Unbalnced faults

download Unbalnced faults

of 20

Transcript of Unbalnced faults

  • 8/10/2019 Unbalnced faults

    1/20

    Unbalanced Faults

    Faults at the Generator Terminals

    1

  • 8/10/2019 Unbalnced faults

    2/20

    Unbalanced Faults

    Common unbalanced faults are SLG, LL and LLG faults.

    Unbalanced faults unbalance the network, but only at

    the fault location.

    This causes a coupling of the sequence networks.

    How the sequence networks are coupled depends upon

    the fault type.

    Well derive these relationships for several common

    faults.

    2

  • 8/10/2019 Unbalnced faults

    3/20

    Single Line-to-Ground (SLG) Faults

    With a SLG fault only one phase has non-zero fault current --

    well assume it is phase A.

    ?

    0

    0

    fa

    fb

    fc

    I

    I

    I

    3

  • 8/10/2019 Unbalnced faults

    4/20

    SLG

    0

    2 0

    2

    Then since

    1 1 1 ?1 1

    1 03 3

    01

    f

    ff f f f a

    f

    I

    I I I I I

    I

    Va = 0 for a single line to ground fault

    V++ V- +V0= 0

    With the generators normally producing balanced three-phase voltages,

    which are positive sequence only, we can write

    4

  • 8/10/2019 Unbalnced faults

    5/20

    SLG Equivalent Circuit

    )( 0ZZZIV f

    3)( 0aa

    fI

    ZZZVI

    0

    )(

    3

    0

    cb

    a

    a

    II

    ZZZ

    VI

    5

  • 8/10/2019 Unbalnced faults

    6/20

    Example

    Consider a system with sequence impedances given byZ+ = j0.2577, Z- = j0.2085, and Z0 = j0.14; find the voltages

    and currents at the fault point for a single line-to-ground fault.

    SolutionThe sequence networks are connected in series for a SLG fault.

    The sequence currents are given by;

    Therefore,

    6

  • 8/10/2019 Unbalnced faults

    7/20

    Sequence Voltages

    7

  • 8/10/2019 Unbalnced faults

    8/20

    Phase Voltages

    8

  • 8/10/2019 Unbalnced faults

    9/20

    Double Line to Ground Fault

    Fault conditions

    Ia= 0

    Vb= Vc=00//ZZZ

    VI

    ZIEV

    VaVVV3

    0

    Z

    VI

    o

    oo

    Z

    VI

    9

  • 8/10/2019 Unbalnced faults

    10/20

    Double line-to-ground fault

    bI

    cI

    a

    b

    c

    nI

    0 cb VV 0aI

    0

    0

    1

    1

    111

    3

    1

    2

    2

    2

    1

    0 a

    a

    a

    a V

    aa

    aa

    V

    V

    V

    aaaa VVVV3

    1021

    2

    1

    0

    2

    1

    0

    2

    1

    0

    00

    00

    00

    0

    0

    a

    a

    a

    f

    a

    a

    a

    I

    I

    I

    Z

    Z

    Z

    V

    V

    V

    V

    10

  • 8/10/2019 Unbalnced faults

    11/20

    Double line-to-ground fault

    2

    1

    0

    2

    1

    0

    11

    11

    11

    00

    00

    00

    0

    0

    a

    a

    a

    f

    af

    af

    af

    I

    I

    I

    Z

    Z

    Z

    V

    ZIV

    ZIV

    ZIV

    2

    1

    0

    1

    2

    1

    0

    11

    11

    11

    00

    00

    00

    0

    0

    a

    a

    a

    f

    af

    af

    af

    I

    I

    I

    Z

    Z

    Z

    V

    ZIV

    ZIV

    ZIV

    11

  • 8/10/2019 Unbalnced faults

    12/20

    Double line-to-ground fault

    2

    1

    0

    2

    1

    0

    11

    11

    11

    100

    010

    001

    a

    a

    a

    af

    faf

    af

    I

    I

    I

    Z

    Z

    Z

    ZIV

    VZIV

    ZIV

    0210 aaaa IIII)( 02

    021

    1

    ZZZZ

    Z

    VI

    f

    a

    fV

    -

    +

    1Z

    2Z 0Z

    - -

    + +

    1aI 2aI 0aI

    -

    +

    1aV 2aV aoV

    12

  • 8/10/2019 Unbalnced faults

    13/20

    Double line-to-ground fault

    Example : Find the line currents and the line-to-line voltages when a

    double line-to-ground fault occurs at the terminals of the generatordescribed in single line-to-ground fault example. Assume that the generator

    was unloaded and operating at rated voltage when the fault occurred. The

    generator has positive sequence reactance of 0.25 , negative sequence

    reactance of 0.35 and zero sequence reactance of 0.10 per unit. The neutral

    of the generator is solidly grounded. Neglect resistance.

    ..05.33278.0

    0.1

    )10.035.0/()10.035.0(25.0

    00.1

    )/( 020211 upj

    jjjjjj

    j

    ZZZZZ

    EI aa

    )25.0)(05.3(111021 jjZIEVVV aaaaa

    ..237.0763.00.1 up

    ..68.035.0

    237.0

    2

    22 upj

    jZ

    VI aa

    ..37.2.010.0

    237.0

    0

    0

    0 upj

    jZ

    VI a

    a

    13

  • 8/10/2019 Unbalnced faults

    14/20

    Double line-to-ground fault

    037.268.005.3021 jjjIIII aaaa

    37.2)68.0)(866.05.0()05.3)(866.05.0(0212

    jjjjjIaIIaI aaab

    ..3.13280.4555.3230.3 0 upj

    37.2)866.0)(866.05.0()05.3)(866.05.0(0221 jjjjjIIaaII aaac ..7.4780.4555.3230.3 0 upj

    ..11.737.233 0 upjjII an

    ..11.7555.3230.3555.3230.3 upjjjIII cbn

    ..711.0237.033 1021 upVVVVV aaaaa 0 cb VV

    ..711.0 upVVV baab

    0bc

    V

    14

  • 8/10/2019 Unbalnced faults

    15/20

    Double line-to-ground fault

    ..711.0 upVVV acca

    Expressed in amperes and volts,

    0aI

    AIb00 3.13240173.13280.4837

    AIc00 7.4740177.4780.4837

    AIn00 9059519011.7837

    kVVab0066.5

    3

    8.13711.0

    0

    bcV

    kVVca018066.5

    3

    8.13711.0

    15

  • 8/10/2019 Unbalnced faults

    16/20

    Line-to-line fault

    bI

    cI

    a

    b

    c

    cb VV 0aI cb II

    c

    c

    a

    a

    a

    I

    I

    aa

    aa

    I

    I

    I 0

    1

    1

    111

    3

    1

    2

    2

    2

    1

    0

    00 aI 12 aa II

    c

    c

    a

    a

    a

    a

    V

    VV

    aa

    aa

    V

    VV

    2

    2

    2

    1

    0

    1

    1111

    3

    1

    16

  • 8/10/2019 Unbalnced faults

    17/20

    Line-to-line fault

    2

    1

    0

    2

    1

    0

    2

    1

    0

    00

    00

    00

    0

    0

    a

    a

    a

    f

    a

    a

    a

    I

    I

    I

    Z

    Z

    Z

    V

    V

    V

    V

    21 aa VV

    22110 ZIZIV aaf

    21

    1ZZ

    VI

    f

    a

    fV

    -

    +

    1Z

    2Z

    - -

    + +

    1aV2aV

    1aI 2aI

    17

  • 8/10/2019 Unbalnced faults

    18/20

    Line-to-line fault

    Example : Find the subtransient currents and the line-to-line voltages at the fault under

    subtransient conditions when a line-to-line fault occurs at the terminals of the generator

    described in the sing line-to-ground fault example. Assume that the generator is unloaded

    and operating at rated terminal voltage when the fault occurs. Neglect resistance.

    unitperjjj

    j

    Ia 667.135.025.0

    00.11

    unitperjII aa 667.112 00 aI

    0667.1667.1021 jjIIII aaaa

    )866.05.0(667.1)866.05.0(667.10212 jjjjIaIIaI aaab unitperjjj 0886.2443.1833.0443.1833.0

    unitperjII bc 0886.2 18

  • 8/10/2019 Unbalnced faults

    19/20

    Line-to-line fault

    in the sing line-to-ground fault example, base current is 837A, and so

    0aI

    01802416837886.2 bI002416837886.2 cI

    unitperjjVV aa 583.0)25.0)(667.1(121

    00 aV (Neutral of generator grounded)

    Line-to-ground voltages are

    ..0166.1583.0583.0 0021 upVVVV aaaa

    0212

    aaab VaVVaV

    )866.05.0(583.0)866.05.0(583.0 jjVV bc

    ..583.0 up 19

  • 8/10/2019 Unbalnced faults

    20/20

    Line-to-line fault

    Line-to-line voltages are

    unitperVVVbaab

    749.1583.0166.1

    unitperVVVcbbc

    0583.0583.0

    unitperVVV acca 749.1166.1583.0 Expressed in volts, the line-to-line voltages are

    kVVab0094.13

    3

    8.13749.1

    kVVbc 0

    kVVca018094.13

    3

    8.13749.1

    20