRUCTIONS

Designated use VIITarget group VIIIImportant user instructions IXDanger categories IXPictograms XInstructions on this manual XIService XIII

Chapter 1 SYSTEM SUMMARY

1.1 System summary 1-3System structure 1-3Type 03:Description of components 1-5Type 05:Description of components 1-9Description of function 1-11

Chapter 2 FITTING

2.1 Fitting the components 2-3Input/output modules 2-4End plates 2-6Hat-rail clamping unit (type 03) 2-8

2.2 Type 03: Fitting the valve terminal 2-9Wall fitting (type 03) 2-9Hat-rail fitting (type 03) 2-10

2.3 Type 05: Fitting the valve terminal 2-12Wall fitting (type 05) 2-12

ContentsVIFB7 - 03/05

9604 III

Page 5: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Chapter 3 INSTALLATION

3.1 General connecting methods 3-3Selecting the operating voltage cable 3-4Connecting the cable to the plugs/sockets 3-5

3.2 Field bus node 3-7Opening and closing the node 3-7Configuring the valve terminal 3-9Setting the operating mode 3-10Setting the field bus baud rate 3-11

3.2.1 Type 03: Connecting theoperating voltages 3-12

3.2.2 Type 05: Connecting the operating voltages 3-19

3.2.3 Connecting the field bus 3-26

3.3 Connecting the input modules 3-28Pin assignment 3-30

3.4 Connecting the output modules 3-31Pin assignment 3-33

VIFB7 - 03/05

IV 9604

Page 6: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Chapter 4 COMMISSIONING

4.1 Basic principles of configuration andaddressing 4-3General 4-3Switching on the operating voltages 4-4

Calculating the configuration data 4-5Calculating the number of inputs/outputs Type 03 4-6 Type 05 4-7Address assignment of the valve terminal 4-9Basic rule 1 4-10Basic rule 2 4-13Basic rule 3 4-13Address assignment afterextension/conversion 4-14Examples of addressing Type 03: MIDI/MAXI valves 4-17 Type 05: ISO valves 4-18

4.2 Beckhoff 4-19II/O bus 4-19Configuration example 4-19Addressing example 4-21

4.3 Eberle 4-23EDP-L system 4-23Configuration example 4-23Addressing example 4-25

4.4 Beckhoff/Siemens S5 4-28

VIFB7 - 03/05

9604 V

Page 7: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Chapter 5 DIAGNOSIS AND ERROR TREATMENT

5.1 Summary of diagnostic possibilities 5-3

5.2 On-the-spot diagnosis 5-4LED displays 5-4 Field bus node 5-4 Valves 5-6 Input/output modules 5-8Testing the valves 5-9

5.3 Diagnosis via field bus 5-11Status bits 5-11

5.4 Error treatment 5-12Reaction to faults in thecontrol system 5-12short circuit/overload at an output module 5-13

Appendix A TECHNICAL APPENDIX

Technical specifications A-3Cable length and cross section A-7Examples of circuitry A-12

Appendix B GLOSSARY

Appendix C INDEX

VIFB7 - 03/05

VI 9604

Page 8: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

GENERAL SAFETY INSTRUCTIONS

Designated use

The valve terminal type 03/05 described in thismanual is designated exclusively for use asfollows:

• for controlling pneumatic and electricalactuators (valves and output modules)

• for interrogating electrical sensor signals bymeans of the input modules.

Use the valve terminal only as follows:

• as designated in the instructions

• in technically faultless condition

• without any modifications.

The specified limit values for pressures, tempe-ratures, electrical data, moments, etc. must beobserved when additional commercially-availablecomponents such as sensors and actuators areconnected.

Please comply also with national and local safetylaws and regulations.

VIFB7 - 03/05 General safety instructions

9604 VII

Page 9: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Target group

This manual is directed exclusively attechnicians who are trained in control andautomation technology and who have experiencein installing, commissioning, programming anddiagnosing programmable logic controllers (PLC)and field bus systems.

VIFB7 - 03/05 General safety instructions

VIII 9604

Page 10: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

IMPORTANT USER INSTRUCTIONS

Danger categories

This manual contains instructions on the hazardswhich may arise from improper or negligent useof the valve terminal.

A distinction is made between the followinginstructions:

WARNINGThis means that injury to human beings aswell as material damage can occur if these in-structions are not observed.

CAUTIONThis means that material damage can occur ifthese instructions are not observed.

PLEASE NOTEThis means that this instruction must also beobserved.

VIFB7 - 03/05 General safety instructions

9604 IX

Page 11: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Pictog rams

Pictograms and symbols supplement the dangerinstructions and draw attention to the conse-quences of dangers. The following pictogramsare used:

Uncontrolled movements of loose tubing.

Uncontrolled movement of the connected actua-tors.

High electric voltage or undefined switchingstates of the electronic components which affectthe connected circuits.

Electrostatically vulnerable components whichwill be destroyed if their contact surfaces aretouched.

The ISO valve terminal type 05 is very heavy.Please ensure that it is fastened correctly andsee that all operating personnel wear safetyshoes.

VIFB7 - 03/05 General safety instructions

X 9604

Page 12: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Instructions on this manual

This manual contains specific information on theinstallation, commissioning, programming anddisgnosis of the valve terminals types 03/05 andthe input/output modules.The following product-specific abbreviations areused in this manual:

Abbreviation Meaning

Terminal or Valve terminal

Valve terminal type 03(MIDI/MAXI) or type 05 (ISO) with/without electric I/Os

Node Field bus node

Valve-sub base

S sub-base

D sub-base

ISO sub-base

Pneumatic sub-base for valves

For two single valves type 03 (MIDI/MAXI)

For two double solenoid valvesor mid-position valves type 03 (MIDI/MAXI)

Sub-base for 4, 8 or 12 ISO valves type 05 (as per ISO 5599/I, size 1 or 2)

IOI/O

InputOutputInput and/or output

P module pneumatic module in general

I/O module Module with digitalinputs/outputs in general (input/output modules

PLC Programmable logic controller;or simply controller

Fig. 0/1: Abbreviations

VIFB7 - 03/05 General safety instructions

9604 XI

Page 13: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

PLEASE NOTE• All information on the pneumatic modules is

to be found in the Pneumatics Manual P.BE-MIDI/MAXI-03-GB or P.BE-ISO-05-GB.

• A valve terminal with four pneumatic valvesub-bases and four input/output modulesis used for the diagrams in this manual.

Fig. 0/2: Standard fitting for the drawings

VIFB7 - 03/05 General safety instructions

XII 9604

Page 14: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

This description of the electronic componentscontains a description of the node and theinput/output modules.

The valve terminals can be connected to thecontrol systems of various manufacturers.This manual deals with the configuration ofthe PLC and the addressing of the terminalsfor the following control systems:

PLEASE NOTEAll information on the pneumatic modules is tobe found in the Pneumatics Manual P.BE-MIDI-/MAXI-03-GB or P.BE-ISO-05-GB.

Service

If you have any technical problems, pleaseconsult your local Festo Service.

Controllermanu-facturer

Controller (PLC) Field bus module Field bus

Beckhoff PC/ATIPC

VME busSMP bus

AT96 bus

C1200C1210C1220C1300C1500C1510C1600

II/O bus

Eberle PLS 514 DP41 EDP-L system

Siemens S5-115U . .S5-155U

C1100 II/O bus

As at 6.93, further systems in preparation

Fig. 0/3: Compatible automation systems/field bus protocols

VIFB7 - 03/05 General safety instructions

9604 XIII

Page 15: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

1. SYSTEM SUMMARY

VIFB7 - 03/05 1. User instructions

9604 1-1

Page 16: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Contents

1.1 SYSTEM SUMMARY 1-3System structure 1-3Type 03:Description of components 1-5Type 05:Description of components 1-9Description of function 1-11

VIFB7 - 03/05 1. User instructions

1-2 9604

Page 17: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

1.1 SYSTEM SUMMARY

System structure

Festo solves your automation tasks at themachine level by means of valve terminals.Valve terminals types 03 and 05 are constructedon a modular basis and permit combinations ofpneumatic and electronic modules. The followinggroupings are possible.

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAA

AAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAA

AAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAA

AAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAA

Valve terminal type 03: MIDI/MAXI valves andelectronic modules

Further field bus slaves

Valve terminal type 05:ISO valves and electronic modules

Valve terminal type 03:MAXI valves only

Field bus

Industrial PCBeckhoff C4000or other masters ...

ASI bus

Fig. 1/1: Summary of system and possible variants of valve terminals

VIFB7 - 03/05 1. User instructions

9604 1-3

Page 18: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The valve terminal with field bus connectionoffers the following advantages:• can be equipped in various ways with digital

I/Os and pneumatic valve locations• subsequent extension/conversion possible• different valve designs can be fitted• can be connected to various control

systems• fewer cabling required due to two-core cables• easy-to-understand system structure due

to physical separation of controller and machine.

• valves already fitted• pre-wired pilot valve solenoid coils• central air supply• central exhaust• valve terminal is tested before leaving the

factory.

A field bus system also offers the followingadvantages:• fewer output assemblies in the controller• economic data transfer over long distances• high baud rate• a large number of slaves can be connected• error diagnosis is made easier

VIFB7 - 03/05 1. User instructions

1-4 9604

Page 19: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Type 03: Description of components

Valve terminal type 03 consists of individualmodules. Each module is assigned with differentfunctions and different elements for connection,display and operation. The diagram below sum-marizes the modules.

No. Modules

1 Node

2 Electronic modules (input/output modules), fitted with

• digital inputs (modules with 4 or 8 inputs)

• digital outputs (modules with 4 outputs)

3 End plate left with hole for additional earth cable connection

4 Pneumatic modules (valve sub-bases) fitted with S valves:

• 5/2 single solenoid valves

• 5/2 double solenoid valves

• 5/3 mid-position valves (exhausted, pressurized, blocked)

• blanking plates S = Auxiliary pilot air

5 Pneumatic MIDI or MAXI modules:

• pressure supply with integrated exhaust (MIDI)

• intermediate air supply with integrated exhaust (MIDI)

• pressure supply adapter with/without regulator (MIDI/MAXI)

• additional air supply module (MAXI)

6 End plate right, depending on the size of the last sub-base:

• with common pneumatic tubing connections and integrated regulator for 5 bar auxiliary pilot air (unregulated pilot air is not permitted)

• with common pneum. tubing connections, but without integrated regulator

• without common pneumatic tubing connections (only MAXI)

3 2 4 51 4 5 4 5 4 6

Fig. 1/2: Modules of the valve terminal type 03

VIFB7 - 03/05 1. User instructions

9604 1-5

Page 20: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The following connection and display elementsare to be found on the electronic modules:

No. Meaning

1 2 3 4 5 6 7 8

9101112

Output socket for electronic outputYellow LED (status display per output)Red LED (error display per output)Input socket for one electrical inputGreen LED (per input)Input socket for two electrical inputsTwo green LEDs (one LED per input)Node with LEDs and field bus connection,detailed description in Chapter "Installation"Right-hand end plateFuse for internal inputs/sensorsOperating voltage connectionASI master for I/O periphery

1 2 3 4 5 6 7 8

11 10 9

A4 A4 E4 E8

12

ASIMaster

Fig. 1/3: Display and connection elements of the electronic modules

VIFB7 - 03/05 1. User instructions

1-6 9604

Page 21: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The following connection, display and operatingelements are to be found on the pneumatic MIDImodules type 03:

No. Meaning

1

2 3 4 5 6 7 8 9

Node with LEDs an field bus connection,further details in the chapter "Installation"Yellow LEDs (state)Manual override for valve solenoid coilsValve location inscription fieldUnused valve location with cover plateCommon pneumatic tubing connectionsWork connections (per valve)Fuse for inputs/sensorsPower supply connection

2 3 4

6

9 8 7

51

Fig. 1/4: Operation, display and connection elements of the pneumatic MIDI modules type 03

VIFB7 - 03/05 1. User instructions

9604 1-7

Page 22: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The following connection, display and operatingelements are to be found on the pneumaticMAXI modules type 03:

No. Meaning

1

2 3 4 5 6 7 8 910

Node with LEDs an field bus connection,further details in the chapter "Installation"Yellow LED (per valve solenoid coil)Manual override (per valve solenoid coil)Valve location inscription field (labels)Unused valve location with cover plateCommon pneumatic tubing connectionsWork connections (2 per valve, placed one obove the other)Regulator for limitted pressure of auxiliary pilot airCommon pneumatic tubing connectionExhausts

31 2 4

6

910

5

78

Fig. 1/5: Operation, display and connection elements of the pneumaticMAXI modules type 03

VIFB7 - 03/05 1. User instructions

1-8 9604

Page 23: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Type 05: Description of components

Valve terminal type 05 consists of individualmodules. Each module is assigned with differentfunctions and different elements for connection,display and operation. The diagram below sum-marizes the modules.

No. Modules

1 Node

2 Electronic modules (input/output modules), fitted with• digital inputs (modules with 4 or 8 inputs)• digital outputs (modules with 4 outputs)

3 End plate left with opening for additional earth connection

4 Adapter plate for ISO sub-base (manifold) as per ISO 5599/I sizes 1 or 2

5 ISO sub-base (manifolds for 4, 8 or 12 locations) fitted with:• Pneumatic valves with hole pattern as per ISO 5599/I

- single pneumatic valves- double pneumatic valves- pneumatic mid-position valves

• components for vertical stacking (regulator plates, flow control plates etc.)

• blanking plates

6 Right-hand end plate with holes for fitting and with threadfor lifting eye bolts (M8)

3 2 41 5 6

Fig. 1/6: Modules of the valve terminal type 05

VIFB7 - 03/05 1. User instructions

9604 1-9

Page 24: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The following connection, display and operatingelements are to be found on the pneumatic ISOmodules type 05:

The electronic modules are described in thesection "Description of components type 03".

No. Meaning

1

23456789101112

Node with LEDs and field bus connection, detailed description see chapter "Installation"Fuse for inputs/sensors (pin 1)Adapter plateOperating voltage connection of valve terminal type 05Fuse for valves (pin 2)Valve location inscription fieldYellow LEDs (per pilot solenoid)Manual override (per pilot solenoid, pressing or locking)External air control connectionCommon connectionsWork connections (per valve)Adapter cable for operating voltage of node and I/O modules

Fig. 1/7: Operating, display and connection elements of ISO modulestype 05

1 2 3 4 6

911

5

12

7 8

10

9

10

VIFB7 - 03/05 1. User instructions

1-10 9604

Page 25: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Description of function

The node controls the following functions:

• connection of the terminal to the field busmodule of the control system and to furtherfield bus slaves via the field bus interface

• adaption of the field bus baud rate and fieldbus protocol to the control system

• control of data transfer to/from the field busmodule of the control system.

• internal control of the terminal.

1

42 ,

42

1

AAAAAAAAA

AAAAAA

Incoming field bus

Continuingfield bus

= Compressd air

= Work air

Fig. 1/8: Function summary of valve terminal type 03/05

electricalsignals flow

Node

VIFB7 - 03/05 1. User instructions

9604 1-11

Page 26: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The input modules process the input signals(e.g. from sensors) and transmit these signalsvia the field bus to the controller. The outputmodules are universal electrical outputs andcontrol small current-consuming devices withpositive logic, e.g. further valves, lights etc..

The pneumatic modules are used for thefollowing:• common channels for supply and exhaust air• electrical signals from all solenoid valve coils.

Work connections 2 and 4 are supplied for eachvalve location on the individual pneumatic modu-les.

By means of the common channels on thepneumatic end plate, the valves are suppliedwith compressed air and both the exhaust airand the pilot air from the valves are vented.Further modules for air supply are also available,in order that different work pressures can beused or in order that either MIDI/MAXI valves orISO valves can be fitted on a terminal.

Further information on their use is to be found inthe Pneumatics Manual for the valve terminal.Only the electronic modules and the node aredescribed here.

VIFB7 - 03/05 1. User instructions

1-12 9604

Page 27: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

2. FITTING

VIFB7 - 03/05 2. Fitting

9604 2-1

Page 28: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Contents

2.1 FITTING THE COMPONENTS 2-3Input/output modules 2-4End plates 2-6Hat rail clamping unit (type 03) 2-8

2.2 TYPE 03: FITTING THEVALVE TERMINAL 2-9Wall fitting (type 03) 2-9Hat rail clamping unit (type 03) 2-10

2.3 TYPE 05: FITTING THEVALVE TERMINAL 2-12Wall fitting (type 05) 2-12

VIFB7 - 03/05 2. Fitting

2-2 9604

Page 29: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

2.1 FITTING THE COMPONENTS

WARNINGBefore fitting the components switch off thefollowing:• the compressed air supply• the power supply for the outputs

(pin 2)• the power supply for the electronic

components (pin 1)

You thereby avoid:• uncontrolled movement of loose tubing• undesired movements of the connected

actuators• undefined switching states of the electronic

components.

CAUTIONThe valve terminal components contain partswhich can be damaged by electrostatic charges. • Do not therefore touch the contact surfaces

of the plug connectors at the side of themodules.

• Observe the instructions for dealing withcomponents liable to damage by electro-static charges.

You thereby avoid destroying the valve terminalcomponents.

VIFB7 - 03/05 2. Fitting

9604 2-3

Page 30: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

PLEASE NOTETreat all the modules and the components ofthe valve terminal with the utmost care. Payspecial attention to the following: • Screw connectors must not be twisted or subjected to mechanical stress.• The screws must fit accurately (otherwise

the threads will be damaged).• The specified torques must be observed.• The modules must be aligned correctly

(IP 65).• The contact surfaces must be clean (avoid

leakage and faulty contacts).• The contacts of the type 03 MIDI valve solenoid coils must not be bent (they

are not resistant to alternate bending and will break off if bent backwards).

In the case of modules and componentsordered at a later stage, observe also the fit-ting instructions included with the product.

Input/output modules

Before the valve terminal can be extended orconverted, it must first be dismantled.

Dismantling (see also following diagram)

• Remove completely the screws of the rele-vant modules. The modules are now heldtogether only by the electrical plug con-nectors.

• Pull the modules carefully and without tippingaway from the electrical plug connectors.

• Replace broken or damaged seals.

VIFB7 - 03/05 2. Fitting

2-4 9604

Page 31: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Fitting (see also following diagram)

PLEASE NOTE• Always place the subsequently ordered modules after the last module before the end plate.• Do not fit more than 12 electronic modules.

Please note also the addressing limits of your field bus protocol.

Fit the modules as follows:• Fit a new seal on the right-hand contact sur-

face facing the node.• Fit the module as shown below.

Seal

Fastening screws max. 1 Nm

Fig. 2/1: Fitting electronic I/O modules

VIFB7 - 03/05 2. Fitting

9604 2-5

Page 32: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

End plates

A left-hand and a right-hand plate are requiredas mechanical termination of the modular termi-nal. These end plates fulfil the following functi-ons:• They comply with protection class IP 65.• They contain connections/contacts for the

protective earth cable.• They contain holes for fitting onto walls and

onto the hat rail clamping unit.

By means of screw connectors and the readyfitted spring contacts, the right-hand end plate ofthe ISO terminal is connected conductively to themanifold sub-bases. It is therefore sufficientlyearthed.

There are various designs of right-hand endplate for the terminls of type 03 (MIDI/MAXI).Each design is already fitted with a protectiveearth cable.

CAUTIONEarth the right-hand end plate with the pro-tective earth cable before fitting the terminaltype 03. You thereby avoid high voltages onthe metal surfaces in the case of a fault.

VIFB7 - 03/05 2. Fitting

2-6 9604

Page 33: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Earth the end plates as follows:

• Right-hand end plate (type 03):To earth the right-hand end plate connect thecable fitted on the inside to the appropriatecontacts on the pneumatic modules or on thenode (see following diagram).

• Left-hand end plate (type 03 and type 05): The left-hand end plate is connected con-ductively to the other components via springcontacts which are already fitted.

Please note:Instructions on earthing the complete valveterminal are to be found in the chapter "Installa-tion".

The diagram below shows how both end platesare fitted.

Seal

Fastening screwsmax. 1 Nm

Ready-fittedearth cable

Contact for earth cable

Seal

Fig. 2/2: Fitting the end plates (example with terminal type 03)

VIFB7 - 03/05 2. Fitting

9604 2-7

Page 34: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Hat rail clamping unit (type 03)

If the terminal is to be fitted onto a hat rail(support rail as per EN 50022), you will requirethe hat rail clamping unit. This unit must befastened to the rear of the end plates as shownin the following diagram.

Before fitting ensure that:• the glueing surfaces are clean

(clean with spirit)• the flat-head screws are tightened (6)

After fitting ensure that:• the levers are secured with the locking screw

(7).

1 Rubber foot, self-adhesive2 Clamping elements3 Left-hand lever *)4 Right-hand lever *)5 O ring6 Flat head screw7 Retaining screw

*) Levers differ in length for MIDI or MAXI

Fig. 2/3: Fitting the hat rail clamping unit

VIFB7 - 03/05 2. Fitting

2-8 9604

Page 35: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

2.2 TYPE 03: FITTING THE VALVE TERMINAL

Wall fitting (type 03)

WARNINGWith long terminals use additional supportbrackets approximately every 200 mm.You thereby avoid: • overloading the fastening eyes

on the end plates• the terminal sagging • natural resonances

Proceed as follows:• Calculate the weight of your terminal

(weigh or estimate). General rule:

• Make sure that the fastening surface can car-ry this weight.

• Fasten the terminal with four M6 screws asshown below (fitting position as desired). Usespacers if necessary.

MIDI MAXI

per pneumatic module 800 g 1200 g

per node 1000 g 1000 g

per electronic module 400 g 400 g

7,6 mm

M6

Fig. 2/4: Fitting the valve terminal typ 03 on the wall

VIFB7 - 03/05 2. Fitting

9604 2-9

Page 36: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Fitting the hat rail (type 03)

The terminal is suitable for fitting onto a hat rail(support rail as per EN 50022). For this purposethere is a guide groove on the rear of allmodules for hanging the terminal on the hat rail.

CAUTION• Hat rail fitting without the hat rail

clamping unit is not permitted.• If the terminal is fitted in a sloping position or at a point subjected to vibration,

protect the hat rail clamping unit against slipping and, by means of the screws (7),

against unintentional loosening/opening.

PLEASE NOTE• If the terminal is fitted in a horizontal position

without vibration, the screws (7) are not required for fastening the hat rail

clamping unit. • If your terminal does not have a hat rail

clamping unit, this can be ordered and fittedlater.

• The use of MIDI or MAXI clamping unitsdepends on the end plates fitted (MIDI/MAXI).

Proceed as follows:• Calculate the weight of your terminal (weigh

or estimate). General rule:• Make sure that the fastening surface can car-

ry this weight.

MIDI MAXI

per pneumatic module 800 g 1200 g

per node 1000 g 1000 g

per electronic module 400 g 400 g

VIFB7 - 03/05 2. Fitting

2-10 9604

Page 37: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

• Fit a hat rail (support rail as per EN 50022 –35x15; width 35 mm, height 15 mm).

• Fasten the hat rail approximately every 100mm on the fastening surface.

• Hang the terminal onto the hat rail. Use thehat rail clamping unit to secure the terminalon both sides against tilting or slipping (seediagram below).

• If the terminal is fitted in a sloping position orat a point subjected to vibration, protect thehat rail clamping unit with two screws (7)against unintentional loosening/opening.

Retaining screw (7)

Valve terminaltype 03

Hat rail clamping unit(locked)

Hat rail clampingunit unlocked

Fig. 2/5: Fitting the valve terminal typ 03 onto a hat rail

VIFB7 - 03/05 2. Fitting

9604 2-11

Page 38: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

2.3 TYPE 05: FITTING THE VALVE TERMINAL

Wall fitting (type 05)

WARNINGWith long terminals use additional supportbrackets approximately every 200 mm.You thereby avoid:• overloading the fastening eyes

on the end plates• the terminal sagging (I/O side) • natural resonances

Proceed as follows:• Calculate the weight of your terminal (weigh

or estimate). General rule:

• Make sure that the fastening surface can car-ry this weight.

ISO size 1 ISO size 2

Sub-base *)- 4 valve locations

incl. valves- 8 valve locations

incl. valves- 12 valve locations

incl. valves

8 kg

14 kg

20 kg

12 kg

20 kg

28 kg

per node 1 kg

per electronic module 0.4 kg

*) Components for vertical stacking:Please see pneumatics manual P.BE-ISO-GBfor weights.

VIFB7 - 03/05 2. Fitting

2-12 9604

Page 39: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Fasten the terminal as follows:• with three M10 screws on the adapter plate

and on the right-hand end plate (2)• with two M6 screws on the left-hand end pla-

te (1)

If required, use the following additional fasteningmethods:• the hole on the bottom of the right-hand end

plate with an M10 thread ("blind hole" (3)

• the supporting angles for the I/O modules(see fitting instructions supplied with theangles)

The terminal can be fitted in any desiredposition. If necessary, use spacers as well asthe mounting and transport threads M8 (e.g.lifting eye bolts for crane hooks).

M10

3

Thread M8 for lifting eye bolts21

M6

Fig. 2/6: Fitting the ISO valve terminal type 05 on the wall

VIFB7 - 03/05 2. Fitting

9604 2-13

Page 40: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3. INSTALLATION

VIFB7 - 03/05 3. Installation

9604 3-1

Page 41: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Contents

3.1 GENERAL CONNECTING METHODS 3-3Selecting the field bus cable 3-4Selecting the operating voltage cable 3-4Connecting the cables to theplugs/sockets 3-5

3.2 FIELD BUS NODE 3-7Opening and closing the node 3-7Configuring the valve terminal 3-9Setting the station number andoperating mode 3-10Field bus baud rate 3-11

3.2.1 Type 03: Connecting the operating voltages 3-12

3.2.2 Type 05: Connecting the operating voltages 3-19

3.2.3 Connecting the field bus 3-26

3.3 CONNECTING THEINPUT MODULES 3-28Pin assignment 3-30

3.4 CONNECTING THEOUTPUT MODULES 3-31Pin assignment 3-33

VIFB7 - 03/05 3. Installation

3-2 9604

Page 42: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3.1 GENERAL CONNECTING METHODS

WARNINGBefore installation or maintenance work is car-ried out, the following must be switched off: • the compressed air supply• the power supply to the electronic

components (pin 1).• the power supply to the outputs/valves

(pin 2).

You thereby avoid:• uncontrolled movement of loose tubing• undesired movements of the connected

actuators• undefined switching states of the electronic

components.

VIFB7 - 03/05 3. Installation

9604 3-3

Page 43: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Selecting the field bus cable

A twisted, screened two-core cable must beused for the field bus cable. The cable types tobe used are specified in the PLC manual foryour controller. Take into account the distanceand the field bus baud rate set.

Selecting the operating voltage cable

Several parameters must be considered whenthe two operating voltages are connected.Further information can be found in the followingchapters:

• Chapter 3: InstallationSection: "Connecting the operating voltage"- Calculating the current consumption- Design of power unit- Cable cross section and length.

• Appendix A: Cable length and cross section- Determining the cross section and length by means of tables- Calculating with a formula.

VIFB7 - 03/05 3. Installation

3-4 9604

Page 44: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Connecting the cables to the plugs/sockets

CAUTIONThe position of the pins is different dependingon whether plugs or sockets are used.• The connections of the input and output

modules have been designed as sockets.• The connections of the field bus interface

and the operating voltage connections have been designed as plugs.

The pin assignment is to be found in the following chapters.

When you have selected suitable cables, con-nect them to the plugs/sockets according to thesequence of steps 1-7.

1. Open the plugs/sockets as follows(see diagram):

• Power supply socket:Insert the power supply socket into the operating voltage connection on the valve terminal. Unscrew the housing of the socket, then remove the connection part ofthe socket which is plugged into the operating voltage connection.

• Sensor plug and field bus socket: Unscrew the centre knurled nut.

VIFB7 - 03/05 3. Installation

9604 3-5

Page 45: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

2. Open the strain relief on the rear part of thehousing. Pass the cable through as shownbelow (see diagram).

Cable outer diameter: PG 7: 4.0 ... 6.0 mm PG 9: 6.0 ... 8.0 mm PG 13.5: 10.0 ...12.0 mmPlugs/sockets (straight/angled):• Power supply socket: PG 7, 9 or 13.5• Sensor plug: PG 7 • Bus cable socket: PG 7, 9 or 13.5

3. Remove 5 mm of insulation from the end ofthe cable.

4. Fit the strands with cable end sleeves.

5. Connect the ends of the conductors.

6. Place the connection part onto the housing ofthe plug/socket again and fasten both partswith screws. Pull the cable back so that it isnot looped inside the housing.

7. Tighten the strain relief.

AAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAA

AAAAAAAA

AAAAAAAAAAAA

AAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAA

AAAAAAAA

AAAAAAAAAAAA Connection

part

Cable

Housing

Strain relief

PlugSocket

Fig. 3/1: Individual plug/socket parts andcable routing

VIFB7 - 03/05 3. Installation

3-6 9604

Page 46: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3.2 FIELD BUS NODE

Opening and closing the node

WARNINGBefore installation or maintenance work is car-ried out, the following must be switched off: • compressed air supply • power supply to the electronic components

(pin 1) • power supply to the outputs/valves (pin 2)

You thereby avoid:• uncontrolled movements of loose hoses• undesired movements of the connected

actuators• undefined switching states of the electronic

components

CAUTIONThe node contains components which can bedestroyed by electrostatic charges.• Do not therefore touch any components• Observe the instructions for dealing with

components which can be destroyed by electrostatic charges.

In this way the electronic components of thenode will not be destroyed.

VIFB7 - 03/05 3. Installation

9604 3-7

Page 47: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The following connection and display elementsare to be found on the cover of the node:

PLEASE NOTEThe cover of the field bus node should only beopened for service work, etc.. The cover is con-nected to the internal PC boards via the opera-ting voltage cable and the cable for the fibre-optical waveguide. It cannot therefore be removed completely.

• Do not bend the fibre-optical waveguide

• Maximum radius 30 mm

• OpeningUnscrew and remove the 6 Philips screws inthe cover and lift the cover up carefully. Donot damage the cable through mechanicalstress.

W-DOG

LWL-ERR

CYCLE

CPU-ERR

IN

II / O LWL

OUT

POWER

Green LEDGreen LED

Plug forfield buscable

Red LED

Fig. 3/2: Cover of the node

VIFB7 - 03/05 3. Installation

3-8 9604

Page 48: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

• ClosingReplace the cover. Place the cables for theoperating voltage connection back into thehousing so that they are not clamped. Tightenthe Philips screws in the cover in diagonallyopposite sequence.

Configuring the valve terminal

There are two PC boards in the node. Board 2contains an LED and two plugs for the field buscables; board 3 contains 4 LED‘s and a switchfor setting the operating mode.

AAAAAAAAA

AAAAAAAAA

AAAAAA

AAA

AAAAAAAAA

AAAAAAAAA

AAAAAAAAA

AAAAAAAAA

12

Green LEDGreen LED

Connectionsfor fibre-opticalwaveguide

Board 3

DIL switchfor operatingmode

Board 2

Board 1

Red LED

Board 4

Flat plug for operating voltage connection

Fig. 3/3: Connection, display and operation elements of the node

VIFB7 - 03/05 3. Installation

9604 3-9

Page 49: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Setting the operating mode

PLEASE NOTEThe operating mode "Test" should only be setfor service work.

The operating mode can be set on the DILswitch:– standard operation (field bus)– test operation (valve test of terminal, see

Chapter 6 "Testing the valves and additionaloutputs").

The DIL switch consists of two switch elements.These are numbered 1 and 2. The position "ON"is marked.

AAAAAA

AAAAAA

12

ON

AAAA1 AA

AA12 2

Bild 3/4: Position and function of DIL switch

DIL Switch position

switch ON OFF

1 Normalmode

Preselectfor tests

2 Reserved Reserved

VIFB7 - 03/05 3. Installation

3-10 9604

Page 50: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Field bus baud rate

PLEASE NOTE Data are transmitted at a fixed baud rate of2500 kBaud.

VIFB7 - 03/05 3. Installation

9604 3-11

Page 51: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3.2.1 Type 03: Connecting the operating voltages

WARNING In order that the operating voltage can be iso-lated reliably, you must use an isolating trans-former with at least 4 kV isolation resistancecomplying with standard EN 60742.

CAUTION The power supply to the outputs/valves (pin 2)must be fused externally with maximum 10 A.The external fuse prevents the valve terminalfrom being destroyed in the event of a shortcircuit.

VIFB7 - 03/05 3. Installation

3-12 9604

Page 52: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The 24V operating voltages are connected at thelower left-hand edge of the node.

The following components of the valve terminalare supplied separately with + 24 V DC via thisconnection:

• The operating voltage for the internal electro-nic components and the inputs of the inputmodules (pin 1: DC + 24 V, tolerance ± 25%).

• The operating voltage for the valve outputsand the ouputs of the output modules (pin 2:DC + 24 V, tolerance ± 10%, external fusemaximum 10 A required).

RecommendationThe operating voltage for the outputs should beconnected to the EMERGENCY OFF circuit orEMERGENCY OFF contacts.

Power supplyconnection

Fig. 3/5: Position of the operating voltageconnection

VIFB7 - 03/05 3. Installation

9604 3-13

Page 53: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

PLEASE NOTEWith common voltage supply for pin 1 (electro-nic components and inputs) and pin 2 (out-puts/valves) the lower tolerance of ±10% forboth circuits must be observed.

Check the 24V operating voltage of the outputswhilst your system is operating. Make sure thatthe operating voltage of the outputs lies withinthe permitted tolerances even during full operati-on.

Recommendation• Use a closed-loop power unit.• Calculate the complete current consumption

according to the following table and selectboth a suitable power unit and cable crosssection.

• Avoid long distances between the power unitand the terminal. Calculate also the permitteddistance according to Appendix A. The following rule applies for type 03:

Operatingvoltage

Cable cross section

Distance

Valve terminal• Pin 1 = 2.2 A• Pin 2 = 10 A• Vo = 24 V

1.5 mm2 ≤ 8 m

2.5 mm2 ≤ 14 m

VIFB7 - 03/05 3. Installation

3-14 9604

Page 54: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Calculating the current consumption (type 03)

The following table shows the calculation of thetotal current consumption for terminal type 03.The values given are rounded up. If you useother valves or modules, you should consult theappropriate technical specifications for their cur-rent consumption.

Current consumption of electronic components node and inputs type 03(pin 1, 24 V ± 25 %)

Node

Number of simultaneously occupied sensor inputs: _____x 0.010 A

Sensor supplies: ____x_____ A(see manufacturer specifications)

+

+

Current consumption of electronic components, node and inputs(pin 1) max. 2.2 A

=

Current consumption of outputs type 03(pin 2, 24 V ± 10 %)

Number of MIDI valve coils(simultaneously under power): ____ x 0.055 A

Number of MAXI valve coils(simultaneously under power): ____ x 0.100 A

Number of simultaneously activated electrical outputs: ____ x 0.010 A

Load current of simultaneouslyactivated electrical outputs ____x_____ A

+

+

Current consumption of outputs (pin 2) max. 10 A

Total current consumptionof valve terminal type 03 =

∑ A

∑ A

∑ A

∑ A

∑ A

0.200 A

A

∑ A

∑ A

∑ A ∑ A

∑ A

= +

+

+

Fig. 3/6: Calculating the total current consumption of terminal type 03

VIFB7 - 03/05 3. Installation

9604 3-15

Page 55: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The diagram below shows the pin assignment ofthe operating voltage connection.

Protective earthing

The valve terminal has two protective earthingconnections as follows:• at the operating voltage connection

(pin 4 incoming socket).• at the left-hand end plate (M4 thread).

PLEASE NOTE• Always connect the earth cable to pin 4

of the operating voltage connection.• Make sure that the housing of the valve

terminal and the earth cable at pin 4 have the same potential and that no equalizing currents flow.

• Connect an earth cable of sufficient cross-section to the left-hand end plate if the valve terminal is not mounted on an earthedmachine stand.

In this way you can avoid interference due toelectromagnetic sources.

0 V

PE(protective earth connection, leading socket)

4

1

2

3

24 V supplyfor electroniccomponentsand inputs

24 V supply valves, outputs

Fig. 3/7: Pin assignment of the operating voltage connection

VIFB7 - 03/05 3. Installation

3-16 9604

Page 56: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Example of connection (type 03)

The following diagram shows the connection ofa common 24V supply for pin 1 and pin 2.Please note that:

• the supply to the outputs/slaves must beprotected against short circuit/overload withan external fuse 10 A max.

• the electronic components and inputs mustbe protected against short circuit/overloadwith an external 3.15 A fuse (recommendati-on).

• the supply to the sensors is also protected bythe internal fuse (2 A).

• the common tolerance of DC 24 V ± 10%must be observed.

• equalizing currents must be avoided whenboth earth cables are connected, e.g. bymeans of cables with appropriate crosssection as voltage compensation.

VIFB7 - 03/05 3. Installation

9604 3-17

Page 57: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3 1 2 4

Protective earth connection pin 4 designed for 12 A

Connection cable forvoltage compensationof earthing connections

EMERGERCY

OFF

External fuses

10 A

AC230 V

DC 24V± 10%

0 V3.15 A24 V

Fuse for inputs/outputs (2A)

Fig. 3/8: Example — connecting a common 24 V supply and both protective earth cables (type 03)

VIFB7 - 03/05 3. Installation

3-18 9604

Page 58: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3.2.2 Type 05: Connecting the operating voltages

WARNING In order that the operating voltage can be iso-lated reliably, you must use an isolating trans-former with at least 4 kV isolation resistancecomplying with standard EN 60742.

CAUTIONThe power supply to the outputs/valves (pin 2)must be fused externally with maximum 10 A.The external fuse prevents the valve terminalfrom being destroyed in the event of a shortcircuit.

VIFB7 - 03/05 3. Installation

9604 3-19

Page 59: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The 24 V operating voltages are connected onthe adapter plate between the node and thevalves. The node and the I/O-modules aresupplied with operating voltage via the adaptercable.

The following components of valve terminal type05 are supplied separately with + 24 V DC viathis connection:• The operating voltage for the internal electro-

nic components and the inputs of the inputmodules (pin 1: DC + 24 V, tolerance ± 25%,external fuse max. 3.15 A recommended).

• The operating voltage for the valve outputsand the ouputs of the output modules (pin 2:DC + 24 V, tolerance ± 10%, external fusemax. 10 A slow-blowing required).

Recommendation:The operating voltage for the outputs/valvesshould be connected to the EMERGENCY OFFcircuit or EMERGENCY OFF contacts.

Operating voltage connection type 05

Fuse for valves(4 A slow blowing)

Adapter cable

Fig 3/9: Position of the operating voltage connection type 05

VIFB7 - 03/05 3. Installation

3-20 9604

Page 60: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

PLEASE NOTEWith common voltage supply for pin 1 (electro-nic components and inputs) and pin 2 (out-puts/valves) the lower tolerance of ±10% forboth circuits must be observed.

Check the 24 V operating voltage of the outputswhilst your system is operating. Make sure thatthe operating voltage of the outputs lies withinthe permitted tolerances even during full operati-on.

Recommendation

• Use a closed-loop power unit.

• Calculate the complete current consumptionaccording to the following table and selectboth a suitable power unit and cable crosssection.

• Avoid long distances between the power unitand the terminal. Calculate also the permitteddistance according to Appendix A. The following rule applies for type 05:

Operatingvoltage*)

Cable cross section

Distance

Valve terminal• Pin 1 = 2.2 A• Pin 2 = 10 A• Vo = 24 V

1.5 mm2 ≤ 8 m

2.5 mm2 ≤ 14 m

*) Please note that the max. total current consumption (pins 1 and 2) is 12.2 A

VIFB7 - 03/05 3. Installation

9604 3-21

Page 61: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Calculating the current consumption (type 05)

The following table shows the calculation of thetotal current consumption for ISO terminal type05. The values given are rounded up. If you useother valves or modules, you shuld consult theappropriate technical specifications for their cur-rent consumption.

Current consumption of electronic components node and inputs type 05(pin 1, 24 V ± 25 %)

Node

Number of simultaneously occupied sensor inputs: ____x 0.010 A

Sensor supplies: ____x_____ A(see manufacturer specifications)

+

+

Current consumption of electroniccomponents, node and inputs(pin 1) max. 2.2 A

=

Current consumption of outputs type 05(pin 2, 24 V ± 10 %)

Number of valve coils(simultaneously under power): ___ x 0.300 A

Number of simultaneously activated electrical outputs: ___ x 0.010 A

Load current of simultaneouslyactivated electrical outputs ____x_____ A

+

+

+

Current consumption of outputs (pin 2) max. 10 A = +

Total current consumptionof valve terminal type 05 =

∑ A

∑ A

∑ A

∑ A

∑ A

0.200 A

A

∑ A

∑ A ∑ A

∑ A

Fig. 3/10: Calculating the total current consumption type 05

VIFB7 - 03/05 3. Installation

3-22 9604

Page 62: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The diagram below shows the pin assignment ofthe operating voltage connection on the adapterplate.

Protective earthing

The valve terminal has two protective earthingconnections as follows:• on the operating voltage connection

(pin 4 leading socket)• on the left-hand end plate (M4 thread)

PLEASE NOTE• Always connect the earth cable to

pin 4 of the operating voltage connection. • Make sure that the valve terminal housing

and the protective earth cable at pin 4 have the same potential and that there are no equalizing currents.

• Connect an earth cable with sufficient crosssection to the left-hand end plate if the valveterminal is not mounted on an earthed machine stand.

In this way you can avoid interference due toelectromagnetic sources.

0 V

PE(protective earth connection, leading socket)

4

1

2

3

24 V supplyfor electroniccomponentsand inputs

24 V supply forvalves/outputs

Fig. 3/11: Pin assignment of the operating voltage connection

VIFB7 - 03/05 3. Installation

9604 3-23

Page 63: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Example of connection (type 05)

The diagram overleaf shows the connection of acommon 24 V supply for pin 1 and pin 2. Pleasenote that:• the outputs/valves must be protected against

short circuit/overload with external 10 A fuse(slow blowing)

• the electronic components and inputs mustbe protected against short circuit/overloadwith an external 3.15 A fuse (recommendati-on)

• the supply of the sensors is protected additio-nally by the internal 2 A fuse

• the valves are protected additionally by theinternal 4 A fuse (slow blowing)

• the common tolerance of DC 24 V ± 10%must be observed

• the node must be supplied via the adaptercable

• equalizing currents must be avoided whenboth earth cables are connected, e.g. by me-ans of cables with appropriate cross sectionas a voltage compensation.

VIFB7 - 03/05 3. Installation

3-24 9604

Page 64: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3 1 2 4

Earth cable connection pin 4 designed for 12 A

Connecting cable for voltagecompensation of earthconnections

10 A

0 V3.15 A

DC 24V± 10%

Connected adapter cable

Operating voltageconnection

AC230V

Emergency off

External fuses

Fuse for valves(4 A, slow blowing)

24 V

Fuse forinputs/sensors (2A)

Fig. 3/12: Example – connecting a common 24V supply and both earth cables (type 05)

VIFB7 - 03/05 3. Installation

9604 3-25

Page 65: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3.2.3 Connecting the field bus

There are two fibre-optical plugs on the node forconnecting the valve terminal to the field bus.One of these connections is for the supply cable,the other for the continuing field bus cable. Theplugs are marked "IN" and "OUT".

W-DOG

LWL-ERR

CYCLE

CPU-ERR

IN

II / O LWL

OUT

POWER

Incoming field bus

Continuing field bus

Fig. 3/9: Connection variant for field bus

VIFB7 - 03/05 3. Installation

3-26 9604

Page 66: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

CAUTIONDo not bend the cable more than the minimumradius of 30 mm.

A plastic fibre-optical cable must be used as thefield bus cable. Please consult the PLC manualfor your controller for the type of cable tobe used. The maximum distance between twoFesto valve terminals must not exceed 45 m(see also Appendix A "Bus topology").

The plug of type F-TNC from Harting ElektronikGmbH, Espelkamp, is suitable for fibre-opticalcable Z1 101 from Beckhoff Industrie Elektronik.All installation instructions are to be found inAppendix B, "Fibre-optical cable".

VIFB7 - 03/05 3. Installation

9604 3-27

Page 67: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3.3 CONNECTING THE INPUT MODULES

WARNINGBefore installation or maintenance work iscarried out, the following must be switched off:• the compressed air supply• the power supply to the electronic

components (pin 1).• the power supply to the outputs/valves

(pin 2).

You thereby avoid:• uncontrolled movements of loose tubing• undesired movements of the connected

actuators• undefined switching states of the electronic

components

VIFB7 - 03/05 3. Installation

3-28 9604

Page 68: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Four or eight inputs are available on the inputmodules of the valve terminal for user applicati-ons. The switching logic depends on the type ofinput module:

Input module (4 inputs) Input module (8 inputs)

Fig. 3/14: Digital PNP input modules (4/8 inputs)

Recommendation for the 8-input modules.Use the Festo DUO cable to connect twosensors via one plug at low costs.

INPUT

Socketseachwith onedigitalinput

Green LED

INPUT

Socketeachwith twodigitalinputs

One greenLED foreachdigitalinput

Type of input module Switching logic

INPUT PNP (position

INPUT-N NPN (negative)

VIFB7 - 03/05 3. Installation

9604 3-29

Page 69: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Pin assignment

The following diagram shows the pin assignmentof all the PNP/NPN inputs.

Pin assignment 4 inputs LED Pin assignment 8 inputs LED

0 0

1

1 2

3

2 4

5

3 6

7

Fig. 3/15: Input module: pin assignment 4/8 inputs (PNP/NPN)

0 V

Input Ix+ 24 V

free

2

41

3

0 V

InputIx+1+ 24 V

free

2

41

3

0 V

InputIx+2+ 24 V

free

2

41

3

0 V

InputIx+3+ 24 V

free

2

41

3

0 V

Input Ix+ 24 V

InputIx+1

2

41

3

0 V

InputIx+2+ 24 V

InputIx+3

2

41

3

0 V

InputIx+4+ 24 V

InputIx+5

2

41

3

0 V

InputIx+6+ 24 V

InputIx+7

2

41

3

VIFB7 - 03/05 3. Installation

3-30 9604

Page 70: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

3.4 CONNECTING THE OUTPUT MODULES

WARNINGBefore installation or maintenance work iscarried out, the following must be switched off:• the compressed air supply• the power supply to the electronic

components (pin 1).• the power supply to the outputs/valves

(pin 2).

You thereby avoid:• uncontrolled movements of loose tubing• undesired movements of the connected

actuators• undefined switching states of the electronic

components

VIFB7 - 03/05 3. Installation

9604 3-31

Page 71: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Four transistor outputs are available for appli-cations on the output modules of the valveterminal.The outputs have positive logic (PNPoutputs).

OUTPUT

Socketeachwith onedigitaloutput

Yellow LED per output

Red LED per output

Output module (4 outputs)

Fig 3/16: Digital output module (4 outputs)

VIFB7 - 03/05 3. Installation

3-32 9604

Page 72: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Pin assignment

The diagram below shows the pin assignment ofall the outputs.

Pin assignment 4 outputs LED

0

1

2

3

Fig. 3/17: Output module: pin assignment (4 outputs)

0 V

OutputOx

free

free

2

41

3

0 V

OutputOx+1

free

free

2

41

3

0 V

OutputOx+2

free

free

2

41

3

0 V

OutputOx+3

free

free

2

41

3

VIFB7 - 03/05 3. Installation

9604 3-33

Page 73: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

4. COMMISSIONING

VIFB7 - 03/05 4. Commissioning

9604 4-1

Page 74: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Contents4.1 Basic principles of configurat ion and

addressing 4-3General 4-3Switching on the operating voltages 4-4

Calculating the configuration data 4-5Calculating the number of inputs/outputs Type 03 4-6 Type 05 4-7Address assignment of the valve terminal 4-9Basic rule 1 4-10Basic rule 2 4-13Basic rule 3 4-13Address assignment afterextension/conversion 4-14Examples of addressing Type 03: MIDI/MAXI valves 4-17 Type 05: ISO valves 4-18

4.2 Beckhoff 4-19II/O bus 4-19Configuration example 4-19Addressing example 4-21

4.3 Eberle 4-23EDP-L system 4-23Configuration example 4-23Addressing example 4-25

4.4 Beckhoff/Siemens S5 4-28

VIFB7 - 03/05 4. Commissioning

4-2 9604

Page 75: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

4.1 BASIC PRINCIPLES OF CONFIGURATION AND ADDRESSING

General

Before commissioning or programming, firstcompile a configuration list of all connected fieldbus slaves. On the basis of this list you can:

• carry out a comparison between NOMINALand ACTUAL configurations in order toeliminate connection faults.

• access these specifications during the syntaxcheck of a program in order to avoidaddressing errors.

Configuration of the valve terminal requires avery accurate procedure, since different configu-ration specifications are required for each termi-nal on account of the modular structure. Pleasenote here the specifications in the sections whichfollow.

VIFB7 - 03/05 4. Commissioning

9604 4-3

Page 76: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Switching on the operating voltages

PLEASE NOTEObserve also the switching-on instructions inthe PLC manual for your controller.

When the controller is switched on, it automat-ically carries out a comparison between theNOMINAL and ACTUAL configurations. It isimportant here that:

• the specifications on the configuration arecomplete and correct

• the power supplies to the PLC and to the fieldbus slaves are switched on either simulta-neously or in the following sequence:

Please observe the following when switching onthe voltage supply:

• Common supply: If there is a common powersupply for the control system and all the fieldbus slaves, the power should be switched onvia a central switch or power unit.

• Separate supply: If the control system andthe field bus slaves have separate powersupplies, the power should be switched on inthe following sequence:

1. power supply to all the field bus slaves2. power supply to the control system

VIFB7 - 03/05 4. Commissioning

4-4 9604

Page 77: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Calculating the configuration data

Before configuring, calculate the exact number ofavailable inputs/outputs. A modular valve termi-nal consists of a different number of I/Os,depending on the type ordered.

PLEASE NOTE• The terminal makes available four status bits

for diagnosis via the field bus. These are automatically assigned within the terminalwhen there are input modules.

• The status bits occupy four extra input addresses.

The following table shows the I/Os required permodule for the configuration.

Module type Number of assigned I/Os *)

S valve sub-base (type 03)

D valve sub-base (type 03)

ISO sub-base (type 05)- 4 valve locations - 8 valve locations - 12 valve locations

Output module (4 digital outputs)

Input module (4 digital inputs)

Input module (8 digital inputs)

Status bits **)

2 outputs

4 outputs

8 outputs16 outputs24 outputs

4 outputs

4 inputs

8 inputs

4 inputs

*) The I/Os are assigned automatically within the terminal,irrespective of whether an input/output is actually used.

**) The status bits are assigned automatically within the terminal, as soon as input modules are available.

Fig. 4/1: Number of I/Os assigned per module

VIFB7 - 03/05 4. Commissioning

9604 4-5

Page 78: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Calculating the number of inputs and outputs(type 03)

Copy this table for further calculations andcalculator the number of inputs and outputs.

Table for calculating the inputs/outputs (type 03)

INPUTS

1. Number of 4-input modules _______ ⋅ 4

2. Number of 8-input modules _______ ⋅ 8

3. The 4 status bits are assigned automatically by the terminalinternally. They must be treated like inputs and must be added to the intermediate sum

+

Total number of inputs to be configured (max. 32)

OUTPUTS

4. Number of S sub-bases (type 03) _______ ⋅ 2

5. Number of D sub-bases (type 03) _______ ⋅ 4

+

Intermediate sum of 4. + 5.

6. Check that the sum of 4. + 5. is divisible by 4 without remainder. This is necessary because of the 4-bit orientated internal addressing of the terminal. A distinction must be made between the following cases:a) If divisible by 4 without remainder then continue with 7b) If this is not the case, round up (+2 O)

7. Number of electronic 4-output modules ______ ⋅ 4

Total number of outputs to be configured (max. 32)

Σ I

Σ I

Σ I

Σ O

Σ O

Σ O

Σ O

+

+

=

=

Σ O

4 I+

Fig. 4/2: Calculating the number of inputs/outputs (type 03)

2O

VIFB7 - 03/05 4. Commissioning

4-6 9604

Page 79: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Calculating the number of inputs and outputs(type 05)

Copy this table for further calculations.

Table for calculating the number of inputs/outputs (type 05)

INPUTS

1. Number of 4-input modules ______ ⋅ 4

2. Number of 8-input modules ______ ⋅ 8

3. The 4 status bits are assigned automatically by the terminalinternally. They must be treated like inputs and must be added to the intermediate sum

+

Total sum of inputs to be configured (max. 32) =

OUTPUTS

4. ISO sub-base modules for• 4 valve locations 8 O• 8 valve locations 16 O• 12 valve locations 24 O

5. Number of electronic output modules _______ ⋅ 4 +

Total sum of outputs to be configured (max. 32) =

Σ I

Σ I

Σ O

Σ O

Σ O

Σ I

4 I+

Fig. 4/3: Calculating the number of inputs/outputs (type 05)

VIFB7 - 03/05 4. Commissioning

9604 4-7

Page 80: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Address assignment of the valve terminal

The address assignment of the outputs of amodular valve terminal depends on theequipment fitted on the terminal. A distinctionmust be made between the following equipmentfitted:• valves and digital I/O modules• valves only• digital I/O modules only

PLEASE NOTEThe valve terminal may be fitted with a diff-erent number of inputs and outputs. Pleasenote therefore the manufacturer-specific confi-guration instructions in the following chaptersand check in the manual for your controllerhow such a fitting must be configured.

The basic rules described overleaf apply to theaddress assignment of these fitting variants.After the basic rules there is a detailed examplefor both type 03 and type 05 terminals.

PLEASE NOTEIf two addresses are assigned for one valvelocation, the following applies:• lower-value address ⇒

pilot solenoid 14• higher-value address ⇒

pilot solenoid 12

VIFB7 - 03/05 4. Commissioning

9604 4-9

Page 81: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Basic rule 1

The address assignment of the valves, of thedigital I/O modules and of the status bits is takeninto account with mixed fittings.

1. Outputs The address assignment of the outputs does not depend on the inputs.

1.1 Address assignment of the valves• Addresses should be assigned

in ascending order without gaps. • Counting must be from left to right .• Single sub-bases always

occupy 2 addresses.• Double sub-bases always

occupy 4 addresses. • ISO valve locations always

occupy 2 addresses. • Maximum 26 valve solenoid

coils can be addressed.1.2 Rounding up to 4 bits: different cases

a) If the number of addresses can be divided evenly by 4, continue with section 1.3.

b) If the number of addresses cannot bedivided evenly by 4, the number mustbe rounded up to 4. The rounded 2 bits in the address range cannot be used.

1.3 Address assignment of output modules:After the valves (rounded to 4-bits), the digital outputs are addressed• Addresses should be assigned

in ascending order without gaps.• Counting must be from right to left .• Counting on the individual modules

is from top to bottom.• Digital output modules always

occupy 4 addresses.

VIFB7 - 03/05 4. Commissioning

4-10 9604

Page 82: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

PLEASE NOTEThe field bus protocol permits maximum32 outputs (including valve coils).

2. InputsThe address assignment of the inputs doesnot depend on the outputs.

2.1 Addressing the input modules• Addresses should be assigned

in ascending order without gaps.• Counting on the node is

from right to left .• Counting on the individual modules

is from top to bottom.• 4-input modules occupy 4 addresses.• 8-input modules occupy 8 addresses.

2.2 Status bitsThe status bits are transferred to the four highest-value positions of the configured address area (28, ..., 31).

PLEASE NOTE The field bus protocol permits up to 32 inputs(28 digital inputs and 4 status bits).

VIFB7 - 03/05 4. Commissioning

9604 4-11

Page 83: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

When the power supply is switched on, the valveterminal recognizes all available pneumatic modules(type 03: max.13 modules; type 05: 4,8,12 valvelocations) and digital input/output modules automat-ically and assigns the appropriate addresses. If avalve location is not used (blanking plate) or if a digitalinput/output is not connected, the appropriate addressis nevertheless assigned. The diagram below showsthe address assignment with mixed fitting.

Remarks on diagram• If single solenoid valves are fitted onto

double sub-bases, four addresses will be as-signed for valve solenoid coils.The higher ad-dress remains unused (see address 3).

• If unused locations are sealed with blankingplates, the addresses will still be assigned(see addresses 12, 13).

• Due to the 4-bit orientated addressing of thevalve terminal, the address of the last loca-tion is always rounded up to the full 4 bits(unless all 4 bits are already used). Two ad-dresses cannot therefore be used (see ad-dresses 14, 15).

8 0 20 16

9 2 21 171

3

10

11

4567

22

23

18

19

0 1 2 4 6 8 10 12 14

3 5 7 9 11 13 15

14

12

14 14 14 14 14 14

12 12 12

I m

odu

le

4 in

puts

I m

odu

le8

inpu

ts

O m

odul

e 4

out

puts

O m

odu

le4

outp

uts

SIN

GLE

sub

-bas

e

DO

UB

LEsu

b-b

ase

Ro

und

upDO

UB

LEsu

b-ba

se

DO

UB

LEsu

b-ba

se

Fig. 4/4: Address assignment of a valve terminal with digital I/Os (e.g.type 03)

VIFB7 - 03/05 4. Commissioning

4-12 9604

Page 84: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Basic rule 2

If only valves are used, the address assignmentwill be as described in basic rule 1.

PLEASE NOTE• Maximum 26 valve solenoid coils can be

addressed.• Rounding of the last two positions

on the valve side is not necessary.• Valve terminals without input modules

do not require a configuration for the inputs.The status bits are not therefore available.

Basic rule 3

If only electrical I/Os are used, the addressassignment will be as described in basic rule 1.

PLEASE NOTE• Counting begins immediately to

the left of the node.• Rounding of the last two positions

on the valve side is not necessary.• With all locations fitted, the terminal

has 32 inputs (28 digital inputs and 4 statusbits) or 32 digital outputs.

Please unfold for page 4-12 Please unfold for page 4-14

VIFB7 - 03/05 4. Commissioning

9604 4-13

Page 85: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Address assignment after extension/conversion

A special feature of the modular valve terminalis its flexibility. If the demands placed on themachine change, the equipment fitted on theterminal can be modified accordingly.

CAUTIONIf the terminal is extended or converted at alater stage, there may be a shifting of theinput/output addresses. This applies in thefollowing cases:• If one or more pneumatic modules are

added or removed at a later stage (type 03).• If a pneumatic module with single valves

is replaced by a new module with double valves or vice versa (type 03).

• If additional input/output modules are inserted between the node and existing input/output modules.

• If existing 4-input modules are replaced by 8-input modules or vice versa.

If the configuration of the inputs is modified, theaddresses of the status bits will always beshifted.

VIFB7 - 03/05 4. Commissioning

4-14 9604

Page 86: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The diagram below shows an extension to thestandard fitting of the previous diagram andshows the modifications which must be made tothe address assignment.

Remarks on diagram Air supply modules and intermediate air supplymodules do not occupy any addresses.

0 1 2 4 6 8 10 12 14

3 5 7 9 11 13 15

16 18 19

17

8 0 24 20

9 2 25 211

3

10

11

4567

26

27

22

23

14

12 12 12 12 12

12

14 14 1414 14 1414 1414 14

Inp

ut m

odul

e 4

inpu

ts

Inpu

t m

odul

e8

in

puts

Out

put

mod

ule

4

outp

uts

Ou

tput

mod

ule

4 ou

tput

s

S v

alve

su

b-ba

se

D v

alv

e su

b-ba

se

No

roun

din

g

D v

alv

e su

b-ba

se

D v

alve

su

b-ba

se

D v

alve

sub

-ba

se

S v

alv

e su

b-ba

se

PO

WE

R S

UP

PL

Y

Fig. 4/5: Address assignment of a valve terminal after extension/conversion

VIFB7 - 03/05 4. Commissioning

9604 4-15

Page 87: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Example of addressing type 03 MIDI/MAXI valves

PLEASE NOTEIf a valve location occupies two addresses, the assignment is as follows:• lower value addresses ⇒ pilot solenoid coil 14• higher value addresses ⇒ pilot solenoid coil 12

4-in

put

mod

ule

8-in

put

mod

ule

4-ou

tput

mod

ule

4-ou

tput

mod

ule

Sin

gle

sub-

base

Dou

ble

sub-

base

Rou

nd u

p

Dou

ble

sub-

base

Dou

ble

sub-

base

Dou

ble

sub-

base

Dou

ble

sub-

base

Fig. 4/6: Address assignment of a valve terminal type 03 (MIDI/MAXI valves)

VIFB7 - 03/05 4. Commissioning

9604 4-17

Page 88: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Example of addressing type 05 ISO valves

9 11 15 14

8 16

9

2

173

10

11

45

0

7

18

196

1

13

12

4 61 3 5 70 128 10

2

14 12 14 12 14 12 14 12 14 12 14 14

20

21

22

23

14

PLEASE NOTEIf a valve location occupies two addresses, the assignment is as follows:• lower value addresses ⇒ pilot solenoid coil14• higher value addresses ⇒ pilot solenoid coil 12

4-in

put

mod

ule

8-in

put

mod

ule

4-ou

tput

mod

ule

4-ou

tput

mod

ule

Sin

gle

sub-

base

Dou

ble

sub-

base

Do

not

roun

d up

Dou

ble

sub-

base

Dou

ble

sub-

base

Dou

ble

sub-

base

Dou

ble

sub-

base

Sin

gle

sub-

base

Dou

ble

sub-

base

Fig. 4/7: Address assignment of a valve terminal type 05 (ISO valves)

VIFB7- 03/05 4. Commissioning

4-18 9604

Page 89: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

4.2 BECKHOFF

II/O bus

If the valve terminal is used on the II/O bus, thefollowing must be observed:

• The Festo valve terminal reacts like an I/Obox with 32 inputs and 32 outputs each.

• Calculation of the total transmission time (tt max) is to be found in the PLC manual foryour controller.

26.2 µs transmission time is required for eachFesto valve terminal.

PLEASE NOTE• The delay time within the Festo valve

terminal is < 200 µs.

• 32 I/Os each are usually transmitted, irrespective of type and size of the valve terminal. The four status bits are therefore always available and can be addressed.

Configuration example

Festo valve terminals are configured with theappropriate entry in the II/O list.

ExampleConfiguring a valve terminalConfigured I/O addresses:Valve terminal with inputs I 20.0 ... I 23.7(VT 1) O 20.0 ... O 23.7

Valve terminal O 38.0 ... O 41.7without inputs (VT 2):

VIFB7 - 03/05 4. Commissioning

9604 4-19

Page 90: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Configuration mask

PLEASE NOTEFesto valve terminals have inputs and outputsin one box. In order that inputs and outputscan be transferred, the column COM mustcontain the same value as the column Box(see mask and manual for programming soft-ware S1000).

Fig. 4/8: Example - configuration with II/O list

VIFB7 - 03/05 4. Commissioning

4-20 9604

Page 91: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Addressing example

CAUTIONPlease note the difference in addressing withword processing between the S1000 program-ming software versions up to 1.7 and from 1.8.

PLEASE NOTEFurther information on addressing and pro-gramming is to be found in the PLC/IPC manual for your controller.

VIFB7 - 03/05 4. Commissioning

9604 4-21

Page 92: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Configured: I 90.0 ... I 93.7O 90.0 ... O 93.7

Fig. 4/9: Example – addressing a Festo valve terminal

0 1 2 4 6 8 10 12 14

3 5 7 9 11 13 15

16 18 19

17

8 0 28 24

10 2 29

26

1

3

12

14

4

567

30

31

20

21

22

23

24 16

25 1817

19

26

27

20

212223

25

27

9

11

13

15

Program::: UN I93.2 "Input 26: U E92.3 "Input 19: = O90.1 "Output 1, valve 2: = O90.6 "Output 6, valve 5: = O92.5 "Output 20, valve 13

VIFB7 - 03/05 4. Commissioning

4-22 9604

Page 93: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

4.3 EBERLE

EDP-L system

If the valve terminal is used on the Eberle EDP-Lsystem, the following must be observed:• The Festo valve terminal reacts like an I/O

box with 32 inputs and 32 outputs.• Calculation of the total transmission time

(tt max) is to be found in the PLC manual foryour controller.

26.2 µs transmission time is required for eachFesto valve terminal.

PLEASE NOTE• The delay time within the Festo valve

terminal is < 200 µs.

• 32 I/Os each are usually transmitted, irrespective of type and size of the valve terminal. The four status bits are therefore always available and can be addressed.

Configuration example

Festo valve terminals are configured with theappropriate entry in the I/O list.

ExampleConfiguring a valve terminal (VT)Configured I/O addresses:Valve terminal 03 I 0200.0 ... I 0207.3with inputs (VT 1): O 0210.0 ... O 0217.3

Valve terminal 03 O 0220.0 ... O 0227.3without inputs (VT 2):

VIFB7 - 03/05 4. Commissioning

9604 4-23

Page 94: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Configuration mask

PLEASE NOTEFesto valve terminals have inputs and outputsin one box. In order that inputs and outputscan be transferred, the column COM mustcontain the same value as the column Box(see mask and system manual for EDP-L).

Fig. 4/10: Example – configuration with I/O list

VIFB7 - 03/05 4. Commissioning

4-24 9604

Page 95: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Addressing example

PLEASE NOTEFurther details on addressing and program-ming can be found in the PLC/IPC manual foryour controller.

Configured: I 0360.0 ... I 0367.3O 0370.0 ... O 0377.3

VIFB7 - 03/05 4. Commissioning

9604 4-25

Page 96: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Fig. 4/11: Example – addressing a Festo valve terminal

0 1 2 4 6 8 10 12 14

3 5 7 9 11 13 15

16 18 19

17

8 0 28 24

10 2 29

26

1

3

12

14

4

567

30

31

20

21

22

23

24 16

25 1817

19

26

27

20

212223

25

27

9

11

13

15

Program extract see page 4-27

VIFB7 - 03/05 4. Commissioning

4-26 9604

Page 97: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Program extract:DAL F 030 #SysDP41

LN F 0300.1 #Cyc_runF 0301.2 #Ready

= F 0310.1 #Bet_Cyc

L F 0300.1 #Cyc_run= NOP

DAL I 036 #Stat_11DAS O 037 #Stat_12

R NOPDAS F 031 #BetDP41

. . .

L I 0366.2 #Swing_3 Input 26A I 0364.3 #Stroke_down Input19 = O 0370.1 #Grip_3 Output 1, valve 2= O 0371.2 #Down_1 Output 6, valve 5= O 0375.1 #Swing_4 Output 20, valve 13

. . .

VIFB7 - 03/05 4. Commissioning

9604 4-27

Page 98: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

4.4 BECKHOFF/SIEMENS S5

The Festo valve terminal is connected via theII/O interface C1100.

See also: Technical description of C1100S5 on II/O interface modulefrom Beckhoff,Industrie-Elektronik,Eisenstr. 5D-33415 Verl, Germany

VIFB7 - 03/05 4. Commissioning

9604 4-28

Page 99: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

5. DIAGNOSIS AND

ERROR TREATMENT

VIFB7 - 03/05 5. Diagnosis/Error treatment

9604 5-1

Page 100: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Contents

5.1 SUMMARY OFDIAGNOSTIC POSSIBILITIES 5-3

5.2 ON-THE-SPOT DIAGNOSIS 5-4LED displays 5-4 Field bus node 5-4 Valves 5-6 Input/output modules 5-8Testing the valves 5-9

5.3 DIAGNOSIS VIA FIELD BUS 5-11Status bits 5-11

5.4 ERROR TREATMENT 5-12Reaction to faults in thecontrol system 5-12Short circuit/overload at an output module 5-13

VIFB7 - 03/05 5. Diagnosis/Error treatment

5-2 9604

Page 101: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

5.1 SUMMARY OF DIAGNOSTIC POSSIBILITIES

The modular valve terminal offers extensive andcomfortable possibilities of diagnosis and errortreatment. Depending on the equipment fitted onthe terminal, the following possibilities areavailable:

Valve terminal

Diagnosticpossibilites

Status bits LEDs

Briefdescription

The four status bitsare transferredcyclically to the fieldbus module as"inputs" with thenormal inputs.

The LEDsshowconfiguration error,hard-ware error,bus erroretc.

Advantage Fast access to errormessages irrespectiveof field bus protocol

Fast "on-the-spot" errorrecognition

Detaileddescription

Chapter 5.3 Chapter 5.2

Fig. 5/1: Possibilities of diagnosis and error treatment

Bit 27 Bit 26 Bit 28 Bit 24

0xxx1

0011x

0101x

0xxxx

x = not relevant

VIFB7 - 03/05 5. Diagnosis/Error treatment

9604 5-3

Page 102: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

5.2 ON-THE-SPOT DIAGNOSIS

LED displays

Field bus node

The LEDs on the cover of the field bus nodeindicate the operating status of the valveterminal.

GreenLED(operatingstatusdisplay)

W-DOG

LWL-ERR

CYCLE

CPU-ERR

IN

II / O LWL

POWER

Red LED (error display)

Green LED(operatingstatusdisplay)

Fig. 5/2: LEDs of the field bus node

VIFB7 - 03/05 5. Diagnosis/Error treatment

5-4 9604

Page 103: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

The possible LED displays of the operatingstatus of the valve terminal are shown in thetable below.

LEDs Operating status Error treatment

POWER alightCYCLEalightLWL-ERRoutCPU-ERRoutW-DOG*

Operating status normal or,

operating status normal butvalves do not switch .Possible causes:• Operating voltage of

outputs not in tolerancerange or not applied.

• Compressed air supply not correct

• Pilot exhaust blocked

None

Check the ... • operating voltage and/or

connection of outputs(pin 2 tolerance rangeDC 21.6 V ... 26.4 V)

• compressed air supply

• pilot exhaust channels

All LEDsout

Operating voltage for electroniccomponents not applied

Check operating voltageconnection

LWL-ERRalight

Fibre-optical cable interrupted Check fibre-optical cable

CYCLEalight

Message received –

W-DOGalight*

Message for this slave received –

CPU-ERRblinking(long intervals)

Module not fitted correctly:• More than 12 I/O modules• Number of I/Os not supported

by protocol set• Module type not permitted

Reduce the ...• number of I/O modules

Use only permittedmodule types

CPU-ERRalight or blinking(short intervals)

Hardware error Service case

* The Watchdog LED is switched on for 100 ms, when the valve terminal receives a message.

Fig. 5/3: LED display of operating status

VIFB7 - 03/05 5. Diagnosis/Error treatment

9604 5-5

Page 104: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Valves

There is a yellow LED for each solenoid valvecoil. This LED shows the switching status of thesolenoid valve coil.

LED Switch positionValve solenoid coil

Meaning

Yellow out Basic position Logic 0 (no signal)

Yellow alight • switch positionor

• basic position

Logic 1 (signal applied)

Logic 1 but:• Operating voltage of outputs is below

permitted tolerance range (DC 21.6V...26.4V) or

• compressed air supply not corrector

• pilot exhaust blockedor

• call servicing personnel

Fig. 5/4: LED display – switching status of solenoid valve coil

YellowLEDs

VIFB7 - 03/05 5. Diagnosis/Error treatment

5-6 9604

Page 105: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

There is a yellow LED for each pilot solenoidcoil. This LED shows the switching status of thepilot solenoid coil.

LED Switch positionValve solenoid coil

Meaning

Yellow out Basic position Logic 0 (no signal)

Yellow alight • switch positionor

• basic position

Logic 1 (signal applied)

Logic 1 but:• Operating voltage of outputs is below

permitted tolerance range (DC 21.6V...26.4V) or

• compressed air supply not corrector

• pilot exhaust blockedor

• call servicing personnel

12 14 12 14 12 14 1214

Yellow LEDs

Fig. 5/5: LED displays – switching status of ISO pilot solenoid coil type

VIFB7 - 03/05 5. Diagnosis/Error treatment

9604 5-7

Page 106: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Input/output modules

There are one or two LEDs (status displays)next to the relevant connections on the input/out-put modules. The colours of these LEDs are:• green (status display of the digital inputs)• yellow (status display of the digital outputs)• red (error display of the digital outputs)

The current signal at each input/output is shownby means of the yellow and green LEDs. Thered LEDs of the outputs indicate short circuit oroverload of the relevant output.

LED Status

Yellow outorgreen out

Logic 0(no signal)

Yellow alightorgreen alight

Logic 1(signal present)

Red out Output without short circuit/overload

Red alight Short circuit/overload at relevant output

Red LEDs (short circuit/overloaddisplay for outputs)

Yellow LEDs(switching status

display for outputs)

Green LEDs(switching status

display for inputs)

I8 I8 I4 O4

Fig. 5/6: LED displays of input/output modules

VIFB7 - 03/05 5. Diagnosis/Error treatment

5-8 9604

Page 107: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Testing the valves

WARNING Switch off the compressed air supply beforetesting the valves.

You thereby avoid undesired or dangerousmovement of the actuators.

CAUTION• This test function runs automatically within

the terminal. All valves are switched on andoff cyclically.

• None of the programmed locking or switch-ing conditions will be taken into account.

The valve terminal has a built-in test function forvalves, which can be activated even when the fibre-optical waveguide bus is not connected.

This function is switched on with the upperswitch element of the operating mode switch.This switch is visible on the right-hand printedcircuit board when the node cover is lifted (seealso Chapter 3.2)

VIFB7 - 03/05 5. Diagnosis/Error treatment

9604 5-9

Page 108: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Starting the test routine

1. Switch off the power supplies (pins 1 and 2).

2. Open the node.

3. Set DIL switch element 1 at OFF.

4. Switch on the power supplies (pins 1 and 2).

5. Start: Set DIL switch element 1 at ON within5 seconds *).

*) Otherwise the valve terminal will assumenormal operation after the waiting period.

During the self-test, the valve terminal firstswitches all valves on and off simultaneouslyseveral times. Then the valves in each group ofeight are switched on and off once individually.

Stopping the test routine

1. Switch off the power supplies (pins 1 and 2)of the terminal.

2. Bring the address selector switch and the DILswitch elements into their original positions.

Please noteFor normal fibre-optical waveguide operation, thetop DIL switch must be switched on (seeChapter 3.2, Setting the operating mode). Other-wise malfunctioning will occur when the opera-ting voltage is switched on, particularly when thecontrol system and the valve terminal have acommon power supply (see Chapter 4.1, Swit-ching on the operating voltages).

VIFB7 - 03/05 5. Diagnosis/Error treatment

5-10 9604

Page 109: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

5.3 DIAGNOSIS VIA FIELD BUS

The modular valve terminal offers the followingpossibility for diagnosis via the field bus:

• four status bits

The four status bits are interrogated like normalinputs. The contents are coded and contain thefollowing information:

Status bits

The status bits are configured like inputs andalways occupy the four highest-value ad-dresses of the available address range (bits 28 ... 31). If the inputs of the addressesthereunder are not used, the terminal will setthem at "logic zero".

The diagnostic information of the four status bitsis coded and contains the following meaning:

Diagnostic information

Coded individual message:

• short circuit/overload of outputs

• operating voltage pin 2 below 21.6 V (Vval)

• operating voltage pin 2 below 10 V (Vout)

• supply to inputs (sensors) under 10 V (Vinp)

Fig. 5/7: Status bits – diagnostic information not dependent on manufacturer

Bit number*) Meaning(x = not relevant)31 30 29 28

0XXX1

0011X

0101X

0XXXX

No errorOutput: short circuit/overloadVvalves < 21.6 VVoutputs < 10 VVinputs < 10 V

*) The status bits can always be addressed with the four highest-valueaddresses of the configured address range.

Fig. 5/8: Coded diagnostic information of the four status bits

VIFB7 - 03/05 5. Diagnosis/Error treatment

9604 5-11

Page 110: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

5.4 ERROR TREATMENT

Reaction to faults in the control system

PLC manu-facturer

Reaction of PLC to faults

in the field bus in the control system

BeckhoffII/O bus

EberleEDP-Lsystem

If faults occur on the II/O buse.g. due to failure of the fieldbus signal or interruption to thefibre-optical waveguide, all outputs (valvesand additional outputs) will beswitched off after 100 ms.

If the control system switchesto STOP, all outputs (valvesand electrical outputs) on thevalve terminal will beswitched off.

Please note:

Beckhoff/Siemens S5

See manual for module C1100 (supplied by Beckhoff, 33415Verl, Germany) • The unilaterally-operated

valves return to the basicposition.

• Double solenoid valvesremain in the currentposition.

• Mid-position valves moveto mid-position and(depending on valve type)are pressurized, exhaustedor blocked.

Fig. 5/9: Reaction of control system to faults

VIFB7 - 03/05 5. Diagnosis/Error treatment

9604 5-12

Page 111: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Short-circuit/overload at an output module

If there is a short circuit or overload:

• the digital output will be switched off

• the red LED will light up

• the error code "short circuit/overload" will beentered in the four status bits

In order to reactivate the output, proceed asfollows:

The output can then be reset at 1. If the shortcircuit still exists, the output will be switched offagain.

Step Explanation

Eliminate short circuit or overload

Set output at 0 (RESET) User-program controlled in the PLCprogramThe error bit in the status bits of theterminal is reset at logic 0.

Fig. 5/10: Eliminating short circuit or overload

VIFB7 - 03/05 5. Diagnosis/Error treatment

5-13 9604

Page 112: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

TECHNICAL APPENDIX

VIFB7- 03/05 Appendix A

9604 A-1

Page 113: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Contents

TECHNICAL SPECIFICATIONS A-3General A-3Operating voltage for electronic components and inputs A-4Operating voltage for outputs/valves A-4Electronic input modules A-5Electronic output modules A-5Field bus A-6Electromagnetic compatibilitiy (EMC) A-6

CABLE LENGTH AND CROSS SECTION A-7Calculating with a graph A-8Calculating with a formula A-10

EXAMPLES OF CIRCUITRY A-12Operating voltage connection (type 03) A-12Operating voltage connection (type 05) A-134-input module PNP A-148-input module PNP A-154-input module NPN A-168-input module NPN A-174-output module A-18

VIFB7 - 03/05 Appendix A

A-2 9604

Page 114: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

TECHNICAL SPECIFICATIONS

General specifications

Protection class(as per DIN 40050)

Temperature during• operation• storage/transport

Chemical resistance

IP 65

- 5oC . . . +50oC-20oC . . . +60oC

s. Festo-PneumaticCatalogue(resistance table)

Vibrations(as per DIN/IEC 68part 2-6 andIEC 721/part 2-3)• transport

• operation/use

Shock(as per DIN/IEC 68part 2-27 and IEC 721)

3.5 mm distance at 2-8 Hz1 g accelerationat 8-25 Hz

0.35 mm distance at25-57 Hz5 g acceleration at 57-150 Hz and1 g acceleration at 150-200 Hz

30 g at 11 ms

VIFB7- 03/05 Appendix A

9604 A-3

Page 115: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Operating voltageelectronic components and inputs

(Pin 1 – operating voltage connection)• Rated value

(protected against incorrect polarity)

• Tolerance

• Residual ripple• Current consumption

(at 24 V)

• Fuse for supply to inputs/sensors

Power consumption (P)• Calculation

DC 24 V, max. 2.2 A

± 25 %(DC18 V . . . 30 V)4Vss200 mA + sum of current consumptionof inputsinternal 2 A, slow blowing

P[W] = (0.2 A +

∑ I Inputs) ⋅ 24 V

Bridging time if logic voltage drops

min. 20 ms

Operating voltage outputs/valves

(Pin 2 – operatingvoltage connection)• Rated value

(protected against incorrect polarity)

• Tolerance

• Residual ripple• Current consumption

(at 24 V)

Power consumption (P)• Calculation

External fuse requiredDC 24 V, max. 10 A

± 10 %(DC 21.6 V ... 26.4 V)4 Vss10 mA + Sum of

current consumption ofelectrical outputs

+ Sum of current con-sumption of theswitched valve solenoidcoils (e.g. per MIDI valve solenoid coil 55 mA)

P[W] = (0.01 A +∑ Ielectrical outputs +

∑ Isolenoid coil) ⋅ 24 V

VIFB7 - 03/05 Appendix A

A-4 9604

Page 116: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Electrical input modules

Input voltage range

Logic level PNP• ON• OFF

Logic level NPN• ON• OFF

Current consumption(at 24V or 0 V) (currentfrom sensor to input at"logic 1")

Response delay (at 24 V)

Common fuse for operating voltage supply to sensors

Galvanic isolation

DC 0 ... 30 V

≥ 12.5 V≤ 7 V

≤ 5 V≥ 11 V

max. 9 mA

typ. 5 ms

2 A, slow blowing

None

Electrical output modules

Loading • per digital output

Current consumption (at 24 V) (own consumptionat "logic 1")

Electronic fuse(short circuit/overload)• Trigger current • Response time

(short circuit)

Galvanic isolation

max. 0.5 A (bulbs max.10 W because of PTCresistor characteristics)

typ. 9 mA

max. 1.5 Amax. 1 s

None

VIFB7- 03/05 Appendix A

9604 A-5

Page 117: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Please refer to the Pneumatic Manual fortechnical specifications on the pneumatic compo-nents and the valves.

Field bus

Design Fibre-optical waveguide

Transmission type Data ring

Protocol II/O

Baud rate 2500 kBaud

Cable length• between 2 valve terminals• total length (see also

Appendix B "Bus topology")

45 m (max.) 11475 m (max.)

Fibre-optical waveguidetype

See manual for yourcontroller

Electromagnetic compatibility (EMC)

Resistance to interferencetested as per EN 50082-2

Radio interference suppression tested as per EN 55011

Limit value severity B

VIFB7 - 03/05 Appendix A

A-6 9604

Page 118: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

CABLE LENGTH AND CROSS SECTION

PLEASE NOTEThe following information assumes that thefacts quoted in the Chapters "Installation" ofthis manual are already known and is to beused exclusively by personnel with thenecessary training in electrotechnology.

A load-dependent voltage drop occurs on allthree cables for the operating voltage supply ofa valve terminal. This can cause the voltage atpin 1 or pin 2 of the operating voltage connecti-on to lie outside the permitted tolerance.

Recommendation

• Avoid long distances between the power unitand the terminal.

• Calculate the suitable length and cross sec-tion of cable in accordance with the followinggraphs or formulae. Please note that:– the graphs supply approximate values for

the cross sections 1.5 and 2.5 mm2.– the formulae supply exact values for all

cross sections.

PLEASE NOTEThe following graphs and formulae assumethat the cross sections of the operating volt-age cables (pins 1, 2 and 3) are the same.

VIFB7 - 03/05 Appendix A

9604 A-7

Page 119: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Calculating with a graph

Proceed as follows:

1. Calculate the maximum current consumptionof the outputs/valves (I2).

2. Calculate the lowest voltage (VOmin) to be ex-pected on the power unit during operation.Take into account here:• the load dependency of the power unit• the fluctuations in the primary power

voltage

3. Read in the table for your cross-section thepermitted cable length.Example for 1.5 mm2:VOmin = 22.8 V, I2 = 2 A; Lmax = 25 m

VIFB7- 03/05 Appendix A

A-8 9604

Page 120: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

10A 6A 4A

21,6

10 20 30 40 50 m

+10%

-10%

26,4

2A

8A

3A

0

12A14A

22

23

24

25

26

VOmin in voltV

Current I2 in ampere

Cable length in metres

Cross section 1.5 mm2

+10% 12A14A

21,6

22

23

24

25

26

10 20 30 40 50 m

-10%

26,4

0

10A 8A

6A

4A

3A

2A

VOmin in voltV

Current I2 in ampere

Cable length in metres

Cross section 2.5 mm2

VIFB7 - 03/05 Appendix A

9604 A-9

Page 121: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Calculating with a formula

Proceed as follows:

1. Calculate the maximum current consumptionof the inputs and electronic components (I1)as well as of the outputs/valves (I2).

2. Calculate the lowest voltage (VOmin) to be ex-pected on the power unit during operation.Take into account here:• the load dependency of the power unit• the fluctuations in the primary power

voltage

3. Enter the values in the appropriate formula.The equivalent circuit diagram and theexample explain the correlation.

AC

DC0 V

VO

EMERGENCY OFF

3.15 AT

10 AT

I1

I2Pin 1Pin 2

Pin 3

Valve terminal

RL0

0 V

VL2 + VL1

Vterm.

Cableresistor (returning)

RI2RI1

VO

RL1

Cable resistor (incoming)

VL1 VL2RL2

Distance (cable length)L

Operating voltage supply Equivalent circuit diagram

I0

Fig. A/3: Cable length (L) and cable resistor (RL)

VIFB7- 03/05 Appendix A

A-10 9604

Page 122: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Formula for cable length

L ≤ (VOmin − VTERMINALmin) ⋅ A ⋅ κCu

2 ⋅ I2 + I1

This means:

• VTERMINAL = 24 V ± 10%, minimum: VTERMINALmin ≥ 21.6 V

• VOmin = minimum operating voltagesupply (at power unit)

• Current I1 = current for electronic componentsand inputs

• Current I2 = current for outputs/valves

• A = cable cross section (uniform e.g. 1.5 mm2)

• k = conductance value of cables

(uniform e.g. κCu = 56 m

mm 2 ⋅ Ω )

Example: I1 = 1 A; I2 = 5 A; VO = 24 V; VTERMINALmin = 21.6 V ;

κCu = 56 m

mm 2 ⋅ Ω;

Result of example:L ≤ 18 m for A = 1.5 mm2

L ≤ 30 m for A = 2.5 mm2

VIFB7 - 03/05 Appendix A

9604 A-11

Page 123: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

CIRCUITRY EXAMPLES

Operating voltage connection (type 03)

Pinassignment(node)

Circuitry example andinternalstructuretype 03

Fig. A/4a: Circuitry example: operating voltage connection type 03

34 2

1

230 V

Power unit(e.g. centralvoltage supply)

AC

DC

3.15 A

10 A

24 V ± 10 %24 V ± 10 %

0 V

PE

Electricalinputs/sensors (fused internally)

Valves (must befused externally)

Electrical outputs

24 V electroniccomponents(fused internally)

2 A

Operating voltageconnection on thenode of valveterminal type 03

EMERG. OFF

2: 24 V supply to outputs/valves

3: 0 V4: PE

1: 24 V supplyto electronic components

VIFB7- 03/05 Appendix A

A-12 9604

Page 124: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Operating voltage connection (type 05)

Pinassignment(adapter plate)

Circuitry example andinternalstructuretype 05

Fig. A/4b: Circuitry example: operating voltage connection type 05

2: 24 V-supply tooutputs/valves

3: 0 V4: PE

1: 24 V-supplyto electroniccomponents

34 2

1

230 V

Power unit(e.g. central power supply)

AC

DC

3.15 A

10 A

24 V ± 10 %24 V ± 10 %

0 V

PE

Electricalinputs/sensors(fused internally)

Adapter cable

Electricaloutputs (must befused externally)

24 V-electronic components (fused internally)

2 A

Operating voltageconnection for adapterplate (type 05)

Emerg.off

Valves max. 50%simultaneity(internally fused)

4 A

VIFB7 - 03/05 Appendix A

9604 A-13

Page 125: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

4-input module PNP

Internal structure

Pinassignment

Circuitryexamples

Fig. A/5: Circuitry example: 4-input module PNP

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAApositive

switchingpositive

switching

Pin1

2

4

3

Logicidentifi-cation Ix

free

PLC/I-PCIx

24 V ± 25 %

0 V

3: 0 V

4: Input Ix

2: free

1: + 24 V

greenLED Ix

ContactTwo-wiresensor

Three-wiresensor

VIFB7- 03/05 Appendix A

A-14 9604

Page 126: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

8-input module PNP

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAA

Sensor 2 (Ix+1) Sensor 1 (Ix)

Pin1

4

3

Logicidentifi-cation Ix

PLC/I-PCIx+1

24 V ± 25 %

0 V

3: 0 V

4: Input Ix

2: Input Ix+1

1: + 24 V

Two-way distributor(T piece e.g. Festo DUO cable)

Logic identi-ficationIx + 1

PLC/I-PCIx

greenLED Ix

green LEDIx + 1

2

Internalstructure

Pinassignment

Circuitry example

Fig. A/6: Circuitry example: 8-input module PNP

VIFB7 - 03/05 Appendix A

9604 A-15

Page 127: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

4-input module NPN

negativeswitching

negativeswitching

4

1

Logicidentifi-cation Ix

free

PLC/I-PCIx

24 V ± 25 %

0 V

3: 0 V

4: Input Ix

2: free

1: + 24 V

greenLED Ix

ContactTwo-wiresensor

Three-wiresensor

2

3PinInternal

structure

Pinassignment

Circuitryexamples

Fig. A/7: Circuitry example: 4-input module NPN

VIFB7- 03/05 Appendix A

A-16 9604

Page 128: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

8-input module NPN

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAA

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA

AAAAAAAAA

Sensor 2 (Ix+1) Sensor 1 (Ix)

Pin3

4

1

Logicidentifi-cation Ix

PLC/I-PCIx+1

24 V ± 25 %

0 V

3: 0 V

4: Input Ix

2: Input Ix+1

1: + 24 V

Two-way distributor(T piece e.g. Festo DUO cable)

Logic identi-ficationIx + 1

PLC/I-PCIx

greenLED Ix

green LEDIx + 1

2

Internalstructure

Pinassignment

Circuitry example

Fig. A/8: Circuitry example: 8-input module NPN

VIFB7 - 03/05 Appendix A

9604 A-17

Page 129: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

4-output module

Internalstructure

Pinassignment

Circuitryexamples

Fig. A/9: Circuitry example : 4-output module

NOTPERMITTED

Example 2

Pin1

4

3

PLC/I-PC

24 V ± 10 %

0 V

3: 0 V

4: Output Ox

2: free

1: free

Example 1

Outputdriver

yellowLED

+ 24 V

red LED

Diagnosis- output status- overload

freefree

2

VIFB7- 03/05 Appendix A

A-18 9604

Page 130: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

GLOSSARY

VIFB7 - 03/05 Appendix B

9604 B-1

Page 131: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Address selector switch

(see also field bus address) The field bus address of the terminal is set onthe address selector switches in the field busnode of the valve terminal.

Baud rate

The baud rate specifies the speed of datatransmission. The unit of data transmissionspeed is 1 baud = 1 bit/s. In all systems, thesender and the receiver must be set at the samebaud rate, otherwise there will be errors intransmission.

Bus topology

The maximum distance between 2 valve termi-nals/valve sensor terminals is 45 m. In order thatthe maximum number of terminals can beconnected to the II/O bus over maximumdistances, we recommend the following bustopology.You should arrange your slaves on the bus sothat a "quasi ring" is made.To do this connect terminal no. 1 directly toterminal no. 3, and connect this to terminal no.5. Then connect the "quasi ring" back to terminalno. 4, then to terminal no. 2.From terminal no. 2 connect the fibre-opticalcable to the field bus module.

A

B

VIFB7 - 03/05 Appendix B

9604 B-3

Page 132: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Data transmission

Transfer of digital data between various compu-ters or modules, or between a computer andperipheral devices (e.g. valve terminals).

D

IN

OUT

OUT

IN

OUT

IN

OUT

IN

OUT

IN

OUT

IN

1

2

3

4

5

45 m

45 m

45 m

45 m

Fig. B/1: Recommended bus topology

PLC/IPC/PC

Valve terminal/valve sensor terminal

Valve terminal/valve sensor terminal

Valve terminal/valve sensor terminal

Valve terminal/valve sensor terminal

Valve terminal/valve sensor terminal

Recommendation:

VIFB7 - 03/05 Appendix B

B-4 9604

Page 133: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Diagnostic byte

The diagnostic byte supplies important informati-on on the status of the valve terminal whenerrors occur. Diagnostic bytes are interrogatedby the user program of the PLC via the field bus.The status information thus acquired can beevaluated with software. Errors can be shown inclear text on the screen.

Exhaust air

Compressed air which escapes into the atmos-phere from a pneumatic device. With valveterminals the exhaust escapes through a com-mon channel. The flow rates must be sufficentand, with centrally ducted systems, non-returnvalves must be supplied for decoupling.

Fibre-optical waveguide

A fibre-optical waveguide transmits light signals.Fibre-glass and fibre-plastic are used as fibreoptical waveguides. Depending on the quality ofthe fibres, an optical waveguide can transmitsignals over a distance of several metres or upto several kilometres. This transmission process is immune to interfe-rence.

E

F

VIFB7 - 03/05 Appendix B

9604 B-5

Page 134: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

In order to guarantee reliable data transmission,a suitable plug connection must be establishedbetween the fibre-optical waveguide and thevalve terminal. The following plug is suitable forthis purpose:type F-TNC (for 5.5 - 6 mm cable with 1 mmpolymer fibres).

Source of supply:Fa. HARTING ELEKTRONIK GmbHPostfach 1140D-32339 EspelkampFederal Republic of GermanyOrder no.: 2010 001 6211

Fig. B/2: Signal transmission via a fibre-optical waveguide

Electrical signal U, I

Light Fibre-opticalwaveguide

Electrical signal

Fig. B/3: Components of a fibre-optical waveguide plug

Screwconnector

Washer

Seal

Cutting ring

Clamping disc

Plughousing

Clip

Guidepin

Light

U, I

VIFB7 - 03/05 Appendix B

B-6 9604

Page 135: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Installation instructions1.Remove about 18 mm of the cable

sleeve with a cable stripping knife.Shorten the strain relief braiding (Kevlar) by about 7 mm. Removeabout 7 mm of the insulation from the fibre covering of the cable with a 1 mm precision insulation stripper.

2.Push the screw connector, washer,seal and cutting ring over the cablesleeve. Then push the clamping discover the fibre coating.

3.Push the guide pin as far as it willgo onto the fibre. To fix it in this position, press the clip above thecable sleeve into the guide pin. The fibre should project about 1 mm out of the guide pin when the cable isfully inserted.

4.With the aid of a grinding/polishingblock, grind down the fibre end surface to a length of about 5.5 mmon abrasive paper (600-1000 grain) on a hard base, e.g. glass plate.

5.For final fitting, clamp the strain relief braiding between the clampingdisc and the cutting ring. Push theseal, washer and screw connector forward to the cutting ring. Place theplug housing over the guide pin, clamping disc, cutting ring, seal andwasher and tighten the screw connector. The strain relief braidingwill then be fastened between the cutting ring and the clamping disc. The cable sleeve will also be sealedagainst the plug body by the seal ring. Cut off the axcess braiding.

* Reprinted by kind permission of HARTING ELEKTRONIK GmbH

Fig. B/4: Fitting a fibre-optical plug

~11mm~7mm

1mm

5,5mm

VIFB7 - 03/05 Appendix B

9604 B-7

Page 136: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Field bus

A serial bus system for the exchange ofinformation between parts of a procedure ortechnical manufacturing process which are phy-sically separated from each other, often at greatdistances.

Field bus address

The address of a field bus slave. This is requiredin order that the slaves can be identified in thefield bus system. The field bus address is set onthe relevant field bus slave.

Field bus module

A module in a control system which enables alarge number of decentrally controlled I/O modu-les (field bus slaves) to be connected.

Field bus protocol

An agreement whereby two or more devicescommunicate with each other, e.g. an agreementis made on the control characters after which atext is to begin or end.

LDR (LaDdeR diagram)

Graphical description for link-orientated controltasks corresponding to the electrical circuitdiagram.

Manual override

A plunger on the pilot valve, e.g. of a solenoidvalve, with which the valve can be switchedwithout an electrical signal.

L

M

VIFB7 - 03/05 Appendix B

B-8 9604

Page 137: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Module

(see Field bus module)

Seals

Seals between the connection blocks of thevalve terminal prevent leakage in the pneumaticsystem. Seals between the electronic mod-ulesof the terminal fulfil protection class IP 65.

Silencers

Silencers are used for reducing noise at theexhaust connections of valves. Pressure supplymodules for the valve terminals can be fitted withexternal or integrated silencers.

Solenoid valves

An electromagnetically operated valve. Inelectropneumatic or electrohydraulic systems thesolenoid valve forms the interface between theelectronic and pneumatic/hydraulic components.

STL (STatement List)

A programming language for programmable logiccontrollers. All logical links and processes canbe programmed with the commands of thislanguage. A statement list can contain bothstep-orientated and link-orientated elements.

S

VIFB7 - 03/05 Appendix B

9604 B-9

Page 138: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Valves

Fluidic elements for controlling the pressure andcompressed air of fluids. A distinction is madebetween directional control valves, pressurevalves, flow control valves and non-return val-ves.

V

VIFB7 - 03/05 Appendix B

B-10 9604

Page 139: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

Index

VIFB7 - 03/05 Appendix C

9604 C-1

Page 140: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

AAbbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . XIAddress

general . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9

CCable

connecting . . . . . . . . . . . . . . . . . . . . . 3-0, 3-5field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4operating voltage . . . . . . . . . . 3-14, 3-21, A-7selecting . . . . . . . . . . . . . . . . . . . . . . . 3-4, A-7

CablesSelecting. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7

Circuity example - inputs. . . . . . . . . . A-14 - A-15Circuity example - inputs NPN . . . . . A-16 - A-17Circuity example - outputs. . . . . . . . . . . . . . A-18Connections

inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28operating voltage . . . . . . . . . . . . . . 3-12, 3-19outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-31

Currentcalculating . . . . . . . . . . . . . . . . . . . 3-15, 3-22fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12fusing . . . . . . . . . . . . . . . . . . 3-12, 3-17, 3-19selection cable . . . . . . . . 3-4, 3-14, 3-21, A-7

Current consumption . . . . . . . . . . . . . . 3-15, 3-22

PLEASE NOTEThe index is based on key words. It thereforesupplements the contents which are based ona function/action-orientated grouping.

In the index you will not therefore find "Con-necting the operating voltage", but the separa-te entries "Connections" and "Voltage".

VIFB7 - 03/05 Appendix C

9604 C-3

Page 141: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

DData transmission

Baud rate . . . . . . . . . . . . . . . . . . . . . . . . . 3-11Diagnosis

Diagnostic byte. . . . . . . . . . . . . . . . . . . . . 5-11LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4Status bits . . . . . . . . . . . . . . . . . . . . . . . . 5-11

EEarthing

components . . . . . . . . . . . . 2-0, 2-6 - 2-7, 2-9valve terminal . . . . . . . . . . . . . . . . . 3-16, 3-23

EMERGENCY OFF . . . . . . . . . . 3-18, 3-25, A-12Errors

Short circuit at output module . . . . . . . . . 5-13Treatment . . . . . . . . . . . . . . . . . . . . . 5-3, 5-12

FFastening eyes . . . . . . . . . . . . . . . . . . . 2-9, 2-12Festo

addressing . . . . . . . . . . . . . . . . . . . . . . . . . 4-3configuration. . . . . . . . . . . . . . . . . . . . . . . . 4-3

Fibre-optical waveguide. . . . . . . . . . . . . . . . . B-5Field bus

node . . . . . . . . . . . . . . . . . . . . . . . . . 1-11, 3-7Function

node . . . . . . . . . . . . . . . . . . . . . . . . . 1-11, 3-7Fusing

external. . . . . . . . . . . . . . . . . 3-12, 3-17, A-12internal . . . . . . . . . . . . . . . . . . . . . . . . . . A-12

VIFB7 - 03/05 Appendix C

C-4 9604

Page 142: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

LLED display

inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8Node. . . . . . . . . . . . . . . . . . . . . . . . . . 3-8, 5-4outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6

MModule AS308-3U . . . . . . . . . . . . . . . . . . . . . . XIII

NNode . . . . . . . . . . . . . . . . . . . . . . . 1-11, 3-7 - 3-8NPN . . . . . . . . . . . . . . . . . . . . . . . . . . A-16 - A-17

PPin assignment

inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-30outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-33

PNP . . . . . . . . . . . . . . . . . . . . . . . . . . A-14 - A-15Programming examples

Beckhoff . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22Eberle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27

VIFB7 - 03/05 Appendix C

9604 C-5

Page 143: Valve terminal type 03/05 - Festo USA · Valve terminal type 03/05 Electronics Manual ... Eberle PLS 514 DP41 EDP-L system Siemens S5-115U.. S5-155U ... Valve terminal type 03:

SSerial bus interface . . . . . . . . . . . . . . . . . . . . . XIIIShort circuit . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12

eliminating . . . . . . . . . . . . . . . . . . . . . . . . 5-13fusing . . . . . . . . . . . . . . . . . . 3-17, 5-13, A-12

Siemensconfiguration. . . . . . . . . . . . . . . . . . . . . . . . 4-3

Switching statusinputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8outputs . . . . . . . . . . . . . . . . . . . . . . . 5-8, 5-13valves . . . . . . . . . . . . . . . . . . . . . . . . . 5-6, 5-9

System structure . . . . . . . . . . . . . . . . . . . . . . . 1-3

TTechnical specifications. . . . . . . . . . . . . . . . . A-3Terminating resistor. . . . . . . . . . . . . . . 3-28, 3-31Test routine for valves. . . . . . . . . . . . . . . . . . . 5-9Type 03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17Type 05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18

VValves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5Voltage

Connecting . . . . . . . . . . . . . . . . . . . . . . . . 3-26connecting type 03. . . . . . . . . . . . . . . . . . 3-12connecting type 05. . . . . . . . . . . . . . . . . . 3-19selection cable . . . . . . . . 3-4, 3-14, 3-21, A-7selection power unit . . . . . . . 3-14, 3-21 - 3-22switching on . . . . . . . . . . . . . . . . . . . . . . . . 4-4

VIFB7 - 03/05 Appendix C

C-6 9604