Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

15
Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of Health Care Facilities Chris P . Rousseau, PE, LEED AP 31 st Annual AHCA Seminar and 53 rd Annual FHEA Meeting Orlando, Florida October 12, 2015

Transcript of Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Page 1: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Updates to ANSI/ASHRAE/ASHEStandard 170-2013Ventilation of Health Care Facilities

Chris P. Rousseau, PE, LEED AP

31st Annual AHCA Seminar and 53rd Annual FHEA Meeting Orlando, Florida October 12, 2015

Page 2: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

2008 Edition vs. 2013 Edition

• 2013 Edition addenda letters will start over with a

• Addenda to both editions are still available on the ASHRAE website

newcomb-boyd.com

Page 3: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Addenda – Overall Status

• 5 Addenda approved (a,b,d,e,ae)

• 5 Addenda in progress (ad,c,f,g,h)

• https://osr.ashrae.org/default.aspx

newcomb-boyd.com

Page 4: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Addendum ad

Status: Issued for 3rd public review

Topic: Exam rooms

a. Applies only to non-emergency department exam rooms.

b. Identifies two types of exam rooms:i. General – reduction in total air

change rate to 4.ii. Special – maintains total air

change rate of 6.

c. Special exam rooms are intended for spaces that might encounter persons with undiagnosed gastrointestinal, respiratory, or skin symptoms.

newcomb-boyd.com

Page 5: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Addendum c

Status: Issued for 3rd public review

Topic: Laboratory work areasa. Terminology coordinated with FGI –

“Laboratory Work Areas” vs. “Laboratories”

b. Reduction allowed via ANSI Z9.5 risk assessment or active sensing of contaminants or appropriate surrogates approach

newcomb-boyd.com

Page 6: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Addendum f

Status: Pending 2nd Public Review

Topic: Operating Room Air Distributiona. Provides a specific definition of the

primary supply diffuser array.

b. Clarifies that no more than 30% of the Primary Supply Diffuser Array may be used for non-diffuser items.

c. Additional diffusers may be located outside of the Primary Supply Diffuser Array if needed to achieve required environmental conditions or air change rates.

newcomb-boyd.com

Page 7: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Addendum g

Status: Pending PublicationTopic: Definitions of Operating & Procedure Rooms

a. Continues re-definition of ORs & Procedure Rooms included in the 2014 FGI Guidelines.

b. Deletes Class A, B, and C terminology and replaces with:

- Operating Room - Procedure Room

c. New definition of Operating Room is equivalent to Class B and C ORs previously.

d. New definition of Procedure Room is equivalent to Class A ORs previously.

e. Definition are included from 2014 FGI Guidelines for these spaces:

- Operating Room - Procedure Room- Invasive Procedure - Restricted Area

newcomb-boyd.com

Page 8: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Addendum h

Status: Pending Public Review

Topic: Temperature in Sterile Processing Department (SPD)

a. Disagreement between design (ASHRAE) and operational (AAMI) standards.

b. Joint meeting with ASHRAE, AAMI, FGI, ASHE, AORN, and APIC April 2015.

c. Agreed on temperature ranges for 3 spaces:Decontamination Room 60°F-73°FClean Workroom 68°F-73°FSterile Storage Max 75°F

d. Reference to AAMI ST-79.

e. Published joint interim guidelines.

newcomb-boyd.com

Page 9: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Republication

newcomb-boyd.com

• November 2017

• Part of 2018 Guidelines

Page 10: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

newcomb-boyd.com

Coordination Efforts

Coordination Efforts – Paul Ninomura

• Standard 55

• Standard 62.1

• Standard 90.1

Page 11: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

newcomb-boyd.com

• Joint ASHRAE/ASHE/FGI Literature Analysis

• Alternate compliance approach

• Walt Vernon• Michael Sheerin

FGI Research

Page 12: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

newcomb-boyd.com

New FGI Guidelines Approach

• FGI 2018 will be three books:• Hospital• Outpatient• Residential

• 170 will be included in its entirety in each book

• Work underway to identify and organize requirements for each occupancy

• Outpatient – John Dombrowski• Residential – Steve Friedman

Page 13: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Current Issues

• Clarification of inpatient and outpatient filtration requirements• Reduction of outpatient occupancy requirements• Reduction of air changes in unoccupied spaces• Clarification of “Recirculating Room HVAC Units”• Terminology and space name coordination with FGI• Residential healthcare requirements• Natural ventilation

newcomb-boyd.com

Page 14: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Future Issues

newcomb-boyd.com

• Patient room air distribution

• Air change rate reductions

• Outside air intake separation from exhaust

• Pharmacy requirements (USP 797 & 800)

• Anesthesia exhaust

• Air distribution terminology

Page 15: Updates to ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of ...

Updates to ANSI/ASHRAE/ASHEStandard 170-2013

Ventilation of Health Care Facilities

Chris P. Rousseau, PE, LEED AP

31st Annual AHCA Seminar and 53rd Annual FHEA Meeting Orlando, Florida

October 12, 2015