UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
Transcript of UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
1/285
" UPS Distribution System" UPS Distribution System
andand
UPS FundamentalsUPS Fundamentals
In The Petrochemical IndustIn The Petrochemical Indust
Presented to the:
IEEE PCIC 2006 Conferenc
Philadelphia, Pennsylvania September 14, 200
Presenters:
Roy E. Coss, Jr., P.E. Donald G. DunnPowell Electrical Systems, Inc. Lyondell Chemicals P
Houston, TX Channelview, TX
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
2/285
TuTu
Introduction (general, historical perspective) Purpose of a UPS
UPS system (types, configurations, trends, redundancy, hoperation)
Battery selection
Magnetic components used in UPS systems (feisolation and constant voltage transformers, re
UPS system application (system design and integratioof distribution and protection equipment in Usecondary networks)
Review load types and design application cons
Power system analysis and harmonic consideratypical applications
System acceptance (testing, commissioning, performanmaintenance)
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
3/285
IntroductionIntroduction
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
4/285
UPS systems installed in petrochemical faciprovide uninterruptible power to process costandby and other critical equipment. Accepinstallation, verification and maintenance asis continuously available. This intensive haltutorial provides the needed background to understand UPS distribution systems and Uapplications in petrochemical industry appli
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
5/285
Historical PHistorical P
UPS Distribution Systems Are Copied FromProject To The Next
Industry practice
This is the way we have always done it
Time-Current Curves not produced Internal protective device not considered
System selectivity not reviewed
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
6/285
Historical PHistorical P
UPS Systems Supply Critical Process Load
DCS & PLCs
Critical Process Alarm Systems
SIS Systems
APC & Custody Transfer Systems Process Analyzers
Gas Detection Systems
Fire Protection Systems
Critical Telephone Circuits
Emergency Lighting Custom Load and Driver Control Systems
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
7/285
What is the PurposeWhat is the Purpose
Uninterruptible PowUninterruptible PowSystem (UPS)?System (UPS)?
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
8/285
It is a modular unit or assembly of componenprovide quality and continuity of AC power fmanufacturing unit or units
Note: The MAJORITY of instruments, process me
process control devices rely the UPS for electrical e
In many instances, a UPS provides AC powerequipment that is deemed MISSION CRITIC
Safety
EnvironmentalReliability & Operational Cost
Purpose of a Uninterruptible Power
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
9/285
Critical Crit ical
Not all instruments and control devices are critical If the LOSS of an instrument or control system creates a ha
condition, can cause an environmental incident, or trips a pis typically deemed a CRITICAL device or system.
Examples
Process Measurement DevicesTransmitters and Switches used in process control
Basic Process Control Systems (BPCS)DCS, PLCs etc.
SIS Systems
Non-critical InstrumentsExamples
Process Measurement Devices that are for indication only
BPCS for non-critical control
Purpose of a Uninterruptible Power
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
10/285
Critical PowCritical Pow
ComplexMultiple Power Supplies
Can be 120 VAC powered 24 VDC sources
UPS System
Batteries
DistributionShort Circuit Protection
Typical Power Source Motor Control Cente
Thermal-Magnetic Breaker
Single Transformer
Typically Double-Ended without Automatic Switch
Separate Power Sources for increased reliability
(i.e. Separate Feeders from Separate Transforme
the Main Substation)
Purpose of a Uninterruptible Power
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
11/285
Critical Power System ExCritical Power System Ex
Provides Reliable Power
Maintains Critical Loads During AbnoSituations
Disturbances such as sags, swells, surges
Short Circuits
Maintenance can be provided online
Purpose of a Uninterruptible Power
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
12/285
What is a UPS?What is a UPS?
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
13/285
TypTyp
Management and Operations Believe it
Unreliable Power System
Trips process units during maintenance
Unavailable Power System
System that has unlimited capacity
OR ALL OF THE ABOVE!
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
14/285
UPS Actual CoUPS Actual Co UPS Components
Rectifier/Charger
Inverter
Ferro & PWM Technologies
Alternate Input
Static Switch Manual Bypass Switch
Battery
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
15/285
RectifiRectifi
Rectifier/Charger Full-wave controlled rectifier for changing
Typically it is a phase-controlled, silicone
rectifier circuit combined with a voltage re
Provides voltage and current control ofoutput
Feeds the battery system
Feeds the UPS inverter
Appropriately Sized Sized for load and to charge the batter
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
16/285
Inverter The inverter converts a DC waveform (supplied by
Rectifier/Charger/Battery) into an AC waveform
Output will be supplied to either the load terminals
the static transfer switch (depends of system config
There are two different technologies to accom Ferroresonant
Norm for many years
Larger System
Commutated square wave bridge with an oscil
filtering components PWM (Pulse Width Modulation)
Utilizes solid-state power electronic devices
Minimum parts count and reduced magnetic el
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
17/285
FeFe
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
18/285
UU
Cybe
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
19/285
UU
SCI
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
20/285
AlternAltern
Alternate Source Redundant Power to UPS system
Inverter synchronizes to Alternate Source
Waveforms are in sync (eliminates tran
Power Source During the Following: Inverter fails
Normal Power Source is lost
And battery system is discharged
Short-circuit or overload conditions Provides BYPASS power for off-line main
the Rectifier and Inverter
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
21/285
ManuManu
Manual Bypass Permits the power to flow from the alterna
the load by bypassing the Inverter and Sta
Permits UPS isolation
Permits maintenance to be performed on thcomponents
Permits start-up and shut-down of the syst
Can be internally or externally mounted
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
22/285
AlternatAlternate
Manual Bypass SwManual Bypass Sw
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
23/285
ManuManu
SwSw
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
24/285
WhaWhat
Static Switch FAST acting
Typically can transfer within cycle (4 m
Is supposed to transfer output power from
to the Alternate Source without any power
Transfer normally at the zero-wave crossin
waveform monitoring
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
25/285
Input CircuInput Circui
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
26/285
Meters and MMeters and M
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
27/285
PP
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
28/285
UPS SYSTEMSUPS SYSTEMS
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
29/285
System Types
Hardware Components / Block Diagr
Configurations
Redundancy
Applicable To Petrochemical Industry
TopicTopic
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
30/285
System Types (from energy storage p Static (chemical energy)
High Efficiency, High EMI / THD pollution
High Reliability and Availability
Most popular
Poor performance with non-linear/non-balanced
High Cost to achieve very high reliability Rotary (kinetic energy)
More reliable than Static UPS
Availability lower from Static UPS
Large size
Electro-mechanical i.e. involved maintenance
Desirable for high power and/or non-linear/non-bapplications
High transient overload capabilities
High efficiency, Low EMI / THD pollution
Hybrids (of static, rotary and engines) (mixture o
SysSys
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
31/285
System Types (from switching perspe Dual Conversion
On-Line UPS
Off-Line UPS
Single Conversion Line-Interactive UPS
SysSys
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
32/285
Static, On-Line UPS
StatiStati
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
33/285
Static, Off-Line UPS #1
StatiStati
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
34/285
Static, Off-Line UPS #2
StatiStati
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
35/285
Static, Line-Interactive UPS #1
StaticStatic Line Line
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
36/285
Static, Line-Interactive UPS #2
StaticStatic Line Line
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
37/285
Rotary UPS
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
38/285
Hybrid, Static-Rotary UPS
HybridHybrid StSt
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
39/285
Most Popular Industrial Systems Con On-Line
Technology
Ferroresonant
PWM
Magnetic / PWM Hybrid / Active Filter / PFC Re
Power
1-phase (< 5-10kVA)
3-phase (>15kVA)
Galvanic Isolation
Redundancy
2x100% or 3x100% Feed-Through
Trends in IndustriaTrends in Industria
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
40/285
2x100% or 3x100% with load sharing
ReRe
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
41/285
2x100% with load sharing, with galvanic is
ReRe
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
42/285
Typical of OneTypical of One
Rectifier
Inverter
StaticSwitch
MBS
AltSourceInputBattery
Set
OutputCircuit
Breaker
InputCircuit
Breaker
UPS System Limitations Difficult to Replace
All Output Power
Runs Through MBS
Not all components
can be PMd orRepaired
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
43/285
AlteAlte
ConfiConfigthe samethe same
Second TapAlternate SCan Backfe
Distribution
Controvers
Allows for ComponentReplacing ESystem witOutage
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
44/285
AlteAlte
CoCoof Anotheof Anothe
Second TapAlternate Sfeed into se
Distribution
Allows for ComponentReplacing ESystem wit
Outage
Rectifier
Inverter
StaticSwitch
MBS
AltSource
InputBatterySet
OutputCircuit
Breaker
InputCircuit
Breaker
AltSourceXfmr
UPS System
Custom Distribution
Panel (Dual Mains w/
independent branch
circuits)
UPS System
480V Distribution
Sources (segregated
from main substation)
A B
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
45/285
Feed-through, concept
ReRe
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
46/285
ReRe
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
47/285
BATTERY SELECTIONBATTERY SELECTION
UPS SYSTEMUPS SYSTEM
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
48/285
Battery Selection F
Battery
Battery Basics (definitions, technologyconstruction, sizing and capacity)
Battery Comparison
Other Considerations
Maintenance
Derating
Standards
Hydrogen Emission Generation
TopicTopic
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
49/285
Battery Selection F
BatteryIn general, storage of electrical energy requireconversion into another form of energy. A Badevice that uses chemical compounds as the smedium. During discharge, a chemical procesthat generates energy, which can be drawn fro
battery in the form of an electric current at a cvoltage.
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
50/285
BatterBatter
Battery Selection F
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
51/285
BatterBatter
Battery Selection F
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
52/285
BatterBatter
Battery Selection F
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
53/285
Voltage - Force which puts electrons into motiNominal Battery Voltage Voltage measured battery terminal which represents the average va discharge period
End of Discharge Voltage (Cut-off Voltage)
which the battery discharge is terminated Maximum System DC System Voltage Max
voltage which can be tolerated by the loads
Minimum System DC Voltage Minimum Vowhich the loads will continue to operate
Nominal System Voltage Arbitrary equipmewhich has been standardized by NEC (12, 24, 110, 220, 240, 360 or 480V)
Battery Selection F
Battery BasicsBattery Basics --
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
54/285
Battery Selection F
Battery BasicsBattery Basics -- TT
Nickel Cadmium Battery Discharge Profile
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
55/285
Battery Selection F
Nickel Cadmium Battery Discharge Profile
Battery BasicsBattery Basics -- TT
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
56/285
Battery Selection F
Deep Discharge
Lead Acid Battery cycle life is limited to less than 15
discharge cycles (The more you discharge the battery th
will reach the end of life)
Discharge below 1.8 volts per cell can permanently d
acid batteries
Battery will sulfate causing higher internal resistancapacity
Severe deep discharge for extended periods of time
internal short circuit failure
For short durations, the end of discharge voltage may
if the discharge is followed by an immediate recharge:
Battery BasicsBattery Basics -- TT
1.65 1 HOUR OR LESS
1.70 3 HOUR OR LESS
1.75 5 HOUR OR LESS
1.80 8 HOUR OR LESS
END OF DISCHARGE
VOLTAGE
DISCHARGE
RATE
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
57/285
Battery Selection F
Proper Sizing and Cell Selection (Most ImportaVoltages Required)
Maximum System DC Voltage (Determines the max
number of cells that can be equalize charged without da
loads)
Minimum System DC Voltage (Determines the end
voltage)
Both of the Following Equations Must be True
Battery BasBattery Basi
sMax.DCVolt cellltsEqualizeVo
ofcells
/
#
DCVoltsMin. = geVolraEndofDisch
ofcells#
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
58/285
Battery Selection F
Float Charging Voltage Normal float charginmaintains a steady float charge to keep the battcharged
Equalize Charging Voltage Elevated charginused to fast charge the battery or as a maintena
Boost Charge Charging elevated above an eqcharge for reviving a battery after manufactureabuse
Battery BasicsBattery Basics --
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
59/285
Battery Selection F
Capacity Measure of the usable energy that cdischarged from a battery (typically the larger tthe more active material to create energy)
Capacity is a Function of:
Temperature
Discharge RateVoltage Window
Battery Age
State of Charge
Note: The slower the battery discharge, the more
energy can be extracted from the battery
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
60/285
Battery Selection F
Capacity varies by end of discharge voltage:
Battery BasicsBattery Basics
[ ]min60/1min1 hr amps 92.9595 =
[ ]min60/1min1 hr amps 32.5319 =
Amps X the time period, the more capacity is the lower end voltage: 1.00 EODV: at 60 seconds
1.14 EODV: at 60 seconds
Amps to 1.00 EODV
Cell 8 5 60 5 1
Type hr hr min min min s
SBM231 29.1 46.2 173 427 595 8
Amps to 1.14 EODV
Cell 8 5 60 5 1
Type hr hr min min min s
SBM231 27.7 43.4 105 228 319 4
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
61/285
Battery Selection F
Battery BasicsBattery BasicsNickel Cadmium Battery Discharge Profile
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
62/285
Battery BasicsBattery BasicsNickel Cadmium
Deep Discharges DO NOT Affect Performance and
Permanent Damage to NICADS
Allows Long Term Open Circuit Storage
Nickel Cadmium Offer the Most Deep Cycles (Full
Discharges) of any Technology Available:
Battery Selection F
TECHNOLOGY # OF CYC
Sintered/PBE NICAD > 20
Pocket Plate NICAD > 15
Flooded Plate Calcium approx . 50
Flooded Plate Antimony 600-8
Flooded Plate Selenium 600-8Flooded Plante' 600-8
Valve Regulate Lead Acid approx. 50
* TO 80% DEPTH OF DISCHARGE
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
63/285
Battery Selection F
Battery BasicsBattery Basics
Capacity varies by rate of discharge: Using thagain, more usable energy is extracted at slow
1.00 EODV at 60 seconds:
[ ]min60/1min1 hr Ahrsamps 92.9595 =
[ ]hr8 Ahrsamps 8.2321.29 =
1.00 EODV at 8 hours:
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
64/285
Battery Construction
Battery Components
Case or Jar
Each Jar Typically has 3-4
Cells
Electrolyte
Grid or Current Collector
Active Material
Separator
Battery Selection F
- +
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
65/285
Battery BasicsBattery Basics
Lead Acid Chemical Reaction
Battery Selection F
Discharge
PbO2 + Pb + 2H2SO4 2PbSO4+
Charge
- + - +
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
66/285
Battery BasicsBattery Basics
NiCad Chemical Reaction
Battery Selection F
Discharge
2NiOOH + Cd + 2H2O 2Ni(OH)2+ Cd(OH
Charge
- + - +
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
67/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
68/285
Battery Selection F
Plate construction
Plant Plate Grid Plate Tubula
Battery BasicsBattery Basics Lead Acid CoLead Acid Co
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
69/285
Electrode Materials of Construction: Pure Lead
Lead Selenium
Lead Antimony
Lead Calcium (Ag, Sn, Zn, Mg)
Alloys in the lead current collector offer NO teadvantage
Used to reduce manufacturing costs by makingeasier to mass produce
Battery Selection F
Battery BasicsBattery Basics Lead Acid CoLead Acid Co
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
70/285
Pure Lead
Lead Selenium
Lead Antimony
Lead Calcium
Battery Selection F
Battery BasicsBattery Basics Lead Acid CoLead Acid Co
Best ElectricalPerformance
L
Poorest ElectricalPerformance
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
71/285
Pure Lead
Lead Selenium
Lead Antimony
Lead Calcium
Battery Selection F
Battery BasicsBattery Basics Lead Acid CoLead Acid Co
Most Reliable H
Least Reliable
+ Plate
Poisoning
+ Plate
Growth
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
72/285
Plastic Bonded ElectrodePowdered active material
Plastic bonded to perforated steel strip
Withstand extreme temperatures
Sintered Plate Electrode
Powdered nickel materialSintered onto perforated steel strip
Impregnated with active material
Pocket Plate ElectrodePowdered active material
Suspended in perforated steel envelope
Fiber Plate ElectrodeMetallic sponge nickel
Impregnated active materials
Battery Selection F
Battery BasicsBattery Basics Nickel Cadmium CoNickel Cadmium Co
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
73/285
Plastic Bonded Electrode
Sintered Plate Electrode
Pocket Plate Electrode
Fiber Plate Electrode
Battery Selection F
Battery BasicsBattery Basics Nickel Cadmium CoNickel Cadmium Co
Best Cycle Life
Poorest Cycle Life
NOTE: Fiber plates are not recommended for continuous float charge to hotspots and can short circuit on float charge and cycling
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
74/285
Battery Selection F
Plate construction
Pocket PlateSintered Plate Fiber P
Battery BasicsBattery Basics Nickel Cadmium CoNickel Cadmium Co
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
75/285
Battery Selection F
Battery BasicsBattery Basics Technology CTechnology C
Battery Type Nickel Cadmium LeElectrolyte Potassium Hydroxide Su
Symbol KOH
Specific Gravity 1.2 1.215, 1.21
Inert to all internal
components
Reacts w
Does not change propertieswith state of charge
Changes po
Battery System
Advantages/Disadvantages
Chemically and physically
strong
Chemica
Minimum maintenanceregardless of temperature
More mai
More resistant totemperature extremes
Sensitive
e
More resistant to electrical
abuses
Le
* different plate technologies have different SG's
Electrolyte
Advantages/Disadvantages
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
76/285
Battery Selection F
Despite all of the advances in power electronics UPS systems
Battery remains the key component in determining syst
Battery chemistry has not changed much over the years
Batteries have a finite age
They are expensiveTheir life is shorter than the manufacturer warrants
Require a tremendous amount of maintenance
One weak cell can yield the complete battery stri
While design and installation are critical, the key
UPS system is BATTERY MAINTENANCEIncludes: connection maintenance, internal diagnostics
leaking post seals
Battery BasicsBattery Basics Other ConsOther Cons
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
77/285
Battery Selection F
Battery sizing is based on the time and load powRefer to IEEE 485 and 1184 for more details
UPS batteries must be matched to the application
Choice of battery design depends on the environmaintenance and application
Maintain approximately 77 deg F for longer battevery + 15 deg F cuts life in half
Colder is not necessarily better because CAPACITY is
New battery assemblies should be certified priorcommissioning
Refer to IEEE 450 for commissioning details
Battery BasicsBattery Basics Other ConsOther Cons
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
78/285
Battery Selection F
Care should be taken when storing batteries prioservice after manufacturer date
Lead Antimony refreshing charge for every 3 months
Lead Calcium refreshing charge for every 6 months o
VRLA storage times vary based on storage temperature
manufacturer)
FAILURE TO GIVE A REFRESHING CHARGE befo
recommended storage interval may result in plate sulfa
adversely affect battery capacity
Battery BasicsBattery Basics Other ConsOther Cons
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
79/285
Battery Selection F
Float current demand in specification ap
when the electrolyte temperature is 77
(25C). The value will double for every (8C) of temperature rise. If temperature
the current value will be halved for ever
(8C) decrease. Some battery float curr
demand will increase with aging.
Float adjustment
Battery BasicsBattery Basics MMa
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
80/285
Battery Selection F
Float characteristics
Battery BasicsBattery Basics MMa
SOURCE: H. A. KIEHNE, BATTERY TECHNOLOGY HANDBOOK, 2003
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
81/285
Proper Flo
Maximize
Maximize
Reduces b
Battery Selection F
Battery BasicsBattery Basics MMa
Battery Type
(Specific gravity 1.24)
Lead Antimony Types:
(Specific gravity 1.215)Lead Calcium Flooded Types:
(Specific gravity 1.215)
Lead Calcium Flooded Types:
(Specific gravity 1.250)
Lead Calcium Flooded Types:
(Specific gravity 1.30)
Pure Lead Plante' Types:
(Specific gravity 1.210)2.27 @ 20 deg C
volts per cell
(-2.4 mv per deg C
rise over 20 deg C
2.15 to 2.25 volts
per cell
Recommended
Float Voltage
RangeLead Selenium / Low
Antimony Al loy Type:
Lead Calcium Valve
Regulated Types:
2.15 to 2.25 volts
per cell
2.15 to 2.17 volts
per cell2.17 to 2.25 volts
per cell
2.23 to 2.33 volts
per cell
2.28 to 2.37 volts
per cell
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
82/285
Initial Charge
Recommended voltages and time periods
Battery Selection F
Battery BasicsBattery Basics MMa
Lead Antimony Types
Cell Volts Cell Volts
2.24 444 - - 2.24 200
2.27 333 - - 2.27 150
2.30 210 - - 2.30 120
2.33 148 333 - 2.33 90
2.36 100 235 400 2.36 75
2.39 67 160 267 2.39 60
2.42 48 108 182
2.45 38 73 125
2.48 36 55 83
2.50 32 44 60
NOTE: Time periods listed in Tables are for cell temperatures from 70
deg F to 90 deg F. For temperatures 55 deg F to 69 deg F double the
number of hours. For temperatures 40 deg F to 54 deg F use four times
the number of hours.
Time-Hrs.
1.250
S.G.
Time-Hrs.
1.300
S.G.
Lead Calcium Types
Time-
Hrs.
1.215
Time-Hrs.
1.215
S.G.
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
83/285
Battery Selection F
Battery BasicsBattery Basics MMa
Float Voltage Float voltage can be a misleadinWhile voltage readings of individual cells are importanThe sum of voltages of all the batteries MUST equal t
charger (resistive losses excluded)
Normal reading does not necessarily indicate the condi
An abnormal reading requires further investigation
Specific Gravity ReadingsSulfate is part of the electrochemical process
Discharged State - some of the sulfate migrates to thacid is reduced in specific gravity
Fully Charged State sulfate is in the acid and the s
normalThe difficulty in interpreting specific gravity readings
cell and ambient temperatures
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
84/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
85/285
Battery Selection F
Battery BasicsBattery Basics MMa
Temperature Effects of temperature extremes (internal) and ambient (external) conditions impTypical battery systems are designed for 20 years @ 7
15 deg F increase in temperature cuts battery life in ha
Increased temperature causes faster positive grid corroother failure modes
Discharge Current and Time Online monitorindischarge current and time calculations to determhours removed and replaced Presumably the benefit allows one to calculate battery
Currently, the only sure way to determine true capacity
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
86/285
Battery Selection F
Battery BasicsBattery Basics MMa Intercell Connection Resistance
One of the more important parameters to testMore than 50% of battery bank failures are related to loose o
connectors
If resistance measurement exceeds the lower end of the ohm
is inadequate
Capacity (load test) Only true method of deterbattery systems actual capacityThe test has limited predictive value depending on how frequ
(each load test subtracts from the life expectancy of the batte
Most manufacturers recommend capacity tests every 3 to 5 y
Impedance Internal impedance tests measure tof a cell to deliver currentComponents of impedance (resistive and capacitive reactanc
capacity
Although the correlation is not 100% it is an excellent way to
Impedance is inversely proportional to capacity
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
87/285
Battery Selection F
Battery BasicsBattery Basics MMa
As impedance increases, battery capacity decrea Batteries do not have to be offline to test interna
End Voltage vs. Impedance
0
0.5
1
1.5
2
2.5
Data Points
Impedance(milliohms)
Cell Number 11 15 16 3 18 22 13 24 10 14 23 20 5 9 6 4 21 8 1 12 2
Z 0.3 0.3 0.3 0.6 0.6 0.6 0.70.7 0.7 0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.9 0.9 0.90.9 1.0
Vdc 2.0 2.0 2.0 2.0 2.0 1.9 1.91.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.81.7 1.8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
88/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
89/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
90/285
Derating with ambient temperature
Battery Selection F
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
91/285
Battery Selection F
Typical discharge characteristics
(equal weight same discharge conditions)
Derating rate of discharge and design margin
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
92/285
Battery Selection F
Derating rate of discharge and design marginBattery BasicsBattery Basics
SOURCE: H. A. KIEHNE, BATTERY TECHNOLOGY HANDBOOK, 2003
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
93/285
Battery Selection F
Derating internal resistance change
Battery BasicsBattery Basics
SOURCE: H. A. KIEHNE, BATTERY TECHNOLOGY HANDBOOK, 2003
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
94/285
Battery Selection F
Discharge available capacity available with amtemperature change
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
95/285
Specification and Sizing:
IEEE 485 Recommended Practice for Sizing L
Batteries for Stationary Applications
IEEE 1115 Recommended Practice for Sizing N
Cadmium Batteries for Stationary Applications
IEEE 1184 Guide for the Selection and Sizing
Uninterruptible Power Supplies
IEEE 1106 Recommended Practice for Installa
Maintenance, Testing, and Replacement of Vente
Batteries for stationary Applications
Battery Selection F
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
96/285
Hydrogen Emission Generation
Battery Selection F
Battery BasicsBattery Basics
Hydrogen Gas Evolution Calculation
VH2IF CapAhr, K, N, CType,( ) IFCapAhr
100 K N CType
Where:
VH2 - Volume of evolved hydrogen per hour
IF - Float current per 100Ahr of installed battery bank capacity in [A] and
temperature compensated
CapAhr - Installed battery bank capacity in [Ahr]
K - Maximum hydrogen evolution rate constant dependent on plate type:
KAntimony_US 2.67 104
ft
3
A
KAntimony_SI 7.56 106
m
3
A
KLead_US 1.474 102
ft3
A
N - Number of cells in battery bank
CType - Constant dependent on battery construction:
CFlooded 1.00
CGNB_AbsolyteIIP 0.01
Hydrogen Gas Evolution Calculation
VH2IF CapAhr, K, N, CType,( ) IFCapAhr
100 K N CType
Where:
VH2 - Volume of evolved hydrogen per hour
IF - Float current per 100Ahr of installed battery bank capacity in [A] and
temperature compensated
CapAhr - Installed battery bank capacity in [Ahr]
K - Maximum hydrogen evolution rate constant dependent on plate type:
KAntimony_US 2.67 104
ft
3
A
KAntimony_SI 7.56 106
m
3
A
KLead_US 1.474 102
ft3
A
N - Number of cells in battery bank
CType - Constant dependent on battery construction:
CFlooded 1.00
CGNB_AbsolyteIIP 0.01
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
97/285
Hydrogen Emission Generation
Battery Selection F
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
98/285
Hydrogen Emission Generation
Battery Selection F
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
99/285
What does this mean?
Battery Selection F
Need to verify with standards and local jurisd
API RP500, Section 6.3.2.1 (2ndEd. Nov 1997) (below 25% of LFL - Low Flammable Limit )
Or
NEC 2005, Art 500, Table 5.1
Or Local jurisdiction requirements
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
100/285
In the example, the hydrogen concentration in room for 8-hour period is much less than 25% allowable requirement for adequate ventilationrequirement per API RP500.
The NFPA 497, Table 2-1 lists Hydrogen LFL=4%
The API RP500 required 24% of LFL=4% calcula Calculated H2 concentration the room is 0.00391%
If flooded batteries were used, H2 concentration w
0.391%
Battery Selection F
Battery BasicsBattery Basics
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
101/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
102/285
Hysteresis Influence on Performance
Transformer
Isolation Transformer
Ferroresonant Transformer / Constant VoltaTransformer
Reactor / Multi-winding Reactor / Combina
Magne
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
103/285
Hysteresis Influence on Performance
Magn
iL
=
HysteresisHysteresis
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
104/285
Hysteresis Influence on PerformanceMagnetic Losses, Regulation and Inrush Current
%100*)()()(
loadfullU
loadfullUloadnoU
= 10*loadcu
PP
histFe PPP eddy +=
2max**
2* )( BfdPFe =
cHBfPhist max***2=
RIPCu *2=
N
lHo
**4.0
)(Im
=
Magne
HysteresisHysteresis
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
105/285
Transformer
Magne
TTr
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
106/285
Construction
Magne
TransformerTransformer -- CoCo
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
107/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
108/285
Constant Voltage Transformer (CVT) / FerrTransformer
Advantages:
Constant voltage output for variation in inpu
Blocks harmonics from saturation in the CVand from input and output of the CVT
Ride through ability (prime reason to use
systems)
Disadvantages
Low efficiency
Intolerant to frequency changes
Magne
Transformer CVT &Transformer CVT & FerFer
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
109/285
Constant Voltage Transformer (CVT) / FerrTransformer
AC INPUT
POWER
AC OUTPUT
POWER
LC RESONANT
CIRCUIT
TANK CIRCUIT
Magne
Transformer CVT &Transformer CVT & FerFer
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
110/285
Constant Voltage Transformer (CVT) / FerrTransformer
Magne
Transformer CVT &Transformer CVT & FerFer
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
111/285
Constant Voltage Transformer (CVT) / FerrTransformer
Magne
Transformer CVT &Transformer CVT & FerFer
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
112/285
Reactor, Multi-Winding Reactor, Combinat
Increase input impedance
Provide di/dt smoothing component
Part of LC filters
Part of specialized filters with different in and pa(Harmonic Mitigating Transformer)
Magne
ReactoReacto
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
113/285
UPS SYSTEM APPLICAUPS SYSTEM APPLICA
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
114/285
System Components
System Design and Integration Consideratio
Distribution and Protection Component Sele
Additional Design Consideration:o Load Types
o Static Switch Operation
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
115/285
System Components
UPS Package:
Components discussed previously in the pre
Primary network:Components connected to UPS System upst
as seen from load perspective
Secondary network:
Components connected to UPS System dowUPS as seen from load perspective
UPS Sy
System CoSystem Co
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
116/285
System Design and Integration Consideratio
General
Reliability
UPS System
Primary network Secondary Network
Enhancement
Special Considerations
Application Location (Onshore, Offshor
etc. ) Unusual requirements
Voltage, Power and Energy Flow effects on
Specification
UPS Sy
System Design & System Design &
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
117/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
118/285
General:
System design and space planning
UPS system primary purpose
Operating Hours
Type (see previous chapters) Capacity (centralized, local)
Battery (see previous chapters)
Systems
Expansion provisions
Cost
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
119/285
General:
Installation and environment
Loading / Offloading conditions
Space (installation, operation and maint
Installation practices
Environment (temperature, humidity, ha
classification etc.)
System heat rejection vs. environmental
System heat rejection vs. backup/battery
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
120/285
General:
Maintenance and operation
Monitoring (on-line) (voltages, currents
battery etc.)
Preventive maintenance (off-line)
Operation Autonomy
System Settings
Connecting components checking
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
121/285
Reliability:
UPS System
Primary network
Secondary Network
Enhancement
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
122/285
Reliability: UPS System (from vendor)
Note:
MTBF, MTTR do not include batteries, interco
cables outside of enclosure and internal operati
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
123/285
Reliability: Primary network
Reliability Indices:
UPS Sy
servedcustomersofnumberTotal
onsinterrupticustomerofnumberTotal=SAIFI
servedcustomersofnumberTotal
durationsoninterrupticustomerallofSum=SAIDI
demandedservicehoursCustomer
tyavailabiliservicehoursCustomer=ASAI
SAIDI
SAIFI=CAIDI
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
124/285
Reliability: Primary network
Parameters Influencing Indices
Location
Routing
Environmental Exposure Voltage
Supply configuration
Improving
Identifying reliability driving elem
Evaluation
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
125/285
Reliability: Secondary Network
Indices not applicable
How fast can be repaired
Plant running or not
Etc.
Parameters Influencing Reliability
Location
Routing
Environmental, process, and other e
Voltage
Supply configuration
Maintenance
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
126/285
Reliability: Enhancement
How much reliability is needed (0.9999
System approach
Redundancy
Complete primary, secondary and
Most fragile components
Enhanced monitoring
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
127/285
System Design and Integration Consideratio
Special Considerations
Application Location
Onshore (petrochemical, pipeline, c
etc.)
Offshore (process, NAV lights, CO
etc.)
Overseas (process, control room, sp
Unusual requirements
i.e. bump-less transfer time no voltage
UPS Sy
System Design & System Design &
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
128/285
UPS Sy
System Design & System Design &
System Design and Integration Consideratio Voltage, Power and Energy Flow
UPS Load Flow - Link
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
129/285
Location of equipment
Application and block diagram
Type Equipment
Primary and secondary networkGrounding
Input Power ratings and quality
Type of Load
Output power rating andquality
Battery and battery charger(options)
Service condition
Monitoring requirements
UPS Sy
System Design & System Design &
System Design and Integration Considerat
Specification List (Minimum Requirement
Monitoring In
Installation re
Provision for (load sharing, current capabi
Maximum inp
Maximum loa
Amps and PF Overload capa
long
Steady state v
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
130/285
Not all UPS Systems areNot all UPS Systems are
UPS Systems
Commercial Grade
Typical utilized in IT applications
Lack flexibility and robustness
Tend to utilize PWM
Static switches are rarely power transist
Utilize contactors
Typically use sealed batteries
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
131/285
SizingSizing
UPS System Sizing Principles
Size for expected loads plus margin for gr
Size batteries at full load for a minimum o
Size normal power source for load for load
+ 25% DO NOT use the typical 125% of UPS
Typically 1-phase below 50kVA and 3-ph
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
132/285
UPS System LUPS System L
UPS System Limitations
Batteries will eventually discharge
UPS is a complex system
Will not last forever
Requires periodic maintenance
Human error
UPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
133/285
DistributiDistributi
Distribution Panels What should I use ? Breaker or a Fuse
UPS Sy
Breaker: Can reset a breaker
Breakers are current limiting
Fuse: Fuse has to be
Fuses are curr
Fuses may
Will be covered in mover detail later in
presentation
SOWhat should be used Breaker or
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
134/285
Fused Panel
UPS Sy
FF
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
135/285
UPS Sy
FF
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
136/285
UPS Sy
FF
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
137/285
UPS Sy
BreBre
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
138/285
Power SuPower SuUPS Sy
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
139/285
OnOn
PP
UPS
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
140/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
141/285
PowePowe
ComCom
UPS S
24 VDC
PowerSupply *
24 VDC
PowerSupply *
24 VDC
Distribution
To
Field Devices
Typical Dual Input
Power Supply
Custom UPS &
Alternate Source
Distributio n Panel
* One or more power supplies as needed.
Rectifier
Inverter
Static
Switch
MBS
Alt
Source
InputBattery
Set
Output
CircuitBreaker
Input
Circuit
Breaker Alt
Source
Xfmr
UPS System
480V Distribution Sources
(segregated from main
substation)
A B
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
142/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
143/285
Load Types in Secondary Distribution Systemnon-liner with high THD, Regenerative)
ITI (CBEMA) Curve
Benchmarks For DCS, PLC and Critical Instru
Short-Circuit Output Magnitude and The Alter
Single-Phase or Three-Phase UPS Output Volt
Protecting The UPS Static Switch
Molded Case Circuit Breakers Versus Fuses
UPS System Loads
Example / Application:
120V UPS Distribution System Selectivity 240V UPS / 480V Distribution System Sele
Example
Application Guideline Summary
Review Load Types & Design Application
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
144/285
Load Types from UPS and static switch opeperspective
RL linear
RC linear
RL non-liner with high THD
Regenerative
Load Types in Secondary Dis
LL
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
145/285
RL linear loads
Static power supplies
Distribution transformers
Long feeders with RL loads
Inverter: operates in design operating range
Static Switch: detection time and transfer tim
increase due to the additional inductance
RL LinRL Lin
Load Types in Secondary Dis
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
146/285
RC linear loads
Any load connected to long cable (transmission
Inverter: operates out of design operating ran
verification with vendor capabilities and stab
Static Switch: detection time and transfer tim
increase due to the additional line capacita
capacitance is so large that influence system
commutation could be unstable and/or long
non-bump-less transfer
RC LinRC Lin
Load Types in Secondary Dis
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
147/285
RL non-linear loads with high THD
Switching power supplies (PC, PLC, DCS etc.)
Emergency lights
Assure THD is in operating spec of UPS
Inverter: operates in design operating range
Static Switch: detection time and transfer tim
will increase/decrease due to the voltage dis
sensing capabilities of UPS circuitry.
RL LinRL Lin
Load Types in Secondary Dis
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
148/285
Regenerative loads:
Regeneration is power produced by load that has
is driven by some other force mechanical or chem
Assure vendor is aware about special requiremen
of load. UPS components will be damaged.
Inverter: not design for 2Q / 4Q operation
Static Switch: detection time and transfer tim
will increase due to the additional line cap
case capacitance is so large that influence sycommutation could be unstable and/or long
non-bump-less transfer
RegeneraRegenera
Load Types in Secondary Dis
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
149/285
What IsWhat Is
The ITI (CBEMA) CuThe ITI (CBEMA) Cu
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
150/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
151/285
What Is TheWhat Is The
New ITI Curve
Refined for modern electronic equipment
Curve applies to 120Vrms, 60Hz nominal equipm
Engineer is responsible for application at other v
frequencies ITI curve describes seven types of events:
Not considered: Line Voltage Swell, Low-FrequenRingwave, High-Frequency Impulse, Voltage Sags
Dropout
No damage region
Prohibited region
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
152/285
1 us.001 c .01 c
1 m
100
200
300
400
500
Percent
ofNominalVoltage(RMSorPe
akEquivalent)
Duration in
ITI (
(R
What Is TheWhat Is The
Dropout A voltage includes both
severe RMS voltage sagsand complete interruptionsof the applied voltage,followed by immediate re-
application of the nominalvoltage
This transient typicallyresults from the occurrenceand subsequent clearing offaults in the ACdistribution system
THE INTERRUPTIONMAY LAST UP TO 20M ILL ISECONDS; FAULTSMUST BE SENSED ANDINTERRUPTED QUICKLY
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
153/285
1 us.001 c .01 c
1 m
100
200
300
400
500
PercentofNo
minalVoltage(RMSor
PeakEquivalent)
Duration in C
ITI (C
(Re
What Is TheWhat Is The
No Damage Region
Events in this region include
sags and dropouts (which
are less than the lower limit
of the steady state tolerance
range)
The normal functional state
of the Information
Technology Equipment
(ITE) is not typically
expected during theseconditions (no damage to
the ITE should result)
NO DA
REG
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
154/285
1 us.001 c .01 c
1 m
100
200
300
400
500
PercentofNo
minalVoltage(RMSor
PeakEquivalent)
Duration in C
ITI (C
(Re
What Is TheWhat Is The
Prohibited Region
This region includes any
surge or swell (which
exceeds the upper limit of
the envelope)
If the ITE is subjected to
such conditions, damage
to the ITE may result
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
155/285
Issues And CIssues And C
ITI Curve is the Benchmark
Fast System Fault Interruption
Voltage Restoration
Concerns
UPS Inverters Typically Supply Limited Fault C Depend On The Alternate Source To Provide Fa
Short-Circuit Sensing
Fast Fault Interruption
Compliance With the ITI Curve During Fau
Requires Fast Transfer to the Static Switch
Requires Fast Interrupting Protective Devices
Maintains Operation of Critical Computer Bus
During Normal and Abnormal System Conditio
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
156/285
Equipment BenchmEquipment Benchma
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
157/285
IndInd
Industry Recognized Voltage Dropout/Rest
Equipment sample for operating facility
Data may not represent your facility
Determine if process equipment will operate with
interruption Table Shows Typical UPS Loads
Some of the data is minimum hold-up time with
Others show the minimum threshold voltage at w
shutdown
Equipm
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
158/285
Sample From Typical
Petrochemical Facility
1 DCS Mfg. #1 17 ms 0 Vrms
2 DCS Mfg. #1 20 ms 0 Vrms
3 DCS Mfg. #1 40 ms 0 Vrms
4 DCS Mfg. #1 25 ms 0 Vrms
5 DCS Mfg. #2 40 ms 0 Vrms
6 DCS Mfg. #2 40 ms 0 Vrms
7 DCS Mfg. #3 40 ms 0 Vrms8 DCS Mfg. #3 20 ms 0 Vrms
9 PLC Mfg. #1 20 ms 0 Vrms
10 PLC Mfg. #1 5 ms 0 Vrms
11 PLC Mfg. #1 20 ms 0 Vrms
12 PLC Mfg. #1 20 ms 0 Vrms
13 PLC Mfg. #1 0 ms 97 Vrms
14 PLC Mfg. #2 8.33 ms 0 Vrms
15 PLC Mfg. #3 40 ms 0 Vrms
16 PLC Mfg. #3 21 ms 0 Vrms
17 Other Mfg. #1 0 ms 90 Vrms
18 Other Mfg. #2 0 ms 88 Vrms
19 Other Mfg. #3 0 ms 95 Vrms
20 Other Mfg. #4 0 ms * 102 Vrms
21 Other Mfg. #5 0 ms * 95 Vrms
22 Other Mfg. #6 0 ms * 95 Vrms
23 Relay #1 30 ms 0 Vrms
24 Relay #2 10 ms 0 Vrms
Reference
Number
* 0 ms below threshold without battery backup
Minimum
"Hold-Up"
Time
Minimum
Threshold
Voltage
Equipment
Description
IndInd
Equipme
1 us.001 c .01 c
1 ms3 m
100
200
300
400
500
PercentofNom
inalVoltage(RMSorP
eakEquivalent)
Duration in Cycl
ITI (CBE
(Revis
SYMBOL DENOTES
EQUIPMENTSHUTDOWN VS.
VOLTAGE AND TIME
FROM TABLE
EQUIPMENT
#13, 17, 18, 19,
20, 21, 22
EQUIPMENT#1, 10, 14, 24
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
159/285
GeGe
Equipm
SOURCE: M.H.J. BOLLEN, UNDERSTANDING POWER QUALITY PROBLEM
Regularegulatfor a peduring
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
160/285
GeGeEquipm
SOURCE: M.H.J. BOLLEN, UNDERSTANDING POWER QUALITY PROBLEM
Voltagcurves compumarket
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
161/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
162/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
163/285
GeGeEquipm
SOURCE: M.H.J. BOLLEN, UNDERSTANDING POWER QUALITY PROBLEM
Voltagcurves
processequipm1 comm
2- more c
contr
3- PLC
4-PLC ne
5-AC con
6-AC conimpo
(sam
7-AC con
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
164/285
GeGeEquipm
SOURCE: M.H.J. BOLLEN, UNDERSTANDING POWER QUALITY PROBLEM
Voltagcurves sodium
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
165/285
GeGeEquipm
SOURCE: T.A. SHORT, DISTRIBUTION RELIBILITY AND POWER QUALITY
Ride-thfor an i
power
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
166/285
GeGeEquipm
SOURCE: T.A. SHORT, DISTRIBUTION RELIBILITY AND POWER QUALITY
Voltagdropouvoltage
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
167/285
ShortShort--Circuit OutpCircuit Outp
Magnitude And ThMagnitude And ThAlternate SourceAlternate Source
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
168/285
What Is UPS Inverter SWhat Is UPS Inverter S
CurrentCurrent
Pulse Width Modulated (PWM)
Typically 1.5 times the full load current for 1/4 c
Ferroresonant
Can supply a maximum of 5 times full load amp(Energy Stored In The Output Filter)
Both Technologies Are Very Limited In SuShort-Circuit Conditions
Short-Circuit Output Magnitude And The A
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
169/285
How Are The UPSHow Are The UPS
System Faults System Faults
UPS Inverter
UPS short-circuit current insufficient for downst
protective device sensing and interruption
UPS senses the sudden rapid voltage reduction a
cycle transfers to alternate source
Alternate Source
Alternate source has significantly greater short-c
capability
Increased fault current is usually adequate for pr
devices to interrupt the fault
Short-Circuit Output Magnitude And The A
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
170/285
Static Switch Alternate Source Issues
Closure into a short-circuit is a severe condition
Must be adequately rated
Must be protected for this severe condition
Assumes the alternate source is available UPS Specifications Should Include:
Short-circuit available from the alternate source
(UPS manufacturer can supply equipment adequ
conditions)
Short-Circuit Output Magnitude And The A
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
171/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
172/285
SingleSingle--PhasePhase
OrOr
Three PhaseThree Phase
UPS Output VoltagUPS Output Voltag
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
173/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
174/285
Protecting The UPS SProtecting The UPS S
SwitchSwitch
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
175/285
Why Does ThWhy Does Th
Switch RequiresSwitch Requires
Why Is An Internal Fuse Or Circuit BreakerProtect The Static Switch?
For 1 to 5 cycles, a typical static transfer switch h
circuit rating of 10 times the full load switch rati
The alternate source short-circuit could exceed th
withstand capability
Hence, an internal solid-state fuse or circuit brea
protect the static transfer switch
Protecting The UP
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
176/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
177/285
Static SwitchStatic Switch
Static Switch Operation
Switching is performed for one or more conditio
Overcurrent > 150% of nominal current*
Undervoltage < 80% of nominal voltage*
Overvoltage > 110% of nominal voltage* Inverter Fault*
* - Manufacturer may not provide function and/or value of threshol
Protecting The UP
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
178/285
Molded Case CircuMolded Case Circu
BreakersBreakers
vs.vs.
FusesFuses
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
179/285
Electrical SystElectrical Syst
Electrical Design Practices
MCCBs are typically used in indoor panelboard
switchgear rooms and offices
Industry practice uses circuit breakers in UPS dis
systems
UPS Manufacturers
Recommend downstream fast-acting, current-lim
with 1/2 cycle clearing time
Molded Case Circuit-Bre
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
180/285
Breaker FunBreaker Fun
Molded Case Circuit Breaker (MCCB) Inter
1.1 cycles for 100A frame
1.5 cycles for 225A-4000A frame
100A MCCB interrupting time
1.1 cycles breaker interruption 0.25 cycles static switch transfer time
1.35 cycles total time
Marginally exceeds the ITI guidelines for mainta
critical instrumentation
This may result in a plant shutdown
Molded Case Circuit-Bre
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
181/285
Fuse Fuse
TYPICAL SELECTIVITY SCHEDULE FOR LOW VO
Exact ratios vary with ampere ratings, system voltage, acurrent.
Molded Case Circuit-Bre
Class L Fuse 601-6000 A 2:1 2:1 2:1 6:1
Class K1 Fuse 0-600 A 2:1 3:1 8:1
Class J Fuse 0-600 A 3:1 3:1 8:1
Class K5 Time-Delay Current
Limiting Fuse 0-600 A1.5:1 1.5:1 2:1
Class J Time-Delay Fuse 0-
600 A1.5:1 1.5:1 8:1
Load side
NOTE For illustration only; from [9]. Refer to fuse manufacturer for specific and up-to-da
Class L
Fuse
601-6000 A
Class K1
Fuse
0-600 A
Class J
Fuse 0-600
A
Class K5
Time-Delay
Fuse0-600 A
Line side
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
182/285
GeGeEquipm
SOURCE: T.A. SHORT, DISTRIBUTION RELIBILITY AND POWER QUALITY
Sensitiprocess
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
183/285
Breaker FunBreaker Fun
Authors Opinion
Based on the collected data
Modern MCCBs operate faster than clearing tim
may provide fault clearing in less than 1.0 cycle
1.1 cycles for 100A frame 1.5 cycles for 225A-4000A frame
Molded Case Circuit-Bre
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
184/285
UPS System LoadUPS System Load
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
185/285
Design ConDesign Con
During the Project UPSDesign Phase
Sized for the anticipated
loads
Plus a nominal margin
for future additions
Try not to procure before
all UPS loads are
identified and kW
requirements are known
UPS
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
186/285
ReviewReview
Very Important To Evaluate All UPS Loads
Segregate UPS loads from general purpose loads
Compressor control panels should be thoroughly
Compressor panels may include lighting, instrum
and space heater Lighting and space heater should be powered fro
purpose AC panel,NOT UPS SYSTEM
Confirm control room creature comfort loads (
heaters, coffee pots, microwaves etc.) are not connected
outlets or feeder circuits
Educate operation and maintenance personnel
UPS
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
187/285
Future LoadFuture Load
To Avoid Overloading The UPS
Review both existing and new UPS loads
Review panel loading
Review UPS loading
All personnel should know the impact of adding
UPS
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
188/285
POWER SYSTEM ANAPOWER SYSTEM ANA
APPLICABLE TO UAPPLICABLE TO USYSTEMS DESIGSYSTEMS DESIG
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
189/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
190/285
Additional analysis for special application o
Harmonic flow (inverter and loads, charger/recti
network)
Passive/Active Filters application
Switching
System modeling
Reliability modeling
EMF/RF modeling
Power System Anal
Analysis for Typical ApAnalysis for Typical Ap
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
191/285
Tools
No special tools are required for most of the typi
applications
Power System Anal
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
192/285
Helpful tools for applications Standard Software (1PH, 3PH, LF-AC/DC, SC-A
Harmonic Flow, Filters, battery charge/dischargereliability)
SKM
ETAP
Hand calcs (LF-AC/DC, SC-AC/DC, Filters, battcharge/discharge, arc-flash)
Excel
MathCad
Special Software (Harmonic Flow, passive/activeswitching, control strategy, reliability)
MathCad
SPICE
Matlab
EMTP type
Power System Anal
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
193/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
194/285
ExamplesExamples
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
195/285
120V UPS Distribution System Selectivity
Phase 1
Phase 2
Phase 2A 240V UPS / 480V Distribution System Sele
Example
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
196/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
197/285
All Loads in the Control Room
UPS
30KVA
120V
1-PHASE
480 V MCC
NORMAL
480 V MCC
ALTERNATE
30KVA
480-120V
1-PHASE
125A
100A 100A 100A
350A
15A
20A
50A
120VAC
PANEL
L115A
50A
LOAD
120VAC
PANELR1
PANELBOARD BP1
NOTE: BP1 AND L1ARE IN ADJACENT
M C C C U B I C L E S .
OTHERWISE, PANEL
L 1 R E Q U I R E S A N
I N C O M I N G M A I N
BREAKER
2-1/C #2
100FT
2-1/C #14
25FT
PHASE 1
FPH1A_
FPH1B_
FPH1C_
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
198/285
Loads Located Greater than 1000 feet
FPH2B_
UPS
30KVA
120V
1-PHASE
480 V MCC
NORMAL
480 V MCC
ALTERNATE
30KVA
480-120V
1-PHASE
125A
100A 100A 100A
350A
15A
20A
100A
T1
10KVA
120-480V
T2
10KVA
480-120V
120VAC
PANEL
R2
INSTR.
SKID
10A
15A
20A
INSTR.
SKID
10A
120VAC
PANEL
AR2
PANELBOARD BP1
100A
2 x 2-1/C#500KCMIL
1000FT
2-1/C #6
150FT
PHASE 2 ALTERNATE
PHASE 2
2-1
FPH1C_
FPH2A_
FPH2A1_FPH2A
FP
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
199/285
120V UPS 120V UPS
SelectivitySelectivity
Fault PWMLocation Isc
FPH1A_ 375A
FPH1B_ 360A
FPH1C_ 310A
1P
2-1/C100F
PANEL
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
200/285
Fault PWMLocation Isc
FPH1A_ 375A
FPH1B_ 360A
FPH1C_ 310A
120V UPS 120V UPS
SelectivitySelectivity
120
PA
2-1/C #2
100FT
PANELBO
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
201/285
120V UPS120V UPS
SelectivitySelectivity
Fault PWMLocation Isc
FPH1A_ 375A
FPH1B_ 360A
FPH1C_ 310A
120
PA
2-1/C #2
100FT
PANELBO
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
202/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
203/285
120V UPS 120V UPS
SelectivitySelectivity
Fault PWMLocation Isc
FPH2A_ 325A
FPH2B_ 282A
12PA
PANELB
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
204/285
120V UPS 120V UPS
Selectivity Selectivity
Fault PWM
Location Isc
FPH2A1_ 86A
FPH2A2_ 58A
FPH2A3_ 219A
FPH2A4_ 186A
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
205/285
120V UPS 120V UPS
Selectivity Selectivity
Fault PWM
Location Isc
FPH2A1_ 86A
FPH2A2_ 58A
FPH2A3_ 219A
FPH2A4_ 186A
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
206/285
Fig. 3. Example 240VAC UPS/480V Distribution System O
Diagram With Traditional Circuit Breaker Protection
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
207/285
UPS
50KVA
240V
1-PHASE
480 V MCC
NORMAL
480 V MCC
ALTERNATE
T3
50KVA
480-240V
1-PHASE
150AT
30A
300A W/O
TRIP UNIT
15A
15A
125A
SKID
LOAD
10A
PANELBOARD PB #2
2 1/C #8
300FT
2 1/C #10
50FT
300A
300A
20A 15A
TO
LOAD
TO
LOAD
150A
T2
50KVA
240-480V
1-PHASE
F1_
T1
10KVA
480-120V
1-PHASE
F2_
15A
PB
#1
F3_ F4_
PP
#1
240V/480V UPS Distribution System
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
208/285
Fault PWM
Location Isc
F1_ 148A
F2_ 144A
F3_ 508A
F4_ 416A
240V UPS240V UPS
SystemSystem
F1_
T1
10KVA
480-120V
1-PHASE
F2_
PANELB
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
209/285
240V UPS240V UPS
SystemSystem
Fault PWM
Location Isc
F1_ 148A
F2_ 144A
F3_ 508A
F4_ 416A
F1_
T1
10KVA
480-120V
1-PHASE
F2_
PANELB
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
210/285
Application GuidelApplication Guidel
SummarySummary
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
211/285
PoinPoint
Application Guideline
Intended as a starting point
Include additional information
Fundamentals
Changes Lessons learned
Exceptions
Application Gui
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
212/285
UPS Distribution System GenerUPS Distribution System Gener
Application GuideliApplication Guideli1. To avoid overloading UPS systems, review UPS loa
2. Segregate panel loads with critical process loads on
3. Perform short-circuit duty check with Alt. Source su
4. ITI curve is the benchmark for computer business eq
5. Review critical loads voltage limits with system con
6. Review UPS static switch timing/triggering paramet
7. When applicable, specify 1-phase UPS systemsRedundant power supply applications may require 3
Application Gui
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
213/285
UPS Distribution System GenerUPS Distribution System Genera
Application GuideliApplication Guideli8. Transfer to the Alt. Source may not be required with
because generally have a greater initial (1/4-1 cycle)
9. UPS manufacturers recommend fast-acting current-
10. Adequate fault current may minimize Static Sw. Alt
11. Confirm UPS internal fuse/circuit breaker configuraConfirm the Alt. Source fault does not exceed the U
12. With UPS internal, single-element CL fuses, includefactory fault testing with upstream and downstream
13. Fuse sizes should be minimized, i.e., less than typic
Application Gui
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
214/285
UPS Distribution System GenerUPS Distribution System Genera
Application GuideliApplication Guideli14. For selectivity, use fuse selectivity ratio tables
manufacturer since fuse selectivity tables are obtaine
15. Specify a 480V MCC fused switch for the feeder the Alternate Source isolation transformer
16. To assure adequate fault clearing current to remoincreased cable sizes may be required
17. To increase Alt. Source short-circuit current, thisolation transformer kVA rating may be increased
18. Use shielded, isolation type Alternate Source transfoOnly use ferroresonant transformers after thorough i
19. For enhanced system reliability, the Alternate Sopowered from a separate upstream source (not the sa
Application Gui
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
215/285
SYSTEM ACCEPTANSYSTEM ACCEPTAN
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
216/285
System acceptance Factory Acceptance Testing (FAT)
Commissioning
Performance verification
Maintenance
Sys
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
217/285
There is no standard for specificationsystem and testing in ANSI world
Testing and acceptance parameters:
Client specification
Vendor internal QA plan
Fusion of multitude different specificatio
Sys
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
218/285
Useful specification: UL 1778 - Standard for Uninterruptible Power Supply
CSA C22/2 NO.17.1 - Commercial and Industrial Pow
NEMA PE-1 - Uninterruptible Power Systems Standar
NEMA PE-5 Utility Type Battery Chargers
IEC 62040 Uninterruptible Power Systems (UPS)
Part 1: General and safety requirements
Part 2: Electromagnetic Compatibility (EMC) Re
Part 3: Method of Specifying the Performance anRequirements
ANSI C62.41, Category A & B - Recommended practvoltages in low voltage power circuits
FCC Rules and Regulations 47, Part 15, Class A - Cercompliance
IEEE Std. 650 Standard for qualification of class 1E
Sys
SpeSpe
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
219/285
Factory Acceptance Testing (FAT)
Industry testing
Vendor internal QC procedures
Client specification
Sys
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
220/285
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
221/285
Commissioning: Assure that FAT testing was performed
NETA specification as a guide
Specific application additional requirements i.e. special volta
dynamic loading, leading power factor, very low power facto
Compare specific values from FAT and site installation i.e. bbattery resistance, insulation resistance etc.
Battery charge and discharge test after installation at site
VERYFY AND RECORD ALL SETTING PARAMETERS
software
Separately commission all distribution primary and secondary
guidelines
Sys
ComComm
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
222/285
Performance verification
Periodic testing
Battery test
Autonomy of operation
Operation test: (AC input power loss test, A
return test, Redundancy test (if applicable fo
applications), Transfer test)
Grounding operation
DC ground detection
AC ground detection
Thermographic scan
On-line monitoring:
Battery status
UPS controller status
Sys
Performance VPerformance V
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
223/285
Maintenance Every month:
Check and record meter readings.
Check indicating lights.
Every year: Perform Manufacturers recommended serv
Every T/A:
Function Check operation by simulating lossource and loss of inverter source.
At 5/10yr intervals:
Perform manufacturers recommended compout.
Sys
MM
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
224/285
UpdateUpdate
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
225/285
InduIndu
There Is A Need To Revise / Update ExistinSystem Standards (IEEE Std. 944-1986, IEEE Std. 4Or Create A New Standard For The Industr
Standard Needs Current Information In The Foll
Construction, system architecture, topology
Principle of operation and conversion Sizing, redundancy, energy storage
Static and transient performance
Protection and selectivity
Acceptance testing, commissioning, and ma
Lessons Learned Industry needs to provide feedback to evaluate a
solutions with the application of UPS systems foloads
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
226/285
Application Application
Ferroresonant UPS Systems Have AdditionLimitations: Some UPS systems with output ferroresonant transfor
overheat during very light load or unloaded condition
Overloaded ferroresonance transformer tend to collap
Static Transfer Switch Timing Performance Dependence on:
Impedance (cables, installation, transformers etc
sources and switch inputs. Also, impedance of th
system connected to the switch output
Voltage detection logic (detection time)
Changes with:
Type of loads connected (RL, RC, RLC, regener
Type of fault (L-G, L-L etc.) and angle when fau
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
227/285
Resources & ReferenResources & Referen
-
8/10/2019 UPS Distribution Systems and UPS Fundamentals in the Petrochemical Industry
228/285
Technical RTechnical R
IEEE 485 Recommended Practice for Sizing Lead-AcidStationary Applications IEEE 1115 Recommended Practice for Sizing Nickel- C
Batteries for Stationary Applications IEEE 1184 Guide for the Selection and Sizing of Batter
Uninterruptible Power Supplies IEEE 1106 Recommended Practice for Installation, Ma
Testing, and Replacement of Vented Ni-Cad Batteries forApplications
NEMA PE-1 Uninterruptible Power Systems IEEE 450 Recommended Practice for Maintenance, Te
Replacement of Large Lead Storage Batteries IEEE 1188 Recommended Practice for Maintenance, T
Replacement of VRLA Batteries (Sealed Type) SCI Technical Papers -
http