uPASS Reach Quick Reference
The following safety precautions should be observed during normal use, service and repair.
• All shields of the mandatory shielded cable shall be connected with safety ground.• The uPASS Reach may only be installed and serviced by qualified service personnel.• Disconnect the power supply before removing or installing any parts.• To be sure of safety, do not modify or add anything to the uPASS Reach other than mentioned in this installation guide or indicated by NEDAP N.V.
Safety precautions
Step 1 Mounting instructions
The uPASS Reach can be mounted to any surface, including directly to metal.Locate an appropriate position. Use the upper two keyholes (K) to mount thereader. Open the service cover to secure the reader using the two lower mountingpositions (L). See the mounting sketch for more information.
Step 2 Opening the server cover
The service cover can be opened to access the connections (including the USB-connector), setup the operating frequency and view the LED indicators. Open thescrews on the bottom of the uPASS Reach to unlock the service cover. Make surethe screws are completely opened (and closed when placing the cover back on).Don’t worry about losing the screws, they cannot fall out.
Wirelead
Screwdriver
WWi
RS232 wiring RS422 wiring
K5
DATA-0DATA-1
GND
Wiegand wiring
K2
Power supply
K1
contactsupply
3
4
3.1
3.2
3.3
Frequency selection
DIP switch
K2 K5 K3 K4
GND: Ground
Ground (black)
GND
RDP: Data
Data-1 (white)
OUT 3
RCP: Clock
Data-0 (green)
OUT2
CLS: Card Loaded
OUT1
Magstripe
Wiegand
Step 3 Connections
Step 4 Digital I/O
Connection procedure with spring cage terminal connectors. Shielded cableshall be used for all connections including the DC-supply connection.1. Strip wire lead for about 9 mm (0.35 inch).2. Push the screwdriver straight down to release the spring cage. Use a slotted, narrow-head screwdriver.3. Insert the wire lead into the wire terminal.4. Remove the screwdriver, this clamps the wire.5. Gently pull on the installed wire to make sure the connection is reliable.Note : Each connector terminal can accommodate only 1 solid or stranded wire. Wiring is normally done without ferrules. However, it is possible to use ferrules, provided that they are properly crimped.
Step 3.1 Power supplyThe uPASS Reach reader requires DC power supply in the range from 12 – 24V.Maximum current consumption is 1A @ 12VDC, 0.5A @ 24VDC.Connections:DC- Power supply 0V.DC+ Power supply 12 - 24VDC.Note: The power supply connection has an auto resetting fuse protection.
Step 3.2 Wiegand / Magstripe connection
Step 3.3 RS232, RS422
The wiegand/magstripe output format is determined by the programmed formatof the tag. Make sure to order the correct tag formatting if you want to use thewiegand or magstripe interface. See also the UHF Tag Order Guide for moreinformation (see table below).
The relay output is automatically activated upon identification of a tag. When the backward compatible processor is selected, the relay output is controlled by the backward compatible processor. Please refer to the firmware manual for details. The ‘smile’ on the front cover lights-up simultaneously with the relay output.
The uPASS Reach reader has an on-board RS232 and RS422 interface.
Note : Maximum cable length 150 meters (500 feet)
Note: Maximum cable length RS232 interface 15 meters (50 ft) Maximum cable length RS422 interface 1200 meters (4000 ft).
RXD Receive data (input) GND Ground TXD Transmit data (output)
connections RS232
NC Relay contact normally closed COM Relay contact common NO Relay contact normally open
connections
Max. switching current: 2A Max. switching voltage: 24VDC Max. switching power: 50W
contact ratings
RX+ Receive line (positive)RX- Receive line (negative)GND GroundTX+ Transmission line (positive)TX- Transmission line (negative)
connections RS422
UHF processor
SW1 SW1
Backward compatibleprocessor (e.g. P61 or Q70)
On-board RS232interface enabled
On-board RS422interface enabled
SW1 SW1
5
5. 1
5. 2
6
Step 5 DIP- SWITCH settings
Step 6 LED indications
Switches SW1-1 through SW1-4 are described. The switches SW2-1 throughSW2-8 are reserved for the backward compatible processor (e.g. P61 or Q70).Please refer to the firmware manual for details.
This selection determines the communication protocol on the RS232/RS422 andUSB interfaces. It also determines the relay output control. When using wiegand ormagstripe communication the setting of this switch has no e�ect.
Step 5.1 Compatibility mode
On-board RS232 or RS422 interface selection.
LED bar indicating the received tag signal strength. ThisLED bar may also indicate the presence of radiointerference. In case of interference, try switching to adifferent frequency.
Read Disable LED. On while reading disabled.
Input 1 status. On when input 1 contact is closed.
Transmit serial data
Receive serial data
Squelch active.
Power supply voltage too high.
Power supply voltage too low.
Internal supply voltage failure.
Temperature critically high.
PLL unlocked. Error indication only.
UHF processor status LED. Should be slowly blinking.
Tag found. RN16 received.Tag data read complete.
Error during tag identification.
Identification. Blinks fast when a valid transponder isidentified (backward compatible processor).
Status LED (only backward compatible processor).Slow blinking: System’s heartbeat (0.8 sec on / 0.8 sec off ) Indicates that the power is on and the processor is running.Fast blinking: Bootloader says hello. Indicated after a restart.Twice blinking: Configuration menu active.Off: Abnormal situation.
Step 5.2 RS232 / RS422 selection
RXLEVEL
RDISIN1
TXDRXD
SQ-ACT
DC-HI
DC-LO
DC-FAIL
T-CRIT
PLL UL
USTSUTAGUREADUERR
ID
STS
Frequency values for Europe
Frequency values for Israel
www.nedapavi.com
Nedap, a unique companyNedap - founded in 1929 and based in the Netherlands - employs approximately 550 people worldwide. Our shares are listed on the Euronext Stock Exchange. Nedap is an innovative, solution-oriented company with a wide range of products, systems and services based on RFID technologies. Our systems are used in a wide variety of markets, offering the ultimate solution in secure and reliable vehicle and driver identification.
AsiaNedap Asia Office583 Orchard Road#16-01/17-01 ForumSingapore 238884
T: +65 683 280 51F: +65 683 280 52E: [email protected]
AmericasNedap US Office500 W. Main, Suite 301Branson, MO 65616USA
T: 417 339 7368F: 417 337 8889E: [email protected]
HeadquartersNedap AVI
PO Box 1037140 AC GroenloThe Netherlands
Parallelweg 2e 7141 DC GroenloThe Netherlands
T: +31 544 471 666F: +31 544 464 255E: [email protected]
Step 7 Frequency selection
The uPASS Reach reader operates on the 860 – 960 MHz band. Specific frequenciesare regulated by region. Each reader is therefor set for a specific region, see theuPASS Install Guide for more info. If local regulations require frequency hopping(FHSS), then the uPASS Reach automatically selects and uses the available channels.Regions without FHSS, allow for selection of frequency channels within the selectedband when using more readers within close vicinity of each other.
If no frequency hopping is required, you should select an available frequencychannel manually. This can be realized as described below.
1. Select an available frequency channel2. Press the UP or DOWN switch once.3. When the display is on, press the UP switch to select a higher frequency and press DOWN to select a lower frequency.4. The display will automatically switch o� after 5 second.5. Alternatively the UHF tool software can be used to setup the frequency channel selection
Display value Frequency1 865.7 MHz2 866.3 MHZ3 866.9 MHz4 867.5 MHz
Display value Frequency1 915.1 MHz2 915.7 MHZ3 916.3 MHz4 916.9 MHz