FEH352a-1

USER’S MANUAL <HARDWARE>Additional Specifications

TYPE: UG520H- UG420H- UG320H- UG221H- UG220H-

FUJI UG 20 SERIES PROGRAMMABLE OPERATION DISPLAY

Page 2: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

Preface

Thank you very much for purchasing the FUJI UG520/420/320/221/220 Series Programmable

Operation Display (POD) (hereinafter called “UG 20 Series” or “POD”).

This manual describes only the functions newly added to the UG00S-CW Ver. 2.50 (Ver.

2.5.0.0).

Please read this manual together with the HARD WARE Volume of the UG 20 Series

User’s Manual (FEH352).

UG Series

[ Notes ]

(1) No part of this manual may be reproduced in any form without prior permission of thepublisher.

(2) The contents of this manual, including the specifications, are subject to change forimprovement without notice.

(3) This manual was prepared with utmost care. However, if you find any ambiguity, errors, etc.,please contact any of our sales offices that are listed at the end of this manual. In so ding,please tell the manual number shown on the cover of this manual.

Page 3: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

ContentsThe following items correspond to those in the HARD WARE Manual (document No. FEH352).

Chapter 1 Hardware Specification1.1 Setting of Dip Switches ....................................................... 1-1

1.2 Connection .......................................................................... 1-2

Chapter 2 Connection to Link Units2.1 Koyo PLC............................................................................. 2-1

2.2 Allen-Bradley PLC (SLC500 series, Micro Logix 1000) .............. 2-6

2.3 GE Fanuc PLC (90 series SNP-X)......................................... 2-10

2.4 SIEMENS PLC (S7-300/400MPI) ......................................... 2-12

2.5 KEYENCE PLC • 1 (KZ series) ............................................. 2-14

2.6 KEYENCE PLC • 2 (KV series) ............................................. 2-16

2.7 LG PLC ............................................................................. 2-18

2.8 SAIA PLC ........................................................................... 2-23

2.9 MOELLER PLC ................................................................... 2-25

2.10 Telemecanique PLC ........................................................... 2-26

2.11 Automationdirect PLC ....................................................... 2-28

Page 4: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

1-1

Setting of Dip Switches (DIPSW)

Setting of Terminal Resistance

• Set DIPSW 8 ON in case of connecting Multi Link 2 or Temperature Controller of RS-485 and a card

recorder (UG00P-MR) and serial extension I/O (UG00P-U2) to MJ2.

This dip switch is invalid for UG220. Keep DIPSW 8 OFF.

• Set DIPSW 7 ON in case of connecting POD to PLC connection of RS-422/485.

• Set DIPSW 6 ON in case of connecting Multi Link 2 or Temperature Controller of RS-485 and a card

recorder (UG00P-MR) and serial extension I/O (UG00P-U2) to MJ 1.

Setting of Memory Extension 2 (This dip switch is invalid for UG220. Keep DIPSW 1 OFF.)

• Set DIPSW 1 ON in case of selecting “Memory Extension 2.”

(Refer to “Operation Instruction for UG00P-D4, UG221P-D4 (Extension Memory).”)

Keep DIPSW 2, 3, 4 and 5 (not used) OFF.

1.1 Setting of Dip Switches

ON

1 2 3 4 5 6 7 8

Terminal resistance of MJ2 (modular jack 2 : invalid for UG220)

RD terminal resistance of pin No. 24 and 25

Terminal resistance of MJ1(modular jack 1)Not used

Memory Extension 2(invalid for UG220)

Chapter 1 Hardware Specification

1.1 Setting of Dip Switches

Page 5: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

1-2

1 : 1 Link Communication

One POD and one PLC are connected.

1 : n Link Communication (Multi-drop)

One POD and multiple PLCs are connected. (n = 1 to 32)

Available PLC for multi-drop communication

run

stop

run

stop

run

stop

run

stop

POD

PLC1 PLC2 PLC3 PLCn

RS-422/485 Maximum length 500m(from POD to the last PLC)

1.2 Connection

run

stop

PODPLC

RS-232C or RS-422(RS-485)

Manufacturer

FUJI

MITSUBISHI

OMRON

SHARP

HITACHI

MATSUSHITA

YOKOGAWA

YASKAWA

TOYOPUC

Koyo

Allen-Bradley

GE Fanuc

TOSHIBA

SIEMENS

SHINKO

SAMSUNG

KEYENCE

LG

FATEK

IDEC

MODICON

TAIAN

Models

MICREX-F series, FLEX-PC series

AnA/N/U series, QnA series, QnH(Q)series, Net10, FX series(A prt)

SYSMAC C, CV, CQM1, CS1 DNA

JW series, JW100/70H COM Port, JW20/30 COM Port

HIDIC-H

MEWNET

FA500, FA-M3, FA-M3R

Memobus, CP9200SH/MP900

TOYOPUC

SU/SG, SR-T

PLC-5, SLC500, Micro Logix 1000

90 series

T series

S7-200 PPI

SELMART

SPC series, N_plus, SECNET

KZ series, KV series

MASTER-K500 / K1000, MASTER-K xxxS CNET

FACON FB series

MICRO3

Modbus RTU

TP02

Universal Serial

1.2 Connection

Page 6: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

1-3

Signal

Link unit

Signal

Link unit

Signal Pin No.

POD (CN1)

Signal

Link unit

FG

+SD

-SD

+RD

-RD

SG

1

12

13

24

25

7

FG

RDA

RDB

SDA

SDB

SG

FG

RDA

RDB

SDA

SDB

SG

FG

RDA

RDB

SDA

SDB

SG

SD/RD terminal resistance(ON)

* Use twist shielded cable.

Multi-drop Communication (RS-485)

Refer to the PLC manual of each manufacturer for connection.

<E.g.>

The following example describes how one POD is connected to three PLCs made by MITSUBISHI.

See MITSUBISHI’s manual for further details.

1.2 Connection

n : 1 Link Communication (Multi-link2)

Up to 4 units can be connected to one PLC.

* Between a PLC and the POD master station is the same as those for 1:1 communication.

Available PLCs for multi-link2.

As of December 2001, the PLCs supported are as follows. All the PLCs which are usable for 1:1 commu-

nication will be supported.

For the I/F driver, the Multi-Link 2 is supported by the version of 1.100 or later (UG Editor : Version of

2.1.4.0 or later) and as for a POD master station, make sure the hardware version of the unit is as follows.

As for UG221/UG220, any version can be used.

· Analog type : UG520H-V ➞ 4, UG420H-V ➞ 5, UG420H-T ➞ 5, UG420H-S ➞ 4, UG320H ➞ 7

· Matrix type : All version

* The Multi-Link 2 cannot be used with a communication interface unit such as UG03I-T, J, E, C, S, P,

UG02I-T, J, S.

* The Multi-Link 2 cannot be used with Temperature controll network.

PLC

terminal

Communication between the stations : RS-485 (2-wire system) Maximum length: 500 m

(a) (b) (c) (d) (e)

POD master(Local Port 1)

POD slave(Local Port 2)

POD slave(Local Port 3)

POD slave(Local Port 4)

CN1CN1CN1CN1 MJ2

Page 7: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

1-4

<Type> <Calendar>GE Fanuc : 90 series Not providedGE Fanuc : 90 series(SNP-X) Not providedTOSHIBA : T series ProvidedSIEMENS : S5 Not providedSIEMENS : S7 Not providedSIEMENS : S5 UG400 Not providedSIEMENS : TI500/505 ProvidedSIEMENS : TI500/505(UG400) ProvidedSIEMENS : S5 PG port Not providedSIEMENS : S7-300MPI(HMI ADP) Not providedSIEMENS : S7-300MPI(PC ADP) Not providedSAMSUNG : SPC series Not providedSAMSUNG : N_plus ProvidedSAMSUNG : SECNET Depends on the modelKEYENCE : KZ series Not providedKEYENCE : KZ-A500 CPU Port ProvidedKEYENCE : KV series Not providedKEYENCE : KZ24/300 series CPU Not providedKEYENCE : KV10/24 series CPU Not providedKEYENCE : KV700 series CPU ProvidedLG : MASTER-K10/60/200 Not providedLG : MASTER-K500/1000 Not providedLG : LGMKX00S Not providedLG : MASTER-KxxxS CNET Not providedLG : GLOFACNET Not providedFANUC : Power Mate Not providedFATEK AUTOMATION: FACON FB series ProvidedIDEC : MICRO3 ProvidedMODICON : Modbus RTU Depends on the modelYAMATAKE : MX series ProvidedTAIAN : TP02 ProvidedSAIA : PCD ProvidedMOELLER : PS4 Not providedTelemecanique : TSX Micro Not providedAutomationdirect : Direct LOGIC Depends on the modelAutomationdirect : Direct LOGIC(K-Sequence) Depends on the model

<Type> <Calendar>FUJI : MICREX-F series Depends on the modelFUJI : MICREX-SX series ProvidedFUJI : MICREX-SX CPU ProvidedFUJI : FLEX-PC series Depends on the modelFUJI : FLEX-PC CPU Depends on the modelFUJI : FLEX-PC COM ProvidedFUJI : FLEX-PC(T) Depends on the modelFUJI : FLEX-PC CPU(T) Depends on the modelMITSUBISHI : AnA/N/U series Provided MITSUBISHI : QnA series ProvidedMITSUBISHI : ACPU Port ProvidedMITSUBISHI : FX series Depends on the modelMITSUBISHI : QnACPU Port ProvidedMITSUBISHI : QnHCPU Port (A) ProvidedMITSUBISHI : QnHCPU Port (Q) ProvidedMITSUBISHI : FX series(A prt) ProvidedMITSUBISHI : FX2N series Depends on the modelMITSUBISHI : FX1S series ProvidedOMRON : SYSMAC C Depends on the modelOMRON : SYSMAC CV ProvidedOMRON : SYSMAC CS1 ProvidedSHARP : JW series ProvidedSHARP : JW100/70H COM Port ProvidedSHARP : JW20 COM Port ProvidedHITACHI : HIDIC-H ProvidedHITACHI : HIDIC-S10/2 alpha Not provided HITACHI : HIDIC-S10/ABS Not providedMATSUSHITA : MEWNET Depends on the modelYOKOGAWA : FA500 ProvidedYOKOGAWA : FA-M3 ProvidedYOKOGAWA : FA-M3R ProvidedYASKAWA : Memobus Depends on the modelYASKAWA : CP9200SH/MP900 Not providedTOYOPUC ProvidedKOYO : SU/SG Depends on the modelKOYO : SR-T ProvidedKOYO : SR-T(K prt) Not providedKOYO : SU/SG(K-Sequence) Depends on the modelA.B : PLC-5 Not providedA.B : SLC500 ProvidedA.B : Micro Logix 1000 Not provided

(b) (c) (d) (e)

Signal

POD slaveCN1+UG00P-TC

POD slaveCN1+UG00P-TC

POD slaveCN1+UG00P-TC

Terminal blockprepared by user

POD masterMJ1/2

Terminal resistor(OFF)

Terminal resistor(OFF)

Signal Signal

Terminal resistor(ON)

Terminal resistor(ON)

Signal

SG

+

-

SG

+

-

FG

+SD

-SD

+RD

-RD

SG

FG

+SD

-SD

+RD

-RD

SG

FG

+SD

-SD

+RD

-RD

SG

Up to 4 units can be connected to one PLC.

Use the terminal converter (UG00P-TC), the optional equipment made by Fuji Electric Co., Ltd.

For detailes, please see the “User’s Manual <Multi-Link 2 Communications> (FEH364)”.

* Wire the shielded FG only at the one of both sides so that they are not connected.

• Set the dip switch (SW1) of UG00P-TC as 2-wire connection when the UG00P-TC terminal converter is used.

• Short-circuit between +RD and +SD, and -RD and -SD when the UG00P-TC terminal converter is not used.

1.2 Connection

Page 8: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

1-5

n : 1 Link Communication (Multi-link)

Multiple POD and a PLC are connected. (n=1 to 32)

Available PLCs for multi-link

Manufacturer

FUJI

MITSUBISHI

MITSUBISHI

OMRON

SHARP

HITACHI

MATSUSHITA

YOKOGAWA

YASKAWA

TOYOPUC

TOSHIBA

SIEMENS

SHINKO

SAMSUNG

LG

Models

MICREX-F series

AnA/N/U series, Net10, FX series(A prt)

QnA CPU port (with UG00P-DI)

SYSMAC C, CV

JW series, JW100/70H COM Port, JW20/30 COM Port

HIDIC-H

MEWNET

FA500, FA-M3, FA-M3R

Memobus, CP9200SH/MP900

TOYOPUC

T series

S7-200 PPI

SELMART

SPC series, SECNET

MASTER-K500 / K1000

• • •• • •• • •• • •

• • •• • •• • •• • •

• • •• • •• • •• • •

• • •• • •• • •• • •

run

stop

PLC

POD 1 POD 2 POD 3 POD n

RS-485 Maximum length 500m(from PLC to the last POD)

run

stop

* The connections shown

below are not recommended.

1.2 Connection

Page 9: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

1-6

Signal

POD+UG00P-TC

Signal

POD+UG00P-TC POD+UG00P-TC

Signal

UG00P-DI

SignalPin No.

RD terminal resistance(ON)

RD/SD terminal resistance(OFF)

RD/SD terminal resistance(OFF)

* Use twist shielded cable.

FG

+SD

-SD

+RD

-RD

SG

FG

+SD

-SD

+RD

-RD

SG

FG

+SD

-SD

+RD

-RD

SG

1

2

3

4

5

7

15

16

17

18

20

21

+RxD

+TxD

+DSR

+DTR

SG

-RxD

-TxD

-DSR

-DTR

Signal

POD+UG00P-TC

Signal

Link unit

Signal

POD+UG00P-TC

Signal

POD+UG00P-TC

RD terminal resistance(ON)

RD/SD terminal resistance(OFF)

RD/SD terminal resistance(OFF)

* Use twist shielded cable.

FG

+SD

-SD

+RD

-RD

SG

FG

+SD

-SD

+RD

-RD

SG

FG

+SD

-SD

+RD

-RD

SG

FG

+RxD

-RxD

+TxD

-TxD

SG

1.2 Connection

When multiple POD are connected to a link unit of PLC, use the terminal converter (UG00P-TC), the

optional equipment made by Fuji Electric Co., Ltd. for RS-485 connection.

• Set the dip switch (SW1) of UG00P-TC as 2-wire connection when the UG00P-TC terminal converter is used.

• Short-circuit between +RD and +SD, and -RD and -SD when the UG00P-TC terminal converter is not used.

When multiple POD are connected directly to MITSUBISHI’s QCPU port, the optional equipment, UG00P-

DI is required.

• Set the dip switch (SW1) of UG00P-TC as 2-wire connection when the UG00P-TC terminal converter is used.

• Short-circuit between +RD and +SD, and -RD and -SD when the UG00P-TC terminal converter is not used.

*An n:1 system can be also configured using optional interface units (UG03I-T, J, E, C, S, P, UG02I-T, J, S).

For the details, refer to the User’s Manual of each optional interface unit.

Page 10: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-1

PLC Link Unit Wiring Diagram Select PLC Type

SR-T(K prt)

SU/SG

SR-T

SU/SG(K-Sequence)

SR-6T (TOYOTA version)

SR-1T (TOYOTA version)

SG-8

SZ-4

PZ3

SU-5/5E/6B/5M/6M

SZ-4M

SU-5E/6B

SU-5M/6M

SU-5M/6M

SZ-4M

SU-5E/6B

SZ-4

G01-DM

U01-DM

Port 1 on a CPU unit

Port on a CPU unit

G01-DM

Terminal blockson a CPU unit

Universal communication port

Port 3 on a CPU unit

Port 2 on a CPU unit

U01-DM

Port 2 on a CPU unit

Port 2 on a CPU unit

Port 1 on a CPU unit

Port 2 on a CPU unit

Port 3 on a CPU unit

Programmer port on a CPU unit

Port 2 on a CPU unit

Port 1 on a CPU unit

Port 1 on a CPU unitPort 2 on a CPU unit

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 4]

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 4]

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 7]

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 3]

RS-232C [Wiring Diagram 2]RS-422 [Wiring Diagram 6]

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 4]

RS-422 [Wiring Diagram 5]

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 7]

RS-232CProgram transfer cable made by Koyo [S-30JG-E]

+Convert connector cable made by Koyo [S-15CNJ]

RS-232CProgram transfer cable made by Koyo [S-30JG-E]

+Convert connector cable made by Koyo [S-15CNJ]

+Convert connector made by Koyo [S-15HCNP1]

RS-485 [Wiring Diagram 8]

RS-232CProgram transfer cable made by Koyo [S-30JG-E]

+Convert connector cable made by Koyo [S-15CNJ]

+Convert connector made by Koyo [S-15HCNP1]

RS-232CProgram transfer cable made by Koyo [S-30JG-E]

+Convert connector cable made by Koyo [S-15CNJ]

RS-232CProgram transfer cable made by Koyo [S-30JG-E]

RS-485 [Wiring Diagram 8]

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 3]

Chapter 2 Connection to Link Units

2.1 Koyo PLC

2.1 Koyo PLC

Available PLC

Page 11: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-2

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

Available Memory

SU/SG, SU/SG(K-Sequence)

SR-1T/SR-T(K prt)

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit Write : unavailable] memory will be output

by one word. Use TYPE number to assign indirect memory for macro programs.

Port "0" for x10, "1" for x1

19200bps

Odd

8

0 (fixed)

Host link system (fixed)

None (fixed)

HEX (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1

Response Delay Time

Function

Time-out

ASCII/HEX

Item Setting of PLC

1

19200bps

Odd

8

1

Comm. Parameter of POD

Available: Unavailable:

Available: Unavailable:

Memory Bit Write TYPE Remarks

SU/SG SU/SG(K)

R (data register) 0

I (input relay) 1

Q (output relay) 2

M (internal relay) 3

S (stage) 4

GI (global inputs) 5

GQ (global outputs) 6

T (timer/contact) 7

C (counter/contact) 8

Memory Bit Write TYPE Remarks

D (data register) 0

X (input relay) 1 X/Y common use

Y (output relay) 2 X/Y common use

M (internal relay) 3

S (stage) 4

K (keep relay) 5

L (link relay) 6

T (timer/contact) 7

C (counter/contact) 8

2.1 Koyo PLC

Page 12: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-3

1

No

3

4

ON

OFF

OFF

Setting Contents

5 OFF

Unit No. 01

6 OFF

1 : N8

OFF7

9

OFF

OFF Slave

2 OFF

1

No

2

3

OFF

OFF

OFF

Setting Contents

HEX mode4 OFF

Communication time-out

Slave

Master/slave control

1

No

2

3

4

5

7

6

8

ON

ON

ON

Setting

ON

OFF

OFF

OFF

OFF

Contents

Parity provided

Response delay time0msec

Self-diagnosis

Same as POD(normally 19200bps)

1

No

3

4

5

6

8

7

9

2

ON

ON

ON

Setting

OFF

OFF

OFF

OFF

OFF

ON

Contents

Parity provided

Self-diagnosis

Turn-around delay

Same as POD(normally 19200bps)

Response delay time 0msec

HEX mode

SW2 Dip Switch:

U-01DM

On-line/off-line switch: on-line

UNIT ADR switch: “0” for 10, “1” for 1

SW4 Dip Switch:

SW5 Dip Switch:

Switch Setting

G-01DM

On-line/off-line switch: on-line

Short plug 1: open

Short plug 2 RS-232C: ENABLE

RS-422: DISENABLE

SW1 Dip Switch:

2.1 Koyo PLC

Page 13: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-4

Wiring Diagram 4

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

+OUT

-OUT

-IN

+IN

14

15

16

17

0V 7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

FG

SD

RD

RS

CS

1

2

3

4

5

SD

RD

RS

CS

SG

2

3

4

5

7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

2.1 Koyo PLC

RS-422

Wiring Diagram 3

Wiring Diagram 2

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

+RTS

-RTS

+CTS

-CTS

+OUT

-OUT

-IN

+IN

-IN

+IN

10

11

12

13

14

15

16

17

24

25150

0V 7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

FG

SD

RD

RS

CS

1

2

3

4

5

TXD

RXD

RTS

CTS

0V

2

3

4

5

7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 15pin(Male: )

* Use twist shielded cables.

*1 High density D-sub 15pin

*1

Page 14: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-5

2.1 Koyo PLC

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

T1

T2

T3

FGSG 7

POD (CN1)D-sub 25pin(Male: )

PLC

* Use twist shielded cables.

Wiring Diagram 5

Wiring Diagram 6

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

0V

TXD+

TXD-

RTS+

RTS-

RXD+

CTS+

CTS-

7

9

10

11

12

13

14

15

RXD- 6SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 15pin(Male: )

* Use twist shielded cables.

*1 High density D-sub 15pin

*1

Wiring Diagram 7

Wiring Diagram 8

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

RXD+

RXD-

CTS1+

TXD1+

TXD1-

RTS1+

RTS1-

CTS1+

9

10

11

14

16

18

19

23

SG 7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

TXD3+

TXD3-

RXD3+

RXD3-

12

13

24

25

SG 7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

In case SU-6M, it is possible to use terminal blocks.

* Use twist shielded cables.

Page 15: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-6

Port 0

9600bps

none (fixed)

8 (fixed)

CRC (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1 (fixed)

Error Check

Item Setting of PLC

0

9600bps

none

8

1

Comm. Parameter of POD

Port

TransmissionControl Mode

RS-232C

RS-422 not supported on Channel 0

0

19200bps

Even

8

Full duplex (fixed)

BCC (fixed)

NO (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1

Protocol

Error Check

Response

Item Setting of PLC

0

19200bps

Even

8

1

Comm. Parameter of POD

PLC Link Unit Wiring Diagram

SLC 5/03 or later modelsRS-232C [Wiring Diagram 2]RS-422 [Wiring Diagram 4]

1747-KE

Port on a CPU unit

CPU (Processor module)RS-232C channel RS-232C [Wiring Diagram 1]

*RS-232C program transfer cable made by A-B +RS-232C [Wiring Diagram 3]

Select PLC Type

SLC500

Micro Logix 1000Micro Logix 1000

*When using RS-232C program transfer cable made by Allen-Bradley, connect the cable of [Wiring Diagram 3] to the D-sub 9 pins side of the program transfer cable to communicate with POD.

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

SLC500 series

Available PLC

2.2 Allen-Bradley PLC

(SLC500 series, Micro Logix 1000)

2.2 Allen-Bradley PLC

Micro Logix 1000

Page 16: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-7

Transmission Parameter Setting

CPU Port Channel 0

Set up the parameters for CPU port channel 0, using the software specifically designed for this purpose.

Baud Rate : 19200

Duplicate Detect : ON

ACK Timeout(x20 ms) : 20

Control Line : NO HANDSHAKING

Parity : EVEN

Error Detect : BCC

NAK Retries : 3

ENQ Retries : 3

Embedded Responses : AUTO-DETECT

Available Memory

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit Write : unavailable] memory will be output

by one word. Use TYPE number to assign indirect memory for macro programs.

Memory Bit Write TYPE Remarks

N (integer) 0

B (bit) 1

T.ACC (timer/current value) 2

T.PRE (timer/set value) 3

C.ACC (counter/current value) 4

C.PRE (counter/set value) 5

I (input) 6

O (output) 7

S (status) 8

T (timer/control) 9

C (counter/control) 10

R (control) 11

R.LEN (control/data length) 12

R.POS (control/data position) 13

D (BCD) 14

A (ASCII) 15

F (Float) 16

ST (String) 17

Available: Unavailable:

2.2 Allen-Bradley PLC

Page 17: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-8

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

FG

SD

RD

RS

CS

1

2

3

4

5

DCD

RXD

TXD

DTR

1

2

3

4

5COM

DSR 6

7

8

RTS

CTS

SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 9pin(Male: )

* Use twist shielded cables.

2.2 Allen-Bradley PLC

1747-KE

Set up the parameters for 1747-KE, using the software specifically designed for this purpose.

DF1 Port Setup Menu

Baudrate : 19200

Bits Per Character : 8

Parity : Even

Stop Bits : 1

DF1 Full-Duplex Setup Parameters

Duplicate Packet Detection : Enabled

Checksum : BCC

Constant Carrier Detect : Disabled

Message Timeout : 400

Hardware Handshaking : Disabled

Embedded Response Detect : Auto Detect

ACK Timeout( 5ms) : 90

ENQuiry Retries : 3

NAK Received Retries : 3

Page 18: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-9

RS-422

Wiring Diagram 4

FG

SG

+SD

-SD

+RD

1

7

12

13

24

TXD-

RXD-

COM

RXD+

1

2

5

6

9TXD+-RD 25

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 9pin(Male: )

*Use twist shielded cables.

2.2 Allen-Bradley PLC

Wiring Diagram 2

FG

SD

RD

RS

CS

1

2

3

4

5

RXD

TXD

DTR

2

3

4

5COM

SG 7 6

7

8

DSR

RTS

CTS

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 9pin(Female: )

* Use twist shielded cables.

FG

SD

RD

RS

CS

SG

1

2

3

4

5

7

RD

SD

RS

2

CD 1

3

4

GND 5

DR 6

RS 7

CS 8

POD (CN1) PLCD-sub 25pin(Male: ) D-sub 9pin(Male: )

* Use twist shielded cables.

Wiring Diagram 3

Page 19: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-10

19200bps

Odd

8

SNP-X (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1

Function

Item Setting of PLC

19200bps

Odd

8

1

Comm. Parameter of POD

PLC Wiring Diagram

RS-485 [Wiring Diagram 1]

Series 90 micro (CPU port)Series 90-30 (CPU port)

Select PLC Type

90 Series(SNP-X)

Available Memory

2.3 GE Fanuc PLC

(90 series SNP-X)

Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

2.3 GE Fanuc PLC

Available: Unavailable:

Memory Bit Write TYPE Remarks

R (data register) 0

I (input) 1

Q (output) 2

M (internal relay) 3

G (global relay) 4

AI (analog input) 5

AQ (analog output) 6

T (temporary memory relay) 7

S (system status) 8 Read only

SA (system status) 9

SB (system status) 10

SC (system status) 11

Page 20: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-11

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-485

Wiring Diagram 1

FG

SG

+SD

-SD

+RD

1

7

12

13

24

RTS(A)

0V

CTS(B')

6

7

8

9RT

-RD 25 10

11

12

RD(A')

RD(B')

SD(A)

SD(B)

RTS(B)

CTS(A')

13

14

15

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 15pin(Male: )

* Use twist shielded cables.

2.3 GE Fanuc PLC

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit Write : unavailable] memory will be output

by one word. Use TYPE number to assign indirect memory for macro programs.

Page 21: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-12

2.4 SIEMENS PLC

(S7-300/400MPI)

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

Set the [MPI SETTING] in the [Comm. Perameter] in UG00S-CW.

Set [Source No] as the different number from that of [Local No.], and make the value of [Node Cnt] equal

to or larger than that of [Screen No]. [Node Cnt] is equivalent for [Local No.] of a PLC. (For example, if

[Local No.] is [13], [Node Cnt] is [15].)

Available PLC

2.4 SIEMENS PLC

38400bpsBaud Rate

Parity

TransmissionCode

Data Length

Stop Bit

Item Setting of PLC

HMI ADP : 38400bps (fixed)

None (fixed)

8 (fixed)

1 (fixed)

Comm. Parameter of POD

PC ADP : 38400bps

Local No.(station no. of PLC) 2 2

CPU Wiring Diagram

S7-300/400 series(MPI port)

RS-232C [Wiring Diagram 1]

Select PLC Type

S7-300MPI(HMI ADP)

S7-300MPI(PC ADP)

SIEMENSHMI Adapter6ES7 972 0CA11-0XA0

SIEMENSPC Adapter6ES7 9720CA23-0XA0

Adapter

ITEM MPI SETTING

Node Cnt 15/31/63/126

Source No(station no.of POD) 0

Page 22: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-13

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

FG

SD

RD

RS

CS

RD

SD

SG

2

3

5

SG

2

1

3

4

5

7

RTS 7

CTS 8

POD (CN1)D-sub 25pin(Male: ) HMI Adapter

PC AdapterD-sub 9pin(Female: )

* Use twist shielded cables.

Available Memory

<E.g.> DB0001: 0000

Block No.Address No.

The assigned memory is indicated while editing the screen as illustrated:

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output Memory] of a switch

whose [Output Action] is [Momentary W], the other bits will be cleared when the bit memory is output,

because the [Bit Write : unavailable] memory will be output by one word. Use TYPE number to assign

indirect memory for macro programs.

2.4 SIEMENS PLC

Available: Unavailable:

Memory Bit Write TYPE Remarks

DB (data register) 0 Use memories more than DB1.

I (input relay) 1 IW as word device

Q (output relay) 2 QW as word device

M (Merker Word) 3 MW as word device

T (timer/current value) 4

C (counter/current value) 5

Page 23: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-14

Available Memory

2.5 KEYENCE PLC • 1

(KZ series)

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

For further information, refer to the communication specifications of KEYENCE link unit.

Available PLC

PLC Link Unit Wiring Diagram

KZ300KZ350 Port 2

RS-232C [Wiring Diagram 2] RS-422 [Wiring Diagram 3]

KZ-L2

Port 1 RS-232C [Wiring Diagram 1]

Select PLC Type

KZSeries

19200bps

Even

7 (ASCII)

ON for RS-422

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 2

Terminal Resistor

Item Setting of PLC

19200bps

0Port 0

Even

7

2

Comm. Parameter of POD

Set the port with the port setting switch, the terminating resistance with terminator, and

the baud rate/data bit/parity/stop bit with SET B dip switches.

2.5 KEYENCE PLC • 1

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit Write : unavailable] memory will be output

by one word. Use TYPE number to assign indirect memory for macro programs.

Available: Unavailable:

Memory Bit Write TYPE Remarks

DM (data memory) 0

CH (input/output relay) 1

Page 24: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-15

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

RS-422

Wiring Diagram 3

Wiring Diagram 2

FG

SD

RD

RS

CS

SD

RD

2

3

SG

2

1

3

4

5

7

4RS

CS

SG

5

7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

FG

SD

RD

SD

RD

2

1

3

RS 4

CS 5

SG

SG 7

POD (CN1)D-sub 25pin(Male: )

PLC

* Use twist shielded cables.

FG

SG

+SD

SDB7

1

12 SDA

-SD 13

+RD

-RD

24

25

RDB

RDA

SG

POD (CN1)D-sub 25pin(Male: )

PLC

* Use twist shielded cables.

2.5 KEYENCE PLC • 1

Page 25: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-16

57600bps

Even

8

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1

Terminal Resistor

Item Setting of PLC

57600bps

0Port 0

Comm. Parameter of POD

* 1

*1 The maximum baud rate is 57600bps. If 115000bps is selected, the POD communicates with a PLC forcibly at 9600bps.

Select PLC Type

KVSeries

KZ 24/300Series CPU

KV 10/24Series CPU

KV 700Series CPU

KZ-10,16,24,40,80,300,350(Program port direct connection)KV series(Program port direct connection)

RS-232C [Wiring diagram 1] orCable made by KEYENCE [OP-26487] + connecter [OP26485]

RS-422 Cable made by KEYENCE [KZ-C20]+ Cable made by Hakko [MB-CPUQ]

PLC Wiring Diagram

KZ-24,300(Program port direct connection)

KZ-V10,24(Program port direct connection)

RS-232C [Wiring diagram 1] orCable made by KEYENCE [OP-26487] + connecter [OP26485]

* When using RS-232C cable made by KEYENCE [OP-26487], attach the D-sub 25 pins connecter [OP-26485] to the modular jack on the POD side to communicate.

KV 700(Program port direct connection)

38400bps

Even

8

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1

Terminal Resistor

Item Setting of PLC

38400bps

0Port 0

Comm. Parameter of POD

* 1

*1 The maximum baud rate is 38400bps. If 57600bps or 115000bps is selected, the POD communicates with a PLC forcibly at 9600bps.

2.6 KEYENCE PLC • 2

2.6 KEYENCE PLC • 2

(KV series)

Communication Setting

KV series / KV 700 Series CPU

The communication parameter setting of POD is done automatically.

KZ24/300 Series CPU

Available PLC

KV10/24 Series CPU

Page 26: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-17

Available Memory

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit Write : unavailable] memory will be output

by one word. Use TYPE number to assign indirect memory for macro programs.

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

FG

SD

RD

SD

SG

2

1

3

RS 4

CS 5

RD

3

4

5

SG 7

123456

RD

SG

SD

POD (CN1)D-sub 25pin(Male: )

Modular Connector 6pinPLC

* Use twist shielded cables.

KV700KZ series

2.6 KEYENCE PLC • 2

*1 High-speed counter/current value

*2 High-speed counter comparator/set value

*3 High-speed counter comparator/contact

Available: Unavailable:

Memory Bit Write TYPE Remarks

DM (data memory) 0

CH (input/output relay) 1

TC (timer/current value) 2

CC (counter/current value) 3

TS (timer/set value) 4

CS (counter/set value) 5

T (timer/contact) 6

C (counter/contact) 7

TM (temporary data memory) 8

CTH (*1) 9 only in KV700

CTC (*2) 10 only in KV700

CT (*3) 11 only in KV700

CR (control relay) 12 only in KV700

CM (control memory) 13 only in KV700

Page 27: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-18

38400bps

None (fixed)

8 (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1 (fixed)

Item Setting of PLC

38400bps

Comm. Parameter of POD

19200bps

None (fixed)

8 (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1 (fixed)

Item Setting of PLC

19200bps

Comm. Parameter of POD

* 1

*1 In case of RS-422, the baud rate is fixed at 9600bps.

9600bps (fixed)

None (fixed)

8 (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1 (fixed)

Item Setting of PLC Comm. Parameter of POD

PLC Wiring Diagram

K10/60/200 RS-232C [Wiring Diagram 1]

K500/1000RS-232C [Wiring Diagram 2]

RS-422 [Wiring Diagram 5]

Select PLC Type

MASTER-K10/60/200

MASTER-K500/1000

LGMKX00S K200S/K300S/K1000S CPU port RS-232C [Wiring Diagram 3]

MASTER-KxxxS CNET

GLOFA CNET

RS-232C [Wiring Diagram 4]

RS-422 [Wiring Diagram 6]G4L-CUEA

K4F-CUEA

2.7 LG PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

MASTER-K10/60/200

Available PLC

MASTER-K500/1000

LGMKX00S

2.7 LG PLC

Page 28: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-19

38400bps

None

8

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1

Item Setting of PLC

38400bps

Comm. Parameter of POD

None

8

1

MASTER-K500/1000Available: Unavailable:

Available Memory

MASTER-K10/60/200

MASTER-KxxxS CNET / GLOFA CNET

Available: Unavailable:

2.7 LG PLC

Memory Bit Write TYPE Remarks

D (data register) 0

M (auxiliary relay) 1

P (input/output relay) 2 Input : Read only

K (keep relay) 3

TC (timer/current value) 4

CC (counter/current value) 5

TS (timer/set value) 6

CS (counter/set value) 7

Memory Bit Write TYPE Remarks

P (input/output) 0 Input : read only

M (relay) 1

L (link relay) 2

K (keep relay) 3

F (special relay) 4 Read only

T (timer/current value) 5

C (counter/set value) 6

D (data register) 7

Page 29: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-20

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit Write : unavailable] memory will be output

by one word. Use TYPE number to assign indirect memory for macro programs.

GLOFA CNET

LGMKX00S

MASTER-KxxxS CNET

Available: Unavailable:

Available: Unavailable:

Available: Unavailable:

2.7 LG PLC

Memory Bit Write TYPE Remarks

P (input/output) 0 Input : read only

M (relay) 1

L (link relay) 2

K (keep relay) 3

F (special relay) 4 Read only

T (timer/current value) 5

C (counter/set value) 6

D (data register) 7

TC (timer/contact) 9

CC (counter/contact) 10

Memory Bit Write TYPE Remarks

P (input/output) 0 Input : read only

PW as word device

M (relay) 1 MW as word device

L (link relay) 2 LW as word device

K (keep relay) 3 KW as word device

F (special relay) 4 Read only

FW as word device

T (timer/current value) 5

C (counter/set value) 6

D (data register) 7

TC (timer/contact) 9

CC (counter/contact) 10

Memory Bit Write TYPE Remarks

M (internal memory) 0 MW as word device

Q (output) 1 QW as word device

I (input) 2 IW as word device

Page 30: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-21

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

FG

SD

RD

RXD2

1

3 TXD

SG 7 GND

2

3

5

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 9pin(Male: )

* Use twist shielded cables.

FG

SD

RD

TXD2

1

3 RXD

SG 7 GND

2

3

7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

Wiring Diagram 2

Wiring Diagram 3

FG

SD

RD

TXD2

1

3 RXD

SG 7

GND

2

3

5

CS 5

RS 4

RTS

CTS

7

8

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

2.7 LG PLC

Page 31: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-22

SD+

SD-

10

11

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

PLCD-sub 25pin(Male: )

POD (CN1)D-sub 25pin(Male: )

* Use twist shielded cables.

RS-422

Wiring Diagram 5

RDA

RDB

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

SDA

SDB

SG 7 SG

PLC

POD (CN1)D-sub 25pin(Male: )

* Use twist shielded cables.

Wiring Diagram 6

Wiring Diagram 4

FG

SD

RD

RXD2

1

3 TXD

SG 7

SG

2

3

5CS 5

RS 4

RTS

CTS

7

8

CD 1

DTR 4

DSR 6

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 9pin(Male: )

* Use twist shielded cables.

2.7 LG PLC

Page 32: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-23

Available Memory

2.8 SAIA PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

Available PLC

19200bps 19200bps

8

Baud Rate

Transmissioncode

Data Length

Stop Bit 1

8

1

Item Setting of PLC

Port 0 0

Comm. Parameter of POD

PCD1PCD

PLC Communication moduleSelect PLC Type Wiring Diagram

RS-232C [Wiring Diagram 1]RS-232C [Wiring Diagram 2]RS-485 [Wiring Diagram 3]

PGU portPCD7.F120PCD4.F110

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write: unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit: unavailable] memory will be output by

one word. Use TYPE number to assign indirect memory for macro programs.

S-BUS Configuration

S-BUS Mode Parity

PGU Port Number 0 (PGU port), 1 (PCD7.F120, PCD4.F110)

Available: Unavailable:

2.8 SAIA PLC

Memory Bit Write TYPE Remarks

R (Register Word) 0

Rfp (Float) 1

T (Timer-Counter Word) 2

C (Timer-Counter Coil) 3

I (Input Bit) 4 read only

O (Output Bit) 5

F (Flag Bit) 6

Page 33: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-24

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

Wiring Diagram 2

FG

RD

SD

SG

1

3

2

7

TX

RX

GND

12

11

10

POD (CN1)D-sub 25pin(Male: )

PLC

* Use twist shielded cables.

PCD7.F120

RS-485

Wiring Diagram 3

FG

+SD

SG

-SD

+RD

-RD

1

12

7

13

24

25

T/R+

T/R-

GND 10

12

11

POD (CN1)D-sub 25pin(Male: )

PLC

* Use twist shielded cables.

PCD7.F110

FG

RD

SD

SG

1

3

2

7

RX

TX

GND

3

2

5

POD (CN1)D-sub 25pin(Male: )

PLC

* Use twist shielded cables.

PGU port

2.8 SAIA PLC

Page 34: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-25

Available Memory

2.9 MOELLER PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

Available PLC

9600bps 9600bps

None

8

Baud Rate

Parity

Transmissioncode

Data Length

Stop Bit 1

8

1

Item Setting of PLC

Port 1 1

Comm. Parameter of POD

None

PS4-201-MM1(PRG port)PS4

PLCSelect PLC Type Wiring Diagram

RS-232C [Wiring Diagram 1]+

ZB4-303-KB1 Cable made by MOELLER

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write: unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit: unavailable] memory will be output by

one word. Use TYPE number to assign indirect memory for macro programs.

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

FG

RD

SD

SG

1

3

2

7

TX

RX

SG

3

2

5

POD (CN1)D-sub 25pin(Male: ) PLC

* Use twist shielded cables.

D-sub 9pin(Male: )

Available: Unavailable:

2.9 MOELLER PLC

Memory Bit Write TYPE Remarks

M (Marker) 0 MW as word device

Page 35: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-26

2.10 Telemecanique PLC

Available PLC

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

TSX Micro

PLC Wiring Diagram

RS-485 [Wiring Diagram 1]

Select PLC Type

TSX Micro

Connection

9600bps

Odd

8 (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1

Item Setting of PLC

Multi-Link (fixed)

9600bps

Odd

8

1

Comm. Parameter of POD

Available Memory

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit Write : unavailable] memory will be output

by one word. Use TYPE number to assign indirect memory for macro programs.

Available: Unavailable:

2.10 Telemecanique PLC

Memory Bit Write TYPE Remarks

MW (memory Word) 0

KW (constant word) 1

M (bit memory) 2

Page 36: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-27

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-485

Wiring Diagram 1

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

D+

D-

1

2

POD (CN1)D-sub 25pin(Male: )

PLCMiniDIN 9pin(Male: )

* Use twist shielded cables.

2.10 Telemecanique PLC

Page 37: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-28

2.11 Automationdirect PLC

Available PLC

Direct LOGIC

PLC Link Unit Wiring Diagram

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 5]

Port 1 on a CPU unit

Select PLC Type

Port 3 on a CPU unit

Port 2 on a CPU unit

RS-232C [Wiring Diagram 1]RS-422 [Wiring Diagram 5]

RS-232C [Wiring Diagram 2]D2-240 Port 2 on a CPU unit

D2-250 Port 2 on a CPU unit RS-232C [Wiring Diagram 3]

D4-430D4-440

D4-450 RS-485 [Wiring Diagram 6]

D4-450

Port 1 on a CPU unit

Direct LOGIC(K-Sequence)

D2-250Port 2 on a CPU unit RS-232C [Wiring Diagram 3]

D4-430D4-440

Port 3 on a CPU unit

Port 0 on a CPU unit

Port 2 on a CPU unit

Port 1 on a CPU unit

RS-232C [Wiring Diagram 2]D2-240 Port 1 on a CPU unitPort 2 on a CPU unit

RS-232C [Wiring Diagram 4]

RS-485 [Wiring Diagram 6]

Communication Setting

The recommended communication parameter setting of both PLC and POD is as follows:

Port "0" for x10, "1" for x1

19200bps

Odd

8

0 (fixed)

Host link system (fixed)

None (fixed)

HEX (fixed)

Baud Rate

Parity

TransmissionCode

Data Length

Stop Bit 1

Response Delay Time

Function

Time-out

ASCII/HEX

Item Setting of PLC

1

19200bps

Odd

8

1

Comm. Parameter of POD

2.11 Automationdirect PLC

Page 38: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-29

FG

SD

RD

SG

RxD

2

1

3

RS 4

CS 5

TxD

1

3

4

SG 7

654321

POD (CN1)D-sub 25pin(Male: )

Modular Connector 6pinPLC

* Use twist shielded cables.

FG

SD

RD

RS

CS

1

2

3

4

5

SD

RD

RS

CS

SG

2

3

4

5

7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

Available Memory

Direct LOGIC, Direct LOGIC(K-Sequence)

Set the memory to the extent of the memory range of each PLC model.

In case of using the [Bit Write : unavailable] memory as the bit device of the [Output

Memory] of a switch whose [Output Action] is [Momentary W], the other bits will be cleared

when the bit memory is output, because the [Bit Write : unavailable] memory will be output

by one word. Use TYPE number to assign indirect memory for macro programs.

Wiring

The following is a diagram to show the wiring of the cable which connects POD to PLC.

RS-232C

Wiring Diagram 1

Wiring Diagram 2

Memory Bit Write TYPE Remarks

DL DL(K)

V (data register) 0

X (input relay) 1

Y (output relay) 2

C (internal relay) 3

S (stage) 4

GX (global inputs) 5

GY (global outputs) 6

T (timer/contact) 7

CT (counter/contact) 8

Available: Unavailable:

2.11 Automationdirect PLC

Page 39: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

2-30

Wiring Diagram 4

RS-422

Wiring Diagram 5

Wiring Diagram 3

Wiring Diagram 6

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

RXD+

RXD-

CTS1+

TXD1+

TXD1-

RTS1+

RTS1-

CTS1+

9

10

11

14

16

18

19

23

SG 7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

* Use twist shielded cables.

FG

+SD

-SD

+RD

-RD

1

12

13

24

25

TXD3+

TXD3-

RXD3+

RXD3-

12

13

24

25

SG 7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 25pin(Male: )

In case SU-6M, it is possible to use terminal blocks.

* Use twist shielded cables.

FG

SD

RD

RS

CS

1

2

3

4

5

TXD

RXD

RTS

CTS

0V

2

3

4

5

7SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 15pin(Male: )

* Use twist shielded cables.

*1 High density D-sub 15pin

*1

FG

SD

RD

RS

CS

1

2

3

4

5

TXD

RXD

0V

2

3

13

SG 7

POD (CN1)D-sub 25pin(Male: )

PLCD-sub 15pin(Male: )

* Use twist shielded cables.

2.11 Automationdirect PLC

Page 40: USER’S MANUAL  Additional Specificationsdownload.gongkong.com/file/company/fuji/ug/English/FEH352a-1_All.pdf · FACON FB series MICRO3 ... FATEK AUTOMATION: FACON

Fuji Electric Co., Ltd.ED & C · EDrive Systems CompanyGate City Ohsaki, East Tower11-2, Osaki 1-chome, Shinagawa-ku, Tokyo, 141-0032, JapanPhone: +81-3-5435-7135~8Fax: +81-3-5435-7456~9

URL http://www.fujielectric.co.jp/kiki/