Unbalnced faults
-
Upload
chutipa-a-reungjit -
Category
Documents
-
view
234 -
download
0
Transcript of Unbalnced faults
-
8/10/2019 Unbalnced faults
1/20
Unbalanced Faults
Faults at the Generator Terminals
1
-
8/10/2019 Unbalnced faults
2/20
Unbalanced Faults
Common unbalanced faults are SLG, LL and LLG faults.
Unbalanced faults unbalance the network, but only at
the fault location.
This causes a coupling of the sequence networks.
How the sequence networks are coupled depends upon
the fault type.
Well derive these relationships for several common
faults.
2
-
8/10/2019 Unbalnced faults
3/20
Single Line-to-Ground (SLG) Faults
With a SLG fault only one phase has non-zero fault current --
well assume it is phase A.
?
0
0
fa
fb
fc
I
I
I
3
-
8/10/2019 Unbalnced faults
4/20
SLG
0
2 0
2
Then since
1 1 1 ?1 1
1 03 3
01
f
ff f f f a
f
I
I I I I I
I
Va = 0 for a single line to ground fault
V++ V- +V0= 0
With the generators normally producing balanced three-phase voltages,
which are positive sequence only, we can write
4
-
8/10/2019 Unbalnced faults
5/20
SLG Equivalent Circuit
)( 0ZZZIV f
3)( 0aa
fI
ZZZVI
0
)(
3
0
cb
a
a
II
ZZZ
VI
5
-
8/10/2019 Unbalnced faults
6/20
Example
Consider a system with sequence impedances given byZ+ = j0.2577, Z- = j0.2085, and Z0 = j0.14; find the voltages
and currents at the fault point for a single line-to-ground fault.
SolutionThe sequence networks are connected in series for a SLG fault.
The sequence currents are given by;
Therefore,
6
-
8/10/2019 Unbalnced faults
7/20
Sequence Voltages
7
-
8/10/2019 Unbalnced faults
8/20
Phase Voltages
8
-
8/10/2019 Unbalnced faults
9/20
Double Line to Ground Fault
Fault conditions
Ia= 0
Vb= Vc=00//ZZZ
VI
ZIEV
VaVVV3
0
Z
VI
o
oo
Z
VI
9
-
8/10/2019 Unbalnced faults
10/20
Double line-to-ground fault
bI
cI
a
b
c
nI
0 cb VV 0aI
0
0
1
1
111
3
1
2
2
2
1
0 a
a
a
a V
aa
aa
V
V
V
aaaa VVVV3
1021
2
1
0
2
1
0
2
1
0
00
00
00
0
0
a
a
a
f
a
a
a
I
I
I
Z
Z
Z
V
V
V
V
10
-
8/10/2019 Unbalnced faults
11/20
Double line-to-ground fault
2
1
0
2
1
0
11
11
11
00
00
00
0
0
a
a
a
f
af
af
af
I
I
I
Z
Z
Z
V
ZIV
ZIV
ZIV
2
1
0
1
2
1
0
11
11
11
00
00
00
0
0
a
a
a
f
af
af
af
I
I
I
Z
Z
Z
V
ZIV
ZIV
ZIV
11
-
8/10/2019 Unbalnced faults
12/20
Double line-to-ground fault
2
1
0
2
1
0
11
11
11
100
010
001
a
a
a
af
faf
af
I
I
I
Z
Z
Z
ZIV
VZIV
ZIV
0210 aaaa IIII)( 02
021
1
ZZZZ
Z
VI
f
a
fV
-
+
1Z
2Z 0Z
- -
+ +
1aI 2aI 0aI
-
+
1aV 2aV aoV
12
-
8/10/2019 Unbalnced faults
13/20
Double line-to-ground fault
Example : Find the line currents and the line-to-line voltages when a
double line-to-ground fault occurs at the terminals of the generatordescribed in single line-to-ground fault example. Assume that the generator
was unloaded and operating at rated voltage when the fault occurred. The
generator has positive sequence reactance of 0.25 , negative sequence
reactance of 0.35 and zero sequence reactance of 0.10 per unit. The neutral
of the generator is solidly grounded. Neglect resistance.
..05.33278.0
0.1
)10.035.0/()10.035.0(25.0
00.1
)/( 020211 upj
jjjjjj
j
ZZZZZ
EI aa
)25.0)(05.3(111021 jjZIEVVV aaaaa
..237.0763.00.1 up
..68.035.0
237.0
2
22 upj
jZ
VI aa
..37.2.010.0
237.0
0
0
0 upj
jZ
VI a
a
13
-
8/10/2019 Unbalnced faults
14/20
Double line-to-ground fault
037.268.005.3021 jjjIIII aaaa
37.2)68.0)(866.05.0()05.3)(866.05.0(0212
jjjjjIaIIaI aaab
..3.13280.4555.3230.3 0 upj
37.2)866.0)(866.05.0()05.3)(866.05.0(0221 jjjjjIIaaII aaac ..7.4780.4555.3230.3 0 upj
..11.737.233 0 upjjII an
..11.7555.3230.3555.3230.3 upjjjIII cbn
..711.0237.033 1021 upVVVVV aaaaa 0 cb VV
..711.0 upVVV baab
0bc
V
14
-
8/10/2019 Unbalnced faults
15/20
Double line-to-ground fault
..711.0 upVVV acca
Expressed in amperes and volts,
0aI
AIb00 3.13240173.13280.4837
AIc00 7.4740177.4780.4837
AIn00 9059519011.7837
kVVab0066.5
3
8.13711.0
0
bcV
kVVca018066.5
3
8.13711.0
15
-
8/10/2019 Unbalnced faults
16/20
Line-to-line fault
bI
cI
a
b
c
cb VV 0aI cb II
c
c
a
a
a
I
I
aa
aa
I
I
I 0
1
1
111
3
1
2
2
2
1
0
00 aI 12 aa II
c
c
a
a
a
a
V
VV
aa
aa
V
VV
2
2
2
1
0
1
1111
3
1
16
-
8/10/2019 Unbalnced faults
17/20
Line-to-line fault
2
1
0
2
1
0
2
1
0
00
00
00
0
0
a
a
a
f
a
a
a
I
I
I
Z
Z
Z
V
V
V
V
21 aa VV
22110 ZIZIV aaf
21
1ZZ
VI
f
a
fV
-
+
1Z
2Z
- -
+ +
1aV2aV
1aI 2aI
17
-
8/10/2019 Unbalnced faults
18/20
Line-to-line fault
Example : Find the subtransient currents and the line-to-line voltages at the fault under
subtransient conditions when a line-to-line fault occurs at the terminals of the generator
described in the sing line-to-ground fault example. Assume that the generator is unloaded
and operating at rated terminal voltage when the fault occurs. Neglect resistance.
unitperjjj
j
Ia 667.135.025.0
00.11
unitperjII aa 667.112 00 aI
0667.1667.1021 jjIIII aaaa
)866.05.0(667.1)866.05.0(667.10212 jjjjIaIIaI aaab unitperjjj 0886.2443.1833.0443.1833.0
unitperjII bc 0886.2 18
-
8/10/2019 Unbalnced faults
19/20
Line-to-line fault
in the sing line-to-ground fault example, base current is 837A, and so
0aI
01802416837886.2 bI002416837886.2 cI
unitperjjVV aa 583.0)25.0)(667.1(121
00 aV (Neutral of generator grounded)
Line-to-ground voltages are
..0166.1583.0583.0 0021 upVVVV aaaa
0212
aaab VaVVaV
)866.05.0(583.0)866.05.0(583.0 jjVV bc
..583.0 up 19
-
8/10/2019 Unbalnced faults
20/20
Line-to-line fault
Line-to-line voltages are
unitperVVVbaab
749.1583.0166.1
unitperVVVcbbc
0583.0583.0
unitperVVV acca 749.1166.1583.0 Expressed in volts, the line-to-line voltages are
kVVab0094.13
3
8.13749.1
kVVbc 0
kVVca018094.13
3
8.13749.1
20