B30 Presentation
Examples
Universal Relay FamilyUniversal Relay Family
![Page 2: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/2.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: RTDS Testing EnvironmentRTDS Testing Environment
Real Time Digital SimulatorPSCAD graphical user interface
Real Time DigitalReal Time DigitalSimulatorSimulator
(RTDS)(RTDS)
Real Time DigitalReal Time DigitalSimulatorSimulator
(RTDS)(RTDS)
•Final product validation•Customer requested tests
Used for:
![Page 3: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/3.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: RTDS Testing EnvironmentRTDS Testing Environment
![Page 4: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/4.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: RTDS Applications and UsersRTDS Applications and Users
RTDS ApplicationsRTDS ApplicationsGEC Alsthom T&D (UK)
Asea Brown Boveri (Sweden) Siemens (Germany)
Hitachi Corp. (Japan)Toshiba Corp. (Japan)
Furnas Centrais Electricas (Brazil)Ontario Hydro Technologies Inc (Canada)
Chugoku Electric (Japan) Korea Electric Power Co. (S. Korea)
Nanjing Automation Research Institute (China) Electric Power Research Institute (China)
Manitoba Hydro (Canada)University of Manitoba (Canada)
LG Systems (S. Korea)Nanyang Technical University (Singapore)
Chanwang University (S. Korea) Kinkei Systems (Japan)
Toshiba Engineering (Japan)University of Canterbury (New Zealand)
RTDS UsersRTDS Users• Conventional TNA type studies • AC System breaker sequences • Power swings due to disturbance • DC Transmission systems with various short circuit ratios • DC System controls studies • Relay test studies • AC & DC System interactions • SVS Applications and controls studies
![Page 5: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/5.jpg)
Power Management The The Universal RelayUniversal Relay
Contents...Contents...
Case 1: External SLG Fault
Case 2: External SLG Fault
Case 3: External LLG Fault
Case 4: External 3P Fault
Case 5: External 3P Fault
Case 6: External SLG Fault
Case 7: External LLG Fault
Case 8: Internal SLG Fault
Case 9: Internal SLG Fault next page
![Page 6: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/6.jpg)
Power Management The The Universal RelayUniversal Relay
Contents...Contents...
Case 10: Internal LLG Fault
Case 11: Internal 3P Fault
Case 12: Internal SLG Fault (weak infeed)
Case 13: Internal SLG Fault (weak infeed)
Case 14: Closing onto Internal SLG Fault
Case 15: Closing onto Internal SLG Fault
Case 16: Closing onto Internal 3P Fault
Case 17: Closing onto External SLG Fault
Case 18: Closing onto External... next page
![Page 7: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/7.jpg)
Power Management The The Universal RelayUniversal Relay
Contents...Contents...
Case 19: External SLG Fault (autorecl.)
Case 20: External 3P Fault (autorecl.)
![Page 8: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/8.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)
• External AG fault on circuit #4
• Point on Wave = 0 deg
• All six circuits connected
• Circuit #4 CT saturates after about 2 ms
• The B30 remains stable
COMTRADE File: B30_case_01
![Page 9: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/9.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)
AG, pow=0o
![Page 10: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/10.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)
![Page 11: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/11.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)
• External AG fault on circuit #4
• Point on Wave = 90 deg
• All six circuits connected
• Circuit #4 CT saturates after about 1.6 ms
• The B30 remains stable
COMTRADE File: B30_case_02
![Page 12: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/12.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)
AG, pow=90o
![Page 13: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/13.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)
![Page 14: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/14.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)
• External ABG fault on circuit #4
• Point on Wave = 0 deg
• All six circuits connected
• Circuit #4 CT saturates after about 2.6 ms
• The B30 remains stable
COMTRADE File: B30_case_03
![Page 15: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/15.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)
ABG, pow=0o
![Page 16: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/16.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)
![Page 17: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/17.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)
• External ABCG fault on circuit #4
• Point on Wave = 0 deg
• All six circuits connected
• Circuit #4 CT saturates after about 2.6 ms
• The B30 remains stable
COMTRADE File: B30_case_04
![Page 18: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/18.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)
ABCG, pow=0o
![Page 19: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/19.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)
![Page 20: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/20.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)
• External ABCG fault on circuit #4
• Point on Wave = 90 deg
• All six circuits connected
• Circuit #4 CT saturates after about 2.3 ms
• The B30 remains stable
COMTRADE File: B30_case_05
![Page 21: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/21.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)
ABCG, pow=90o
![Page 22: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/22.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)
![Page 23: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/23.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)
• External AG fault on circuit #1
• Point on Wave = 0 deg
• All six circuits connected
• Circuit #1 CT saturates after about 6 ms
• The B30 remains stable
COMTRADE File: B30_case_06
![Page 24: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/24.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)
AG, pow=0o
![Page 25: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/25.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)
![Page 26: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/26.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)
• External ABG fault on circuit #1
• Point on Wave = 0 deg
• All six circuits connected
• Circuit #1 CT saturates after about 5.5 ms
• The B30 remains stable
COMTRADE File: B30_case_07
![Page 27: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/27.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)
ABG, pow=0o
![Page 28: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/28.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)
![Page 29: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/29.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)
• Internal AG fault
• Point on Wave = 0 deg
• All six circuits connected
• The B30 operates in 10.0 msec (fast form-C)
COMTRADE File: B30_case_08
![Page 30: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/30.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)
AG, pow=0o
![Page 31: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/31.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)
Phase A operates in 10.0 msec
Phase A operates in 10.0 msec
![Page 32: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/32.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)
• Internal AG fault
• Point on Wave = 90 deg
• All six circuits connected
• The B30 operates in 10.7 msec (fast form-C)
COMTRADE File: B30_case_09
![Page 33: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/33.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)
AG, pow=90o
![Page 34: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/34.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)
Phase A operates in 10.7 msec
Phase A operates in 10.7 msec
![Page 35: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/35.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)
• Internal ABG fault
• Point on Wave = 0 deg
• All six circuits connected
• The B30 operates in 9.3 msec (fast form-C)
COMTRADE File: B30_case_10a,b
![Page 36: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/36.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)
ABG, pow=0o
![Page 37: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/37.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)
Phase A operates in 9.3 msec
Phase A operates in 9.3 msec
![Page 38: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/38.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)
Phase B operates in 10.5 msec
Phase B operates in 10.5 msec
![Page 39: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/39.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)
• Internal ABCG fault
• Point on Wave = 0 deg
• All six circuits connected
• The B30 operates in 8.8 msec (fast form-C)
COMTRADE File: B30_case_11a,b,c
![Page 40: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/40.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)
ABCG, pow=0o
![Page 41: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/41.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)
Phase A operates in 11.4 msec
Phase A operates in 11.4 msec
![Page 42: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/42.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)
Phase B operates in 8.8 msec
Phase B operates in 8.8 msec
![Page 43: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/43.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)
Phase C operates in 13.8 msec
Phase C operates in 13.8 msec
![Page 44: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/44.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)
• Internal AG fault
• Point on Wave = 0 deg
• Circuits 3 (wye winding of the transformer: zero-sequence infeed), 4 (weak infeed) and 5 (load) connected
• The B30 operates in 17.7 msec (fast form-C)
COMTRADE File: B30_case_12
![Page 45: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/45.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)
AG, pow=0o
![Page 46: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/46.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)
Phase A operates in 17.7 msec
Phase A operates in 17.7 msec
![Page 47: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/47.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)
• Internal AG fault
• Point on Wave = 90 deg
• Circuits 3 (wye winding of the transformer: zero-sequence infeed), 4 (weak infeed) and 5 (load) connected
• The B30 operates in 13.5 msec (fast form-C)
COMTRADE File: B30_case_13
![Page 48: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/48.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)
AG, pow=90o
![Page 49: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/49.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)
Phase A operates in 13.5 msec
Phase A operates in 13.5 msec
![Page 50: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/50.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)
• Internal AG fault pre-exists on the bus
• The bus is energized from the circuit #1
• Closing onto the fault at the Point on Wave = 0 deg
• The B30 operates in 7.6 msec (fast form-C)
COMTRADE File: B30_case_14
![Page 51: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/51.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)
AG, pow=0o
![Page 52: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/52.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)
Phase A operates in 7.6 msec
Phase A operates in 7.6 msec
![Page 53: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/53.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)
• Internal AG fault pre-exists on the bus
• The bus is energized from the circuit #1
• Closing onto the fault at the Point on Wave = 90 deg
• The B30 operates in 7.9 msec (fast form-C)
COMTRADE File: B30_case_15
![Page 54: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/54.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)
AG, pow=90o
![Page 55: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/55.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)
Phase A operates in 7.9 msec
Phase A operates in 7.9 msec
![Page 56: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/56.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)
• Internal ABCG fault pre-exists on the bus
• The bus is energized from the circuit #1
• Closing onto the fault at the Point on Wave = 0 deg
• The B30 operates in 6.4 msec (fast form-C)
COMTRADE File: B30_case_16a,b,c
![Page 57: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/57.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)
ABCG, pow=0o
![Page 58: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/58.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)
Phase A operates in 8.8 msec
Phase A operates in 8.8 msec
![Page 59: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/59.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)
Phase B operates in 6.4 msec
Phase B operates in 6.4 msec
![Page 60: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/60.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)
Phase C operates in 8.8 msec
Phase C operates in 8.8 msec
![Page 61: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/61.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)
• Internal ABCG fault pre-exists on the circuit #4
• The circuit #4 is connected to the de-energized bus
• The bus is energized from the circuit #1
• Closing onto the fault at the Point on Wave = 0 deg
• The B30 remains stable
COMTRADE File: B30_case_17
![Page 62: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/62.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)
ABCG, pow=0o
![Page 63: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/63.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)
![Page 64: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/64.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)
• Internal AG fault pre-exists on the circuit #4
• The circuit #4 is connected to the de-energized bus
• The bus is energized from the circuit #1
• Closing onto the fault at the Point on Wave = 0 deg
• The B30 remains stable
COMTRADE File: B30_case_18
![Page 65: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/65.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)
AG, pow=0o
![Page 66: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/66.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)
![Page 67: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/67.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)
• External AG fault on the circuit #4
• The fault is cleared in 100 msec
• Two AR shots are executed with the dead-time of 0.5 sec
• The AR fails - the breaker opens after 70 msec during each shot
• The B30 remains stable
COMTRADE File: B30_case_19
![Page 68: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/68.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)
AG, pow=0o
![Page 69: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/69.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)
Fault InceptionFault Inception 2nd AR shot2nd AR shot
![Page 70: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/70.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)
![Page 71: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/71.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)
• External ABCG fault on the circuit #4
• The fault is cleared in 100 msec
• Two AR shots are executed with a dead-time of 0.5 sec
• The AR fails - the breaker opens after 70 msec during each shot
• The B30 remains stable
COMTRADE File: B30_case_20
![Page 72: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/72.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)
ABCG, pow=0o
![Page 73: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/73.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)
Fault InceptionFault Inception 2nd AR shot2nd AR shot
![Page 74: Universal Relay Family](https://reader035.fdocuments.net/reader035/viewer/2022081603/5681572c550346895dc4c8dc/html5/thumbnails/74.jpg)
Power Management The The Universal RelayUniversal Relay
Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)