  • Use of R32 refrigerant in HVAC-R equipment

    Comparison with refrigerants R22 and R410A

    Hrvoje Krapani, Daikin Airconditioning Central Europe

    47. Meunarodni kongres i izloba o KGH, Beograd, 30.112.12.201647th International HVAC&R Congress and Exhibition, Belgrade, Nov.30Dec.2 2016

  • 47. Meunarodni kongres i izloba o KGH, Beograd, 30.112.12.201647th International HVAC&R Congress and Exhibition, Belgrade, Nov.30Dec.2 2016

    What is HFC32 (R32) Benefits of R32 Toxicity & Flammability classification Main differences between R32, R410A & R22 Guidelines for installation/service works

    Transport Room size limits Brazing Pressure Refrigerant charging & recovery

    Tools Summary Conclusion

    Outline/Agenda

  • What is HFC32 (R32)

    HFC32 = R32 = difluoromethane, a single component HFC refrigerant

    Known as a component of the blend refrigerant R410A (=50%R32+50%R125)

    Already used in millions of air conditioners/ heat pumps in many parts of the world including in high ambient temperature zones

    SNAP approved for Packaged Terminal air conditioners & heat pumps

    Refrigerants ODP GWP(IPCC4)Flammability

    (ISO817)

    R320 675 2L

    R220.055 1810 1

    R410A

    0 2088 1

    ClC

    H

    FF

    CHH

    F

    F

    CHH

    F

    F

    CC

    F FF

    FFH

    50% R32

    50% R125

    3

  • Benefits of R32R32 is a refrigerant that addresses a range of environmental, safety and economic considerations:

    Zero Ozone depletion potential (ODP)

    Lower Global Warming Potential (GWP) about one third of R410A

    R32 allows for reduced refrigerant charge, compact design and high energy efficiency

    Easier to charge, recover and reuse because it is not a blend

    Safe to use in many applications because it is an A2L classified refrigerant (low toxicity and lower flammability)

    The potential global warming impact (GWP x kg) can be up to 75% less than that of R410A. Energy efficiency can also be improved by 5-10% depending on models.

    Global Warming Potential(GWP)

    Charge (kg) Global Warming Impact (GWPxkg)

    Up to 75% lower global warming impact than R410A

    4

  • New oils already available whichare optimal for both R32 & R410A

    Previously used oils for R410A are not suitable for R32

    No issue in most conditions(*)

    (*) With R32, In very low ambient heating condition, discharge temperature may need to be controlled, e.g. by wet suction control

    Main differences between R32, R410A & R22

    5

  • R32 belongs to the ISO817 toxicity class A (low toxicity), same class as R410A and R22.

    6

    Refrigerant ATEL (% in air)Higher value is safer

    ISO817ASHRAE34

    Toxicity class

    R32 22% A

    R410A 17% A

    R22 5.9% A

    ATEL = Acute Toxicity Exposure Limit. Higher value is safer.

    R32 toxicity classification

  • Flammability classification of R32

    Standards Safety data sheets, cylinder labels

    Code ISO817 GHS (UN Globally Harmonised System of Classification and Labelling of Chemicals) R32

    Flammability Classification

    Class 2LLower flammable refrigerant

    Flammable GasCategory 1

    SymbolIEC60335-2-40

    5th edition

    Criteria

    LFL greater than 3.5% by volume* and Heat of Combustion less than 19MJ/kg and Burning Velocity less than 10cm/s

    Gases, which at 20C and a standard pressure of 101.3kPa : (a) Are ignitable when in a mixture of 13% or less by

    volume in air; or(b) Have a flammable range with air of at least 12

    percentage points regardless of the lower flammable limit

    DangerExtremely

    flammable gas

    * When tested in air at 23C and if no flame propagation is detected then tested at 60C & 101.3kPa

    R32 flammability characteristics

    Lower flammable limit LFL 14,5 % v/v

    Upper flammable limit UFL 31% v/v

    Heat of Combustion HoC 9,5 MJ/kg

    Burning Velocity BV 6,7 cm/s

    Minimum Ignition Energy MIE > 15-100 mJ

    MIE of R32 varies depending on contact size / spacing and test apparatus. This is typical for difficult to ignite gases. Ammonia exhibits similar variations

    7

  • Guidelines for installation/service- Transport -

    The installer/service van Permanent ventilation required (Note : R32 is heavier than air

    so outlet should be at the bottom) No smoking, no ignition sources or hot surfaces Follow the instructions for transport of the cylinders and

    equipment Check local and trans-border transport regulations.

    Remark: Similar precautions are already required for transporting acetylenefor brazing.

    8

  • Charge/room size limitations

    Charge limits for R32 installations based on EN60335-2-40 5th edition (depends on location of indoor unit). There are no room size limitations for refrigerant charges below 1.23 kg.

    9

    Amin = 2.5 x LFL5/4 x h0M 2

    Amin = minimum room area (m)M = refrigerant charge (kg)h0 = height of leakLFL = Lower Flammability Limit in kg/m

    Formula for minimum floor area for given flammable refrigerant charge

    Chart1

    1.2281.2281.228

    1.2283.97452889663.251887279

    1.28256163924.70272601043.8476849176

    1.32757742244.86778388223.9827322673

    1.53295436445.62083266954.5988630933

    1.71389508266.28428196965.1416852479

    1.87747799596.8840859855.6324339877

    2.02790800977.43566270246.0837240292

    2.16792485277.94905779316.503774558

    2.29943154667.9826.8982946399

    2.42381367037.9827.271441011

    2.54211722387.9827.6263516713

    2.65515484497.9827.9654645346

    2.76357278197.9827.982

    2.86789501067.9827.982

    2.9685533627.9827.982

    3.06590872887.9827.982

    3.16026638197.9827.982

    3.2518872797.9827.982

    3.34099657987.9827.982

    3.42779016537.9827.982

    3.51243970597.9827.982

    3.5950966557.9827.982

    3.67589543237.9827.982

    3.75495599187.9827.982

    3.83238591117.9827.982

    3.90828210887.9827.982

    3.98273226737.9827.982

    4.05581601957.9827.982

    4.12760594717.9827.982

    4.19816842517.9827.982

    4.267564347.9827.982

    4.33584970537.9827.982

    4.40307619047.9827.982

    4.4692915787.9827.982

    4.53454016197.9827.982

    4.59886309337.9827.982

    4.66229868437.9827.982

    4.7248826757.9827.982

    4.78664846877.9827.982

    4.84762734077.9827.982

    4.90784862297.9827.982

    4.96733986927.9827.982

    5.02612700267.9827.982

    5.08423444757.9827.982

    5.14168524797.9827.982

    5.19850117437.9827.982

    5.25470282037.9827.982

    5.31030968977.9827.982

    5.36534027557.9827.982

    5.41981213177.9827.982

    ceiling mounted

    floor mounted

    wall mounted

    GG.2 @ 0,6m

    GG.2 @2,2m

    GG.2 @ 1,8m

    Room Area (m)

    allowed charge (kg)

    Refrigerants values

    R1234yfR32R290R600aR152R410AR717

    LFL (kg/m3)0.2990.3070.0380.0380.1300.116

    Practical limit (kg/m3)0.0600.0610.0080.0110.0270.4400.000

    h (m) (room height)2.5002.5002.5002.5002.5002.5002.500

    ATEL/ODLNA0.3870.000

    RCL (kg/m3)0.0600.0610.3900.390

    QLMV (kg/m3)0.0620.0630.4200.420

    QLAV (kg/m3)0.1500.1600.4200.420

    Necessary charge

    necessary charge/kW

    refrigerant typecapacity (kW)capacity (kW)

    3.501.00

    chargeR410A1.200.34

    R320.840.24

    R2900.370.11

    R12341.320.38

    IEC proposal

    1.84215.96479.821.8421.8420000

    1.84215.96479.821.8423.9745288966103.3771.5754

    1.84215.96479.821.8424.7027260104144.72782.2055.6

    1.84215.96479.821.8424.8677838822155.06552.36256

    1.84215.96479.821.8425.6208326695206.7543.158

    1.84215.96479.821.8426.2842819696258.44253.937510

    1.84215.96479.821.87747799596.8840859853010.1314.72512

    1.84215.96479.822.02790800977.43566270243511.81955.512514

    1.84215.96479.822.16792485277.94905779314013.5086.316

    1.84215.96479.822.29943154668.43124900434515.19657.087518

    1.84215.96479.822.42381367038.88731679125016.8857.87520

    1.84215.96479.822.54211722389.32109648715518.57358.662522

    1.84215.96479.822.65515484499.73556776456020.2629.4524

    1.84215.96479.822.763572781910.13310020046521.950510.237526

    1.84215.96479.822.867895010610.51561503897023.63911.02528

    1.84215.96479.822.96855336210.88469566057525.327511.812530

    1.84215.96479.823.065908728811.24166533918027.01612.632

    1.84215.96479.823.160266381911.58764340028528.704513.387534

    1.84215.96479.823.25188727911.92358668979030.39314.17536

    1.84215.96479.823.340996579812.25032079269532.081514.962538

    1.84215.96479.823.427790165312.568563939310033.7715.7540

    1.84215.96479.823.512439705912.878945588410535.458516.537542

    1.84215.96479.823.59509665513.182021068311037.14717.32544

    1.84215.96479.823.675895432313.478283251911538.835518.112546

    1.84215.96479.823.754955991813.7681719712040.52418.948

    1.84215.96479.823.832385911114.052081673912542.212519.687550

    1.84215.96479.823.908282108814.330367732313043.90120.47552

    1.84215.96479.823.982732267314.603351646713545.589521.262554

    1.84215.96479.824.055816019514.871325404714047.27822.0556

    1.84215.96479.824.127605947115.134555139414548.966522.837558

    1.84215.96479.824.198168425115.393284225415050.65523.62560

    1.84215.96479.824.2675643415.647735913515552.343524.412562

    1.84215.96479.824.335849705315.898115586216054.03225.264

    1.84215.96479.824.403076190415.96416555.720525.987566

    1.84215.96479.824.46929157815.96417057.40926.77568

    1.84215.96479.824.534540161915.96417559.097527.562570

    1.84215.96479.824.598863093315.96418060.78628.3572

    1.84215.96479.824.662298684315.96418562.474529.137574

    1.84215.96479.824.72488267515.96419064.16329.92576

    1.84215.96479.824.786648468715.96419565.851530.712578

    1.84215.96479.824.847627340715.96420067.5431.579.82

    1.84215.96479.824.907848622915.96420569.228532.287579.82

    1.84215.96479.824.967339869215.96421070.91733.07579.82

    1.84215.96479.825.026127002615.96421572.605533.862579.82

    1.84215.96479.825.084234447515.96422074.29434.6579.82

    1.84215.96479.825.141685247915.96422575.982535.437579.82

    1.84215.96479.825.198501174315.96423077.67136.22579.82

    1.84215.96479.825.254702820315.96423579.359537.012579.82

    1.84215.96479.825.310309689715.96424079.8237.879.82

    1.84215.96479.825.365340275515.96424579.8238.587579.82

    1.84215.96479.825.419812131715.96425079.8239.37579.82

    m3*2

    m2*2

    m1*1,5

    GG.2 @ 0,6m

    GG.2 @ 2,2m

    QLMV

    UNV.

    QLAV

    m1*1,5

    m2*2

    m3*2

    GG.2 @ 0,6m

    GG.2 @2,2m

    unv. L2T

    QLMV

    QLAV

    Room (m)

    charge (kg)

    IEC 5th edition

    1.2281.2281.228

    1.2283.97452889663.251887279

    1.28256163924.70272601043.8476849176

    1.32757742244.86778388223.9827322673

    1.53295436445.62083266954.5988630933

    1.71389508266.28428196965.1416852479

    1.87747799596.8840859855.6324339877

    2.02790800977.43566270246.0837240292

    2.16792485277.94905779316.503774558

    2.29943154667.9826.8982946399

    2.42381367037.9827.271441011

    2.54211722387.9827.6263516713

    2.65515484497.9827.9654645346

    2.76357278197.9827.982

    2.86789501067.9827.982

    2.9685533627.9827.982

    3.06590872887.9827.982

    3.16026638197.9827.982

    3.2518872797.9827.982

    3.34099657987.9827.982

    3.42779016537.9827.982

    3.51243970597.9827.982

    3.5950966557.9827.982

    3.67589543237.9827.982

    3.75495599187.9827.982

    3.83238591117.9827.982

    3.90828210887.9827.982

    3.98273226737.9827.982

    4.05581601957.9827.982

    4.12760594717.9827.982

    4.19816842517.9827.982

    4.267564347.9827.982

    4.33584970537.9827.982

    4.40307619047.9827.982

    4.4692915787.9827.982

    4.53454016197.9827.982

    4.59886309337.9827.982

    4.66229868437.9827.982

    4.7248826757.9827.982

    4.78664846877.9827.982

    4.84762734077.9827.982

    4.90784862297.9827.982

    4.96733986927.9827.982

    5.02612700267.9827.982

    5.08423444757.9827.982

    5.14168524797.9827.982

    5.19850117437.9827.982

    5.25470282037.9827.982

    5.31030968977.9827.982

    5.36534027557.9827.982

    5.41981213177.9827.982

    ceiling mounted

    floor mounted

    wall mounted

    GG.2 @ 0,6m

    GG.2 @2,2m

    GG.2 @ 1,8m

    Room Area (m)

    allowed charge (kg)

    R32

    EN378 (2008)EN 378 (2014)IEC proposal 2014IEC proposal 2015

    class Aclass Bclass Cclass Aclass Bclass Cclass Aclass A

    A(m2)V (M3)4 x LFL38 x LFL132 x LFLhuman comfortC.3 --- h0 = 0,6mhuman comfortC.3 --- h0 = 2,2mother systems: PLXRV

  • Basic rules for refrigerant pipes-- Dry, clean , tight --

    10

  • Brazing

    As per common HFC or HCFC refrigerants such as R410A & R22, R32 will decompose and release toxic substances if heated to high temperatures over 570C.

    To avoid the possibility of this occurring during brazing, the system should be purged with dry nitrogen to ensure that there is no residual refrigerant present.

    The risk of toxic by-products when R32 comes in contact with a flame or very hot surface is the same risk that has existed for over 40 years with R22.

    Same procedures as for R410A or R22

    11

  • Pressure

    Pressure graph for R32 is similar to R410A

    12

  • Charging & Recovery

    Because it is not a blend, R32 can be charged in liquid or gas phase (as was the case for R22)

    R410A needs to be charged in liquid state. Adding R410A in gas form may cause the refrigerant composition to change, preventing normal operation

    R32 is also easier to recover, recycle or reclaim compared to blend refrigerants

    13

  • 14

    Tools

    Tool R32 R410A R22

    Gauge manifold

    Charge hose

    Scale

    Pipe bender

    Pipe cutter

    Flaring tool

    Torque wrench

    Cylinder thread adaptor

    Vacuum pump

    Recovery pump

    Electr. Leak detector

    Refrigerant recovery cylinder

    Slightly different scale for HFC32 and R410A so check with tool supplier if manifold is shareable

    Common

    R22 type can be used by changing the work process

    Some flare nuts widths are different, others can be shared

    Common

    Common

    Check with tool supplier if shareable

    Common

    Common

    Common

    Common

    Check with tool supplier if shareable

    Not applicableDepends on the cylinder some have different thread for flammable gases

    Torch type models CANNOT be used.

  • Installation/service - Dos

    Ventilate the area if brazingVentilate the area in the event of any refrigerant leakPressure test the system to 4.0MPaEvacuate the system to a minimum of 500microns Signpost and restrict access to the area if brazing or if a leak occursHave a fire extinguisher at handRemove any potential source of ignition

    15

    Summary

  • Installation/service - Donts

    Charge R32 into systems other than those designed for R32

    Charge an R32 system with oil other than that specified by the manufacturer

    Use a reclaim cylinder other than an R32 reclaim cylinder

    Install pipe work with diameters that are not specified for that model

    Forget to add additional refrigerant if required

    16

    Summary

  • Conclusions

    Installation/service practices for R32 are :

    Similar to R410A : similar pressure, shareable tools Similar to R410A and R22 : basic rules for piping & brazing Different from R22 : : higher pressure, different oil type Different from R410A and R22 : because R32 is flammable, specific guidance

    and regulations need to be followed (transport, room size limits, work instructions). Always

    follow guidance from gas and equipment providers and the local regulations.

    17

  • HVAC-R industry was and is looking for the answer on the pressure coming from efforts to reduce GWP in the world and EU.

    Some producers decided to go with R32 refrigerant, since it is perceived as the best solution in given circumstances, taking lots of aspects into consideration like: reduction of CO2 technical utilisation of available technologies, Safety during installation and in use economic component to keep the competitiveness and prices to the consumers, availability of the refrigerant,

    Having all this in mind R32 is optimal (and preferable) choice as the key refrigerant for the next period when we talk about airconditioners and heat pumps.

    18

    Conclusions

  • Use of R32 refrigerant in HVAC-R equipmentSlide Number 2What is HFC32 (R32)Benefits of R32Main differences between R32, R410A & R22Slide Number 6Flammability classification of R32Guidelines for installation/service - Transport - Charge/room size limitationsBasic rules for refrigerant pipesBrazingPressureCharging & RecoverySlide Number 14Slide Number 15Slide Number 16Slide Number 17Slide Number 18Slide Number 19