Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. ·...
Transcript of Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. ·...
![Page 1: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/1.jpg)
29 January 2021
Modelling Approach to Certify the Accuracy Class of Current Transformers (CTs) and Voltage Transformers (VTs)
Alexander Dierks, Alectrix (Pty) Ltd
SAIEE Presentation
Using a Modelling Approach to Certify the Accuracy Class of Metering Class Current Transformers (CTs) and Voltage Transformers (VTs) According to IEC60044 / IEC61869c
![Page 2: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/2.jpg)
Presentation Overview
1) Background / Introduction
2) Mathematical model of a current transformer
3) Test solution to characterize a CT model: OMICRON CT Analyzer
4) Case studies of Class M and Class P CTs
5) Mathematical model of a voltage transformer
6) Test solution to characterize a VT model: OMICRON VOTANO 100
7) Case studies of Class M and Class 3P VTs
8) Certification and calibration of calibration equipment
9) Summary and conclusion
10) Questions and discussion
Page 2© OMICRON
![Page 3: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/3.jpg)
NRS 057:2009 / SANS 474:2009
> “Subsequent recalibration of metering system components requires the same
full laboratory process as for new components. On-site testing and calibration
is acceptable for this purpose as long as the requirements of this code of
practise are complied with” (NRS 057:2009; Ch. 4.4.3.4)
> “Metering system components” consists of the energy meter(s) as well as the
instrument transformer(s).
> Focus of this presentation is the verification of the current transformers (CTs)
and voltage transformer (VTs).
> “Recalibration” means ‘comparison’ or ‘verification of accuracy’
> Calibration of inductive CTs - IEC 60044-1 / IEC 61869-2:Accuracy verification at 5%, 20%, 100% and 120% Inom for 25% and 100% rated burden.
> Calibration of inductive VTs - IEC 60044-2 / IEC 61869-3:Accuracy verification at 80%, 100% and 120% Vnom for 25% and 100% rated burden –
for all other windings unloaded AND fully loaded.
Page 3© OMICRON
Customer Load CT & VT Accuracy Verification Interval
> 10MVA class 0.2 5 years
100kVA to 10MVA class 0.5 10 years
<100kVA class 1 20 years
![Page 4: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/4.jpg)
Conventional Verification by Primary Injection
Page 4© OMICRON
![Page 5: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/5.jpg)
Page 5© OMICRON
> Current Transformers (CT)
![Page 6: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/6.jpg)
Ideal Current Transformer
Page 6© OMICRON
1
2
2
121
I
I
n
nü ===Losses are not considered:
Connected burden is not considered
![Page 7: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/7.jpg)
Real Current Transformer (Detailed Electrical Model)
Parameters to determine:
1) RCT – secondary winding resistance
2) Non-linear iron losses:
Hysteresis losses RH, magnetizing inductance Lm and the eddy losses Reddy.
3) Ideal transformation ratio Np/Ns
Page 7© OMICRON
![Page 8: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/8.jpg)
Accuracy Graph for a Metering CT
Page 8© OMICRON
Beware of underburdening
a metering CT!
![Page 9: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/9.jpg)
Accuracy Graph for a Protection CT
Page 9© OMICRON
Beware of overburdening
a protection CT!
![Page 10: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/10.jpg)
> Portable, compact size and low weight (< 8 kg)
> Field calibration of CTs up to the 0.1 accuracy class
> Fast testing time (<1min per core)
> Automatic result assessment as per IEC 60044-1
and IEC61869-2 standards directly after the test
> Simulation and re-assessment with changed
CT parameters
> Safety: max. 120 V output voltage
> Reliable: high noise immunity for on-site testing
> Multi-tap CTs can be tested with
CT SB2 extension box (up to five taps)
Page 10© OMICRON
OMICRON CT Analyzer for CT Calibrations
![Page 11: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/11.jpg)
Case Study 1: Post Type CTs
Page 11© OMICRON
![Page 12: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/12.jpg)
Special applications: Bushing Type CTs
Page 12© OMICRON
Coax measurement cables
![Page 13: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/13.jpg)
Special applications: GIS
Page 13© OMICRON
Utility line
disconnected
Gas-insulated busbar Earthing switch
Circuit breaker
Burden
3 m max.
Coax measurement cables
100 m max.
![Page 14: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/14.jpg)
Page 14© OMICRON
Case Study 1: 66kV CT: 1200A:1A, 10VA, Class 0.2
![Page 15: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/15.jpg)
Page 15© OMICRON
-1.0000
-0.8000
-0.6000
-0.4000
-0.2000
0.0000
0.2000
0.4000
0.6000
0.8000
1.0000
0.00 50.00 100.00 150.00 200.00 250.00
Cu
rre
nt
rati
o e
rro
r [%
]
I/Ipn [%]
Current ratio error in % at % of rated current at rated burden (10.00 VA)
10.000 VA
5.000 VA
2.500 VA
1.250 VA
Limits
Limits
Case Study 1: 66kV CT: 1200A:1A, 10VA, Class 0.2
![Page 16: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/16.jpg)
Page 16© OMICRON
Case Study 1: 66kV CT: 1200A:1A, 10VA, Class 0.2
![Page 17: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/17.jpg)
Case Study 2: 100A:1A, 10VA, Class 1
Page 17© OMICRON
![Page 18: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/18.jpg)
Page 18© OMICRON
Case Study 2: 100A:1A, 10VA, Class 1
![Page 19: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/19.jpg)
Page 19© OMICRON
Case Study 2: 100A:1A, 10VA, Class 1
![Page 20: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/20.jpg)
Case Study 3: 300:1, 15VA Protection Core
Page 20© OMICRON
![Page 21: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/21.jpg)
Page 21© OMICRON
Case Study 3: 300:1, 15VA Protection Core
0.01
0.10
1.00
10.00
100.00
1000.00
0.00 0.00 0.001 0.01 0.10 1.00 10.00
Vo
ltag
e [
V]
Ie [A]
Excitation curve
X1_X2_1
![Page 22: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/22.jpg)
Page 22© OMICRON
Case Study 3: 300:1, 15VA Protection Core
![Page 23: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/23.jpg)
Page 23© OMICRON
> Voltage Transformers (VT)
![Page 24: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/24.jpg)
Real Voltage Transformer (Detailed Electrical Model)
Parameters to determine:
1) Secondary winding resistance R1 and R2
2) Short circuit impedances yielding Rp”, Xp”, X1 and X2
3) Non-linear iron losses Rm and Xm
Page 24© OMICRON
![Page 25: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/25.jpg)
Page 25© OMICRON
Safe area
High-voltage
environment
OMICRON VOTANO 100 for VT Calibrations
> Portable, compact size and low weight (8kg + 7kg)
> Field calibration of VTs up to the 0.1 accuracy class
> VTs with up to FIVE secondary windings
> Software-guided test procedure ensures short testing time (<20min)
> Automatic result assessment as per IEC 60044-2 and IEC61869-3
standards directly after the test
> Simulation and re-assessment with changed VT parameters
> Safety: Local isolation between high voltage and test equipment
Double action to start test; Emergency OFF button
![Page 26: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/26.jpg)
Page 26© OMICRON
Case Study 4:
Two Winding 33kV:110V, 30VA; Class 0.5 / 3P
![Page 27: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/27.jpg)
Page 27© OMICRON
Case Study 4:
Two Winding 33kV:110V, 30VA; Class 0.5 / 3P
![Page 28: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/28.jpg)
Page 28© OMICRON
Case Study 4:
Two Winding 33kV:110V, 30VA; Class 0.5
![Page 29: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/29.jpg)
Case Study 4:
Two Winding 33kV:110V, 30VA; Class 0.5
Page 29© OMICRON
![Page 30: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/30.jpg)
Page 30© OMICRON
Case Study 4:
Two Winding 33kV:110V, 30VA; 3P winding
![Page 31: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/31.jpg)
Case Study 4:
Two Winding 33kV:110V, 30VA; 3P winding
Page 31© OMICRON
![Page 32: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/32.jpg)
Case Study 5:
Two Winding 66kV:110V, 100VA; Class 0.2 / 3P
Page 32© OMICRON
![Page 33: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/33.jpg)
Page 33© OMICRON
Case Study 5:
Two Winding 66kV:110V, 100VA; Class 0.2 / 3P
![Page 34: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/34.jpg)
Page 34© OMICRON
Case Study 5:
Two Winding 66kV:110V, 100VA; Class 0.2 / 3P
![Page 35: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/35.jpg)
Page 35© OMICRON
Case Study 5:
Two Winding 66kV:110V, 100VA; Class 0.2 / 3P
![Page 36: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/36.jpg)
Page 36© OMICRON
> Certifications
![Page 37: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/37.jpg)
Certified Accuracy of Calibration Equipment
Page 37© OMICRON
![Page 38: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/38.jpg)
Summary
> Regular and accurate verification of instrument transformers, as required by the Code of
Electricity Metering, can conveniently be conducted in the field by utilizing a modelling
verification, instead of following a conventional primary injection calibration.
> The modelling approach consists of accurately characterizing the electrical model of a CT
(or VT), then calculating the amplitude and phase angle accuracy of the device under
test for the required burden ‘connected’ to the CT (or VT) and ‘injecting’ the required
primary current (or primary voltage).
> Calibration of inductive CTs - IEC 60044-1 / IEC 61869-2:Accuracy verification at 5%, 20%, 100% and 120% Inom for 25% and 100% rated burden.
> Calibration of inductive VTs - IEC 60044-2 / IEC 61869-3:Accuracy verification at 80%, 100% and 120% Vnom for 25% and 100% rated burden –for all other windings unloaded AND fully loaded.
> Case studies for various metering and protection CTs (and VTs) – with both passed and
failed results - have been presented and results discussed.
> The PTB (and other certification institutes) have certified the accuracy of the modelling
verification approach of instrument transformers.
Page 38© OMICRON
![Page 39: Using a Modelling Approach to Certify the Accuracy Class of … · 2021. 2. 4. · alex@alectrix.co.za SAIEE Presentation Using a Modelling Approach to Certify the Accuracy Class](https://reader035.fdocuments.net/reader035/viewer/2022071512/6132dabddfd10f4dd73ab70d/html5/thumbnails/39.jpg)
Page 39© OMICRON
Thank You for Your Attention!