continuos power protection availability
10 November 2011 Newave SA 1Unmatched Power Performance, Ed. 10.11.2011
PowerWave 33
10 November 2011 Newave SA 2
PowerWave 33
Contents
• The range
• The performances
• Options
• Additional info
10 November 2011 Newave SA 3
PowerWave 33
PowerWave 33
Unmatched Power Performances
10 November 2011 Newave SA 4
The full range
Technology: On-Line, transformer lessPower range: 60-80-100-120-160-200-250-300-400-500 kVA/kW (3/3)Rated at PF = 1
120-160-200 kW
60-80-100 kW
250-300 kW
400-500 kW
10 November 2011 Newave SA 5
60-80-100 kVAwith Battery Enclosure A
up to 80 battery blocks (2 x 40)
60-80-100 kVAwith Battery Enclosure B
Up to 120 battery blocks (3 x 40)
The range with battery enclosures
60-80-100 kW
Power range: 60-80-100 kVA/kW (3/3)Rated at PF = 0.9
10 November 2011 Newave SA 6
PowerWave 33
• Design
• Compactness
• Type of ventilation
• Battery’s enclosures and enhancement
• Input electrical performances
Unmatched power performances
• Efficiency
• Full output active power kVA=kW
10 November 2011 Newave SA 7
The Design of PowerWave 33
Mix & Match
IT design
10 November 2011 Newave SA 8
Mix & Match Data Centre & technical room environment
The Design of PowerWave 33
10 November 2011 Newave SA 9
The compactness of PowerWave 33
60-80-100 kW550 x 1820 x 750 mmFrom 230 to 245kg
60-80-100 kVA with BAT-ENC A970 x 1820 x 750 mmFrom 250 to 285 kg (w/o batt.)
Compact size
Space costs savings
BENEFITS
FEATURES
Low weight
Less transportation costsNo need for special floor basement
Full front access only
No rear access needed
60-80-100 kVA with BAT-ENC B1180 x 1820 x 750 mmFrom 270 to 305 kg (w/o batt.)
10 November 2011 Newave SA 10
120-160-200 kW850 x 1820 x 750 mmFrom 280 to 310 kg
250-300 kW1100 x 1920 x 750 mmFrom 390 to 410 kg
400-500 kW1650 x 1994 x 850 mmFrom 950 to 1000 kg
Compact size
Space costs savings
BENEFITS
FEATURES
Low weight
Less transportation costsNo need for special floor basement
Front access only
No rear access needed400-500kVA can be placed against the wall
The compactness of PowerWave 33
10 November 2011 Newave SA 11
The ventilation of PowerWave 33
60-300kW: front - rear 400-500kW: front - top
10 November 2011 Newave SA 12
The battery’s enclosures and chargers
40 block in each battery side
column
Battery Encl. AUp to 80 battery blocks of 28Ah
Battery Encl. BUp to 120 battery blocks of 28Ah
60-100kW: 25A battery charger120-200kW: 50A battery charger250-300kW: 60A battery charger400-500kW: 100A battery charger
Battery chargers
10 November 2011 Newave SA 13
BENEFITS
FEATURES
Battery
Ripple free through battery chargerNo battery operation during load jumpBattery temp. compensation (option)
Flexibility for autonomy rating
Increase of battery life expectancy
Battery’s enhancement
60-160kW: from 44 to 50 battery blocks200kW: 50 battery Blocks250-300kW: from 44 to 50 battery blocks400-500kW: from 44 to 50 battery blocks
Allowable battery blocks at full power
10 November 2011 Newave SA 14
Input electrical performances
Input
Wide input voltage range: 300-460V @ 100 % load (-25%/+15%) 280-460V @ 80% load (-30%/+15%) 240-460V @ <60 % load (-40%/+15%)
Less need for battery operationIncrease of battery expectance life
BENEFITS
FEATURES
Wide input frequency range: 35–70 Hz
10 November 2011 Newave SA 15
BENEFITS
FEATURESRectifier
Improved input PFC:>0.99 @ 100% load
Low input THDI:<3.5% @ 100% load
Smaller cables and fuse sizeNo phase compensation device required
No malfuntion and false trippingNo extra heating losses in transformersNo gen-set oversizedLonger plant lifeLess energy costs
Input electrical performances
10 November 2011 Newave SA 16
Unmatched power performanceEfficiency
AC/AC
BENEFITS
FEATURES
Best in class efficiency:up to 96% in on-line modeUp to 99% in eco-mode
Energy bill savingsAir conditioning cost savings Reduced TCO
10 November 2011 Newave SA 17
The efficiency of PowerWave 33
Do not look only at the initial costsbut consider the operating ones for ROI calculation
COST SAVINGS (Euros)
561’394280’697416’493208’247274’693137’3461000
280’696140’348208’247104’123137’34668’673500
56’13928’06941’64920’82527’46913’734100
10 years5 years 10 years5 years10 years5 yearsLoad (kW)
4%3%2%Difference inefficiency
• kWh cost = 0.10 Euro• Cooling factor = 0.4
10 November 2011 Newave SA 18
Inverter
BENEFITS
FEATURES
Voltage tolerance:THDU < 2% with linear loadTHDU < 3% with non-linear load
Voltage regulation:Static +/-1%, Dynamic +/-4%
Rated up to a power factor = 1
Excellent voltage quality/stability
Compatible with all loads (blade servers)without de-rating
Unmatched power performanceFull output active power kVA=kW
10 November 2011 Newave SA 19
Master your power
≥ 44 batt. blocks (except 200kVA only 50 blocks)
11% more active power than UPS rated at 0.925% more active power than UPS rated at 0.8
10 November 2011 Newave SA 20
Master your power
* Only with 50 battery blocks
10 November 2011 Newave SA 21
Master your power
10 November 2011 Newave SA 22
Manage your power
* Only with 50 battery blocks
10 November 2011 Newave SA 23
Parallelability (optional)
• Up to 10 UPS in DPA parallel configuration
• Parallel Kit factory mounted only
• Synchronisation Kit (only if equipped with parallel kit and
only factory mounted)
STS
Parallel configuration using Static Transfer Switch
Load
10 November 2011 Newave SA 24
Customers Interfaces (standard)
RS232 on D-Sub 9P port (UPS Protocol)
Customer Interfaces : Inputs DRY PORT
1 Remote Shut down 1 GEN-ON 1 Programmable Customer’s Inputs (60-300kVA) , External manual by-pass (400-500kVA)1 Temp. Sensor for Battery Control
Customer Interfaces : OutputsDRY PORT
5 voltage free contacts(60-300kVA), 6 voltage free contacts(400-500kVA)
For remote signalling and automatic computer shutdown
1 x RS485 on RJ45 port (remote panel)1 x RS485 on RJ45 port (Multidrop)
1 x SNMP Slot
1 x NWWatch slot
RS232 on USB port (UPS Protocol)
10 November 2011 Newave SA 25
Options
Available and structured options• Back feed protection• Parallel kit (one additional PCB + one parallel adapter)• Parallel cables with different lenghts• Synchronization kit (available only with parallel kit)• Connectivity (SNMP,Multidrop,etc.)• Elevation kit• Manual by-pass switch (only for 400-500kVA)
On request• I/O transformers• IP 21 Protection (60-300kW only)
10 November 2011 Newave SA 26
400-500kVA front view
Manual by-pass SW
Customer interface
Back-feed CB
Rectifier SW
By-pass SW
Output SW
Output CB
Optional
10 November 2011 Newave SA 27
Certificate
•Electrosuisse certificate
Newave will get a performance certificate from ElectroSuisse for a 100–200–300-500kVA
(independent institute comparable to TŰV)
10 November 2011 Newave SA 28