Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Tom Overbye Fox Family Professor of ECE Fox Family Professor of ECE University of Illinois at Urbana- University of Illinois at Urbana- Champaign Champaign Jim Gronquist Jim Gronquist Bonneville Power Administration (BPA) Bonneville Power Administration (BPA)

Transcript of Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of...

Page 1: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Validation and Accreditation of Transient Stability (TS) Results

Tom OverbyeTom Overbye

Fox Family Professor of ECEFox Family Professor of ECE

University of Illinois at Urbana-ChampaignUniversity of Illinois at Urbana-Champaign

Jim GronquistJim Gronquist

Bonneville Power Administration (BPA)Bonneville Power Administration (BPA)

Page 2: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Overview

• Goal of project is to perform validation of the transient stability (TS) packages• Commonly thought that different TS packages give different

results for the same system conditions• Software validation is (according to DOD), “The process of

determining the degree to which a model or simulation and its associated data are an accurate representation of the real world from the perspective of the intended uses of the model.”

• This project is just focused on validating the packages against each other, as opposed to with real world data (which would be a natural follow-on)

2

Page 3: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Project Importance

• TS looks at the time-domain response of a system following a disturbance (contingency) for several seconds to minutes• Integration used here was ¼ cycle

• Assessing angular and short-term voltage stability

• System stability is a growing concern, partially because of more wind integration

• PMUs providing more dynamic observability

3

Page 4: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Background

• Project grew out of PSERC effort from 2010 to 2011 funded entirely by BPA involving UIUC and WSU to research the validation of the PSLF, PSSE, TSAT, and PowerWorld Simulator TS packages• UIUC took the lead with PSSE and PowerWorld, WSU with

PowerTech, and BPA with PSLF

• Most of the PSLF solutions were done by BPA, with just several of the earlier (2010) PSLF runs provided by WSU. Just solution results were provided to UIUC.

• None of the results presented here involve PSLF solutions done by UIUC.

4

Page 5: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Project Challenges

• Key challenges include the sheer number of models that need to be validated. • WECC case has more than 3300 generators, 8200 loads, more

than 70 different dynamic models (in PSLF)• Individual dynamic models can have dozens of parameters that

can substantially affect the behavior of the models

• The PSLF and PSSE packages often use different models to represent the same generators/loads• PowerWorld Simulator implements both sets

• Model parameters are sometimes incorrect, with values often automatically “corrected”

5

Page 6: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Model Example: GGOV1

6

Page 7: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

PSERC Project Caveats

• Project required a deep knowledge of the TS solution process and the ability to solve large systems using the different TS packages• Net gain to industry when students graduate, but there

is also a loss of university expertise

• Project focused primarily on PSLF and PowerWorld, and on the WECC system• Pointing out problems is not meant to imply they are

“worse” than others, such as the Eastern Interconnect model; it just wasn’t studied

7

Page 8: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Data Confidentiality

• Many of the studies done for this project utilized confidential information that was provided to UIUC and WSU under NDAs

• Data presented in these slides uses WECC results. Public release can be made at the discretion of WECC

8

Page 9: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

The Starting Point

9

0 5 10 15 20 25 3059.75

59.8

59.85

59.9

59.95

60

60.05Double Palo Verde Contingency: 36411 DIABLO 1 25.00

Fre

quen

cy:

Hz

Time: Seconds

TSAT

GEPowerWorld

In May 2010, as the projectwas just beginning, we wereable to do comparisons for a full WECC case (provided by BPA)between PSLF, TSAT andPowerWorld Simulator. The plot on the right showsthe variation in a bus frequency following thedouble Palo Verde generatortrip contingency for the three packages

We moved forward with both a top-down(full system) and bottom-up (individual

model) approach

Page 10: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

The Top-Down Approach

10

0 5 10 15 20 25 3059.75

59.8

59.85

59.9

59.95

60

60.05Double Palo Verde Contingency: 36411 DIABLO 1 25.00

Fre

quen

cy:

Hz

Time: Seconds

TSAT

GEPowerWorld

Within a week or two we were able to determine that abug in how the frequencydeviations for the inductionmotor loads were beinghandled by PowerWorldwas causing some of thefrequency variation. Thenew run is shown on the right. The oscillation in thePowerWorld frequencies weretracked down to a model error.

Model error was associated with a generator line drop

compensation; fixed by auto-correction

Page 11: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Bottom Up Approach

11

• The bottom-up approach consists of creating two bus equivalents for the most common WECC generator models, and then running them in the PowerWorld and PSSE packages.

• This has resulted in several PowerWorld changes with the new code often giving quite close matches

Graph shows a comparison of thefield voltage at generator for a fault on thetwo bus equivalent system betweenPSSE, and two versions of PowerWorld Simulator

Page 12: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

The Bottom-Up Approach

• While there are lots of models, project initially focused on the most widely used models.

• WECC case has a total of 17,709 models in 77 model types. But the 20 most common model typescontain 15,949 (90%) of these models. These are the key focus areas for the bottom-up analysis.

12

Page 13: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Post-PERC Work

• Since the PSERC project finished in August 2011, UIUC and BPA have continued the validation work focusing on comparisons between PowerWorld and PSLF

• The bottom line is the two packages now agree quite closely for the studied scenarios, certainly within the bounds of variability due to input data errors.• This close match allows for detailed comparisons!

13

Page 14: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Power Flow Solutions

• The power flow solution provides the starting point for the TS. PSLF and PowerWorld have very similar solutions. • Key difference is the distribution of reactive

power at multi-generator buses. The net bus injection is the same, resulting in the same power flow solution. But the algorithms to distribute reactive power to the generators differ, resulting in slightly different initial transient stability generator field voltages

14

Page 15: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Initial TS Variable Values

• Power flow operating point is back-solved to determine the initial TS states and related variables. Ideally this should result in an equilibrium point, so without a disturbance none of the variables should change. But some may if there is an initial limit violation.

• Largest field voltage change in two seconds was 0.34 pu in both packages at gen 42177 due to an initial Vr limit violation.

15

Page 16: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Efd at Gen 42117

16

PowerWorld includes an option to automatically modify the limits to provide a “flat” solution

Page 17: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Initialization Pmech: Match is Good

• The initial values for the governor mechanical power input and Efd were compared for all generators. Very little difference was observed• Largest differences for mechanical power

were 4 MWs at the wind turbines (wndtrb), which was associated with how the rotor losses are modeled

17

Page 18: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Initialization Efd: Match is Good

• For the Efd values, the average error was just 0.003761 per unit (typical Efd values of 1 to 3)

• Just 200 units (out of a total of 2322) had initial differences greater than 0.01 per unit.

• In a small number of comparisons between PSLF, PowerWorld and PSSE; PowerWorld and PSSE matched closely• Example gen #QF at 24815 PW had Efd=1.8409, PSSE

1.8404 and PSLF 1.8691 (Qg=-72.4 Mvar)• Example gen #G1 at 24815 PW had Efd= 1.0459, PSSE

had 1.0471 and PSLF 1.013.(Qg=-2.9Mvar)

18

Page 19: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Simulation Comparison Methodology

• Study involved the Double Palo Verde contingency

• The case comparison methodology involved looking at time results for selected values, and differences between the min/max values for different time periods for all key variables (Efd, Pmech, stabilizer output)

• Case is quite stressed so small variations can significantly impact the results

19

Page 20: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Validation Issues: IEEEG1

20

HP

ΔωSPEED

4

1

1 sT2

1

(1 )

1

K sT

sT

3

1

T

CU

OU

1

s

MAXP

MINP

1K

5

1

1 sT

3K

6

1

1 sT

5K

7

1

1 sT

7K

2K 4K 6K 8K

HPPMECH

LPPMECH

M1P

M2P

Model supported by PSLF includes hysteresis that is read but not implemented in Simulator

Model supported by PSSE does not include hysteresis and nonlinear gain

GVP

GV

1db

2db

3 4 5

12

1 - Governor Output

2 - Lead-Lag

3 - Turbine Bowl

4 - Reheater

5 - Crossover

6 - Double Reheat

States

6

refP

With the IEEEG1 governor, PowerWorld “auto-corrects” high K1to K8 values. Gens 56503, 57503 and 58503 have K1=20.4, whichcauses very high Pmech outputs in the PSLF results

Page 21: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

56503 Output PSLF vs PowerWorld

21

Graph compares the Pmech between PSLF and PowerWorld with K1=20.4 or auto-corrected. Note the turbine rating is 71.2 MVA. Behavior is similar at 57503 and 58503.

Page 22: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Unexpected PSLF Behavior

22

Graph compares the Pmech between PSLF and PowerWorld for G1 at 40559 (Ice Harbor). Unit is modeled with an IEEEG3 Governor. Turbine rating is 103 MVA.

PowerWorldcannotcompensatefor thisdifference.To some extent itoffsets theK1 issue.

Page 23: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

40687 (Malin) Freq. Comparison

23

Note whether the K1 issue is corrected has a large impact on the resultant frequency. The two PowerWorld results mostly bracket the PSLF results. The 40559 issue also has a significant impact.

Page 24: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

40687 (Malin) Volt Comparison

24

Again the two PowerWorld solutions mostly bound the PSLFresults

Page 25: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

24801 (Devers) Freq. Comparison

25

Results are similar for a bus in Southern California. Again the PowerWorld results (with the K1 issue either high or fixed) bracket the PSLF results.

Page 26: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

24801 Voltage Comparison

26

Page 27: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Potential EXST1 Issue

• In comparing the initial field response for the four units at 36405/6 (Moss Landing), PSLF may be ignoring the feedback term for the EXST1 exciter when Ta = 0

27

Page 28: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Gen 36406H Efd for Varying Ta

28

Note changing Ta slightly has little impact on the PowerWorld results but gives a significantly fast PSLF response. The ratefeedback should limit the change in Efd.

Page 29: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Key Differences: Modeler Intent

• Some key differences in the packages arise in how they handle “modeler intent” in cases in which the input data is either ambigous or wrong.

• Example: At gens 56503, 57503 and 58503 the IEEEG1 governor has K1=20.2, which means the maximum output of the units is 20 times the normal value• PowerWorld catches this as an error, allowing the

value to be autocorrected

29

Page 30: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Key Differences: Modeler Intent

• Other examples include• Handling exciter saturation when SE1=0 and SE2 >

0. PowerWorld fits a quadratic to these two points• Issues when GV/PGV data is not increasing.

PowerWorld raises a validation error.• Reading in models with blank IDs. PowerWorld had

defaulted if there was one gen at the bus• WSCCST stabilizer behavior when vcutoff < 0.

PowerWorld ignores the parameter, PSLF sets stabilizer response to zero (33141/2/3)

30

Page 31: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Possible Issue with PSLF EXAC1

31

Graphs compares the field voltage for the generator at 15914. This generator uses an EXAC1 exciter. The limit on Ve should prevent a negative field voltage. The PSLF results show negative values, with PowerWorld clamping the value at zero.

Page 32: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Conclusion

• PSLF and PowerWorld match quite closely and both can be used for WECC studies.

• Using multiple packages can help to track down issues either within the packages or within the data. Hence there is a net gain.

• Individual package innovation, such as improved error checking or options, can result in better results for all.

32

Page 33: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Moving Forward

• The PSERC project has concluded, but this work is too important to stop.

• We are continuing to move forward with funding provided by the Illinois Center for a Smarter Electric Grid (ICSEG)

• Industrial participants are invited to join us• BPA has already expressed an interest to

continue participating in this effort• Email [email protected] if interested

33

Page 34: Validation and Accreditation of Transient Stability (TS) Results Tom Overbye Fox Family Professor of ECE University of Illinois at Urbana-Champaign Jim.

Questions?

34