Underground Storage Tanks (USTs)
NCDENRDivision of Waste Management
Underground Storage Tank Section
Rev 12-10
![Page 2: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/2.jpg)
USTs
Release prevention
Release detection
![Page 3: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/3.jpg)
Release Prevention
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection5. Compatibility
![Page 4: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/4.jpg)
Release PreventionVapor Recovery
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection5. Compatibility
![Page 5: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/5.jpg)
Vapor Recovery
We DO NOT regulate this
Inspector checks:
•Present
•Operational
•Exceptions
Dual Point
Coaxial
![Page 6: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/6.jpg)
Spill and overfill prevention
Eliminate the potential for a release during fuel deliveries
![Page 7: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/7.jpg)
Spill and overfill prevention
UST-10B
![Page 8: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/8.jpg)
What’s the difference?
Spill prevention:◦ Contains drips and spills of fuel that occur when delivery hose is uncoupled from fill port
Overfill prevention◦ Provides transporter with indication that tank is approaching full during delivery
![Page 9: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/9.jpg)
Release PreventionSpill Prevention
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection5. Compatibility
![Page 10: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/10.jpg)
Spill prevention on UST-10B
![Page 11: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/11.jpg)
Spill prevention equipment
Fuel delivered to tank here
![Page 12: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/12.jpg)
Spill prevention equipment
Fill port/spill bucket
![Page 13: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/13.jpg)
Spill prevention equipment
Fill ports must have spill buckets
Temporarily contains product
Typically 5 – 25 gallons
![Page 14: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/14.jpg)
Spill bucket maintenance**
Not designed to “store” fuel
Free of water, fuel, and debris
Free of holes or defects
If there is already liquid inthe spill bucket before youget a delivery, then the spill
bucket can’t do it’s job
![Page 15: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/15.jpg)
UST Site Diagram
UST Site Diagram for: _____________________________________________
*
USTRaleigh Blvd
Fuel Mart 27
Hart Road
Fuel Mart 27
Spill Bucket
Vapor Recovery
•
•
![Page 16: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/16.jpg)
Release PreventionOverfill Prevention
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection5. Compatibility
![Page 17: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/17.jpg)
Overfill prevention on UST-10B
![Page 18: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/18.jpg)
Overfill prevention equipment**
Ball float valve
Overfill alarm
Flapper valve
![Page 19: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/19.jpg)
Overfill prevention equipment
Ball float valve at
vapor recoveryport
Fill tube with flapper valve
![Page 20: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/20.jpg)
Release PreventionOverfill Prevention
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention
• Ball float valve• Overfill Alarm• Flapper Valve
4. Corrosion Protection5. Compatibility
![Page 21: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/21.jpg)
Ball float valves
Reduces product flow
Installed to slow delivery at 90% capacity or 30 min
before overfilling
![Page 22: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/22.jpg)
Ball float valve restrictions**
Incompatible with UST systems that:
◦ Receive pressurized deliveries
◦ Have suction piping
◦ Have coaxial vapor recovery
![Page 23: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/23.jpg)
Release PreventionOverfill Prevention
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention
• Ball float valve• Overfill Alarm• Flapper Valve
4. Corrosion Protection5. Compatibility
![Page 24: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/24.jpg)
Overfill alarms
Activates an audible and/or visual warning
Alerts at 90% capacity
Must be located where alarm can be seen and/or heard from delivery site
Unable to restrict or stop flow
![Page 25: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/25.jpg)
Release PreventionOverfill Prevention
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention
• Ball float valve• Overfill Alarm• Flapper Valve
4. Corrosion Protection5. Compatibility
![Page 26: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/26.jpg)
Flapper valves (automatic shutoff devices)
Slows down and then stops delivery
Installed to stop fuel at 95% capacity
Not for systems that receive pressurized deliveries
![Page 27: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/27.jpg)
Flapper valves
![Page 28: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/28.jpg)
Your overfill responsibilities
Ensure amount of product ordered will fit
Monitor deliveries◦ Lock any extra fill ports that don’t have overfill equipment
◦ Have response supplies ready
Use signs◦ Notify delivery person of overfill device
![Page 29: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/29.jpg)
UST Site Diagram
UST Site Diagram for: _____________________________________________
*
Fuel Mart 27
Raleigh Blvd
Hart Road
Fuel Mart 27
UST
Spill Bucket
Overfill PreventionFlapper Valve
*
*
*
Vapor Recovery
•
•
![Page 30: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/30.jpg)
Release PreventionCorrosion protection
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection5. Compatibility
![Page 31: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/31.jpg)
Compliance Plan
![Page 32: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/32.jpg)
Compliance Plan
Refer to your inspection checklist and site diagram
For each topic we cover, fill in the blanks with the correct info for YOUR facility
End result should be a basic compliance plan for your facility
![Page 33: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/33.jpg)
Corrosion protection on UST-10B
![Page 34: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/34.jpg)
Corrosion protection on compliance plan
![Page 35: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/35.jpg)
Corrosion protection
Non-corrodible material
Internal lining
Cathodic protection
![Page 36: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/36.jpg)
Release PreventionCorrosion protection
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection
• Non-corrodible material• Internal lining• Cathodic Protection
5. Compatibility
![Page 37: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/37.jpg)
Non-corrodible material on UST-10B
![Page 38: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/38.jpg)
Non-corrodible material**
FRP Tank
![Page 39: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/39.jpg)
Non-corrodible material**
Jacketed Tank
![Page 40: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/40.jpg)
Non-corrodible material records
Written verification of tank material◦ Installation invoice
◦ Repair invoice
Visual verification◦ Not typical for tanks
![Page 41: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/41.jpg)
If you have non-corrodible materials…
Non-corrodible material (FRP,
CLAD)
N/A
Installation invoice
N/A
![Page 42: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/42.jpg)
Release PreventionInternal lining
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection
• Non-corrodible material• Internal lining• Cathodic Protection
5. Compatibility
![Page 43: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/43.jpg)
Internal lining on UST-10B
![Page 44: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/44.jpg)
Internal lining
Applying non-corrodible lining inside UST
![Page 45: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/45.jpg)
Internal lining testing
Internal inspection within 10 years of installation,
Then every 5 years thereafter
Tightness test after every inspection
![Page 46: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/46.jpg)
Internal lining records
National code or standard used for installation
Repair invoices
Most recent internal inspection results
Most recent tightness test results
![Page 47: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/47.jpg)
If you have internal lining…
Internal lining
Inspection &TTT every
5 years
Inspection results,
TTT results
--/--/--(5 years
from previous Inspection)
![Page 48: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/48.jpg)
Release PreventionCathodic Protection
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection
• Non-corrodible material• Internal lining• Cathodic Protection
5. Compatibility
![Page 49: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/49.jpg)
Cathodic protection on UST-10B **
![Page 50: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/50.jpg)
Cathodic protection systems
What does “cathodic protection” mean?
Two types:
◦ Galvanic (sacrificial anode) systems
◦ Impressed current (IC or rectifier) systems
![Page 51: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/51.jpg)
Galvanic/SA systemsImpressed current
systems
![Page 52: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/52.jpg)
Cathodic protection systems**
BOTH types must be designed by a “corrosion expert”
◦ National Association of Corrosion Engineers (NACE)
or
◦ Professional Engineer (PE)
◦ If installed after 3/1/06, must prove system design was certified by “corrosion expert”
![Page 53: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/53.jpg)
Release PreventionGalvanic Systems
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection
• Non-corrodible material• Internal lining• Cathodic Protection
• Galvanic/SA Systems• Impressed Current Systems
5. Compatibility
![Page 54: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/54.jpg)
Galvanic/SA systems
Anode corrodes instead of UST
Most common: StiP3
![Page 55: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/55.jpg)
Galvanic/SA systems
Anodes (zinc or magnesium) connected to structure by welding or lead wires
![Page 56: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/56.jpg)
Test every three years **
Submit Galvanic test results on UST-7A form
Must be tested by a qualified cathodicprotection tester
![Page 57: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/57.jpg)
If you have a cathodic protection system…
Galvanic/SA system(STIP-3)
Test every 3 years
System design,UST-7A
--/--/--(3 years
from previous test)
![Page 58: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/58.jpg)
Release PreventionGalvanic Systems
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection
• Non-corrodible material• Internal lining• Cathodic Protection
• Galvanic/SA Systems• Impressed Current Systems
5. Compatibility
![Page 59: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/59.jpg)
Impressed current systems
Anodes located in soil around structures to be protected
Electrical current is applied to anodes
![Page 60: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/60.jpg)
Impressed current requirements
•Requires dedicated and protected circuit
•Power must not be interrupted (except during testing)
•Breaks in wiring result in system failure
![Page 61: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/61.jpg)
Impressed current requirements
60 Day Readings from RECTIFIER BOX:
•Operator must inspect system every 60 days
•Record meter reading on UST-21 form
•Make sure meter NOT reading “zero”
•Make sure meter never loses power
![Page 62: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/62.jpg)
Additional impressed current requirements
UST-21 form can be found on website
![Page 63: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/63.jpg)
Additional impressed current requirements
Compare your 60-day readings to “as-left” readings on UST-7B
![Page 64: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/64.jpg)
Add Rectifier Box to Site Diagram
![Page 65: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/65.jpg)
UST Site Diagram
UST Site Diagram for: _____________________________________________
*
Fuel Mart 27
Raleigh Blvd
Hart Road
Fuel Mart 27
*
*
*
UST
Spill Bucket
Overfill PreventionFlapper Valve
Vapor RecoveryCoaxial
STP
ATG
Dispenser
ATG Console
Rectifier Box
probe
![Page 66: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/66.jpg)
Test every three years**
Submit Impressed Current test results on UST-7B form
Must be tested by a qualified cathodicprotection tester
![Page 67: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/67.jpg)
If you have a cathodic protection system…
IC system
60-day readings,
Test every 3 years
UST-21,UST-7B
--/--/--(ex. 1st of
every month)--/--/--
(3 years from previous
test)
![Page 68: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/68.jpg)
Failed or inoperative cathodicprotection systems
IC or galvanic system test FAILS
IC system is/was without electricity
Specific requirements for each situation◦ See memo on website under “Guidance Documents”
![Page 69: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/69.jpg)
Cathodic protection system problems
IC system lines to anodes broken
![Page 70: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/70.jpg)
Cathodic protection system problems
No power to the rectifier
![Page 71: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/71.jpg)
Release PreventionCompatibility
Five topics
1. Vapor Recovery2. Spill prevention3. Overfill prevention4. Corrosion Protection5. Compatibility
![Page 72: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/72.jpg)
Most Common Alternative Fuels**
◦ E-10 10% ethanol 90% gasoline
◦ B-20 20% biodiesel 80% petroleum diesel
◦ E-85 85% ethanol 15% gasoline
Follow the same rules that apply to traditional gas and diesel
Extra requirements!
![Page 73: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/73.jpg)
Example of Accelerated Corrosion
Standard, non-E85 fuel STP E85 STP
Photos courtesy Iowa DNR
Same facility, same install date
![Page 74: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/74.jpg)
UST-20 Form**
PRIOR to dispensing >10% ethanol or >20% biodiesel
![Page 75: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/75.jpg)
UST-20 Form
Sections completed by UST owner/operator AND equipment contractor or PE
Include◦ Documents verifying compatibility OR
◦ Compatibility analysis by PE
![Page 76: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/76.jpg)
EXAM
Tank Release PreventionPlease answer questions # 11-17
![Page 77: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/77.jpg)
USTs
Release prevention◦ Spill prevention
◦ Overfill prevention
◦ Corrosion protection
Release detection
![Page 78: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/78.jpg)
Release Detection
![Page 79: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/79.jpg)
What is leak detection?
The activities and equipment used to detect releases from UST systems
![Page 80: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/80.jpg)
Why conduct leak detection?
REQUIRED for all regulated systems
Discover a release before a major contamination incident occurs
![Page 81: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/81.jpg)
Leak detection on UST-10B
![Page 82: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/82.jpg)
Leak detection on compliance plan
![Page 83: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/83.jpg)
Monthly methods
![Page 84: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/84.jpg)
Leak detection requirements**
Must be conducted monthly (at least once every 30 days)
Must detect a release from any portion of the tank
Must be installed, calibrated, operated, and maintained per manufacturer’s instructions
![Page 85: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/85.jpg)
Leak detection requirements**
Third Party Certified
◦ Documentation that your leak detection method works for your UST system
◦ http://www.nwglde.org
◦ Keep documents for inspection
◦ Pay attention to limitations Tank size Manifolded tanks Throughput Etc.
![Page 86: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/86.jpg)
Monthly methods – most common**
Automatic Tank Gauging (ATG)
Systems
Secondary Containment with
Interstitial Monitoring
Statistical Inventory
Reconciliation (SIR)
![Page 87: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/87.jpg)
ATG System
![Page 88: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/88.jpg)
How do I know if I use an ATG?
Console located inside facility
Probe installed at tank
![Page 89: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/89.jpg)
ATG Probe
Check:
•Capped
•Wires intact
![Page 90: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/90.jpg)
ATG Console
•Present and powered on
•No warnings or alarms
![Page 91: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/91.jpg)
UST Site Diagram
UST Site Diagram for: _____________________________________________
*
Fuel Mart 27
Raleigh Blvd
Hart Road
Fuel Mart 27
UST
Spill Bucket
Overfill PreventionFlapper Valve
*
*
*
Vapor RecoveryCoaxial
STP
ATG
Dispenser
ATG Console
probe
![Page 92: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/92.jpg)
ATG system on UST-10B
![Page 93: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/93.jpg)
ATG system description
Probe permanently installed
Wired to monitor
Product level and temperature info recorded
Calculates changes in product volume
![Page 94: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/94.jpg)
ATG system testing modes
Periodic (static) test mode◦ Tank needs “quiet” time
◦ Data collected over a period of time
Continuous test mode◦ Data gathered during many short
periods when no product is being
added to or taken from tank
◦ Ex. CSLD or SCALD
![Page 95: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/95.jpg)
ATG system operation and maintenance
Tank size
Manifolded tanks
Minimum fuel levels
Type of product (e.g. waste oil, E-85)
Maximum allowable monthly throughput
Duration of test
Waiting period after fuel delivery before test
Make sure your system is certified for your particular facility:
![Page 96: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/96.jpg)
ATG system operation and maintenance
Know how to access and printout leak test results
Check testing printouts routinely
Follow manufacturer’s recommendations for system tests and service
Check console after electrical storms
Do not ignore warnings or alarms
![Page 97: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/97.jpg)
ATG system testing **
How much is 0.2 gph leak?
![Page 98: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/98.jpg)
ATG system records
Must keep one valid 0.2 gph test result per tank, per month, for 12 months
![Page 99: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/99.jpg)
If you have an ATG system…
ATG system
12 months test results
--/--/--(ex. Every Monday)
Conduct test every
30 days
![Page 100: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/100.jpg)
Secondary Containment with Interstitial Monitoring
![Page 101: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/101.jpg)
How do I know if I use Secondary containment with interstitial monitoring?
Double-walled tank
May have sensors monitoring space between inner and outer walls
May have console located at facility
![Page 102: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/102.jpg)
Interstitial monitoring on UST-10B
![Page 103: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/103.jpg)
Interstitial monitoring description**
Periodic monitoring◦ Check interstice manually for liquids
Continuous monitoring◦ Electronic sensors in interstice connected to console
![Page 104: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/104.jpg)
Interstitial monitoring description**
Electronic sensors:
◦ Detect leaked substance
liquid or
gaseous
OR
◦ Detect change in condition
loss of vacuum or
monitoring liquid level change
![Page 105: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/105.jpg)
Interstitial monitoring requirements
Periodic monitoring:
◦ Manually check interstice and document at least once every 30 days
Continuous monitoring:
◦ Continuously monitor interstice with electronic sensors
◦ Check and print sensor status at least once every 30 days
![Page 106: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/106.jpg)
Interstitial monitoring records
Must keep all records per tank, per month, for 12 months
![Page 107: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/107.jpg)
If you have a secondary containment system with interstitial monitoring…
Interstitialmonitoring
12 months Periodic checks OR Sensor status
results
--/--/--(ex. Every Monday)
Manually check interstice
ORCheck sensor status
every 30 days
![Page 108: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/108.jpg)
Statistical Inventory Reconciliation(SIR)
![Page 109: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/109.jpg)
How do I know if I use SIR?
Use a tank stick to take daily measurements
Contract with a SIR vendor
Receive monthly SIR reports
![Page 110: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/110.jpg)
SIR on UST-10B
![Page 111: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/111.jpg)
SIR description
Statistical analysis of inventory, delivery, and dispensing data using computer software to
detect leaks
![Page 112: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/112.jpg)
SIR operation and maintenance**
Measure to nearest 1/8th inch daily
Measure water levels monthly
Supply daily inventory to SIR vendor at end of month
Know limitations listed in third-party certification provided by SIR vendor
![Page 113: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/113.jpg)
SIR operation and maintenance
Use appropriate calibration charts
Replace broken or unreadable tank sticks
Have same person stick tanks every day
Stick tanks and read meters at same time every day
Review SIR reports when received from vendor
![Page 114: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/114.jpg)
SIR records
Must keep DAILY product measurements per tank, for 12 months
Must keep one water measurement per tank, per month, for 12 months
![Page 115: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/115.jpg)
SIR records
Must keep SIR reports per tank, per month, for 12 months
![Page 116: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/116.jpg)
If you are using SIR…
SIR
Calibration charts,12 months daily fuel and
monthly water measurements,
12 months SIR reports
TODAY(product measurement)
--/--/--(30 days from previous
water measurement)--/--/--
(day of the month to send off data to vendor)
Measure product daily,Measure water every 30 days,
Submit to vendorevery 30 days
![Page 117: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/117.jpg)
Other Methods of Leak Detection
![Page 118: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/118.jpg)
Other methods on UST-10B
• Enhanced leak detection page 16
• Inventory control and tightness testing page 12
• Manual tank gauging and tightness testing page 13
• Groundwater monitoring page 15
• Vapor monitoring page 14
![Page 119: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/119.jpg)
EXAMTank Release DetectionPlease answer questions # 18-23
![Page 120: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/120.jpg)
Enhanced leak detection
![Page 121: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/121.jpg)
Enhanced leak detection on UST-10B
![Page 122: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/122.jpg)
UST systems required to conduct enhanced leak detection
Installed after Jan 1, 1991 and before May 1, 2000
AND
Within 100-500 feet of a public water supply well, and/or
Within 50-100 feet of any other well for human consumption, and/or
Within 500 feet of high class surface waters
![Page 123: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/123.jpg)
Enhanced leak detection description
Required for certain UST systems
A combination of monitoring and well sampling
Temporary method until upgrade required
![Page 124: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/124.jpg)
Enhanced leak detection testing
Conduct 0.1 gph ATG test at least once every 30 days OR
Conduct 0.2 gph ATG test at least once every 7 days
AND
Sample wells within zones specified at least once a year
![Page 125: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/125.jpg)
Enhanced leak detection records
Must keep one water sampling result per well for 12 months
AND
Must keep one valid 0.1 gph ATG test per tank, per month, for 12 months OR
Must keep one valid 0.2 gph ATG test per tank, per week, for 52 weeks
![Page 126: Underground Storage Tanks (USTs)](https://reader035.fdocuments.net/reader035/viewer/2022071602/613d5727736caf36b75c2c2d/html5/thumbnails/126.jpg)
Enhanced leak detection upgrade
Must upgrade to .0900 secondary containment standards by Jan 1 of:
◦ 2005 – all steel or metal connected piping and ancillary equipment
◦ 2008 – all fiberglass or non-metal connected piping AND all USTs installed on or before Jan 1, 1991
◦ 2016 – all USTs installed after Jan 1, 1991