V OL UM E III - Engineering...

38
ANISO9001&14001COMPANY TENDER DOCUMENT TENDER No: NERO/CON/ASR/LAITKOR/283 dated: 27/12/2017 FOR TENDER FOR PROVISION OF ADDITION/ALTERATION OF ARTB HOSPITAL, AR HOSPITAL, PROVISION OF IMPROVEMENT TO TYPE-II QTRS AND TYPE-III QTRS FOR LAITKOR, SHILLONG (MEGHALAYA) VOLUME–III PRICE BID/BILL OF QUANTITY

Transcript of V OL UM E III - Engineering...

Page 1: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

ANISO9001&14001COMPANY

TENDER DOCUMENT

TENDER No: NERO/CON/ASR/LAITKOR/283 dated: 27/12/2017

FOR

TENDER FOR PROVISION OF ADDITION/ALTERATION OF ARTB HOSPITAL, AR HOSPITAL, PROVISION OF

IMPROVEMENT TO TYPE-II QTRS AND TYPE-III QTRS FOR LAITKOR, SHILLONG (MEGHALAYA)

VOLUME–III

PRICE BID/BILL OF QUANTITY

Page 2: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl No. Description Amount(A) Provision of Addition/Alteration of ARTB Hospital at

Laitkor,Shillong(Meghalaya)(Annexure - I)(B) Provision of Addition/Alteration of Assam Rifles Hospital at

Laitkor,(Meghalaya)1 Structural Part (Annexure - II)2 Internal Electrification (Annexure-III)3 Internal water Services

(i) Sanitary Instalation (Annexure-IV)(ii) Internal Water supply(Annexure-V)(iii) Internal Drainage(Annexure-VI)

(C) Provn of improvement to OR married accomodation (12Blocks) Type-II Qtr for, Laitkor. Garrison (Meghalaya).

1 Building(Annexure - VII)2 Electrical(Annexure - VIII)

(D) Provn of improvement to Type-III (JCO marriedaccomodation) (Building No. P-III) (A,B,C,D,E,F) for, Laitkor.Garrison (Meghalaya).

1 Building(Annexure - IX)2 Electrical(Annexure -X)

TOTAL (A + B + C + D)

Tender No. NERO/CON/ASR/LAITKOR/283 Dated: 27.12.2017

ENGINEERING PROJECTS (INDIA) LIMITED

ABSTRACTTender for Provision of addition/alteration of ARTB Hospital,AR Hospital,Provision of

improvement to Type-II Qtrs and Type-III Qtrs for Laitkor,Shillong (Meghalaya)

(A GOVERNMENT OF INDIA ENTERPRISE)NERO,Guwahati

Page 3: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure - I

Sl No. Description of Works A/U Quantity Rate(Rs)

Amount(Rs)

Building Works

1

Demolishing cement concrete manually/by mechanical means includingdisposal of material within 50 metres lead as per direction of Engineer -in - charge. Nominal concrete 1:4:8 or leaner mix (i/c equivalent designmix)

Cum 237.60

2

Providing and laying vitrified floor tiles in different sizes (thickness to bespecified by the manufacturer) with water absorption's less than 0.08%and conforming to IS : 15622 of approved make in all colours andshades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarsesand) including grouting the joints with white cement and matchingpigments etc., complete. Size of Tile 600x600 mm

Cum 864.00

3

Providing and laying rectified Glazed Ceramic floor tiles 300x300 mm ormore (thickness to be specified by the manufacturer) of 1st qualityconforming to IS : 15622 of approved make in all colours, shades,except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thickCement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing thejoints with white cement and matching pigments etc., complete.

Cum 872.00

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

(A)Name of Work : Provision of Addition/Alteration of ARTB Hospital at Laitkor,Shillong(Meghalaya)

NERO,Guwahati

Page 4: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

415 mm cement plaster on the rough side of single or half brick wall ofmix : 1:4 (1 cement: 4 fine sand) Sqm 79.20

5Wall painting with plastic emulsion paint of approved brand andmanufacture to give an even shade : One or more coats on old work. Sqm 1980.00

6

Steel work in built up tubular ( round, square or rectangular hollowtubes etc.) trusses etc. including cutting, hoisting, fixing in position andapplying a priming coat of approved steel primer, including welding andbolted with special shaped washers etc. complete. Hot finishedseamless type tubes.

Kg 92.42

7

Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steelprimer using structural steel etc. as required. In gratings, frames, guardbar, ladder, railings, brackets, gates and similar works.

Kg 52.56

Page 5: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

8

Providing and laying water proofing treatment on roofs of slabs byapplying cement slurry mixed with water proofing cement compoundconsisting of applying: a) after surface preparation, first layer of slurryof cement @ 0.488 kg/sqm mixed with water proofing cementcompound @ 0.253 kg/sqm. b) laying second layer of Fibre glass clothwhen the first layer is still green. Overlaps of joints of fibre cloth shouldnot be less than 10 cm. c) third layer of 1.5 mm thickness consisting ofslurry of cement @ 1.289 kg/sqm mixed with water proofing cementcompound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This willbe allowed to air cure for 4 hours followed by water curing for 48 hours.The entire treatment will be taken upto 30cm on parapet wall andtucked into groove in parapet all around. d) fourth and final layer ofbrick tiling with cement mortar (which will be paid for separately For thepurpose of measurement the entire treated surface will be measured.

Sqm 960.00

9Cement concrete pavement with 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) including finishingcomplete.

Cum 27.60

10

Providing and fixing Powder coated aluminium work for doors, windows,ventilators and partitions with extruded built up standard sections andother sections of approved make conforming to IS: 733 and IS: 1285,fixing with dash fasteners of required dia and size, including necessaryfilling up the gaps at junctions, i.e. at top, bottom and sides withrequired EPDM rubber/ neoprene gasket etc. Aluminium sections shallbe smooth, rust free, straight, mitred and jointed mechanically whereverrequired including cleat angle, Aluminium snap beading for glazing /paneling, C.P. brass / stainless steel screws, all complete forFixed/Openable and any kind of portion as per architectural drawingsand the directions of Engineer-in-charge.

Sqm 138.30

Total carried forward to abstract Sl. No. A

Page 6: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure - II

Sl No Description of Works A/U Quantity Rate

(Rs)Amount

(Rs)Structural Part

1

Earth work in excavation by mechanical means (Hydraulic excavator) / manual means infoundation trenches of walls, retaining walls, footings of column or drains (not exceeding 1.5 min width or 10 sqm on plan) including dressing of sides and ramming of bottom lift upto 1.5 m,including getting out the excavated soil and disposal of surplus excavated soil as directed, withina lead of 50 m.

a) All Kinds of Soil. Cum 10.00

2Filling with available excavated earth (excluding rock) in trenches, plinth, sides of foundation etcin layers not exceeding 20 cm in depth, consolidationg each deposited layer by ramming andwatering lead upto 50 m and lift upto 1.5 m

Cum 10.00

3Dismantling stone slab flooring laid in cement mortar including stacking of serviceable materialand disposal of unserviceable material within 50 metres lead. Sq.M 150.00

4Hacking of CC roof slab including cleaning for surface etc. complete as per direction of theEngineer-in-Charge. Sq.M 125.00

5Dismantling old plaster or skirting raking out joints and leaning the surface for plaster includingdisposal of rubbish to the dumping ground within 50 metres lead. Sqm 150.00

6Providing and laying in position cement concrete of specified grade excluding the cost ofcentering and shuttering - All work up to plinth

a) 1:2:4 (1 Cement : 2 fine sand : 4 graded stone aggregate 20 mm nominal size) Cum 3.00b) 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) Cum 3.00

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

NERO,Guwahati

(B) Name of Work: Provn. of Addition/alteration of Assam Rifles Hospital at Laitkar, Meghalaya.

Page 7: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl No Description of Works A/U Quantity Rate

(Rs)Amount

(Rs)

7

Providing and laying in position machine mixed and machine batched cement concrete ofspecified grade for reinforced cement concrete structural members for foundation, plinth,columns, beams, walls (any thikness) including attached pilasters, buttresses .All work uptoplinth level.

a) 1:1:2 (1 cement : 1coarse sand : 2 graded stone aggregate of 20 mm nominal size) Cum 30.00

8Centring and shuttering with steel plate / 12mm thick water proof ply board including strutting,propping etc. and removal of form at all levels for :

a) Foundations, footings, bases of columns (any thicknes) etc. Sqm 150.00b) Plinth beams, tie beams (any thicknes) etc. Sqm 150.00

9Supplying, fitting and fixing in position thermo-mechanically treated reinforcement to relevent IScode for R.C.C work including straightening, cleaning, cutting and bending to proper shapes andlength etc all complete as per specifications and drawings

Kg 5000.00

10Providing brick work with F.P.S bricks of class designation 75 in cement morter 1 : 6 (1 cement :6 coarse sand)

a) Superstructure above plinth level upto floor five level. Cum 35.00

11Brick work with common burnt clay F.P.S. (non modular) bricks ofclass designation 7.5 infoundation and plinth in:

a) Cement moter 1:6 (1 cement : 6coarse sand) Cum 0.00

12Providing of 18 mm thick cement plaster in single coat of mix 1 : 6 (1 cement : 6 fine sand) ontop layer 6mm thick cement plaster Sqm 360.00

13 12mm thick cement plaster of mix.a) 1:4 ( 1 cement:4 find sand) Sqm 400.00

14Providing and applying white cement based putty of average I mm thichness of approved brand---even and smooth surface completed. Sqm 400.00

15 distempering with oil bound washable distemper of approved brand and manufactureing Sqm 400.00

Page 8: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl No Description of Works A/U Quantity Rate

(Rs)Amount

(Rs)

16Steel work in build up tubular(round,square or rectangular hollow tubes etc) trusses etc.including cutting ,hoisting,fixing in position and applying a priming coat of approved steel primerincluding welding and bolted special shaped washers etc.complete.

Hot finished welded type tubes Kg 12000.0017 Marble stone flooring with 18mm thik marble stone as per sample of marble overcement moter

Makrana white second quality Sqm 10.00

18

Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to bespecified by the manufacturer), of approved make,in all colours, shades except burgundy, bottlegreen, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps anddados,over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing withgrey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment ofmatching shade complete.

Sqm 150.00

19 Approved quality vitrified floor tiles------------- with matching pigment Sqm 275.00

20 Fully Perforated Gypsum plaster board----------------------direction of the Engineering incharge. Sqm 275.00

21providing and fixing aluminium for door, windows, ventilation and partition etc.(For fixed portion)

Power coated aluminium (50mm thich micron) kg 1000.00

22For shuttersand doors,windows and ventilation including providing and fixing hinges/pivots ----------- etc.Power coated aluminium works(minimum coated 50 micron) kg 1000.00

23 Providing and fixing glazing in aluminium door window, ventilation shutter and partitions etc.

with float glasspanes of 4.0mm thickness Sqm 150.00

24Finishing wall with water proofing cement paint of approved brand and manufacture of requiredshade on new wall surface to give an even shade, after throughly brooming the surfaces toremove all dirt and remains of loose powdered materials.

Sqm 400.00

Page 9: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl No Description of Works A/U Quantity Rate

(Rs)Amount

(Rs)

25

Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch ofcorrugation as approved by Engineer-in-charge) 0.50 mm (+0.05 %) total coated thickness withzinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxyprimer on both side of the sheet and polyester top coat 15-18 microns. Sheet should haveprotective guard film of 25 microns minimum to avoid scratches during transportation and shouldbe supplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shallbe fixed using self drilling / self tapping screws of size (5.5x 55 mm) with EPDM seal, completeupto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters andtrusses and including cutting to size and shape wherever required.

Sqm 350.00

25

Providing and fixing precoated galvanised steel sheet roofing accessories 0.50mm (+0.05%)total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns usingself drilling/ self tapping screws complete :12.51.1 Ridges plain (500 - 600mm)

mtr 25.00

26

Providing and laying of 150 mm compacted thickness with Stone aggregate of 90 to 40 mm sizeincluding supply of screenings, kankar, moorum, red bajri etc sorting, spreading to template andconsolidation with power road roller of 8 to 10 tonne capacity in two layers etc complete. CUM 3.00

Total carried forward to abstract Sl. No. B 1

Page 10: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure - III

Sl. No. Description Unit QTY Rate Amount Rs

SUB HEAD-1: W I R I N G & SUBMAIN

1.0

Wiring for light point/ fan point/ exhaust fan point/ call bell point with1.5 sq.mm FRLS PVC insulated copper conductor single core cablein surface / recessed medium class PVC conduit, with modularswitch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLS PVC insulated copper conductor single core cable etcas required.

Group-B Point 160.00

2.0

Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulatedcopper conductor single core cable in surface/ recessed mediumclass PVC conduit alongwith 1 No 4 sq. mm FRLS PVC insulatedcopper conductor single core cable for loop earthing as required.

Metre 240.00

3.0

Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, single corecable in surface/ recessed medium class PVC conduit as required.

2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Metre 160.00

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

NERO,Guwahati

(B) Name of Work :Provn. of Addition/alteration of Assam Rifles Hospital at Laitkar , Meghalaya.

Page 11: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No. Description Unit QTY Rate Amount Rs

4.0 2 X 6 sq. mm + 1 X 6 sq. mm earth wire Metre 150.00

5.0Supplying and fixing following modular switch/ socket on theexisting modular plate & switch box including connections butexcluding modular plate etc. as required.

6.0 Bell push Each 8.00

7.0Supplying and fixing stepped type electronic fan regulator on theexisting modular plate switch box including connections butexcluding modular plate etc. as required.

Each 24.00

8.0Supplying and fixing modular blanking plate on the existing modularplate & switch box excluding modular plate as required. Each 10.00

9.0

Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modularswitch, connection etc. as required. (For light plugs to be used innon residential buildings).

Each 160.00

10.0

Supplying and fixing suitable size GI box with modular plate andcover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 ampsmodular switch, connection etc. as required.

Each 24.00

11.0Supplying and fixing call bell/ buzzer suitable for single phase, 230volts, complete as required. Each 8.00

Page 12: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No. Description Unit QTY Rate Amount Rs

12.0

Installation, testing and commissioning of ceiling fan, including wiringthe down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLSPVC insulated, copper conductor, single core cable, includingproviding and fixing phenolic laminated sheet cover on the fan boxetc. as required.

Each 24.00

13.0Installation of exhaust fan in the existing opening, including makinggood the damage, connection, testing, commissioning etc. asrequired.

Upto 450 mm sweep Each 12.00

14.0Extra for fixing the louvers/ shutters complete with frame for aexhaust fan of all sizes. Each 12.00

SUB HEAD -II : DISTRIBUTION BOARD

1.0

Supplying and fixing following way, single pole and neutral, sheetsteel, MCB distribution board, 240 V, on surface/ recess, completewith tinned copper bus bar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthing etc. as required.(But without MCB/RCCB/Isolator)

2+8 Way Double Door Each 8.00

2.0

Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C"curve, miniature circuit breaker suitable for inductive load of followingpoles in the existing MCB DB complete with connections, testing andcommissioning etc. as required.

Single pole Each 56.00Double Pole each 8.00

Page 13: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No. Description Unit QTY Rate Amount Rs

3.0Supplying and fixing single pole blanking plate in the existing MCBDB complete etc. as required. Each 8.00

SUB HEAD - IV : EARTHING & LIGHTNING PROTECTIONSYSTEM

1.0

Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thickincluding accessories, and providing masonry enclosure with coverplate having locking arrangement and watering pipe of 2.7 metre longetc. with charcoal/ coke and salt as required.

Set 6.00

2.0Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipefrom earth electrode including connection with G.I. nut, bolt, spring,washer excavation and re-filling etc. as required.

Metre 20.00

3.0Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recessfor connections etc. as required. Metre 10.00

4.0

Providing and fixing of lightning conductor finial, made of 25 mm dia300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6mm thick G.I. base plate including holes etc. complete as required. Each 2.00

5.0Jointing copper / G.I. tape (with another copper/ G I tape, base of thefinial or any other metallic object) by riveting / nut bolting/ sweatingand soldering etc as required.

Each 2.00

6.0Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet orsurface of wall for lightning conductor complete as required.(Forhorizontal run)

Metre 80.00

Page 14: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No. Description Unit QTY Rate Amount Rs

7.0Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet orsurface of wall for lightning conductor complete as required.(Forvertical run)

Metre 94.00

8.0Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I.strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts andspring washers etc. complete as required.

Each 10.00

9.0Providing and laying G.I. tape 32 mm X 6 mm from earth electrodedirectly in ground as required. Metre 104.00

SUB HEAD - V : LIGHTING FIXTURE & FAN

1.0

Installation, testing and commissioning of pre-wired, fluorescentfitting / compact fluorescent fitting of all types, complete with allaccessories and tube etc. directly on ceiling/ wall, includingconnection with 1.5 sq. mm FRLS PVC insulated, copper conductor,single core cable and earthing etc. as required.

Each 80.00

2.0

Installation, testing and commissioning of ceiling fan, including wiringthe down rods of standard length (upto 30 cm) with 1.5 sq. mm FRPVC insulated, copper conductor, single core cable, includingproviding and fixing phenolic laminated sheet cover on the fan boxetc. as required.

Each 24.00

Page 15: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No. Description Unit QTY Rate Amount Rs

TV TELEPHONE

3.0

Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solidcopper conductor PE insulated, shielded with fine tinned copper braidand protected with PVC sheath in the existing surface/ recessedsteel/ PVC conduit as required.

Metre 120.00

4.0

Supplying and fixing of following sizes of medium class PVC conduitalong with accessories in surface/recess including cutting the walland making good the same in case of recessed conduit as required.

25 mm Metre 80.00

5.0Supplying and fixing following modular switch/ socket on theexisting modular plate & switch box including connections butexcluding modular plate etc. as required.

TV antenna socket outlet Each 8.00

6.0Supplying and fixing following size/ modules, GI box alongwithmodular base & cover plate for modular switches in recess etc asrequired.

1 or 2 Module (75mmX75mm) Each 8.00

Supply of Light fixture as given below

1.0Supply of 20W wall mounted LED Batten light Equivalent to Philips,Wipro, Bajaj, Havels. Each 24.00

2.0Supply of 10W surface mounted circular LED light Equivalent toPhilips, Wipro, Bajaj, Havels. Each 38.00

Page 16: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No. Description Unit QTY Rate Amount Rs

3.0Supply of 12W LED Wall Bracket Light. Equivalent to Philips, Wipro,Bajaj, Havels. Each 32.00

4.0Supply of 9W PL Bulk head light. Equivalent to Philips, Wipro, Bajaj, Havels. Each 0.00

5.0Supply of Ceiling Fan of 1200mm sweep complete erected inposition with all accessories.(Make- Havels) or Equivalent to Orient,Cropton Greave.

Each 24.00

6.0Supplying of Exhaust Fan Heavy duty 230V A.C 50 cycles 375 mm1400 RPM complete erected in position with all accessories.(Make-Havels)

Each 12.00

7.0Supply of 2X 20W wall mounted LED Batten light. Make- Philips,Wipro, Bajaj, Havels. eACH

METER BOARD

8

Supply, installation, testing and commissioning of front operated,front / back access, cubicle type, indoor duty, floor / wall / recess /surface mounted (as specified), totally enclosed dust and verminproof switchboards / panels with minimum Ingress protectionclassification of IP 44, fabricated from 2 mm thick CRCA sheets withdip coat priming and epoxy powder coated finish. The panel must besuitable for 415 volts 3 phase, 4 wire, 50 Hz, system , must be able towithstand symmetrical fault level of 50 KA for 1 sec at 415 V andmust include all interconnections, earthing and bonding requirementsetc. The panel must conform to standards, as required and as givenbelow.

Page 17: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No. Description Unit QTY Rate Amount Rs

The Switchboard shall be provided with detachable gland plates forentry of cables from the top / bottom as required.

All live accessible parts shall be shrouded and all equipment shall befinger touch proof. The busbars shall be insulated with heatshrinkable sleeves. SMC / DMC shrouds and busbar supportssuitably spaced shall be used. Hinged doors with padlocking facilityshall be provided on all outgoing feeders with switch handleslockable in OFF position.

The panel shall have aluminium busbars with bar type feederconnections, spacers etc. with full sized neutral.

Earthing all components, frame etc. to a common internal earth barof size 25 x 6 mm Cu.Panel / Switchboard board design shall be compact and components/ accessories of compact sizes shall be used to economise the roomspace available. Employer reserve the right to seek compact itemsinplace of larger ones.

Incoming

1 No. 63 A, TPN, 35 kA, MCCB having Thermal Magnetic Trip Unitwith protection against Overload & Short Circuit, 0-63 A DigitalAmmeter with inbuilt ASS, 3 Nos. CT 63/5A, class 1.0 for meteringand LED Indication Lamp for ON, OFF & TRIP.

Page 18: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No. Description Unit QTY Rate Amount Rs

Bus BarsElectrolytic high conductivity 3P, 4W aluminium conductor bus-barsrated 100 Amps, suitable to withstand symetrical fault level of 35 KAfor 1 second at 415 volts and with necessary heat shrinkablesleeving.

Outgoings:

8 Nos. 40 A DP MCB 15 KA

8 Nos. 10-40 A Single -phase, 2-wire, 220 V AC Digital Energymeter

2 Nos. 10A DP MCBMeter Board complete as above and as required.

Each 1.00

Total carried forward to abstract Sl. No. B 2

Page 19: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure - IV

Sl. No Description Unit QTY. Rate

(Rs) Amount

(Rs)

1

Providing and fixing white vitreous china pedestal type water closet (European typeW.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, includingflush pipe, with manually controlled device (handle lever), conforming to IS : 7231,with all fittings and fixtures complete, including cutting and making good the walls andfloors wherever required :

WC pan ISI marked white solid plastic seat and lid Each 14.00

2Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32mm C.P. brass waste of standard pattern, including painting of fittings and brackets,cutting and making good the walls wherever require:

a White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P.brass pillar tap Each 14.00

3 Providing and fixing white vitreous china pedestal for wash basin completelyrecessed at the back for the reception of pipes and fittings Each 14.00

4Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS: 13983 withC.I. brackets and stainless steel plug 40 mm, including painting of fittings andbrackets, cutting and making good the walls wherever required :

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

NERO,Guwahati

(B)Name of Work :Provn. of Addition/alteration of Assam Rifles Hospital at Laitkar , Meghalaya.i) Sanitary Instalation

Page 20: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No Description Unit QTY. Rate

(Rs) Amount

(Rs) 510x1040 mm bowl depth 200 mm Each 8.00

5Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. wastefittings complete.Flexible pipe

a 32 mm dia Each 14.00 b 40 mm dia Each 14.00

6Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approvedquality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P.brass screws and washers complete.

Each 14.00

7Providing and fixing 600x120x5mm glass shelf with edges round of supported onanodised aluminium angle frame with C.P. brass brackets and guard rail completefixed with 40mm long screws,rawl plugs etc., complete

Each 14.00

8 Providing and fixing toilet paper holder

Vitreous china Each 8.00

9Providing and fixing PTMT towel ring trapezoidal shape 215 mm long,200 mm widewith minimum distances of 37 mm from wall face with concealed fittings arrangementof approved quality and colour, weighing not less than 88 gms.

Each 14.00

10Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleatswith CP brass screws with concealed fittings arrangement of approved quality andcolour.450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of88 mm, weighing not less than 170 gms Each 14.00

Page 21: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Sl. No Description Unit QTY. Rate

(Rs) Amount

(Rs)

11Providing and fixing uplasticised PVC connection pipe with brass unions : 45 cmlength15 mm nominal bore Each 14.00

12 Providing and Fixing shower rose with 15 or 20mm inlet150mm diameter Nos. 32.00

13 Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :

a) 15 mm nomial bore Nos. 16.00

14 Providing and fixing C.P. brass long nose bib cock of approved quality conforming toIS standards and weighing not less than 810 gms.15 mm nominal bore Nos. 48.00

15 Providing and fixing C.P. brass stop cock (concealed) of standard design and ofapproved make conforming to IS:8931.15 mm nominal bore Nos. 14.00

16Providing and fixing C.P. brass angle valve for basin mixer and geyser points ofapproved quality conforming to IS:8931

a) 15 mm nominal bore Nos. 48.00

17Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth102mm, height of 75mm with concealed fitting arrangements, weighing not less than106 gms.

Nos. 14.00

Total carried forward to abstract Sl. No. B 3 (i)

Page 22: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure-V

Sl. No. Description UNIT QTY. Rate(Rs)

Amount (Rs)

1

Providing and Fixing Chlorinated Polyvinyl Chloride (CPVC) Pipes, having thermalstability for hot & cold water supply including all CPVC plain & brass threadedfittings including fixing the pipe with suports, clamps at 1.00 m spacing. Thisincludes jointing of pipes & fittings with one step CPVC solvent cement and the costof cutting chases and making good the same including testing of joints complete asper direction of Engineer-In-Charge.Concealed work including cutting chases and making good the walls etc.

a 15 mm dia Metre 220.00b 20 mm dia Metre 40.00

2

Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermalstability for hot & cold water supply, including all CPVC plain & brass threadedfittings, including fixing the pipe with clamps at 1.00 m spacing. This includesjointing of pipes & fittings with one step CPVC solvent cement and testing of jointscomplete as per direction of Engineer in Charge.Internal work - Exposed on wall and terrace

a 15 mm nominal outer dia Pipes Metre 22.00b 20 mm nominal outer dia Pipes Metre 16.50c 25 mm nominal outer dia Pipes Metre 198.00d 32 mm nominal outer dia Pipes Metre 52.803 Providing and Fixing brass Stop Cock of Approved Quality

15 mm nominal bore each 16.00

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

NERO,Guwahati

(B)Name of Work: Provn. of Addition/alteration of Assam Rifles Hospital at Laitkar, Meghalaya.

ii) Internal Water supply

Page 23: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

1

Providing and Fixing Chlorinated Polyvinyl Chloride (CPVC) Pipes, having thermalstability for hot & cold water supply including all CPVC plain & brass threadedfittings including fixing the pipe with suports, clamps at 1.00 m spacing. Thisincludes jointing of pipes & fittings with one step CPVC solvent cement and the costof cutting chases and making good the same including testing of joints complete asper direction of Engineer-In-Charge.

4Providing and fixing gun metal gate valve with C.I. wheel of approvedquality(screwed end )

a 25 mm nominal bore each 8.00b 32 mm nominal bore. each 1.00

5Providing and fixing ball valve (brass) of approved quality, High or low pressure,with plastic floats complete :

a 20 mm nominal bore each 8.00

6

Providing and placing on terrace (at all floor levels) polyethylene water storagetank, ISI:12701 marked, with cover and suitable locking arrangement and makingnecessary holes for inlet, outlet and overflow pipes but without fittings and the basesupport for tank.

per litre 4000.00

Total carried forward to abstract Sl. No. B 3 (ii)

Page 24: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

(Annexure-VI)

Sl. No Description Unit QTY. Rate(Rs)

Amount (Rs)

1

Excavating trenches of required width for pipes, cables, etc including excavation forsockets, anddressing of sides, ramming of bottoms, depth up to 1.5 m, includinggetting out the excavated soil, and then returning the soil as required, in layers notexceeding 20 cm in depth, including consolidatingeach deposited layer by ramming,watering, etc. and disposing of surplus excavated soil as directed,within a lead of 50m :All kinds of soil

Pipes, cables etc, not exceeding 80 mm dia. Metre 10

2Steel work welded in built up sections/framed work including cutting hoisting, fixing inposition and applying a priming coat of approved steel primer using structural steeletc.as required.

In gratings, frames, guard bar, ladders, railings, brackets, gates & similar works. kilogram 50.00

3Providing and fixing on wall face unplasticised Rigid PVC rain water pipesconforming to IS : 13592 Type A, including jointing with seal ring conforming to IS :5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.

75 mm diameter Metre 21.00

iii) Internal Drainage

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

NERO,Guwahati

(B)Name of Work :Provn. of Addition/alteration of Assam Rifles Hospital at Laitkar, Meghalaya.

Page 25: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

1

Excavating trenches of required width for pipes, cables, etc including excavation forsockets, anddressing of sides, ramming of bottoms, depth up to 1.5 m, includinggetting out the excavated soil, and then returning the soil as required, in layers notexceeding 20 cm in depth, including consolidatingeach deposited layer by ramming,watering, etc. and disposing of surplus excavated soil as directed,within a lead of 50m :

4

Providing and fixing on wall face unplasticised-PVC moulded fittings / accessories forunplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A includingjointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermalexpansion.

a Single Push fit coupler75 mm diameter each 9.00

b Single Tee with door75x75x75 mm dia each 18.00

c Bend 87.5 Deg75 mm dia each 2.00

d Shoe (Plain)75 mm Dia. each 2.00

5

Providing and Fixing on wall face unplasticised - PVC pipe clips of approved designto unplasticised - PVC rain water pipes by means of 50 x 50 x 50 mm hard woodplugs, screwed with M.S. screws of required length including cutting brick work andfixing in cement mortar 1:4 (1 Cement: 4 Coarse sand) and making good the wallsetc. complete75 mm dia each 14.00

6 Providing and fixing PTMT grating of approved quality and colour.

a Circular type

b 125 mm nominal dia with 25 mm waste hole Nos. 42.00

Page 26: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

1

Excavating trenches of required width for pipes, cables, etc including excavation forsockets, anddressing of sides, ramming of bottoms, depth up to 1.5 m, includinggetting out the excavated soil, and then returning the soil as required, in layers notexceeding 20 cm in depth, including consolidatingeach deposited layer by ramming,watering, etc. and disposing of surplus excavated soil as directed,within a lead of 50m :

7Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture ofcement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing ofjoints etc. complete :150 mm diameter Metre 15

8Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 gradedstone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete asper standard design :

150 mm diameter S.W. pipe Metre 15

9

Providing and fixing square-mouth S.W. gully trap class SP-1 complete withh C.I.grating brick masonry chamber withh water tight C.I. cover withh frame o f 300 x300mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be notless than 2.70 kg as per standard design:100x100 mm size P type withh common burnt clay F.P.S. (non modular) bricks ofclass designation 7.5 Nos. 4

10

Constructing brick masonry manhole in cement mortar 1:4 (1 cement : 4 coarse sand) withh R.C.C. top slab withh 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stoneaggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarsesand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thickwithh cement mortar 1:3 (1 cement : 3 coarse sand) finished withh floating coat ofneat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarsesand : 4graded stone aggregate 20 mm nominal size) finished with a floating coat ofneat cement complete as per standard design :

Page 27: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

1

Excavating trenches of required width for pipes, cables, etc including excavation forsockets, anddressing of sides, ramming of bottoms, depth up to 1.5 m, includinggetting out the excavated soil, and then returning the soil as required, in layers notexceeding 20 cm in depth, including consolidatingeach deposited layer by ramming,watering, etc. and disposing of surplus excavated soil as directed,within a lead of 50m :Inside size 90x80 cm and 45 cm deep including C.I. cover withh frame (light duty)455x610 mm internal dimensions, total weight of cover and frame to be not less than38 kg (weight of cover 23 kg and weight of frame 15 kg) :

a Withh common burnt clay F.P.S. (non-modular) bricks of class designation 7.5 Nos. 8MARKET RATE ITEMS

1

Supplying and fixing PVC pipes conforming to IS 4985 class III, 6 kg/sq.cm pressurefor lines with all required specials such as plain bends, single junctions, elbows,crosses, unions, shoes, door bends, double junctions, vent cowls,traps etc. with orwithout door including cutting masonry or concrete floors, sunshades, etc andmaking the holes good after finishing the work. wherever necessary and jointingpipes with approved quality resin cement and fixing pipes with MS fixing clampsscrewed on to wooden plugs embedded in masonry wherever required and paintingthe clamps with two coats of enamel paint over one coat primer. This includestesting of joints complete at all levels. for waste water lines

110mm or nearest outer dia. RM 230Total carried forward to abstract Sl. No. B 3 (iii)

Page 28: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure - VII

Sl No. Description of Works A/U Quantity Rate(Rs)

Amount(Rs)

Building Works (A)

1Dismantling stone slab flooring laid in cement mortar including stacking ofserviceable material and disposal of unserviceable material within 50 metreslead.

Sq.M 600.00

2 Hacking of CC roof slab including cleaning for surface etc. complete as perdirection of the Engineer-in-Charge.

Sq.M 350.00

3Dismantling old plaster or skirting raking out joints and leaning the surface forplaster including disposal of rubbish to the dumping ground within 50 metres lead. Sqm 600.00

4

Providing and laying water proofing treatment on roofs of slabs by applyingcement slurry mixed with water proofing cement compound consisting of applying: a) after surface preparation, first layer of slurry of cement @ 0.488 kg/sqm mixedwith water proofing cement compound @ 0.253 kg/sqm. b) laying second layer of Fibre glass cloth when the first layer is still green.Overlaps of joints of fibre cloth should not be less than 10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/sqmmixed with water proofing cement compound @ 0.670 kg/sqm and coarse sand @1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curingfor 48 hours. The entire treatment will be taken upto 30 cm on parapet wall andtucked into groove in parapet all around. d) fourth and final layer of brick tiling with cement mortar (which will be paid forseparately. For the purpose of measurement the entire treated surface will bemeasured.

Sqm 350.00

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

NERO,Guwahati

(C) Name of Work : Provn of improvement to OR married accomodation (12 Blocks) type-II Qtr for, Laitkor. Garrison (Meghalaya).

Page 29: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

5

Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm ormore (thickness to be specified by the manufacturer), of 1st quality conforming toIS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey,Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarsesand), including pointing the joints with white cement and matching pigments etc.,complete

Sqm 750.00

6

Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS:15622(thickness to be specified by the manufacturer), of approved make, in all colours,shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cementmortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @3.3kg per sqm, including pointing in white cement mixed with pigment of matchingshade complete.

Sqm 350.00

7

Marble stone flooring with 18 mm thick marble stone, as per sample of marbleapproved by Engineer-in-charge,over 20 mm (average) thick base of cementmortar 1:4 (1 cement : 4 coarse sand) laid and jointed with grey cement slurry,including rubbing and polishing complete with: Udaipur green marble

Sq.M 300.00

8

Providing and laying water proofing treatment to vertical and horizontal surfaces ofdepressed portions of W.C.,kitchen and the like consisting of :(i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofingcompound conforming to IS 2645 in recommended proportions including roundingoff junction of vertical and horizontal surface.(ii) IInd course of 20 mm cement plaster 1:3 (1 cement:3 coarse sand) mixed withwater proofing compound in recommended proportion including rounding offjunction of vertical and horizontal surface.(iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg.persqm of area.(iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheetshould be 100 mm wide and pasted to each other with bitumen @ 1.7 kg/sqm).

Sqm 400.00

912 mm cement plaster of mix :1:4 (1 cement: 4 coarse sand) Sqm 850.00

1015 mm cement plaster on rough side of single or half brick wall of mix:1:4 (1 cement: 4 coarse sand) Sqm 850.00

Page 30: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

11

Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additivesof required shade: New work (Two or more coats applied @ 1.43 ltr/10sqm overand including priming coat of exterior primerapplied @ 2.20 kg/ 10 sqm)

Sqm 850.00

12

Renewing wooden battens in roofs, including making good the holes in wall andpainting with oil type wood preservative of approved brand and manufacturecomplete, including removal of rubbish to the dumping ground, all complete as perdirection of Engineer-in-Charge.

Cum 7.50

13

Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS: 13983with C.I. brackets and stainless steel plug 40 mm, including painting of fittings andbrackets, cutting and making good the walls wherever required:Kitchen sink without drain board610x510 mm bowl depth 200 mm

Kitchen sink with drain board510x1040 mm bowl depth 200 mm Each 12.00

14Kitchen sink without drain board610x510 mm bowl depth 200 mm. Each 36.00

15Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C.waste fittings complete.Flexible pipe. 40 mm dia

Each 48.00

16

Distempering with oil bound washable distemper of approved brand andmanufacture to give an even shade:New work (two or more coats) over and including water thinnable priming coat withcement primer

sqm 850.00

17Providing and applying white cement based putty of average thickness 1 mm, ofapproved brand and manufacturer, over the plastered wall surface to prepare thesurface even and smooth complete.

sqm 850.00

18Dismantling precast concrete /stone slabs / walls, Partition walls etc. includingstacking within 50 metres lead : sqm 75.00

Page 31: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

19

Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermalstability for hot & cold water supply, including all CPVC plain & brass threadedfittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing ofpipes & fittings with one step CPVC solvent cement and the cost of cutting chasesand making good the same including testing of joints complete as per directionof Engineer in Charge.Concealed work, including cutting chases and making good the walls etc.15 mm nominal outer dia Pipes

mtr 75.00

20Providing and fixing uplasticised PVC connection pipe with brass unions :15 mm nominal bore each 48.00

21Providing and fixing C.P. brass long nose bib cock of approved quality conformingto IS standards and eighing not less than 810 gms.15 mm nominal bore

each 48.00

22Providing and fixing C.P. brass stop cock (concealed) of standard design and ofapproved make conforming to IS:8931.15 mm nominal bore

each 48.00

23Providing and fixing C.P. brass bib cock of approved quality conforming to IS:893115 mm nominal bore each 48.00

24

Providing and fixing precoated galvanised iron profile sheets (size, shape andpitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05 %) totalcoated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpasteel grade, 5-7 microns epoxy primer on both side of the sheet and polyester topcoat 15-18 microns. Sheet should have protective guard film of 25 micronsminimum to avoid scratches during transportation and should be supplied in singlelength upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixedusing self drilling / self tapping screws of size (5.5x 55 mm) with EPDM seal,complete upto any pitch in horizontal/ vertical or curved surfaces, excluding thecost of purlins, rafters and trusses and including cutting to size and shapewherever required.

Sqm 2300.00

Page 32: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

25

Providing and fixing precoated galvanised steel sheet roofing accessories 0.50mm (+ 0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS:277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheetand polyester top coat 15-18 microns using self drilling/ self tapping screwscomplete :12.51.1 Ridges plain (500 - 600mm)

mtr 100.00

Total carried forward to abstract Sl. No. C 1

Page 33: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure - VIII

Sl No. Description of Works A/U Quantity Rate(Rs)

Amount(Rs)

External Electrification(B)

1

Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5sq.mm FR PVC insulated copper conductor single core cable in surface /recessed medium class PVC conduit, with piano type switch, phenoliclaminated sheet, suitable size M.S.box and earthing the point with 1.5sq.mm. FR PVC insulated copper conductor single core cable etc asrequired.(Including PVC Surface Casing)Group-B Point 96.00

2

Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copperconductor single core cable in surface/ recessed medium class PVCconduit alongwith 1 No 4 sq. mm FRLS PVC insulated copper conductorsingle core cable for loop earthing as required.

Metre 48.00

3

Supplying and fixing suitable size GI box with modular plate and cover infront on surface or in recess, including providing and fixing 6 pin 5/6 &15/16 amps modular socket outlet and 15/16 amps modular switch,connection etc. as required.

Each 48.00

4Supply of 20W wall mounted LED Batten light Equivalent to Philips, Wipro,Bajaj, Havels. Each 96.00

Total carried forward to abstract Sl. No. C 2

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

NERO,Guwahati

ELECTRICAL

(C) Name of Work : Provn of improvement to OR married accomodation (12 Blocks) type-II Qtr for, Laitkor. Garrison (Meghalaya).

Page 34: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure - IX

Sl No. Description of Works A/U Quantity Rate(Rs)

Amount(Rs)

Building Works(A)

1Dismantling stone slab flooring laid in cement mortar including stacking of serviceablematerial and disposal of unserviceable material within 50 metres lead. Sq.M 635.00

2Hacking of CC roof slab including cleaning for surface etc. complete as per direction of theEngineer-in-Charge. Sq.M 1260.00

3Dismantling old plaster or skirting raking out joints and leaning the surface for plasterincluding disposal of rubbish to the dumping ground within 50 metres lead. Sqm 1105.00

4

Providing and laying water proofing treatment on roofs of slabs by applying cement slurrymixed with water proofing cement compound consisting of applying: a) after surface preparation, first layer of slurry of cement @ 0.488 kg/sqm mixed withwater proofing cement compound @ 0.253 kg/sqm. b) laying second layer of Fibre glass cloth when the first layer is still green. Overlaps ofjoints of fibre cloth should not be less than 10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/sqm mixed withwater proofing cement compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. Thiswill be allowed to air cure for 4 hours followed by water curing for 48 hours. The entiretreatment will be taken upto 30 cm on parapet wall and tucked into groove in parapet allaround. d) fourth and final layer of brick tiling with cement mortar(which will be paid for separately.For the purpose of measurement the entire treated surface will be measured.

Sqm 1260.00

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

(D) Name of Work : Provn of improvement toType-III (JCO md accommodation) (Building No P-III) (A,B,C,D,E & F) for, Laitkor. Garrison(Meghalaya).

NERO,Guwahati

Page 35: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

5

Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more(thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, ofapproved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laidon 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand), including pointing thejoints with white cement and matching pigments etc., complete

Sqm 480.00

6

Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thicknessto be specified by the manufacturer), of approved make, in all colours, shades exceptburgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting,risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarsesand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in whitecement mixed with pigment of matching shade complete.

Sqm 1100.00

7

Marble stone flooring with 18 mm thick marble stone, as per sample of marble approved byEngineer-in-charge, over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4coarse sand) laid and jointed with grey cement slurry, including rubbing and polishingcomplete with :Udaipur green marble

Sq.M 268.00

8

Providing and laying water proofing treatment to vertical and horizontal surfaces ofdepressed portions of W.C., kitchen and the like consisting of:(i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compoundconforming to IS 2645 in recommended proportions including rounding off junction ofvertical and horizontal surface.(ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with waterproofing compound in recommended proportion including rounding off junction of verticaland horizontal surface.(iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg.per sqm of area.(iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be100 mm wide and pasted to each other with bitumen @ 1.7 kg/sqm).

Sqm 1200.00

912 mm cement plaster of mix :1:4 (1 cement: 4 coarse sand) Sqm 1200.00

Page 36: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

1015 mm cement plaster on rough side of single or half brick wall of mix:1:4 (1 cement: 4 coarse sand) Sqm 1500.00

11

Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives ofrequired shade :New work (Two or more coats applied @1.43 ltr/ 10 sqm over and including priming coat ofexterior primer applied @ 2.20 kg/ 10 sqm)

Sqm 1500.00

12

Renewing wooden battens in roofs, including making good the holes in wall and paintingwith oil type wood preservative of approved brand and manufacture complete, includingremoval of rubbish to the dumping ground, all complete asper direction of Engineer-in-Charge.

Cum 7.50

13

Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS: 13983 with C.I.brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cuttingand making good the walls wherever required :Kitchen sink without drain board 610x510 mm bowl depth 200 mmKitchen sink with drain board510x1040 mm bowl depth 200 mm Each 20.00

14 Kitchen sink without drain board610x510 mm bowl depth 200 mm. Each 22.00

15

Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittingscomplete.Flexible pipe.40 mm dia

Each 42.00

16

Distempering with oil bound washable distemper of approved brand and manufacture togive an even shade :New work (two or more coats) over and including water thinnable priming coat with cementprimer

sqm 1800.00

17Providing and applying white cement based putty of average thickness 1 mm, of approvedbrand and manufacturer, over the plastered wall surface to prepare the surface even andsmooth complete.

sqm 1400.00

Page 37: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

18Dismantling precast concrete /stone slabs / walls, Partition walls etc. including stackingwithin 50 metres lead : sqm 85.00

19

Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stabilityfor hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing thepipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one stepCPVC solvent cement and the cost of cutting chases and making good the same includingtesting of joints complete as per direction of Engineer in Charge. Concealed work,including cutting chases and making good the walls etc.15 mm nominal outer dia Pipes

mtr 100.00

20Providing and fixing uplasticised PVC connection pipe with brass unions :15 mm nominal bore each 42.00

21Providing and fixing C.P. brass long nose bib cock of approved quality conforming to ISstandards and eighing not less than 810 gms.15 mm nominal bore

each 42.00

22Providing and fixing C.P. brass stop cock (concealed) of standard design and of approvedmake conforming to IS:8931.15 mm nominal bore

each 42.00

23Providing and fixing C.P. brass bib cock of approved quality conforming to IS:893115 mm nominal bore each 42.00

Total carried forward to abstract Sl. No. D 1

Page 38: V OL UM E III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3441_Vol-3.pdfAnnexure - I Sl No. Description of Works A/U Quantity Rate (Rs) Amount (Rs) Building Works

Annexure - X

Sl No. Description of Works A/U Qty Rate(Rs)

Amount(Rs)

External Electrification (B)

1.00

Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRPVC insulated copper conductor single core cable in surface / recessed mediumclass PVC conduit, with piano type switch, phenolic laminated sheet, suitable sizeM.S.box and earthing the point with 1.5 sq.mm. FR PVC insulated copperconductor single core cable etc as required.(Including PVC Surface Casing)

Group-B Point 42.00

2

Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copperconductor single core cable in surface/ recessed medium class PVC conduitalongwith 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cablefor loop earthing as required.

Metre 218.40

3

Supplying and fixing suitable size GI box with modular plate and cover in front onsurface or in recess, including providing and fixing 6 pin 5/6 & 15/16 ampsmodular socket outlet and 15/16 amps modular switch, connection etc. asrequired.

Each 42.00

4Supply of 20W wall mounted LED Batten light Equivalent to Philips, Wipro, Bajaj,Havels.

Each126.00

ENGINEERING PROJECTS (INDIA) LIMITED(A GOVERNMENT OF INDIA ENTERPRISE)

ELECTRICAL

(D) Name of Work : Provn of improvement toType-III (JCO md accommodation) (Building No P-III) (A,B,C,D,E & F) for, Laitkor. Garrison(Meghalaya).

NERO,Guwahati

Total carried forward to abstract Sl. No. D 2