SECURED POWER PROTECTION
ChromScience Sdn Bhd
Slide 2 04/09/23
POWER PROBLEMS
Power failures
Power sags
Power surges
Under voltages
Electrical line noise
Over voltages
Frequency variations
Switching transients
Harmonics distortion
ChromScience Sdn Bhd
Slide 3 04/09/23
1. POWER FAILURES
CAUSE BY :
- Power line downed- Lightning strikes- Grid over demand- Natural disaster
A total loss of powerEFFECTS :
- Hardware damage- Data loss- Force shutdown
ChromScience Sdn Bhd
Slide 4 04/09/23
2. POWER SAG
Short term low voltage
EFFECTS :
- System halts/crash- Loss of data- Hardware damage
CAUSE BY :
- Trigger by the startup large load ( eg: from Air Condition ) - Utility switching
ChromScience Sdn Bhd
Slide 5 04/09/23
3. POWER SURGE (SPIKE)
Short term high voltage above 110% of nominal
EFFECTS :
- Loss of data- Hardware damage
CAUSE BY :
- Lightning strike
ChromScience Sdn Bhd
Slide 6 04/09/23
4. UNDER VOLTAGE (BROWNOUT)
Reduced line voltage for few seconds/minutes/days
EFFECTS :
- System halts/crash.- Loss of data- Hardware damage
CAUSE BY :
- Intentionally utility voltage reduction- Heavy loads that exceed supply capacity.
ChromScience Sdn Bhd
Slide 7 04/09/23
5. OVER VOLTAGE
Reduced line voltage for extended periods of a few minutes/days
EFFECTS :
- System halts/crash.- Loss of data- Hardware damage
CAUSE BY :
- Rapid reduction in power load- Heavy equipment turn off- Utility switching
ChromScience Sdn Bhd
Slide 8 04/09/23
6. ELECTRICAL LINE NOISE
High frequency waveform caused by RFI/EMI interference
EFFECTS :
- System halts/crash.- Loss of data- Hardware damage
CAUSE BY :
- Transmitters (radio)- Welding devices- Ineffective grounding
ChromScience Sdn Bhd
Slide 9 04/09/23
7. SWITCHING TRANSIENT
Instantaneous under voltage in nanoseconds
EFFECTS :
- Hardware damage
CAUSE BY :
- Variable speed drives by electrical equipments
ChromScience Sdn Bhd
Slide 10 04/09/23
9. HARMONIC DISTORTION
EFFECTS :
- Communication errors- Overheating- Hardware damage
CAUSE BY :
- Non linear loads (ex: copier, fax machines)
Distortion of the normal line waveform
ChromScience Sdn Bhd
Slide 11 04/09/23
HOW TO SOLVE POWER PROBLEM
generator how generator works ?
Weaknesses :
- Voltage and frequency variations- Takes time to stabilize before passing the electricity- Regular maintenance
ChromScience Sdn Bhd
Slide 12 04/09/23
HOW TO SOLVE POWER PROBLEM
AVR (Automatic
Voltage Regulator)
Specification :
-170 to 250 Vac only
Weaknesses :
What if < 170 Vac ?What if > 250 Vac ?
ChromScience Sdn Bhd
Slide 13 04/09/23
HOW TO SOLVE POWER PROBLEM
UPS ( Uninterruptible Power Supply )
Specification :
- Combination of Generator + AVR function.
ChromScience Sdn Bhd
Slide 14 04/09/23
UPS TECHNOLOGY
VO
LT
AG
E
TIME
TNB UPS
OFF-LINE ON-LINE
VO
LTA
GE
TIME
TNB UPS
ChromScience Sdn Bhd
Slide 15 04/09/23
UPS TECHNOLOGY
OFF-LINE UPS / STANDBY
ON-LINE UPS / DOUBLE CONVERSION
ChromScience Sdn Bhd
Slide 16 04/09/23
POWER BASIC
UPS SIZING ( if u know VA )
VA = voltage x ampere= 240V x 5amp= 1,200VA / 1.2kVA
UPS > 1.2kVA
ChromScience Sdn Bhd
Slide 17 04/09/23
POWER BASIC
UPS SIZING ( if you know Watt )
VA = 700 Watt / pf= 700 / 0.7= 1,000VA / 1 kVA
UPS > 1 kVA
ChromScience Sdn Bhd
Slide 18 04/09/23
EXAMPLES – SIZING UPS
IT EQUIPMENTS CURRENT UPS
PC – ACER M1800 3.15 Amp 756 V
Server – HP Z400 6 Amp 1,440 V
LAN Switch – HP Pro Curve 3500yl 24
0.6 Amp 144 V
Gigabit Switch – HP Pro Curve 3500yl 48G
5 Amp 1,200 V
Gigabit Swich + PoE – HP Pro Curve 3500yl 48G+PoE
3.3 Amp + 398W 1,361 V
ChromScience Sdn Bhd
Slide 19 04/09/23
VA
While UPSs aregenerally measuredin VA . . .
Watts
. . . The true outputpower of a UPS is
measured in watts
POWER DENSITY
ChromScience Sdn Bhd
Slide 20 04/09/23
POWER FACTOR
Power factor is the ratio of watts to VA:
Apparent power to Real power. VA
(apparent)Watts(real)
eg: 10kVA UPS
If pf 0.6 10kVA / 6kW pf 0.7 10kVA / 7kW pf 0.9 10kVA / 9kW
ChromScience Sdn Bhd
Slide 21 04/09/23
WHY POWERWARE IS THE BEST ?
• ABM (Advance Battery Management)
• Power Management Software
• Power Density
• X Slot Connectivity Option
ChromScience Sdn Bhd
Slide 22 04/09/23
ABM – ADVANCE BATTERY MGMT
Charger
Like other UPSs, the Powerware UPS is equipped with a charger that charges the battery.
However, Powerware uses a unique charging technique that extends the life of the battery . . .
ChromScience Sdn Bhd
Slide 23 04/09/23
ABM – ADVANCE BATTERY MGMT
ABM uses a 3-stagecharging system:
First, the battery is quickly charged to 90% to make surethe UPS is prepared for thenext power outage.
Second, ABM finishescharging the battery witha more moderate float charge.
Charger
ChromScience Sdn Bhd
Slide 24 04/09/23
ABM – ADVANCE BATTERY MGMT
Charger
Third, ABM turns the charger off.
This prevents the batteriesfrom being overcharged.
Feature Focus:
Turning the charger OFF
ChromScience Sdn Bhd
Slide 25 04/09/23
The Result?
The service life of the batteries is doubled so youwon’t have to replace them as often as you would with competitive models.
ABM – ADVANCE BATTERY MGMT
ChromScience Sdn Bhd
Slide 26 04/09/23
• Doubles battery service life by charging only when needed
• Optimizes recharge time
• Does not trickle charge & starve the electrolyte
• Microprocessor controlled - Only true & automatic battery check (periodic, controlled discharge) for most accurate advanced failure protection
• Sleep Feature - no unnecessary battery “drain”
ABM – ADVANCE BATTERY MANAGEMENT
ChromScience Sdn Bhd
Slide 27 04/09/23
Feature Focus: Buck/Double Boost Voltage Regulation
LanSafe III demonstrates Buck and Boost voltage regulation in action(Buck mode displayed)
ChromScience Sdn Bhd
Slide 28 04/09/23
ChromScience Sdn Bhd
Slide 29 04/09/23
PRODUCT LINE – Low Cost
Eaton NV Series- 1 UPS for PC, Network Switch
•Basic line interactive•800 VA
ChromScience Sdn Bhd
Slide 30 04/09/23
PRODUCT LINE – Rack mount
Model 5115 RM- For distribution rack switches, space conscious
• 700 – 1500VA• Line Interactive UPS• ABM• Optional interface card for remote monitoring
ChromScience Sdn Bhd
Slide 31 04/09/23
PRODUCT LINE – Complete Solutions
• 700 – 3000VA, 0.9 pf• Double conversion, On-Line technology• Rack mount / tower design• Remote monitoring
Eaton Powerware 9130- For servers, core switches.
ChromScience Sdn Bhd
Slide 32 04/09/23
PRODUCT LINE – Centralised UPS
Eaton Powerware 9155 - 9355- Single protection for Data Center
• 8 – 40kVA, 0.9 pf• Double Conversion, On-Line UPS• ABM
ChromScience Sdn Bhd
Slide 33 04/09/23
- Base in Raleigh, USA. Presence at 125 countries worldwide. - Global leader in electrical systems, components of power quality & control.
- 40 years in power protection business. - Mission : to give customers confidence that power problems will not disrupt their systems, data, and operation.
- 2007 : acquire MGE UPS. - Ranked no:1 in UPS market >5 kVA , no:2 in < 5kVA market.
WHY EATON POWERWARE
ChromScience Sdn Bhd
Slide 34 04/09/23
Incorporated : 21 September 1994 ( 16 years in operation )
Register : Kem. Kewangan ( Bumiputera Status ) No: 357-00033309
Kepala Bidang : perkakasan elektrik, stesen janakuasa elektrik dan peralatan generator /alat ganti, motor dan alatubah, pembekalan peralatan kelengkapan saintifik dan perubatan, perkakasan perubatan pakai buang, kimia dan makmal
Pejabat Operasi : Batu Caves, Selangor ( Ibu Pejabat ) Lain-lain cawangan di Pulau Pinang, Kuala Trengganu dan Kota Bharu.
Staff Strength : 16 orang.
Installation Base : SUK Perak, SUK Kedah Univ. Islam Antarabangsa, UiTM Shah Alam, Machang BIMB, Bank Muamalat Kilang NSTP, Naza, Proton HUSM, HUKM, H.B KTrengganu, H.Selayang
WHO WE ARE ?
ChromScience Sdn Bhd
Slide 35 04/09/23
‘Thanks for listening’
SHAMSUL BAHRI013 - 9229965
Kota Bharu branch09- 7648609
FEEDBACK