USING THE NONLINEAR PARTICLE SWARM OPTIMIZATION (PSO ...
Transcript of USING THE NONLINEAR PARTICLE SWARM OPTIMIZATION (PSO ...
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
18
USING THE NONLINEAR PARTICLE SWARM OPTIMIZATION (PSO)
ALGORITHM TO REDUCE THE MAGNETIC FIELDS FROM OVERHEAD
HIGH VOLTAGE TRANSMISSION LINES
M. S. H. Al Salameh1, I. M. Nejdawi
2 & O. A. Alani
3
1 Department of Electrical Engineering, University of Science and Technology, Irbid 22110, Jordan,
1 Electricity Regulatory Commission, Amman 11821, PO Box 1865, Jordan.
1 Bin Ghannam Contracting, P.O. Box 31119, Dubai, UAE.
Email: [email protected]
ABSTRACT
Using particle swarm optimization (PSO), the influence of the geometrical configuration of conductors is studied in
order to minimize the magnetic field near both single circuit and double circuit high voltage overhead power
transmission lines. New arrangements of high voltage "green lines" are proposed. The results indicate that the
magnetic field can be reduced up to 48% under the influence of wind and ice, and 80%, neglecting them.
Accordingly, the necessary ROW (Right Of Way) width, so that the magnetic field outside ROW does not exceed an
example reference value of 0.4 μT, can be reduced by up to 48% if wind and ice are taken into account and by up to
90% if not, for the same range of line heights. Complex and real image theories were implemented to find the
magnetic and electric fields, respectively, near the transmission line. The electric field is evaluated and it is found
that it is acceptable. Also, results showed that the bundling affects the electric field only.
Keywords: High voltage lines, PSO, Reduce fields, Image theory, EMC, Health.
1. INTRODUCTION
The 50/60 Hz electric power transmission lines can interfere with nearby electrical and electronic equipment [1]. In
addition, concern has arisen regarding the controversial issue of possible adverse effects on human health associated
with exposure to electromagnetic fields from 50/60 Hz electric power transmission, sub-transmission and/or
distribution lines, and other sources including appliances. Because of this, many studies have focused on the fields
emanating from electrical devices and transmission lines [2]-[6]. The greater the field around the transmission lines,
the greater the current induced in the human body [3]. The International Agency for Research on Cancer (IARC)
classified power frequency electromagnetic fields as “possibly carcinogenic to humans” based on a fairly consistent
statistical association between doubling the risk of childhood leukemia and extremely low frequency (ELF)
magnetic field exposure above 0.4 μT [4]. Thus, in some cases there is a need to reduce the fields, especially the
magnetic field which cannot be easily shielded [7], when the transmission line interferes with the adjacent electrical
and electronic equipment. Also, as most building materials are nonmagnetic, magnetic fields of high voltage lines
are not attenuated by common materials such as building walls. In contrast to that, building walls can shield electric
fields to some extent.
The shielding of power lines was investigated in order to reduce the emitted magnetic flux density to a few
microteslas which is the limit for new installations in some countries [7]. Unlike radio frequency fields which can be
shielded with relatively thin films, ELF magnetic fields require very thick, high permeability materials for effective
shielding [8]. Comparing different configurations revealed that the magnetic field at ground is low for the equilateral
delta configuration and high for the horizontal configuration [9]. Another way to reduce magnetic field is “active
shielding”, namely, by a separately energized circuit introduced near an existing power line [10]. Such systems
require dynamic feedback systems to keep the phase and magnitude of the shielding circuit current at optimum
interference with the power circuit, and can be costly. Underground power lines with multiple conductors can be
configured to minimize the magnetic field at ground level [10]. Since the earth shields only the electric field,
underground lines can sometimes emit greater magnetic fields than equivalent overhead lines because the burial
depth may be only four to six feet as opposed to the 20 to 30 feet clearance of an overhead line. Recently, TenneT,
the operator of electric power net in Netherlands, has provided new designs of high-voltage transmission lines in
which conductors are suspended closer together than in traditional high-voltage lines, thus reducing the intensity of
the magnetic field generated along the line [11]. This TenneT project was in response to the precautionary policy
adopted by Dutch Ministry of Housing, Spatial Planning and the Environment which is aimed at minimizing
unnecessary long-term human exposure to magnetic fields generated by high-voltage lines. The ministry defined a
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
19
limit value of 0.4 T for exposure to magnetic fields in 2005 as part of strict guidelines for the extension of high-
voltage lines and the construction of new buildings near existing high-voltage lines. The article [12] considers a
specific arrangement of the phase conductors along with reducing dimensions (compaction) of the line to reduce the
magnetic and electric fields.
We choose, in this paper, to reduce the magnetic field of an arbitrary line by arranging its phase conductors, without
assuming certain templates in advance. To the authors' knowledge, there is no published systematic method to find
the optimum arrangement of conductors for any high voltage transmission line in order to produce minimum
magnetic field. For all the cases investigated, we found that minimizing the magnetic field is automatically
associated with reducing the electric field. To achieve this goal, we used particle swarm optimization (PSO) which is
a nonlinear constrained method that can lead to optimum solutions without knowing the gradient of the problem
beforehand [13], [14]. Our solution represents a two-dimensional cross section of a transmission line, and thus the
line height is considered at the point along the line where the cross-section is taken.
Minimizing the magnetic field by arranging the transmission line conductors has the advantage of minimizing the
magnetic field without adding any equipment or shield to the line. Extensive simulations were performed (not shown
in this paper due to paper size limitations) for various configurations, where it was noticed in most cases that
optimized lines (with minimum magnetic fields) have more compact arrangements (shorter conductor spacings)
compared with unoptimized arrangements. This indicates that the cost of installing a high voltage line with
minimum field is probably lower than or comparable to unoptimized line. Anyway, the cost analysis will be
considered in a future work.
In this paper, the intelligence of the swarm is used to find the optimal arrangement of conductors that would produce
minimum magnetic field near high voltage overhead power transmission lines. Toward that end, a swarm of 49
particles (different arrangements of line conductors) is used to minimize the field. At each iteration, the fitness
function (magnetic field due to all conductors) is evaluated for each particle in the swarm. The best fitness values for
each particle as well as for the whole swarm are stored. Swarms continue to move (iterate) until the targeted best
value is obtained. The transmission line configuration (conductors arrangement) associated with this targeted best
value is the optimum solution. Matlab computer programs were written and executed to calculate and minimize the
magnetic field for overhead transmission lines. Also, the electric field is computed where we found that the electric
field is also reduced.
2. PARTICLE SWARM OPTIMIZATION (PSO)
The PSO is a robust stochastic nonlinear evolutionary computation technique based on the movement and
intelligence of swarms [15]. In comparison with other stochastic evolutionary algorithms like genetic algorithms,
PSO has fewer complicated operations, fewer defining parameters, and generally fewer lines of code [16]. PSO
depends on the social interaction between independent agents, here called particles, during their search for the
optimum solution using the concept of fitness. The fitness defines how well the position vector of each particle
satisfies the requirements of the optimization problem.
Note that most buildings represent good conductors at 50/60 Hz frequency, and thus can shield the electric field. On
the contrary, these buildings are almost transparent to magnetic fields [3]. Based on that, only the magnetic field is
minimized here, i.e., the magnetic field value is the fitness function. In fact, when we included both the magnetic
and electric fields in the fitness function, we obtained essentially similar results to that when only the magnetic field
is considered.
A population (swarm) size of about 30 is suitable for many problems. Although 36 particles worked properly in this
paper, 49 were chosen since the execution time of the computer program is a fraction of a second. The specific
values of 36 and 49 are dictated by the way we wrote the code since nested do-loops with equal number of steps
were used for incrementing the x and y positions. Each particle remembers its personal best position found (called
its local best) and also knows the best position found by the swarm (called the global best). The x and y components
of the velocity and the position represented by the x, y coordinates, for each particle m, are updated by the following
equations [13]:
t t 1 t t t 1 t t t 1
mn,x mn,x 1 n1 mn,x mn 2 n2 n,x mn
t t 1 t
mn mn mn,x
t t 1 t t t 1 t t t 1
mn,y mn,y 1 n1 mn,y mn 2 n2 n,y mn
t t 1 t
mn mn mn,y
v w v c U (p x ) c U (g x )
x x t (v )
v w v c U (p y ) c U (g y )
y y t (v )
(1)
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
20
where superscripts t and t-1 are time indices of the current and the previous iterations, Un1 and Un2 are two different
uniformly distributed random numbers in the interval {0,1}, w is the “inertial weight” in the range {0,1}, and pmn, gn
are the personal and global best positions (the subscripts x, y refer to the x and y components), respectively. The
parameters c1 and c2 are scaling factors of local and global bests; a value of 2 is a good choice for both parameters
[17]. The subscript m is the particle number in the swarm while n indicates the parameter to be optimized, and the
time-step Δt is usually chosen to be one. In this paper, reflecting walls are used as boundary conditions; when a
particle reaches the boundary, it is reflected back as shown in Fig. 1.
Fig. 1: Particles are looking for a minimum field value with “reflecting walls”.
Since PSO is a stochastic optimization method, each trial would give a somewhat different solution. Our results
represent the best obtained solutions for each configuration analyzed. We have reported the best solution for each
case after making at least 100 trials using different random seeds.
3. SOLUTION ALGORITHM
The following algorithm minimizes the magnetic field under overhead transmission lines.
I. Specify the constraints of the problem: minimum spacings between conductors, and limits of the region in
which the particles will search for suitable arrangement of conductors (see Fig. 1).
II. Distribute the particles (different arrangements of conductors) in the selected region, specify a time step for
particle movement (here unity), initialize the population with a random velocity (v) vector (here zero initial
velocity), and initialize the stop criterion with a value much smaller than 0.40 μT (here 0.01 μT). Specify the
maximum number of iterations that should not be exceeded.
III. Evaluate the fitness function (here the magnetic field value) for each particle.
IV. If the magnetic field value < the personal best value, then replace the personal best value by the new magnetic
field value.
V. If the magnetic field value < the global best value, then replace the global best value by the new magnetic field
value.
VI. If the fitness is ≤ the stop criterion or maximum number of iterations is reached, then stop; a solution is found.
Otherwise, update position and velocity of particles according to (1) (c1=c2=2 and w=0.7), and go to step 3.
4. MAGNETIC FIELD MODEL
The frequency of the power system (50/60 Hz) is small enough that the magnetic and electric fields in air can be
considered independent. The magnetic fields associated with electric power transmission lines are readily predicted
using mathematical equations given line load data and wire configuration [18]. The magnetic field of overhead high
voltage lines can be found by superimposing the individual contributions of the phase conductors taking into
Reflecting walls
Upper limit for line height
Lower limit of clearance to ground
Within this
region,
particles are
looking for
minimum
field value
Upper limit for line width
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
21
account the earth return currents. The geometry considered to evaluate the magnetic field at (xj, yj) due to the phase
conductor at (xi, yi) taking into account the complex image at (xi’, yi’) is illustrated in Fig. 2.
Fig. 2: Geometry to find the magnetic field at the point (xj, yj) due to the phase conductor at (xi, yi) taking into account the
complex image at (xi’, yi’).
To take into account return currents in the expression of the magnetic field it is necessary to start from the mutual
impedance presented by [19]. The magnetic field Hj (fitness function in this paper) at the point (xj, yj) is obtained by
considering the contribution of all N phase conductors:
Η
j
4N N
i iij ij'
i iij ij
1 2u 1 u '
2 r 2 r' 3 r (2)
where
2 2 ' 2 2
ij j i j i ij j i j i
j ii j i j i j'
ij x y ij x y' '
ij ij ij ij
2j ( j ), r (x x ) (y y ) ,r (x x ) (y y )
2y y
y y x x x xu u u ,u u u
r r r r
where σ, ε, μ are conductivity, permittivity, permeability of the earth, respectively, and ω is angular frequency. Ii is
the phase current, and ux, uy are the unit vectors along the x and y axes. Note that in (2), the first term is the
contribution of the line conductors whereas the second term is the contribution of the line images. The magnetic
field density is B= μH, and its magnitude of B0 is:
2 2
0 0x 0yB B B (3)
where B0x and B0y are the amplitudes in the x and y directions.
5. ELECTRIC FIELD MODEL
For the electric field computation, the earth effect is represented by image charges located below the conductors at a
depth equal to the conductor height [20]. The phase capacitance C in µF/km (considering three phase conductors
with phase-to-phase distances of D12, D13, D23) is calculated as [21]:
Field point
(xj ,yj)
rij
rij’
Line conductor
(xi ,yi)
yi+yj+2/γ
Imag{yi+yj+2/γ }
Imaginary
axis
y
x
Real{yi+yj+2/γ}
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
22
1/ 3
12 23 31
1C , GMD D D D
18 (GMD/ r)
ln (4)
where r is the conductor radius and GMD is the geometric mean distance (equivalent conductor spacing). Then, the
electric field at (x,y) due to a line conductor at (x0,h) is:
y 0 x y 0 x
2 2 2 2
0 0 0
2(y h)u 2(x x )u 2(y h)u 2(x x )uCVE(x,y)
4 (y h) (x x ) (y h) (x x )
(5)
where V is the phase voltage. Note that in (5), the first term is the contribution of a line conductor whereas the
second term is the contribution of the line image. The total electric field is the superposition of the fields from all
conductors.
6. RESULTS
This study is focused on minimizing the magnetic field of single circuit and double circuit configurations of 132 kV
Condor type transmission lines. However, the algorithm in this paper can deal with other transmission lines voltages.
In order to verify the validity of equations and computer programs, the computed magnetic fields are compared with
measured fields at a height of 1 m above the surface of the ground. For each case analyzed, two cases of IEC-71
standards were applied, first, ignoring the effects of wind and ice where minimum spacing between phases is 1.1 m,
and second, the practical case which considers the effects of wind and ice where minimum spacing between phases
is 3.5 m. The optimized solutions offer reduced ROW widths. The heights of the optimized and unoptimized lines
were kept almost the same, since increasing line height would automatically decrease fields near the surface of the
earth. The execution time of each simulated case is less than one second on the computer used (Genuine Intel(R)
CPU T2300 @ 1.66 GHz, 1.49 GB RAM) and the number of iterations range is 20 to 200. The electric field is also
computed for the transmission line before and after minimizing the magnetic field. The following examples are
intended to show the validity and accuracy of the presented method.
Example 1: Single Circuit Horizontal Line
The horizontal transmission line distances are shown in Fig. 3. The mean current in the conductors at the moment of
the measurements was 482 A (approximately 60% of its full load value) with a light unbalance between phases (485,
472, and 488 A for the phases A, B, and C, respectively) [3]. Fig. 4(a) shows the calculated magnetic field profile
under the line, where the maximum magnetic field for the existing line is 7.6 μT which is very close to the measured
value 7.36 μT as illustrated in Table 1. Some relative error values in the table exceed 10% due to the corresponding
small field values. So the absolute errors are calculated to show that error is actually small.
Table 1: Calculated and measured magnetic flux density B in μT at y= 1 m under existing unoptimized 132 kV overhead
horizontal line with 485,472, and 488 A in each phase.
Distance (m) from
line center Measured B [3] Calculated B Relative Error % Absolute Error
-50 0.51 0.45 11.76 0.06
-40 0.79 0.71 10.12 0.08
-30 1.36 1.2 11.76 0.16
-20 2.6 2.5 3.84 0.1
-15 3.79 3.8 0.26 0.01
-10 5.25 5.5 4.76 0.25
-5 6.81 7 2.79 0.19
0 7.36 7.6 3.26 0.24
5 7.06 7.2 1.98 0.14
10 5.64 5.8 2.83 0.16
15 3.97 4.09 3.02 0.12
20 2.66 2.78 4.51 0.12
30 1.48 1.4 5.4 0.08
40 0.84 0.84 0 0
50 0.59 0.56 5.08 0.03
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
23
Table 2: Data extracted from simulations and measurements of single circuit horizontal line.
Horizontal line Existing line Optimum with wind &
ice effects
Optimum without wind
& ice effects
Maximum B 7.6 μT 4.37 μT 1.5 μT
ROW width 114 m 72 m 38 m
Maximum E Field 1.9 kV/m 1.18 kV/m 0.48 kV/m
7.8 m 7.8 m
12.12 mphase A phase B phase C
y
x
(a) Existing
3.5 m 3.5 m
12.12 m
phase A phase B phase C
y
x
(b) Optimized line with wind and ice effects
1.1 m 1.1 m
12.12 m
phase A phase B phase C
y
x
(c) Optimized line with wind and ice effects neglected
Fig. 3: Example 1, conductor arrangements of 132 kV overhead horizontal line.
The optimum solution when wind and ice effects are ignored gives a maximum value of the magnetic field of 1.5 μT
in Fig. 4(a) which means that the field is decreased by 80% compared with an unoptimized line. When the effects of
wind and ice are taken into account, a 42.5% decrease is obtained. The maximum value of the electric field is 1.9
kV/m for the existing line, but for the new configuration the electric field is decreased by 38 % after optimization
when the effects of wind and ice are considered and by 75% when the effects of wind and ice are neglected as
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
24
-50 0 50-10-20-30-40 10 20 30 400
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
Distance from center in meter
Ele
ctri
c fi
eld
in
KV
/m
shown in Fig. 4(b) and Table 2. Also Table 2 shows thatthe ROW width, for a reference value of 0.4 μT, is
significantly reduced after optimization.
Fig. 4: Example 1, Fields under the horizontal line. Solid curve: before optimization, dashed curve: after optimization for
practical standard, and dotted curve: when wind and ice effect are neglected.
Example 2: Single Circuit Triangular Line
The triangular line distances are shown in Fig 5.
11.6 m
phase A
phase C
phase B
1.6 m
2.7 m
3.1 m
6.2 m
12.4 m phase A phase C
phase B3.35 m
3.5m
1.75 m
y y
x x
(line center) (line center)
12.53 m phase A phase C
phase B1.23 m
1.1 m
0.55 m
y
x
Tower location
(line center)
-50 -40 -30 -20 -10 0 10 20 30 40 500
2
4
6
8
Distance from center in meter at y=1 m
Mag
neti
c f
lux
den
sity
in
mic
rote
sla
(a) Magnetic flux density (b) Electric field
(a) Existing
(b) Optimized line with wind and ice effects
(c) Optimized line with wind and ice effects neglected
Fig. 5: Example 2, Conductor arrangement for overhead triangular 132 kV line.
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
25
The current at the moment of measurements was 35.5 A in each phase [3]. The maximum measured magnetic field
for the unoptimized line was 0.31 μT. The computed values are very close to measured values as shown in Table 3.
After PSO is applied, the maximum value of the magnetic field is reduced to 0.08 μT as shown in Fig 6(a) when
wind and ice effects are neglected. When effects of wind and ice are considered, the magnetic field is reduced by
34% (the maximum value is 0.205 μT).
Fig. 6: Example 2, Fields under the triangular line.
As can be seen in Fig 6(b), the maximum value of the electric field is 1.28 kV/m before optimization and the field
profile is not symmetrical since the conductor distribution is not symmetrical. After the redistribution of conductors,
the electric field is reduced to 0.78 kV/m when wind and ice effects are considered (decreased by 39 %), and the
new profile is symmetrical due to the symmetrical configuration of the line. The electric field will be 0.4 kV/m when
the effects of wind and ice are neglected (decreased by 69%). Although ROW width is zero in this example,
optimized solutions have considerably lower values of magnetic fields as shown in Table 4. Table 3: Calculated and measured magnetic flux density in μT at y=1 m under unoptimized overhead triangular line with 35.5 A
in each phase.
Distance (m) from line
center Measured B [3] Calculated B Relative Error %
-40 0.02 0.02 0
-35 0.03 0.03 0
-30 0.04 0.04 0
-25 0.05 0.05 0
-20 0.07 0.07 0
-15 0.1 0.1 0
-10 0.15 0.15 0
-5 0.22 0.22 0
0 0.31 0.31 0
5 0.29 0.29 0
10 0.23 0.23 0
15 0.16 0.15 6.25
20 0.1 0.1 0
25 0.07 0.07 0
30 0.05 0.05 0
35 0.04 0.04 0
40 0.03 0.03 0
-50 0 5010 20 30 40-10-20-30-400
0.05
0.1
0.15
0.2
0.25
0.3
0.35
Distance from center in meter at y=1 m
Mag
neti
c f
lux
den
sity
in
mic
rote
sla
-50 0 50-10-20-30-40 10 20 30 400
0.2
0.4
0.6
0.8
1
1.2
1.4
Distance from center in metre at y=1 m
Ele
ctri
c fi
eld
in
kV
/m
(a) Magnetic flux density (b) Electric field
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
26
Table 4: Data extracted from simulations and measurements of the triangular line.
Triangle line Existing line Optimum with wind &
ice effects
Optimum without wind
& ice effects
Maximum B 0.31 μT 0.205 μT 0.07 μT
Maximum E Field 1.28 kV/m 0.78 kV/m 0.4 kV/m
Example 3: Double Circuit with Phases in Parentheses
The double circuit overhead line (one at each side of the tower) with phases in parentheses is shown in Fig. 7.
9.12 m
phase A
phase B
phase C
2.8 m
3.3 m
3 m
Circuit 1 Circuit 2
4 m
4 m
x
line center
(a) Existing line (line is symmetric).
9.78 m
phase A
phase B
phase C
8.2 m
6 m
3.58 mCircuit 1 Circuit 2
4 m
3.94 m
y
x
line center
(b) Optimized line with wind and ice effects considered (line is symmetric)
11.8 m
phase A
phase B
phase C
1.8 m
2 m
1.2 m
Circuit 1 Circuit 2
1.7 m
1.5 m
y
x
line center
(c) Optimized line with wind and ice effects neglected (line is symmetric)
Fig. 7: Example 3, conductor arrangements for an overhead 132 kV line with phases in parentheses, with 91 and 104 A.
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
27
The arrangement of the phases (A, B, C) is the same in both circuits and the phase current is 91 A for the left circuit,
and 104 A for the right one. The calculated magnetic field as a function of distance from the center of the line is
shown in Fig 8(a). Table 5 shows computed and the measured values of the magnetic field for the installed un-
optimized line, where the maximum computed value is 1.65 μT. After optimization, the maximum magnetic field is
reduced by 59% and is equal to 0.67 μT when the effects of wind and ice are neglected, while the maximum
magnetic field is reduced by 48% as shown by Fig 8(a) when wind and ice effects are considered.
Fig. 8: Example 3, Fields under the line with phases in parentheses.
Table 5: Calculated and measured magnetic flux density in μT at y=1 m under overhead double circuit line with phases in
parentheses without optimization, with 91 and 104 A.
Distance (m) from
line center Measured [3] Calculated Relative Error %
Absolute
Error
-50 0.09 0.1 11.11 0.01
-40 0.15 0.15 0 0
-30 0.26 0.256 1.53 0.004
-20 0.5 0.49 2 0.01
-15 0.74 0.72 2.7 0.02
-10 1.12 1.08 3.57 0.04
-5 1.58 1.517 3.98 0.063
0 1.73 1.65 4.62 0.08
5 1.56 1.58 1.28 0.02
10 1.13 1.13 0 0
15 0.76 0.74 2.63 0.02
20 0.51 0.505 0.98 0.005
30 0.27 0.266 1.48 0.004
40 0.16 0.157 1.87 0.003
50 0.1 0.1 0 0
Table 6: Data extracted from simulations and measurements of the double circuit line with phases in parentheses.
double circuit line Existing line Optimum with wind & ice
effects
Optimum without
wind & ice effects
Maximum B 1.65 μT 0.86 μT 0.67 μT
ROW width 46 m 46 m 22 m
Maximum E Field 6.3 kV/m 2.8 kV/m 2.9 kV/m
-50 0 50-10-20-30-40 10 20 30 400
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
Distance from center in meter at y=1 m
Mag
neti
c f
lux
den
sity
in
mic
rote
sla
-50 0 50-10-20-30-40 10 20 30 400
1
2
3
4
5
6
7
Distance from center in meter at y=1 m
Ele
ctr
ic f
ield
in
kV
/m
(a) Magnetic flux density (b) Electric field
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
28
Although the configuration is symmetric, the magnetic field profile is not symmetric due to the different currents in
the circuits. The maximum value of the electric field is 6.3 kV/m. It decreases to 2.8 kV/m when the conductors are
rearranged for the case when wind and ice effects are considered, and to 2.9 kV/m when wind and ice effects are
neglected as shown in Table 6 and Fig. 8(b). ROW width is significantly reduced after optimization when wind and
ice effects are neglected.
Example 4: Double Circuit Horizontal Line
Consider two lines in a horizontal arrangement with two conductors per phase (bundled) as shown in Fig 9.
5 m 5 m
15.6 m
phase A
phase B phase C5 m 5 m
13.2 m
phase A phase B phase C0.5 m
29 m
y
x
line center
24 m
(a) Existing Line
3.8 m 4.1 m
15.55 m
phase A phase B phase C
4.1 m 3.8 m
15.55 m
phase Aphase Bphase C
11.9 m
y
x
line center
7.8 m
(b) Optimized line with wind and ice effects considered.
1.6 m 1.1 m
15 m
phase B phase C
1.1 m 1.6 m
15 m
phase Aphase Bphase C
4.9 m
y
x
line center
3.8 m
(c) Optimized line with wind and ice effects neglected.
Fig. 9: Example 4, conductor arrangement of the overhead double circuit horizontal 132 kV line with 246 and 226 A.
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
29
At the moment of measuring the magnetic field, mean currents of 246 A, 226 A circulated through the left line
and right line conductors, respectively [3]. The magnetic field of the installed line has a maximum value 2.15 μT
as shown in Fig 10(a). Table 7 compares calculated with measured magnetic field values at different distances
from the center. Note that the sequences of the new lines are A,B,C and C,B,A as shown in Fig 9. Fig. 10(a)
shows that the magnetic field is 0.47 μT (reduced by 78%) when wind and ice are neglected, and 1.85 μT
(reduced by 14%) when wind and ice are considered. The bundle contributed a very small value of around 10-12
μT when the field value is around 1 μT. Therefore modeling the bundle did not affect the magnetic field value.
The nonsymmetrical conductors caused a nonsymmetrical field distribution under the unoptimized line as shown
in Fig 10. The maximum value of the electric field of the existing line is 3.88 kV/m, while it is 4.3 kV/m for the
optimized line when wind and ice effects are considered as shown in Table 8. The increase in the electric field
may be attributed to the increase of the coupling capacitance. But when wind and ice are neglected the field
decreases to 1.43 kV/m as shown in Fig 10(b). ROW width is significantly reduced after optimization.
Fig. 10: Example 4, calculated magnetic flux density under the double-circuit horizontal line.
Table 7: Calculated and measured magnetic flux density in μT at y=1 m under double circuit horizontal line without optimization,
with 246 and 226 A.
Distance (m) from
line center Measured B [3] Calculated B Relative Error % Absolute Error
-60 0.45 0.448 0.44 0.002
-55 0.56 0.57 1.78 0.01
-50 0.75 0.75 0 0
-45 0.99 0.99 0 0
-40 1.29 1.3 0.77 0.01
-35 1.57 1.57 0 0
-30 1.7 1.63 4.11 0.07
-25 1.44 1.38 4.16 0.06
-20 0.98 0.91 7.14 0.07
-15 0.51 0.444 12.94 0.066
-10 0.47 0.453 3.61 0.017
-5 1.04 1.03 0.96 0.01
0 1.72 1.75 1.74 0.03
5 2.1 2.15 2.38 0.05
10 2.04 2.1 2.94 0.06
15 1.63 1.63 0 0
20 1.2 1.176 2 0.024
25 0.85 0.84 1.17 0.01
30 0.63 0.62 1.58 0.01
35 0.48 0.475 1.041 0.005
40 0.38 0.373 1.84 0.007
-100 -50 0 50 100-25-75 25 750
0.5
1
1.5
2
2.5
Distance from center in meter at y=1 m
Mag
neti
c f
lux
den
sity
in
mic
rote
sla
-50 0 50-10-20-30-40 10 20 30 400
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Distance from center in meter at y=1 m
Ele
ctr
ic f
ield
kV
/m
(a) Magnetic flux density (b) Electric field
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
30
Table 8: Data extracted from simulations and measurements of double circuit horizontal line.
Vertical double circuit
line Existing line
Optimum with wind and
ice effects
Optimum without wind
and ice effects
Maximum B 2.15 μT 1.85 μT 0.47 μT
ROW width 101 m 53 m 10 m
Maximum E Field 3.88 kV/m 4.3 kV/m 1.43 kV/m
7. DISCUSSION
The authors have conducted extensive simulations on various configurations. Due to page limitations, only the
above examples are presented. General trends extracted from these simulations are listed below, although it does not
necessarily apply to all other cases.
1) For single circuit lines, when the distances between conductors are decreased the fields are also decreased due
to the cancellation between the field components. The other factor that affects the magnetic field is the current
that flows in the conductors; it is directly proportional to the magnetic field where higher current produces a
higher magnetic field. Therefore PSO gives the solution at a minimum distance between phases. This means
that for single circuit lines, it is not necessary to use PSO to get the minimum fields but we need only to choose
minimum distances between phases in the design of a transmission line.
2) For double circuit lines, the results showed that decreasing the distance does not necessarily minimize the
magnetic field. Therefore optimization is necessary to minimize the field.
3) For both single and double circuit lines, the height of the overhead high voltage line is inversely proportional to
the magnetic and electric field values. Consequently, increasing the line height decreases the field on the
ground. The effect of bundling can be neglected in the magnetic field calculations where the contribution of
bundling is about 10-12
μT when the field value is around 1 μT.
8. CONCLUSIONS
Particle swarm optimization is successfully applied to reduce the magnetic field under 132 kV overhead high
voltage transmission lines. The ROW width can be decreased for both single and double circuit lines and decreases
more when the wind and ice effects are neglected. The magnetic field under overhead transmission line is a strong
function of distance like any other source and it is also a function of electric current, i.e., high current implies high
magnetic field. The algorithm presented in this paper can be used for higher voltages, such as 400 kV, by adjusting
the minimum clearance between phases in addition to the transmission line height.
REFERENCES:
[1] J. Tang, and R. Zeng, “Influence of magnetic field of AC transmission lines on parallel DC transmission
systems”, IEEE International Symposium on Electromagnetic Compatibility, 1, 14-18 Aug. 2006, USA.
[2] N. Wertheimer and E. Leeper, “Electrical Wiring Configurations and Childhood Cancer”, American Journal of
Epidemiology, March 1979, vol. 109, pp. 273 - 284.
[3] C. Garrido, and A. Otero, "Low frequency magnetic fields from electrical appliances and power lines”, IEEE
Transactions on Power Delivery, 18, 1310-1319, 4 October 2003.
[4] IARC, “Static and extremely low-frequency (ELF) electric and magnetic fields: IARC monographs on the
evaluation of carcinographic risks to humans,” International Agency for Research on Cancer, Lyon, France,
Vol. 80, 2002.
[5] C. Sage, and D. O. Carpenter, “Public health implications of wireless technologies”, Pathophysiology, Volume
16, Issue 2, Pages 233-246, August 2009.
IJRRAS 4 (1) ● July 2010 Al-Salameh & al. ● Reducing Magnetic Fields from Overhead High Voltage Transmission Lines
31
[6] R. R. Neutra, V. DelPizzo, and G. M. Lee, “An Evaluation of the Possible Risks From Electric and Magnetic
Fields (EMFs) from Power Lines, Internal Wiring, Electrical Occupations and Appliances,” California EMF
Program, Oakland, California, USA, June 2002.
[7] M. Amore, E. Menghi, and M. S. Sarto, “Shielding techniques of the low-frequency magnetic field from cable
power lines”, IEEE International Symposium on Electromagnetic Compatibility, 1, 203 - 208 , 18-22 Aug.
2003, USA.
[8] B. Clairmont, and R. Lordan, “3-D modeling of thin conductive sheets for magnetic field shielding calculations
and measurements”, IEEE Transactions on Power Delivery, 14, 1382-1393, 4 October 1999.
[9] General Electric Company, “Transmission Line Reference Book – 345 kV and above”, second edition, Palo
Alto, Electric Power Research Institute, 1982, California.
[10] C. Durkin, R. Fogarty, T. Halleran, D. Mark and A. Mukhopadhyay, “Five years of magnetic field
management”, IEEE Transactions on Power Delivery, 10, 219-228, January 1995.
[11] "TenneT Presents New Innovative Pylon Design," Transmission & Distribution World Magazine, Apr 24, 2008.
[12] G. Filippopoulos, D. Tsanakas, G. Kouvarakis, J. Voyatzakis, M. Amman, and K. O. Papailiou, "Optimum
conductor arrangement of compact lines for electric and magnetic field minimization- calculations and
measurements,"
[13] Website: http://us.pfisterer.com/download.php?dkat=13&coc=11
[14] J. Robinson, and R. Yahya,”Particle swarm optimization in electromagnetic,” IEEE Trans. on Antennas and
Propagation, 52, 397-407, 2 February 2004.
[15] C. Chen, and F. Ye, “Particle swarm optimization algorithm and its application to clustering analysis”, IEEE
International Conference on Networking, Sensing and Control, 789 – 794, 2, 2004, USA.
[16] J. Kennedy, and R. C. Eberhart, “Particle swarm optimization,” Proc. IEEE Int. Conf. Neural Networks,
Piscataway, NJ, 1995; 1942–1948.
[17] G. Ciuprina, D. Ioan, and I. Munteanu. “Use of intelligent-particle swarm optimization in electromagnetics”,
IEEE Trans. Magn, 2002 Mar; 38(2): 1037-1040.
[18] R. C. Eberhart, Y. Shi, “Particle swarm optimization: developments, applications and resources”, 2001 Congr.
Evolutionary Computation 2001, USA.
[19] J. D. Glover, and M. S. Sarma, “Power System Analysis and Design,” Fourth Edition, PWS Publishing
Company, 2007, Boston.
[20] Y. Wang, and S. Liu, “A review of methods for calculation of frequency-dependent impedance of overhead
power transmission lines,” Proc. Natl. Sci. Roc(A), 25, 6, 2006, 329-338. USA.
[21] W. Hayt, and J. Buck, “Engineering Electromagnetics”, Seventh Edition, McGraw Hill, 2006, USA.
[22] H. Saadat,” Power system analysis”, Second Edition, McGraw Hill, 2002, USA.