UN6800 (Excitation)Alarm and Event List

523
UNITROL® 6800 Alarm and Event List FOR SW RELEASE V 2.1.21 Contents Document No.: 3BHS258033 E01 Rev. - Version 07 / 2008

Transcript of UN6800 (Excitation)Alarm and Event List

Page 1: UN6800 (Excitation)Alarm and Event List

UNITROL® 6800 Alarm and Event List

FOR SW RELEASE V 2.1.21

Contents

Document No.: 3BHS258033 E01 Rev. -

Version 07 / 2008

Page 2: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

2 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Display events on the ECT (Excitation Control Terminal):

Touch Events

The Event Logger contains a table with the last 1000 entries. As soon as this window is selected, an automatic upload will start. If a new entry occurs, the panel reads this out of the UNITROL System and the table will automatically be updated.

Dynamic list of actual events

Event logger table

Page 3: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

3 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1 20000 ThyrFlt_Rp_CCI1

CCI1. Thyristor Rp Fault: The monitoring of Converter 1 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 4: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

4 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

2 20001 ThyrFlt_Tn_CCI1

CCI1. Thyristor Tn Fault: The monitoring of Converter 1 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 5: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

5 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

3 20002 ThyrFlt_Sp_CCI1

CCI1. Thyristor Sp Fault: The monitoring of Converter 1 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 6: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

6 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

4 20003 ThyrFlt_Rn_CCI1

CCI1. Thyristor Rn Fault: The monitoring of Converter 1 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 7: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

7 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

5 20004 ThyrFlt_Tp_CCI1

CCI1. Thyristor Tp Fault: The monitoring of Converter 1 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 8: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

8 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

6 20005 ThyrFlt_Sn_CCI1

CCI1. Thyristor Sn Fault: The monitoring of Converter 1 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

7 20006 FuseFlt_Rp_CCI1

CCI1. Fuse Rp Fault: Branch Fuse Rp blown Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters:

Page 9: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

9 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

8 20007 FuseFlt_Tn_CCI1

CCI1. Fuse Tn Fault: Branch Fuse Tn faulty Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 10: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

10 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

9 20008 FuseFlt_Sp_CCI1

CCI1. Fuse Sp Fault: Branch Fuse Sp faulty Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

10 20009 FuseFlt_Rn_CCI1

CCI1. Fuse Rn Fault: Branch Fuse Rn faulty Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 11: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

11 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

11 20010 FuseFlt_Tp_CCI1

CCI1. Fuse Tp Fault: Branch Fuse Tp faulty Possible reasons: - high current due to internal short circuit (thyristor lost blocking capability) - high current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 12: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

12 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

12 20011 FuseFlt_Sn_CCI1

CCI1. Fuse Sn Fault: Branch Fuse Sn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

13 20012 TOCD_R_CCI1

CCI1. Overcurrent in Phase R detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Page 13: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

13 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

14 20013 TOCD_S_CCI1

CCI1. Overcurrent in Phase S detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

Page 14: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

14 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

15 20014 TOCD_T_CCI1

CCI1. Overcurrent in Phase T detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

16 20015 UfOpCeil_CCI1

CCI1. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon Further steps: ----

Page 15: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

15 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

17 20016 DevTypeErr_CCI1

CCI1. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 1 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

18 20017 AddressErr_CCI1

CCI1. Address Error Possible reasons: - Wrong HEX Switch setting at CCI 1 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

Page 16: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

16 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

19 20018 LinkFault_CCI1

CCI1. Link Fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to CCI

20 20019 RedPwrFail1_CCI1

CCI1. Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Converter Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

21 20020 RedPwrFail2_CCI1

CCI1. Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:1-2) Default reaction: - Converter Redundancy Fault Related parameters:

Page 17: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

17 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

22 20021 PrciPwrFail_CCI1

CCI1. Precision Power fail Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

23 20022 CPUWatchdog_CCI1

CCI1. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Converter Trip Related parameters: ---- Further steps:

Page 18: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

18 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reboot device - Download installer archive - Replace board

24 20023 UfFreeze_CCI1

CCI1. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UfEnaADCFreezeMon Further steps: - Replace board

25 20024 USynInPhase_CCI1

CCI1. Synchronous Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaInPhaseMon Further steps: - Check cabling

Page 19: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

19 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

26 20025 USynOpCeil_CCI1

CCI1. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon Further steps: - Replace board

27 20026 USynFreeze_CCI1

CCI1. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaADCFreezeMon Further steps: - Replace board

28 20027 USynAllLost_CCI1

CCI1. Synchronous Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaAllLostMon

Page 20: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

20 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling

29 20028 SelfTrip_CCI1

CCI1. Link Fault detected by CCI Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to AC 800PEC

30 20029 AdvFuseBlow_CCI1

CCI1. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses Possible reasons: - Internal short circuit at a TWIN confuguration (Cold Standby) Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown Further steps: - Check thyristors - Check fuses

Page 21: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

21 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

31 20030 IConvOpCeil_CCI1

CCI1. Converter Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Trip Related parameters: Prot_Protection \ IconvEnaADCFreezeMon Further steps: - Replace board

32 20031 IConvFreeze_CCI1

CCI1. Converter Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon Further steps: - Replace board

Page 22: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

22 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

33 20032 CoolingFailure_CCI1

CCI1. Cooling failure Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters Default reaction: - Converter TRIP Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor

34 20033 Fan1Supply1Flt_CCI1

CCI1. Fan 1 Supply 1 fault Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

Page 23: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

23 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace pressure sensor

35 20034 Fan1Supply2Flt_CCI1

CCI1. Fan 1 Supply 2 fault Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 24: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

24 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

36 20035 Fan2Supply1Flt_CCI1

CCI1. Fan 2 Supply 1 fault Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

37 20036 Fan2Supply2Flt_CCI1

CCI1. Fan 2 Supply 2 fault Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps:

Page 25: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

25 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

38 20037 MCB1Fault_CCI1

CCI1. Fan Supply Miniature Circuit Breaker 1 fault Possible reasons: - Fan 1 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

39 20038 MCB2Fault_CCI1

CCI1. Fan Supply Miniature Circuit Breaker 2 fault Possible reasons: - Fan 2 defective Default reaction: - Converter Redundancy fault Related parameters:

Page 26: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

26 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

40 20039 ThyrTemp1Lev1Fl_CCI1

CCI1. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 27: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

27 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

41 20040 ThyrTemp2Lev1Fl_CCI1

CCI1. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

42 20041 ThyrTemp3Lev1Fl_CCI1

CCI1. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 28: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

28 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

43 20042 ThyrTemp4Lev1Fl_CCI1

CCI1. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 29: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

29 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

44 20043 ThyrTemp5Lev1Fl_CCI1

CCI1. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

45 20044 ThyrTemp6Lev1Fl_CCI1

CCI1. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 30: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

30 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

46 20045 AirTemp1Lev1Flt_CCI1

CCI1. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 31: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

31 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

47 20046 AirTemp2Lev1Flt_CCI1

CCI1. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

48 20047 ThyrTemp1SensFl_CCI1

CCI1. Thyristor Rp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 32: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

32 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Re-check sensor circuit

49 20048 ThyrTemp2SensFl_CCI1

CCI1. Thyristor Tn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor short-circuit < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 33: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

33 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

50 20049 ThyrTemp3SensFl_CCI1

CCI1. Thyristor Sp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

51 20050 ThyrTemp4SensFl_CCI1

CCI1. Thyristor Rn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 34: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

34 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

52 20051 ThyrTemp5SensFl_CCI1

CCI1. Thyristor Tp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

53 20052 ThyrTemp6SensFl_CCI1

CCI1. Thyristor Sn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 35: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

35 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

54 20053 AirTemp1SensFlt_CCI1

CCI1. Air Temperature 1 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

55 20054 AirTemp2SensFlt_CCI1

CCI1. Air Temperature 2 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

Page 36: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

36 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

56 20055 SnubberSwiFlt_CCI1

CCI1. Snubber Switch fault Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch Default reaction: N-1 - Converter alarm TWIN - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord Further steps: - Re-check sensor circuit

57 20056 SnubberFuseFlt_CCI1

CCI1. Snubber Fuse fault Possible reasons: ---- Default reaction: ---- Related parameters: ---- Further steps: ----

Page 37: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

37 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

58 20057 ThyristorFuseFl_CCI1

CCI1. Thyristor Fuse fault Possible reasons: - Digital input for fuse supervision activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Check and replace faulty thyristors - Check and replace blown fuses

59 20058 DoorFlt_CCI1

CCI1. Converter cabinet Door fault Possible reasons: - Digital input for open door activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Close converter cabinet door

60 20059 VersionFlt_CCI1

CCI1. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Converter Trip Related parameters: ----

Page 38: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

38 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Download required software version

61 20060 NegConvFault_CCI1

CCI1. NegConvFault_CCI1 Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord Further steps: - Re-check HW input

62 20061 PulseBlockFault_CCI1

CCI1. PulseBlock_CCI1 of HW Possible reason: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive Default reaction: - Converter trip Related parameters: ---- Further steps: - Re-check of HW input

63 20062 TestPosition_CCI1

Page 39: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

39 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

64 20063 Event2_31_CCI1

65 20064 ThyrTemp1Lev2Fl_CCI1

CCI1. Thyristor Rp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

66 20065 ThyrTemp2Lev2Fl_CCI1

CCI1. Thyristor Tn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature

Page 40: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

40 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

fault of the other converters (n-1) - Clean air inlet filters

67 20066 ThyrTemp3Lev2Fl_CCI1

CCI1. Thyristor Sp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 41: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

41 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

68 20067 ThyrTemp4Lev2Fl_CCI1

CCI1. Thyristor Rn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

69 20068 ThyrTemp5Lev2Fl_CCI1

CCI1. Thyristor Tp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 42: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

42 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

70 20069 ThyrTemp6Lev2Fl_CCI1

CCI1. Thyristor Sn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 43: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

43 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

71 20070 AirTemp1Lev2Flt_CCI1

CCI1. Air Temperature 1 ( Thyristor Cooler Input ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

72 20071 AirTemp2Lev2Flt_CCI1

CCI1. Air Temperature 2 ( Air outlet chimney ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level

Page 44: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

44 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

73 20072 Event3_08_CCI1

74 20073 Event3_09_CCI1

75 20074 Event3_10_CCI1

76 20075 Event3_11_CCI1

77 20076 Event3_12_CCI1

78 20077 Event3_13_CCI1

79 20078 Event3_14_CCI1

80 20079 Event3_15_CCI1

81 20080 Event3_16_CCI1

82 20081 Event3_17_CCI1

83 20082 Event3_18_CCI1

84 20083 Event3_19_CCI1

85 20084 Event3_20_CCI1

86 20085 Event3_21_CCI1

87 20086 Event3_22_CCI1

88 20087 Event3_23_CCI1

89 20088 Event3_24_CCI1

90 20089 Event3_25_CCI1

Page 45: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

45 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

91 20090 Event3_26_CCI1

92 20091 Event3_27_CCI1

93 20092 Event3_28_CCI1

94 20093 Event3_29_CCI1

95 20094 Event3_30_CCI1

96 20095 Event3_31_CCI1

97 20100 ThyrFlt_Rp_CCI2

CCI2. Thyristor Rp Fault: The monitoring of Converter 2 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 46: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

46 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

98 20101 ThyrFlt_Tn_CCI2

CCI2. Thyristor Tn Fault: The monitoring of Converter 2 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 47: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

47 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

99 20102 ThyrFlt_Sp_CCI2

CCI2. Thyristor Sp Fault: The monitoring of Converter 2 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 48: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

48 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

100 20103 ThyrFlt_Rn_CCI2

CCI2. Thyristor Rn Fault: The monitoring of Converter 2 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 49: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

49 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

101 20104 ThyrFlt_Tp_CCI2

CCI2. Thyristor Tp Fault: The monitoring of Converter 2 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 50: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

50 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

102 20105 ThyrFlt_Sn_CCI2

CCI2. Thyristor Sn Fault: The monitoring of Converter 2 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

103 20106 FuseFlt_Rp_CCI2

CCI2. Fuse Rp Fault: Branch Fuse Rp blown Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters:

Page 51: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

51 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

104 20107 FuseFlt_Tn_CCI2

CCI2. Fuse Tn Fault: Branch Fuse Tn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 52: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

52 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

105 20108 FuseFlt_Sp_CCI2

CCI2. Fuse Sp Fault: Branch Fuse Sp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

106 20109 FuseFlt_Rn_CCI2

CCI2. Fuse Rn Fault: Branch Fuse Rn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 53: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

53 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

107 20110 FuseFlt_Tp_CCI2

CCI2. Fuse Tp Fault: Branch Fuse Tp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 54: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

54 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

108 20111 FuseFlt_Sn_CCI2

CCI2. Fuse Sn Fault: Branch Fuse Sn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

109 20112 TOCD_R_CCI2

CCI2. Overcurrent in Phase R detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Page 55: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

55 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

110 20113 TOCD_S_CCI2

CCI2. Overcurrent in Phase S detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

Page 56: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

56 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

111 20114 TOCD_T_CCI2

CCI2. Overcurrent in Phase T detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

112 20115 UfOpCeil_CCI2

CCI2. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon Further steps: ----

Page 57: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

57 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

113 20116 DevTypeErr_CCI2

CCI2. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 2 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

114 20117 AddressErr_CCI2

CCI2. Address Error Possible reasons: - Wrong HEX Switch setting at CCI 2 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

Page 58: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

58 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

115 20118 LinkFault_CCI2

CCI2. Link Fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to CCI

116 20119 RedPwrFail1_CCI2

CCI2. Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Converter Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

117 20120 RedPwrFail2_CCI2

CCI2. Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:1-2) Default reaction: - Converter Redundancy Fault Related parameters:

Page 59: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

59 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

118 20121 PrciPwrFail_CCI2

CCI2. Precision Power fail Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

119 20122 CPUWatchdog_CCI2

CCI2. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Converter Trip Related parameters: ---- Further steps:

Page 60: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

60 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reboot device - Download installer archive - Replace board

120 20123 UfFreeze_CCI2

CCI2. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UfEnaADCFreezeMon Further steps: - Replace board

121 20124 USynInPhase_CCI2

CCI2. Synchronous Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaInPhaseMon Further steps: - Check cabling

Page 61: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

61 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

122 20125 USynOpCeil_CCI2

CCI2. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon Further steps: - Replace board

123 20126 USynFreeze_CCI2

CCI2. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaADCFreezeMon Further steps: - Replace board

124 20127 USynAllLost_CCI2

CCI2. Synchronous Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaAllLostMon

Page 62: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

62 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling

125 20128 SelfTrip_CCI2

CCI2. Link Fault detected by CCI Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to AC 800PEC

126 20129 AdvFuseBlow_CCI2

CCI2. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby) Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown Further steps: - Check thyristors - Check fuses

Page 63: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

63 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

127 20130 IConvOpCeil_CCI2

CCI2. Converter Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaADCFreezeMon Further steps: - Replace board

128 20131 IConvFreeze_CCI2

CCI2. Converter Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon Further steps: - Replace board

Page 64: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

64 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

129 20132 CoolingFailure_CCI2

CCI2. Cooling failure Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters Default reaction: - Converter TRIP Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor

130 20133 Fan1Supply1Flt_CCI2

CCI2. Fan 1 Supply 1 fault Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

Page 65: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

65 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace pressure sensor

131 20134 Fan1Supply2Flt_CCI2

CCI2. Fan 1 Supply 2 fault Possible reasons: - Fan 1 defective - Supply 2 missing - pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 66: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

66 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

132 20135 Fan2Supply1Flt_CCI2

CCI2. Fan 2 Supply 1 fault Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

133 20136 Fan2Supply2Flt_CCI2

CCI2. Fan 2 Supply 2 fault Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps:

Page 67: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

67 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

134 20137 MCB1Fault_CCI2

CCI2. Fan Supply Miniature Circuit Breaker 1 fault Possible reasons: - Fan 1 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

135 20138 MCB2Fault_CCI2

CCI2. Fan Supply Miniature Circuit Breaker 2 fault Possible reasons: - Fan 2 defective Default reaction: - Converter Redundancy fault Related parameters:

Page 68: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

68 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

136 20139 ThyrTemp1Lev1Fl_CCI2

CCI2. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 69: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

69 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

137 20140 ThyrTemp2Lev1Fl_CCI2

CCI2. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

138 20141 ThyrTemp3Lev1Fl_CCI2

CCI2. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 70: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

70 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

139 20142 ThyrTemp4Lev1Fl_CCI2

CCI2. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 71: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

71 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

140 20143 ThyrTemp5Lev1Fl_CCI2

CCI2. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

141 20144 ThyrTemp6Lev1Fl_CCI2

CCI2. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 72: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

72 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

142 20145 AirTemp1Lev1Flt_CCI2

CCI2. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 73: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

73 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

143 20146 AirTemp2Lev1Flt_CCI2

CCI2. Air Temperature 2 ( Air outlet chimmey ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

144 20147 ThyrTemp1SensFl_CCI2

CCI2. Thyristor Rp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 74: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

74 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Re-check sensor circuit

145 20148 ThyrTemp2SensFl_CCI2

CCI2. Thyristor Tn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 75: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

75 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

146 20149 ThyrTemp3SensFl_CCI2

CCI2. Thyristor Sp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

147 20150 ThyrTemp4SensFl_CCI2

CCI2. Thyristor Rn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 76: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

76 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

148 20151 ThyrTemp5SensFl_CCI2

CCI2. Thyristor Tp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

149 20152 ThyrTemp6SensFl_CCI2

CCI2. Thyristor Sn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 77: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

77 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

150 20153 AirTemp1SensFlt_CCI2

CCI2. Air Temperature 1 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

151 20154 AirTemp2SensFlt_CCI2

CCI2. Air Temperature 2 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

Page 78: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

78 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

152 20155 SnubberSwiFlt_CCI2

CCI2. Snubber Switch fault Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch Default reaction: N-1 - Converter alarm TWIN - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord Further steps: - Re-check sensor circuit

153 20156 SnubberFuseFlt_CCI2

CCI2. Snubber Fuse fault Possible reasons: ---- Default reaction: ---- Related parameters: ---- Further steps: ----

Page 79: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

79 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

154 20157 ThyristorFuseFl_CCI2

CCI2. Thyristor Fuse fault Possible reasons: - Digital input for fuse supervision activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Check and replace faulty thyristors - Check and replace blown fuses

155 20158 DoorFlt_CCI2

CCI2. Converter cabinet Door fault Possible reasons: - Digital input for open door activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Close converter cabinet door

156 20159 VersionFlt_CCI2

CCI2. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Converter Trip Related parameters: ----

Page 80: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

80 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Download required software version

157 20160 NegConvFault_CCI2

CCI2. NegConvFault_CCI2 Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord Further steps: - Re-check HW input

158 20161 PulseBlockFault_CCI2

CCI2. PulseBlock_CCI2 by hardware Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive Default reaction: - Converter Trip Related parameters: ---- Further steps: - Re-check HW input

159 20162 TestPosition_CCI2

Page 81: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

81 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

160 20163 Event2_31_CCI2

161 20164 ThyrTemp1Lev2Fl_CCI2

CCI2. Thyristor Rp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

162 20165 ThyrTemp2Lev2Fl_CCI2

CCI2. Thyristor Tn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas

Page 82: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

82 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

163 20166 ThyrTemp3Lev2Fl_CCI2

CCI2. Thyristor Sp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 83: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

83 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

164 20167 ThyrTemp4Lev2Fl_CCI2

CCI2. Thyristor Rn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

165 20168 ThyrTemp5Lev2Fl_CCI2

CCI2. Thyristor Tp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 84: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

84 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

166 20169 ThyrTemp6Lev2Fl_CCI2

CCI2. Thyristor Sn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 85: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

85 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

167 20170 AirTemp1Lev2Flt_CCI2

CCI2. Air Temperature 1 ( Thyristor Cooler Input ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

168 20171 AirTemp2Lev2Flt_CCI2

CCI2. Air Temperature 2 ( Air outlet chimney ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level

Page 86: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

86 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

169 20172 Event3_08_CCI2

1'341 21500 Event4_14

171 20174 Event3_10_CCI2

172 20175 Event3_11_CCI2

173 20176 Event3_12_CCI2

174 20177 Event3_13_CCI2

175 20178 Event3_14_CCI2

176 20179 Event3_15_CCI2

177 20180 Event3_16_CCI2

178 20181 Event3_17_CCI2

179 20182 Event3_18_CCI2

180 20183 Event3_19_CCI2

181 20184 Event3_20_CCI2

182 20185 Event3_21_CCI2

183 20186 Event3_22_CCI2

184 20187 Event3_23_CCI2

185 20188 Event3_24_CCI2

186 20189 Event3_25_CCI2

187 20190 Event3_26_CCI2

Page 87: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

87 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

188 20191 Event3_27_CCI2

189 20192 Event3_28_CCI2

190 20193 Event3_29_CCI2

191 20194 Event3_30_CCI2

192 20195 Event3_31_CCI2

193 20200 ThyrFlt_Rp_CCI3

CCI3. Thyristor Rp Fault: The monitoring of Converter 3 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 88: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

88 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

194 20201 ThyrFlt_Tn_CCI3

CCI3. Thyristor Tn Fault: The monitoring of Converter 3 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 89: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

89 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

195 20202 ThyrFlt_Sp_CCI3

CCI3. Thyristor Sp Fault: The monitoring of Converter 3 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 90: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

90 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

196 20203 ThyrFlt_Rn_CCI3

CCI3. Thyristor Rn Fault: The monitoring of Converter 3 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 91: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

91 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

197 20204 ThyrFlt_Tp_CCI3

CCI3. Thyristor Tp Fault: The monitoring of Converter 3 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 92: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

92 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

198 20205 ThyrFlt_Sn_CCI3

CCI3. Thyristor Sn Fault: The monitoring of Converter 3 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

199 20206 FuseFlt_Rp_CCI3

CCI3. Fuse Rp Fault: Branch Fuse Rp blown Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters:

Page 93: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

93 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

200 20207 FuseFlt_Tn_CCI3

CCI3. Fuse Tn Fault: Branch Fuse Tn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 94: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

94 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

201 20208 FuseFlt_Sp_CCI3

CCI3. Fuse Sp Fault: Branch Fuse Sp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

202 20209 FuseFlt_Rn_CCI3

CCI3. Fuse Rn Fault: Branch Fuse Rn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 95: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

95 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

203 20210 FuseFlt_Tp_CCI3

CCI3. Fuse Tp Fault: Branch Fuse Tp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 96: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

96 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

204 20211 FuseFlt_Sn_CCI3

CCI3. Fuse Sn Fault: Branch Fuse Sn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

205 20212 TOCD_R_CCI3

CCI3. Overcurrent in Phase R detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Page 97: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

97 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

206 20213 TOCD_S_CCI3

CCI3. Overcurrent in Phase S detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

1'342 20214 SW_Reboot

Page 98: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

98 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

207 20215 TOCD_T_CCI3

CCI3. Overcurrent in Phase T detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

208 20216 UfOpCeil_CCI3

CCI3. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon Further steps: ----

Page 99: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

99 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

209 20217 DevTypeErr_CCI3

CCI3. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 3 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

210 20218 AddressErr_CCI3

CCI3. Address Error Possible reasons: - Wrong HEX Switch setting at CCI 3 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

Page 100: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

100 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

211 20219 LinkFault_CCI3

CCI3. Link Fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to CCI

212 20220 RedPwrFail1_CCI3

CCI3. Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Converter Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

213 20221 RedPwrFail2_CCI3

CCI3. Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:1-2) Default reaction: - Converter Redundancy Fault Related parameters:

Page 101: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

101 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

214 20222 PrciPwrFail_CCI3

CCI3. Precision Power fail Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

215 20223 CPUWatchdog_CCI3

CCI3. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Converter Trip Related parameters: ---- Further steps:

Page 102: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

102 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reboot device - Download installer archive - Replace board

216 20224 UfFreeze_CCI3

CCI3. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UfEnaADCFreezeMon Further steps: - Replace board

217 20225 USynInPhase_CCI3

CCI3. Synchronous Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaInPhaseMon Further steps: - Check cabling

Page 103: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

103 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

218 20226 USynOpCeil_CCI3

CCI3. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon Further steps: - Replace board

219 20227 USynFreeze_CCI3

CCI3. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaADCFreezeMon Further steps: - Replace board

220 20228 USynAllLost_CCI3

CCI3. Synchronous Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaAllLostMon

Page 104: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

104 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling

221 20229 SelfTrip_CCI3

CCI3. Link Fault detected by CCI Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to AC 800PEC

222 20230 AdvFuseBlow_CCI3

CCI3. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby) Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown Further steps: - Check thyristors - Check fuses

Page 105: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

105 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

223 20231 IConvOpCeil_CCI3

CCI3. Converter Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaADCFreezeMon Further steps: - Replace board

224 20232 IConvFreeze_CCI3

CCI3. Converter Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon Further steps: - Replace board

Page 106: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

106 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

225 20233 CoolingFailure_CCI3

CCI3. Cooling failure Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters Default reaction: - Converter TRIP Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor

226 20234 Fan1Supply1Flt_CCI3

CCI3. Fan 1 Supply 1 fault Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

Page 107: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

107 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace pressure sensor

227 20235 Fan1Supply2Flt_CCI3

CCI3. Fan 1 Supply 2 fault Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 108: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

108 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

228 20236 Fan2Supply1Flt_CCI3

CCI3. Fan 2 Supply 1 fault Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

229 20237 Fan2Supply2Flt_CCI3

CCI3. Fan 2 Supply 2 fault Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps:

Page 109: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

109 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace preasure sensor

230 20238 MCB1Fault_CCI3

CCI3. Fan Supply Miniature Circuit Breaker 1 fault Possible reasons: - Fan 1 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

231 20239 MCB2Fault_CCI3

CCI3. Fan Supply Miniature Circuit Breaker 2 fault Possible reasons: - Fan 2 defective Default reaction: - Converter Redundancy fault Related parameters:

Page 110: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

110 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

232 20240 ThyrTemp1Lev1Fl_CCI3

CCI3. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 111: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

111 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

233 20241 ThyrTemp2Lev1Fl_CCI3

CCI3. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

234 20242 ThyrTemp3Lev1Fl_CCI3

CCI3. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 112: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

112 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

235 20243 ThyrTemp4Lev1Fl_CCI3

CCI3. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 113: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

113 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

236 20244 ThyrTemp5Lev1Fl_CCI3

CCI3. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

237 20245 ThyrTemp6Lev1Fl_CCI3

CCI3. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 114: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

114 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

238 20246 AirTemp1Lev1Flt_CCI3

CCI3. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 115: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

115 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

239 20247 AirTemp2Lev1Flt_CCI3

CCI3. Air Temperature 2 ( Air outlet chimmey ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

240 20248 ThyrTemp1SensFl_CCI3

CCI3. Thyristor Rp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 116: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

116 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Re-check sensor circuit

241 20249 ThyrTemp2SensFl_CCI3

CCI3. Thyristor Tn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 117: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

117 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

242 20250 ThyrTemp3SensFl_CCI3

CCI3. Thyristor Sp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

243 20251 ThyrTemp4SensFl_CCI3

CCI3. Thyristor Rn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 118: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

118 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

244 20252 ThyrTemp5SensFl_CCI3

CCI3. Thyristor Tp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

245 20253 ThyrTemp6SensFl_CCI3

CCI3. Thyristor Sn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 119: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

119 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

246 20254 AirTemp1SensFlt_CCI3

CCI3. Air Temperature 1 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

247 20255 AirTemp2SensFlt_CCI3

CCI3. Air Temperature 2 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

Page 120: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

120 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

248 20256 SnubberSwiFlt_CCI3

CCI3. Snubber Switch fault Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch Default reaction: N-1 - Converter alarm TWIN - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord Further steps: - Re-check sensor circuit

249 20257 SnubberFuseFlt_CCI3

CCI3. Snubber Fuse fault Possible reasons: ---- Default reaction: ---- Related parameters: ---- Further steps: ----

Page 121: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

121 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

250 20258 ThyristorFuseFl_CCI3

CCI3. Thyristor Fuse fault Possible reasons: - Digital input for fuse supervision activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Check and replace faulty thyristors - Check and replace blown fuses

251 20259 DoorFlt_CCI3

CCI3. Converter cabinet Door fault Possible reasons: - Digital input for open door activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Close converter cabinet door

252 20260 VersionFlt_CCI3

CCI3. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Converter Trip Related parameters: ----

Page 122: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

122 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Download required software version

253 20261 NegConvFault_CCI3

CCI3. NegConvFault_CCI3 Possible reasons: - The DI12 signal of Converter I/O does not match converter configuration Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord Further steps: - Re-check HW input

254 20262 PulseBlockFault_CCI3

CCI3. PulseBlock_CCI3 by hardware Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive Default reaction: - Converter Trip Related parameters: ---- Further steps: - Re-check HW input

255 20263 TestPosition_CCI3

Page 123: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

123 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

256 20264 Event2_31_CCI3

257 20265 ThyrTemp1Lev2Fl_CCI3

CCI3. Thyristor Rp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

258 20266 ThyrTemp2Lev2Fl_CCI3

CCI3. Thyristor Tn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature

Page 124: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

124 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

fault of the other converters (n-1) - Clean air inlet filters

259 20267 ThyrTemp3Lev2Fl_CCI3

CCI3. Thyristor Sp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

1'343 20268 ForceAuto

Page 125: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

125 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

260 20269 ThyrTemp4Lev2Fl_CCI3

CCI3. Thyristor Rn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

261 20270 ThyrTemp5Lev2Fl_CCI3

CCI3. Thyristor Tp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 126: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

126 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

262 20271 ThyrTemp6Lev2Fl_CCI3

CCI3. Thyristor Sn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 127: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

127 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

263 20272 AirTemp1Lev2Flt_CCI3

CCI3. Air Temperature 1 ( Thyristor Cooler Input ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

264 20273 AirTemp2Lev2Flt_CCI3

CCI3. Air Temperature 2 ( Air outlet chimney ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level

Page 128: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

128 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

265 20274 Event3_08_CCI3

266 20275 Event3_09_CCI3

267 20276 Event3_10_CCI3

268 20277 Event3_11_CCI3

269 20278 Event3_12_CCI3

270 20279 Event3_13_CCI3

271 20280 Event3_14_CCI3

272 20281 Event3_15_CCI3

273 20282 Event3_16_CCI3

274 20283 Event3_17_CCI3

275 20284 Event3_18_CCI3

276 20285 Event3_19_CCI3

277 20286 Event3_20_CCI3

278 20287 Event3_21_CCI3

279 20288 Event3_22_CCI3

280 20289 Event3_23_CCI3

281 20290 Event3_24_CCI3

282 20291 Event3_25_CCI3

Page 129: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

129 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

283 20292 Event3_26_CCI3

284 20293 Event3_27_CCI3

285 20294 Event3_28_CCI3

286 20295 Event3_29_CCI3

287 20300 Event3_30_CCI3

288 20301 Event3_31_CCI3

289 20302 ThyrFlt_Rp_CCI4

CCI4. Thyristor Rp Fault: The monitoring of Converter 4 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 130: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

130 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

290 20303 ThyrFlt_Tn_CCI4

CCI4. Thyristor Tn Fault: The monitoring of Converter 4 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 131: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

131 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

291 20304 ThyrFlt_Sp_CCI4

CCI4. Thyristor Sp Fault: The monitoring of Converter 4 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 132: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

132 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

292 20305 ThyrFlt_Rn_CCI4

CCI4. Thyristor Rn Fault: The monitoring of Converter 4 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

293 20306 ThyrFlt_Tp_CCI4

CCI4. Thyristor Tp Fault: The monitoring of Converter 4 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip

Page 133: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

133 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

294 20307 ThyrFlt_Sn_CCI4

CCI4. Thyristor Sn Fault: The monitoring of Converter 4 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos&Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps:

Page 134: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

134 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

----

295 20308 FuseFlt_Rp_CCI4

CCI4. Fuse Rp Fault: Branch Fuse Rp blown Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 135: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

135 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

296 20309 FuseFlt_Tn_CCI4

CCI4. Fuse Tn Fault: Branch Fuse Tn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

297 20310 FuseFlt_Sp_CCI4

CCI4. Fuse Sp Fault: Branch Fuse Sp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 136: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

136 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

298 20311 FuseFlt_Rn_CCI4

CCI4. Fuse Rn Fault: Branch Fuse Rn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 137: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

137 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

299 20312 FuseFlt_Tp_CCI4

CCI4. Fuse Tp Fault: Branch Fuse Tp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

300 20313 FuseFlt_Sn_CCI4

CCI4. Fuse Sn Fault: Branch Fuse Sn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 138: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

138 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

301 20314 TOCD_R_CCI4

CCI4. Overcurrent in Phase R detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

Page 139: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

139 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

302 20315 TOCD_S_CCI4

CCI4. Overcurrent in Phase S detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

1'344 20316 ForceManual

303 20317 TOCD_T_CCI4

CCI4. Overcurrent in Phase T detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps:

Page 140: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

140 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

----

304 20318 UfOpCeil_CCI4

CCI4. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon Further steps: ----

305 20319 DevTypeErr_CCI4

CCI4. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 4 Default reaction: - Converter Trip

Page 141: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

141 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: ---- Further steps: ----

306 20320 AddressErr_CCI4

CCI4. Address Error Possible reasons: - Wrong HEX Switch setting at CCI 4 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

307 20321 LinkFault_CCI4

CCI4. Link Fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to CCI

Page 142: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

142 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

308 20322 RedPwrFail1_CCI4

CCI4. Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Converter Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

309 20323 RedPwrFail2_CCI4

CCI4. Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:1-2) Default reaction: - Converter Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

310 20324 PrciPwrFail_CCI4

CCI4. Precision Power fail Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing Default reaction: - Converter Trip Related parameters: ----

Page 143: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

143 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling and power supply - Replace board

311 20325 CPUWatchdog_CCI4

CCI4. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Converter Trip Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

312 20326 UfFreeze_CCI4

CCI4. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UfEnaADCFreezeMon

Page 144: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

144 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Replace board

313 20327 USynInPhase_CCI4

CCI4. Synchronous Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaInPhaseMon Further steps: - Check cabling

314 20328 USynOpCeil_CCI4

CCI4. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon Further steps: - Replace board

Page 145: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

145 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

315 20329 USynFreeze_CCI4

CCI4. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaADCFreezeMon Further steps: - Replace board

316 20330 USynAllLost_CCI4

CCI4. Synchronous Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaAllLostMon Further steps: - Check cabling

317 20331 SelfTrip_CCI4

CCI4. Link Fault detected by CCI Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) Default reaction: - Converter Trip Related parameters: ----

Page 146: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

146 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check optical link cabling to AC 800PEC

318 20332 AdvFuseBlow_CCI4

CCI4. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby) Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown Further steps: - Check thyristors - Check fuses

319 20333 IConvOpCeil_CCI4

CCI4. Converter Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaADCFreezeMon Further steps:

Page 147: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

147 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace board

320 20334 IConvFreeze_CCI4

CCI4. Converter Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon Further steps: - Replace board

321 20335 CoolingFailure_CCI4

CCI4. Cooling failure Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters Default reaction: - Converter TRIP Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord Further steps: - Replace fan(s)

Page 148: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

148 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters - Replace pressure sensor

322 20336 Fan1Supply1Flt_CCI4

CCI4. Fan 1 Supply 1 fault Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 149: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

149 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

323 20337 Fan1Supply2Flt_CCI4

CCI4. Fan 1 Supply 2 fault Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

324 20338 Fan2Supply1Flt_CCI4

CCI4. Fan 2 Supply 1 fault Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps:

Page 150: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

150 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace preasure sensor

325 20339 Fan2Supply2Flt_CCI4

CCI4. Fan 2 Supply 2 fault Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 151: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

151 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

326 20340 MCB1Fault_CCI4

CCI4. Fan Supply Miniature Circuit Breaker 1 fault Possible reasons: - Fan 1 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

327 20341 MCB2Fault_CCI4

CCI4. Fan Supply Miniature Circuit Breaker 2 fault Possible reasons: - Fan 2 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

Page 152: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

152 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

328 20342 ThyrTemp1Lev1Fl_CCI4

CCI4. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

329 20343 ThyrTemp2Lev1Fl_CCI4

CCI4. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 153: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

153 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

330 20344 ThyrTemp3Lev1Fl_CCI4

CCI4. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 154: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

154 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

331 20345 ThyrTemp4Lev1Fl_CCI4

CCI4. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

332 20346 ThyrTemp5Lev1Fl_CCI4

CCI4. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 155: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

155 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

333 20347 ThyrTemp6Lev1Fl_CCI4

CCI4. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 156: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

156 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

334 20348 AirTemp1Lev1Flt_CCI4

CCI4. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

335 20349 AirTemp2Lev1Flt_CCI4

CCI4. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas

Page 157: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

157 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

336 20350 ThyrTemp1SensFl_CCI4

CCI4. Thyristor Rp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 158: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

158 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

337 20351 ThyrTemp2SensFl_CCI4

CCI4. Thyristor Tn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

338 20352 ThyrTemp3SensFl_CCI4

CCI4. Thyristor Sp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 159: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

159 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

339 20353 ThyrTemp4SensFl_CCI4

CCI4. Thyristor Rn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

340 20354 ThyrTemp5SensFl_CCI4

CCI4. Thyristor Tp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 160: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

160 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

341 20355 ThyrTemp6SensFl_CCI4

CCI4. Thyristor Sn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

342 20356 AirTemp1SensFlt_CCI4

CCI4. Air Temperature 1 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

Page 161: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

161 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

343 20357 AirTemp2SensFlt_CCI4

CCI4. Air Temperature 2 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

344 20358 SnubberSwiFlt_CCI4

CCI4. Snubber Switch fault Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch Default reaction: N-1 - Converter alarm TWIN - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord Further steps: - Re-check sensor circuit

Page 162: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

162 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

345 20359 SnubberFuseFlt_CCI4

CCI4. Snubber Fuse fault Possible reasons: ---- Default reaction: ---- Related parameters: ---- Further steps: ----

346 20360 ThyristorFuseFl_CCI4

CCI4. Thyristor Fuse fault Possible reasons: - Digital input for fuse supervision activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Check and replace faulty thyristors - Check and replace blown fuses

347 20361 DoorFlt_CCI4

CCI4. Converter cabinet Door fault Possible reasons: - Digital input for open door activated Default reaction: - Converter alarm Related parameters: ----

Page 163: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

163 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Close converter cabinet door

348 20362 VersionFlt_CCI4

CCI4. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Converter Trip Related parameters: ---- Further steps: - Download required software version

349 20363 NegConvFault_CCI4

CCI4. NegConvFault_CCI4 Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord Further steps: - Re-check HW input

Page 164: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

164 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

350 20364 PulseBlockFault_CCI4

CCI4. PulseBlock_CCI4 by hardware Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive Default reaction: - Converter Trip Related parameters: ---- Further steps: - Re-check HW input

351 20365 TestPosition_CCI4

352 20366 Event2_31_CCI4

353 20367 ThyrTemp1Lev2Fl_CCI4

CCI4. Thyristor Rp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 165: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

165 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

354 20368 ThyrTemp2Lev2Fl_CCI4

CCI4. Thyristor Tn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

355 20369 ThyrTemp3Lev2Fl_CCI4

CCI4. Thyristor Sp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 166: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

166 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

1'345 20370 ForceChannel1

356 20371 ThyrTemp4Lev2Fl_CCI4

CCI4. Thyristor Rn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 167: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

167 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

357 20372 ThyrTemp5Lev2Fl_CCI4

CCI4. Thyristor Tp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

358 20373 ThyrTemp6Lev2Fl_CCI4

CCI4. Thyristor Sn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 168: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

168 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

359 20374 AirTemp1Lev2Flt_CCI4

CCI4. Air Temperature 1 ( Thyristor Cooler Input ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 169: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

169 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

360 20375 AirTemp2Lev2Flt_CCI4

CCI4. Air Temperature 2 ( Air outlet chimney ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

361 20376 Event3_08_CCI4

362 20377 Event3_09_CCI4

363 20378 Event3_10_CCI4

364 20379 Event3_11_CCI4

365 20380 Event3_12_CCI4

366 20381 Event3_13_CCI4

367 20382 Event3_14_CCI4

368 20383 Event3_15_CCI4

369 20384 Event3_16_CCI4

370 20385 Event3_17_CCI4

371 20386 Event3_18_CCI4

372 20387 Event3_19_CCI4

373 20388 Event3_20_CCI4

374 20389 Event3_21_CCI4

Page 170: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

170 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

375 20390 Event3_22_CCI4

376 20391 Event3_23_CCI4

377 20392 Event3_24_CCI4

378 20393 Event3_25_CCI4

379 20394 Event3_26_CCI4

380 20395 Event3_27_CCI4

381 20400 Event3_28_CCI4

382 20401 Event3_29_CCI4

383 20402 Event3_30_CCI4

384 20403 Event3_31_CCI4

385 20404 ThyrFlt_Rp_CCI5

CCI5. Thyristor Rp Fault: The monitoring of Converter 5 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 171: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

171 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

386 20405 ThyrFlt_Tn_CCI5

CCI5. Thyristor Tn Fault: The monitoring of Converter 5 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 172: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

172 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

387 20406 ThyrFlt_Sp_CCI5

CCI5. Thyristor Sp Fault: The monitoring of Converter 5 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 173: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

173 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

388 20407 ThyrFlt_Rn_CCI5

CCI5. Thyristor Rn Fault: The monitoring of Converter 5 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 174: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

174 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

389 20408 ThyrFlt_Tp_CCI5

CCI5. Thyristor Tp Fault: The monitoring of Converter 5 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 175: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

175 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

390 20409 ThyrFlt_Sn_CCI5

CCI5. Thyristor Sn Fault: The monitoring of Converter 5 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

391 20410 FuseFlt_Rp_CCI5

CCI5. Fuse Rp Fault: Branch Fuse Rp blown Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters:

Page 176: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

176 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

392 20411 FuseFlt_Tn_CCI5

CCI5. Fuse Tn Fault: Branch Fuse Tn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 177: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

177 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

393 20412 FuseFlt_Sp_CCI5

CCI5. Fuse Sp Fault: Branch Fuse Sp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

394 20413 FuseFlt_Rn_CCI5

CCI5. Fuse Rn Fault: Branch Fuse Rn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 178: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

178 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

395 20414 FuseFlt_Tp_CCI5

CCI5. Fuse Tp Fault: Branch Fuse Tp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 179: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

179 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

396 20415 FuseFlt_Sn_CCI5

CCI5. Fuse Sn Fault: Branch Fuse Sn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

397 20416 TOCD_R_CCI5

CCI5. Overcurrent in Phase R detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Page 180: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

180 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

398 20417 TOCD_S_CCI5

CCI5. Overcurrent in Phase S detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

1'346 20418 ForceChannel2

Page 181: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

181 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

399 20419 TOCD_T_CCI5

CCI5. Overcurrent in Phase T deteced Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

400 20420 UfOpCeil_CCI5

CCI5. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon Further steps: ----

Page 182: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

182 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

401 20421 DevTypeErr_CCI5

CCI5. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 5 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

402 20422 AddressErr_CCI5

CCI5. Address Error Possible reasons: - Wrong HEX Switch setting at CCI 5 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

Page 183: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

183 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

403 20423 LinkFault_CCI5

CCI5. Link Fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to CCI

404 20424 RedPwrFail1_CCI5

CCI5. Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Converter Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

405 20425 RedPwrFail2_CCI5

CCI5. Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:1-2) Default reaction: - Converter Redundancy Fault Related parameters:

Page 184: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

184 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

406 20426 PrciPwrFail_CCI5

CCI5. Precision Power fail Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

407 20427 CPUWatchdog_CCI5

CCI5. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Converter Trip Related parameters: ---- Further steps:

Page 185: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

185 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reboot device - Download installer archive - Replace board

408 20428 UfFreeze_CCI5

CCI5. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UfEnaADCFreezeMon Further steps: - Replace board

409 20429 USynInPhase_CCI5

CCI5. Synchronous Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaInPhaseMon Further steps: - Check cabling

Page 186: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

186 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

410 20430 USynOpCeil_CCI5

CCI5. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon Further steps: - Replace board

411 20431 USynFreeze_CCI5

CCI5. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaADCFreezeMon Further steps: - Replace board

412 20432 USynAllLost_CCI5

CCI5. Synchronous Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaAllLostMon

Page 187: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

187 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling

413 20433 SelfTrip_CCI5

CCI5. Link Fault detected by CCI Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to AC 800PEC

414 20434 AdvFuseBlow_CCI5

CCI5. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby) Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown Further steps: - Check thyristors - Check fuses

Page 188: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

188 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

415 20435 IConvOpCeil_CCI5

CCI5. Converter Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaADCFreezeMon Further steps: - Replace board

416 20436 IConvFreeze_CCI5

CCI5. Converter Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon Further steps: - Replace board

Page 189: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

189 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

417 20437 CoolingFailure_CCI5

CCI5. Cooling failure Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters Default reaction: - Converter TRIP Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor

418 20438 Fan1Supply1Flt_CCI5

CCI5. Fan 1 Supply 1 fault Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

Page 190: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

190 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace pressure sensor

419 20439 Fan1Supply2Flt_CCI5

CCI5. Fan 1 Supply 2 fault Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 191: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

191 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

420 20440 Fan2Supply1Flt_CCI5

CCI5. Fan 2 Supply 1 fault Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

421 20441 Fan2Supply2Flt_CCI5

CCI5. Fan 2 Supply 2 fault Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps:

Page 192: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

192 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

422 20442 MCB1Fault_CCI5

CCI5. Fan Supply Miniature Circuit Breaker 1 fault Possible reasons: - Fan 1 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

423 20443 MCB2Fault_CCI5

CCI5. Fan Supply Miniature Circuit Breaker 2 fault Possible reasons: - Fan 2 defective Default reaction: - Converter Redundancy fault Related parameters:

Page 193: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

193 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

424 20444 ThyrTemp1Lev1Fl_CCI5

CCI5. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 194: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

194 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

425 20445 ThyrTemp2Lev1Fl_CCI5

CCI5. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

426 20446 ThyrTemp3Lev1Fl_CCI5

CCI5. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 195: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

195 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

427 20447 ThyrTemp4Lev1Fl_CCI5

CCI5. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 196: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

196 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

428 20448 ThyrTemp5Lev1Fl_CCI5

CCI5. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

429 20449 ThyrTemp6Lev1Fl_CCI5

CCI5. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 197: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

197 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

430 20450 AirTemp1Lev1Flt_CCI5

CCI5. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 198: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

198 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

431 20451 AirTemp2Lev1Flt_CCI5

CCI5. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

432 20452 ThyrTemp1SensFl_CCI5

CCI5. Thyristor Rp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 199: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

199 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Re-check sensor circuit

433 20453 ThyrTemp2SensFl_CCI5

CCI5. Thyristor Tn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 200: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

200 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

434 20454 ThyrTemp3SensFl_CCI5

CCI5. Thyristor Sp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

435 20455 ThyrTemp4SensFl_CCI5

CCI5. Thyristor Rn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 201: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

201 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

436 20456 ThyrTemp5SensFl_CCI5

CCI5. Thyristor Tp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

437 20457 ThyrTemp6SensFl_CCI5

CCI5. Thyristor Sn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 202: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

202 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

438 20458 AirTemp1SensFlt_CCI5

CCI5. Air Temperature 1 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

439 20459 AirTemp2SensFlt_CCI5

CCI5. Air Temperature 2 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

Page 203: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

203 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

440 20460 SnubberSwiFlt_CCI5

CCI5. Snubber Switch fault Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch Default reaction: N-1 - Converter alarm TWIN - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord Further steps: - Re-check sensor circuit

441 20461 SnubberFuseFlt_CCI5

CCI5. Snubber Fuse fault Possible reasons: ---- Default reaction: ---- Related parameters: ---- Further steps: ----

Page 204: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

204 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

442 20462 ThyristorFuseFl_CCI5

CCI5. Thyristor Fuse fault Possible reasons: - Digital input for fuse supervision activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Check and replace faulty thyristors - Check and replace blown fuses

443 20463 DoorFlt_CCI5

CCI5. Converter cabinet Door fault Possible reasons: - Digital input for open door activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Close converter cabinet door

444 20464 VersionFlt_CCI5

CCI5. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Converter Trip Related parameters: ----

Page 205: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

205 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Download required software version

445 20465 NegConvFault_CCI5

CCI5. NegConvFault_CCI5 Possible reasons: - The DI 12 signal of Converter I/O does not match to converter configuration Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord Further steps: - Re-check HW input

446 20466 PulseBlockFault_CCI5

CCI5. PulseBlock_CCI5 by hardware Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive Default reaction: - Converter Trip Related parameters: ---- Further steps: - Re-check HW input

447 20467 TestPosition_CCI5

Page 206: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

206 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

448 20468 Event2_31_CCI5

449 20469 ThyrTemp1Lev2Fl_CCI5

CCI5. Thyristor Rp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

450 20470 ThyrTemp2Lev2Fl_CCI5

CCI5. Thyristor Tn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature

Page 207: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

207 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

fault of the other converters (n-1) - Clean air inlet filters

451 20471 ThyrTemp3Lev2Fl_CCI5

CCI5. Thyristor Sp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

1'347 20472 ForceBU

Page 208: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

208 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

452 20473 ThyrTemp4Lev2Fl_CCI5

CCI5. Thyristor Rn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

453 20474 ThyrTemp5Lev2Fl_CCI5

CCI5. Thyristor Tp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 209: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

209 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

454 20475 ThyrTemp6Lev2Fl_CCI5

CCI5. Thyristor Sn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 210: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

210 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

455 20476 AirTemp1Lev2Flt_CCI5

CCI5. Air Temperature 1 ( Thyristor Cooler Input ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

456 20477 AirTemp2Lev2Flt_CCI5

CCI5. Air Temperature 2 ( Air outlet chimney ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level

Page 211: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

211 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

457 20478 Event3_08_CCI5

458 20479 Event3_09_CCI5

459 20480 Event3_10_CCI5

460 20481 Event3_11_CCI5

461 20482 Event3_12_CCI5

462 20483 Event3_13_CCI5

463 20484 Event3_14_CCI5

464 20485 Event3_15_CCI5

465 20486 Event3_16_CCI5

466 20487 Event3_17_CCI5

467 20488 Event3_18_CCI5

468 20489 Event3_19_CCI5

469 20490 Event3_20_CCI5

470 20491 Event3_21_CCI5

471 20492 Event3_22_CCI5

472 20493 Event3_23_CCI5

473 20494 Event3_24_CCI5

474 20495 Event3_25_CCI5

Page 212: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

212 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

475 20500 Event3_26_CCI5

476 20501 Event3_27_CCI5

477 20502 Event3_28_CCI5

478 20503 Event3_29_CCI5

479 20504 Event3_30_CCI5

480 20505 Event3_31_CCI5

481 20506 ThyrFlt_Rp_CCI6

CCI6. Thyristor Rp Fault: The monitoring of Converter 6 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 213: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

213 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

482 20507 ThyrFlt_Tn_CCI6

CCI6. Thyristor Tn Fault: The monitoring of Converter 6 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 214: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

214 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

483 20508 ThyrFlt_Sp_CCI6

CCI6. Thyristor Sp Fault: The monitoring of Converter 6 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 215: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

215 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

484 20509 ThyrFlt_Rn_CCI6

CCI6. Thyristor Rn Fault: The monitoring of Converter 6 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 216: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

216 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

485 20510 ThyrFlt_Tp_CCI6

CCI6. Thyristor Tp Fault: The monitoring of Converter 6 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 217: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

217 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

486 20511 ThyrFlt_Sn_CCI6

CCI6. Thyristor Sn Fault: The monitoring of Converter 6 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

487 20512 FuseFlt_Rp_CCI6

CCI6. Fuse Rp Fault: Branch Fuse Rp blown Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters:

Page 218: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

218 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

488 20513 FuseFlt_Tn_CCI6

CCI6. Fuse Tn Fault: Branch Fuse Tn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 219: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

219 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

489 20514 FuseFlt_Sp_CCI6

CCI6. Fuse Sp Fault: Branch Fuse Sp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

490 20515 FuseFlt_Rn_CCI6

CCI6. Fuse Rn Fault: Branch Fuse Rn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 220: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

220 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

491 20516 FuseFlt_Tp_CCI6

CCI6. Fuse Tp Fault: Branch Fuse Tp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 221: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

221 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

492 20517 FuseFlt_Sn_CCI6

CCI6. Fuse Sn Fault: Branch Fuse Sn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

493 20518 TOCD_R_CCI6

CCI6. Overcurrent in Phase R detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Page 222: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

222 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

494 20519 TOCD_S_CCI6

CCI6. Overcurrent in Phase S detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

1'348 20520 NoCHAlarmActive

Page 223: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

223 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

495 20521 TOCD_T_CCI6

CCI6. Overcurrent in Phase T detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

496 20522 UfOpCeil_CCI6

CCI6. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon Further steps: ----

Page 224: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

224 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

497 20523 DevTypeErr_CCI6

CCI6. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 6 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

498 20524 AddressErr_CCI6

CCI6. Address Error Possible reasons: - Wrong HEX Switch setting at CCI 6 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

Page 225: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

225 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

499 20525 LinkFault_CCI6

CCI6. Link Fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to CCI

500 20526 RedPwrFail1_CCI6

CCI6. Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Converter Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

501 20527 RedPwrFail2_CCI6

CCI6. Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:1-2) Default reaction: - Converter Redundancy Fault Related parameters:

Page 226: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

226 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

502 20528 PrciPwrFail_CCI6

CCI6. Precision Power fail Possible reasons: - Internal power fail on CCI - Both pover supply inputs are missing Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

503 20529 CPUWatchdog_CCI6

CCI6. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Converter Trip Related parameters: ---- Further steps:

Page 227: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

227 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reboot device - Download installer archive - Replace board

504 20530 UfFreeze_CCI6

CCI6. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UfEnaADCFreezeMon Further steps: - Replace board

505 20531 USynInPhase_CCI6

CCI6. Synchronous Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaInPhaseMon Further steps: - Check cabling

Page 228: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

228 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

506 20532 USynOpCeil_CCI6

CCI6. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon Further steps: - Replace board

507 20533 USynFreeze_CCI6

CCI6. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaADCFreezeMon Further steps: - Replace board

508 20534 USynAllLost_CCI6

CCI6. Synchronous Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaAllLostMon

Page 229: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

229 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling

509 20535 SelfTrip_CCI6

CCI6. Link Fault detected by CCI Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to AC 800PEC

510 20536 AdvFuseBlow_CCI6

CCI6. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby) Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown Further steps: - Check thyristors - Check fuses

Page 230: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

230 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

511 20537 IConvOpCeil_CCI6

CCI6. Converter Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaADCFreezeMon Further steps: - Replace board

512 20538 IConvFreeze_CCI6

CCI6. Converter Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon Further steps: - Replace board

Page 231: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

231 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

513 20539 CoolingFailure_CCI6

CCI6. Cooling failure Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters Default reaction: - Converter TRIP Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor

514 20540 Fan1Supply1Flt_CCI6

CCI6. Fan 1 Supply 1 fault Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

Page 232: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

232 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace pressure sensor

515 20541 Fan1Supply2Flt_CCI6

CCI6. Fan 1 Supply 2 fault Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 233: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

233 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

516 20542 Fan2Supply1Flt_CCI6

CCI6. Fan 2 Supply 1 fault Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

517 20543 Fan2Supply2Flt_CCI6

CCI6. Fan 2 Supply 2 fault Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps:

Page 234: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

234 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

518 20544 MCB1Fault_CCI6

CCI6. Fan Supply Miniature Circuit Breaker 1 fault Possible reasons: - Fan 1 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

519 20545 MCB2Fault_CCI6

CCI6. Fan Supply Miniature Circuit Breaker 2 fault Possible reasons: - Fan 2 defective Default reaction: - Converter Redundancy fault Related parameters:

Page 235: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

235 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

520 20546 ThyrTemp1Lev1Fl_CCI6

CCI6. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 236: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

236 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

521 20547 ThyrTemp2Lev1Fl_CCI6

CCI6. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

522 20548 ThyrTemp3Lev1Fl_CCI6

CCI6. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 237: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

237 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

523 20549 ThyrTemp4Lev1Fl_CCI6

CCI6. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 238: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

238 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

524 20550 ThyrTemp5Lev1Fl_CCI6

CCI6. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

525 20551 ThyrTemp6Lev1Fl_CCI6

CCI6. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 239: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

239 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

526 20552 AirTemp1Lev1Flt_CCI6

CCI6. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 240: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

240 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

527 20553 AirTemp2Lev1Flt_CCI6

CCI6. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

528 20554 ThyrTemp1SensFl_CCI6

CCI6. Thyristor Rp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 241: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

241 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Re-check sensor circuit

529 20555 ThyrTemp2SensFl_CCI6

CCI6. Thyristor Tn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 242: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

242 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

530 20556 ThyrTemp3SensFl_CCI6

CCI6. Thyristor Sp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

531 20557 ThyrTemp4SensFl_CCI6

CCI6. Thyristor Rn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 243: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

243 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

532 20558 ThyrTemp5SensFl_CCI6

CCI6. Thyristor Tp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

533 20559 ThyrTemp6SensFl_CCI6

CCI6. Thyristor Sn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 244: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

244 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

534 20560 AirTemp1SensFlt_CCI6

CCI6. Air Temperature 1 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

535 20561 AirTemp2SensFlt_CCI6

CCI6. Air Temperature 2 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

Page 245: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

245 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

536 20562 SnubberSwiFlt_CCI6

CCI6. Snubber Switch fault Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch Default reaction: N-1 - Converter alarm TWIN - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord Further steps: - Re-check sensor circuit

537 20563 SnubberFuseFlt_CCI6

CCI6. Snubber Fuse fault Possible reasons: ---- Default reaction: ---- Related parameters: ---- Further steps: ----

Page 246: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

246 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

538 20564 ThyristorFuseFl_CCI6

CCI6. Thyristor Fuse fault Possible reasons: - Digital input for fuse supervision activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Check and replace faulty thyristors - Check and replace blown fuses

539 20565 DoorFlt_CCI6

CCI6. Converter cabinet Door fault Possible reasons: - Digital input for open door activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Close converter cabinet door

540 20566 VersionFlt_CCI6

CCI6. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Converter Trip Related parameters: ----

Page 247: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

247 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Download required software version

541 20567 NegConvFault_CCI6

CCI6. NegConvFault_CCI6 Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord Further steps: - Re-check HW input

542 20568 PulseBlockFault_CCI6

CCI6. PulseBlock_CCI6 by hardware Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive Default reaction: - Converter Trip Related parameters: ---- Further steps: - Re-check HW input

543 20569 TestPosition_CCI6

Page 248: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

248 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

544 20570 Event2_31_CCI6

545 20571 ThyrTemp1Lev2Fl_CCI6

CCI6. Thyristor Rp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

546 20572 ThyrTemp2Lev2Fl_CCI6

CCI6. Thyristor Tn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature

Page 249: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

249 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

fault of the other converters (n-1) - Clean air inlet filters

547 20573 ThyrTemp3Lev2Fl_CCI6

CCI6. Thyristor Sp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 250: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

250 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

548 20574 ThyrTemp4Lev2Fl_CCI6

CCI6. Thyristor Rn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

549 20575 ThyrTemp5Lev2Fl_CCI6

CCI6. Thyristor Tp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 251: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

251 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

550 20576 ThyrTemp6Lev2Fl_CCI6

CCI6. Thyristor Sn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 252: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

252 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

551 20577 AirTemp1Lev2Flt_CCI6

CCI6. Air Temperature 1 ( Thyristor Cooler Input ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

552 20578 AirTemp2Lev2Flt_CCI6

CCI6. Air Temperature 2 ( Air outlet chimney ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level

Page 253: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

253 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

553 20579 Event3_08_CCI6

554 20580 Event3_09_CCI6

555 20581 Event3_10_CCI6

556 20582 Event3_11_CCI6

557 20583 Event3_12_CCI6

558 20584 Event3_13_CCI6

559 20585 Event3_14_CCI6

560 20586 Event3_15_CCI6

561 20587 Event3_16_CCI6

562 20588 Event3_17_CCI6

563 20589 Event3_18_CCI6

564 20590 Event3_19_CCI6

565 20591 Event3_20_CCI6

566 20592 Event3_21_CCI6

567 20593 Event3_22_CCI6

568 20594 Event3_23_CCI6

569 20595 Event3_24_CCI6

570 20600 Event3_25_CCI6

Page 254: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

254 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

571 20601 Event3_26_CCI6

572 20602 Event3_27_CCI6

573 20603 Event3_28_CCI6

574 20604 Event3_29_CCI6

575 20605 Event3_30_CCI6

576 20606 Event3_31_CCI6

577 20607 ThyrFlt_Rp_CCI7

CCI7. Thyristor Rp Fault: The monitoring of Converter 7 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 255: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

255 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

578 20608 ThyrFlt_Tn_CCI7

CCI7. Thyristor Tn Fault: The monitoring of Converter 7 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 256: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

256 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

579 20609 ThyrFlt_Sp_CCI7

CCI7. Thyristor Sp Fault: The monitoring of Converter 7 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 257: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

257 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

580 20610 ThyrFlt_Rn_CCI7

CCI7. Thyristor Rn Fault: The monitoring of Converter 7 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 258: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

258 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

581 20611 ThyrFlt_Tp_CCI7

CCI7. Thyristor Tp Fault: The monitoring of Converter 7 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 259: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

259 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

582 20612 ThyrFlt_Sn_CCI7

CCI7. Thyristor Sn Fault: The monitoring of Converter 7 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

583 20613 FuseFlt_Rp_CCI7

CCI7. Fuse Rp Fault: Branch Fuse Rp blown Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters:

Page 260: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

260 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

584 20614 FuseFlt_Tn_CCI7

CCI7. Fuse Tn Fault: Branch Fuse Tn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 261: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

261 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

585 20615 FuseFlt_Sp_CCI7

CCI7. Fuse Sp Fault: Branch Fuse Sp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

586 20616 FuseFlt_Rn_CCI7

CCI7. Fuse Rn Fault: Branch Fuse Rn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 262: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

262 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

587 20617 FuseFlt_Tp_CCI7

CCI7. Fuse Tp Fault: Branch Fuse Tp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 263: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

263 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

588 20618 FuseFlt_Sn_CCI7

CCI7. Fuse Sn Fault: Branch Fuse Sn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

589 20619 TOCD_R_CCI7

CCI7. Overcurrent in Phase R detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Page 264: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

264 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

590 20620 TOCD_S_CCI7

CCI7. Overcurrent in Phase S detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

Page 265: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

265 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

591 20621 TOCD_T_CCI7

CCI7. Overcurrent in Phase T detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

592 20622 UfOpCeil_CCI7

CCI7. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon Further steps: ----

Page 266: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

266 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

593 20623 DevTypeErr_CCI7

CCI7. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 2 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

594 20624 AddressErr_CCI7

CCI7. Address Error Possible reasons: - Wrong HEX Switch setting at CCI 2 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

Page 267: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

267 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

595 20625 LinkFault_CCI7

CCI7. Link Fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to CCI

596 20626 RedPwrFail1_CCI7

CCI7. Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Converter Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

597 20627 RedPwrFail2_CCI7

CCI7. Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:1-2) Default reaction: - Converter Redundancy Fault Related parameters:

Page 268: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

268 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

598 20628 PrciPwrFail_CCI7

CCI7. Precision Power fail Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

599 20629 CPUWatchdog_CCI7

CCI7. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Converter Trip Related parameters: ---- Further steps:

Page 269: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

269 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reboot device - Download installer archive - Replace board

600 20630 UfFreeze_CCI7

CCI7. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UfEnaADCFreezeMon Further steps: - Replace board

601 20631 USynInPhase_CCI7

CCI7. Synchronous Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaInPhaseMon Further steps: - Check cabling

Page 270: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

270 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

602 20632 USynOpCeil_CCI7

CCI7. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon Further steps: - Replace board

603 20633 USynFreeze_CCI7

CCI7. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaADCFreezeMon Further steps: - Replace board

604 20634 USynAllLost_CCI7

CCI7. Synchronous Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaAllLostMon

Page 271: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

271 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling

605 20635 SelfTrip_CCI7

CCI7. Link Fault detected by CCI Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to AC 800PEC

606 20636 AdvFuseBlow_CCI7

CCI7. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby) Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown Further steps: - Check thyristors - Check fuses

Page 272: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

272 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

607 20637 IConvOpCeil_CCI7

CCI7. Converter Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaADCFreezeMon Further steps: - Replace board

608 20638 IConvFreeze_CCI7

CCI7. Converter Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon Further steps: - Replace board

Page 273: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

273 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

609 20639 CoolingFailure_CCI7

CCI7. Cooling failure Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters Default reaction: - Converter TRIP Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor

610 20640 Fan1Supply1Flt_CCI7

CCI7. Fan 1 Supply 1 fault Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

Page 274: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

274 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace pressure sensor

611 20641 Fan1Supply2Flt_CCI7

CCI7. Fan 1 Supply 2 fault Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 275: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

275 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

612 20642 Fan2Supply1Flt_CCI7

CCI7. Fan 2 Supply 1 fault Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

613 20643 Fan2Supply2Flt_CCI7

CCI7. Fan 2 Supply 2 fault Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps:

Page 276: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

276 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

614 20644 MCB1Fault_CCI7

CCI7. Fan Supply Miniature Circuit Breaker 1 fault Possible reasons: - Fan 1 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - replace fan (HW-schematic page 410) - re-check cabling

615 20645 MCB2Fault_CCI7

CCI7. Fan Supply Miniature Circuit Breaker 2 fault Possible reasons: - Fan 2 defective Default reaction: - Converter Redundancy fault Related parameters:

Page 277: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

277 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

616 20646 ThyrTemp1Lev1Fl_CCI7

CCI7. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 278: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

278 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

617 20647 ThyrTemp2Lev1Fl_CCI7

CCI7. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

618 20648 ThyrTemp3Lev1Fl_CCI7

CCI7. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 279: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

279 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

619 20649 ThyrTemp4Lev1Fl_CCI7

CCI7. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 280: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

280 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

620 20650 ThyrTemp5Lev1Fl_CCI7

CCI7. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

621 20651 ThyrTemp6Lev1Fl_CCI7

CCI7. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 281: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

281 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

622 20652 AirTemp1Lev1Flt_CCI7

CCI7. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 282: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

282 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

623 20653 AirTemp2Lev1Flt_CCI7

CCI7. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

624 20654 ThyrTemp1SensFl_CCI7

CCI7. Thyristor Rp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 283: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

283 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Re-check sensor circuit

625 20655 ThyrTemp2SensFl_CCI7

CCI7. Thyristor Tn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 284: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

284 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

626 20656 ThyrTemp3SensFl_CCI7

CCI7. Thyristor Sp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

627 20657 ThyrTemp4SensFl_CCI7

CCI7. Thyristor Rn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 285: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

285 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

628 20658 ThyrTemp5SensFl_CCI7

CCI7. Thyristor Tp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

629 20659 ThyrTemp6SensFl_CCI7

CCI7. Thyristor Sn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 286: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

286 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

630 20660 AirTemp1SensFlt_CCI7

CCI7. Air Temperature 1 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

631 20661 AirTemp2SensFlt_CCI7

CCI7. Air Temperature 2 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

Page 287: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

287 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

632 20662 SnubberSwiFlt_CCI7

CCI7. Snubber Switch fault Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch Default reaction: N-1 - Converter alarm TWIN - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord Further steps: - Re-check sensor circuit

633 20663 SnubberFuseFlt_CCI7

CCI7. Snubber Fuse fault Possible reasons: ---- Default reaction: ---- Related parameters: ---- Further steps: ----

Page 288: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

288 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

634 20664 ThyristorFuseFl_CCI7

CCI7. Thyristor Fuse fault Possible reasons: - Digital input for fuse supervision activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Check and replace faulty thyristors - Check and replace blown fuses

635 20665 DoorFlt_CCI7

CCI7. Converter cabinet Door fault Possible reasons: - Digital input for open door activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Close converter cabinet door

636 20666 VersionFlt_CCI7

CCI7. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Converter Trip Related parameters: ----

Page 289: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

289 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Download required software version

637 20667 NegConvFault_CCI7

CCI7. NegConvFault_CCI7 Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord Further steps: - Re-check HW input

638 20668 PulseBlockFault_CCI7

CCI7. PulseBlock_CCI7 by hardware Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive Default reaction: - Converter Trip Related parameters: ---- Further steps: - Re-check HW input

639 20669 TestPosition_CCI7

Page 290: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

290 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

640 20670 Event2_31_CCI7

641 20671 ThyrTemp1Lev2Fl_CCI7

CCI7. Thyristor Rp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

642 20672 ThyrTemp2Lev2Fl_CCI7

CCI7. Thyristor Tn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature

Page 291: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

291 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

fault of the other converters (n-1) - Clean air inlet filters

643 20673 ThyrTemp3Lev2Fl_CCI7

CCI7. Thyristor Sp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 292: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

292 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

644 20674 ThyrTemp4Lev2Fl_CCI7

CCI7. Thyristor Rn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

645 20675 ThyrTemp5Lev2Fl_CCI7

CCI7. Thyristor Tp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 293: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

293 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

646 20676 ThyrTemp6Lev2Fl_CCI7

CCI7. Thyristor Sn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 294: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

294 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

647 20677 AirTemp1Lev2Flt_CCI7

CCI7. Air Temperature 1 ( Thyristor Cooler Input ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

648 20678 AirTemp2Lev2Flt_CCI7

CCI7. Air Temperature 2 ( Air outlet chimney ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level

Page 295: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

295 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

649 20679 Event3_08_CCI7

650 20680 Event3_09_CCI7

651 20681 Event3_10_CCI7

652 20682 Event3_11_CCI7

653 20683 Event3_12_CCI7

654 20684 Event3_13_CCI7

655 20685 Event3_14_CCI7

656 20686 Event3_15_CCI7

657 20687 Event3_16_CCI7

658 20688 Event3_17_CCI7

659 20689 Event3_18_CCI7

660 20690 Event3_19_CCI7

661 20691 Event3_20_CCI7

662 20692 Event3_21_CCI7

663 20693 Event3_22_CCI7

664 20694 Event3_23_CCI7

665 20695 Event3_24_CCI7

666 20700 Event3_25_CCI7

Page 296: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

296 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

667 20701 Event3_26_CCI7

668 20702 Event3_27_CCI7

669 20703 Event3_28_CCI7

670 20704 Event3_29_CCI7

671 20705 Event3_30_CCI7

672 20706 Event3_31_CCI7

673 20707 ThyrFlt_Rp_CCI8

CCI8. Thyristor Rp Fault: The monitoring of Converter 8 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 297: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

297 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

674 20708 ThyrFlt_Tn_CCI8

CCI8. Thyristor Tn Fault: The monitoring of Converter 8 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 298: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

298 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

675 20709 ThyrFlt_Sp_CCI8

CCI8. Thyristor Sp Fault: The monitoring of Converter 8 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 299: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

299 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

676 20710 ThyrFlt_Rn_CCI8

CCI8. Thyristor Rn Fault: The monitoring of Converter 8 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 300: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

300 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

677 20711 ThyrFlt_Tp_CCI8

CCI2. Thyristor Tp Fault: The monitoring of Converter 2 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 301: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

301 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

678 20712 ThyrFlt_Sn_CCI8

CCI2. Thyristor Sn Fault: The monitoring of Converter 2 has detected a non conducting thyristor Possible reasons: - Pulse cable broken - Thyristor faulty - Gate driver interface card (UN S0881) faulty - Pulse card (PC D231) faulty - Current transformer faulty (Pos & Neg thyristor at same time) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

679 20713 FuseFlt_Rp_CCI8

CCI8. Fuse Rp Fault: Branch Fuse Rp blown Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters:

Page 302: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

302 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

680 20714 FuseFlt_Tn_CCI8

CCI8. Fuse Tn Fault: Branch Fuse Tn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 303: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

303 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

681 20715 FuseFlt_Sp_CCI8

CCI8. Fuse Sp Fault: Branch Fuse Sp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

682 20716 FuseFlt_Rn_CCI8

CCI8. Fuse Rn Fault: Branch Fuse Rn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold

Page 304: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

304 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFFDnumOfPeriods Further steps: ----

683 20717 FuseFlt_Tp_CCI8

CCI8. Fuse Tp Fault: Branch Fuse Tp faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

Page 305: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

305 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

684 20718 FuseFlt_Sn_CCI8

CCI8. Fuse Sn Fault: Branch Fuse Sn faulty Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter redundancy fault Twin - Converter Trip Related parameters: Prot_ConvFaultDetect \ TFCDthreshold TFFDthreshold TFFDnumOfPeriods Further steps: ----

685 20719 TOCD_R_CCI8

CCI8. Overcurrent in Phase R detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold

Page 306: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

306 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

686 20720 TOCD_S_CCI8

CCI8. Overcurrent in Phase S detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

Page 307: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

307 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

687 20721 TOCD_T_CCI8

CCI8. Overcurrent in Phase T detected Possible reasons: - High current due to internal short circuit (thyristor lost blocking capability) - High current due to external short circuit (short circuit at DC-side of converter) Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_ConvFaultDetect \ TOCDthreshold Further steps: ----

688 20722 UfOpCeil_CCI8

CCI8. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: N-1 - Converter alarm Twin - Converter alarm Related parameters: Prot_Protection \ UfEnaOpAmpCeilMon Further steps: ----

Page 308: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

308 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

689 20723 DevTypeErr_CCI8

CCI8. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI 8 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

690 20724 AddressErr_CCI8

CCI8. Address Error Possible reasons: - Wrong HEX Switch setting at CCI 8 Default reaction: - Converter Trip Related parameters: ---- Further steps: ----

Page 309: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

309 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

691 20725 LinkFault_CCI8

CCI8. Link Fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to CCI

692 20726 RedPwrFail1_CCI8

CCI8. Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Converter Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

693 20727 RedPwrFail2_CCI8

CCI8. Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:1-2) Default reaction: - Converter Redundancy Fault Related parameters:

Page 310: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

310 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

694 20728 PrciPwrFail_CCI8

CCI8. Precision Power fail Possible reasons: - Internal power fail on CCI - Both power supply inputs are missing Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

695 20729 CPUWatchdog_CCI8

CCI8. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Converter Trip Related parameters: ---- Further steps:

Page 311: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

311 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reboot device - Download installer archive - Replace board

696 20730 UfFreeze_CCI8

CCI8. Field Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UfEnaADCFreezeMon Further steps: - Replace board

697 20731 USynInPhase_CCI8

CCI8. Synchronous Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaInPhaseMon Further steps: - Check cabling

Page 312: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

312 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

698 20732 USynOpCeil_CCI8

CCI8. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaOpAmpCeilMon Further steps: - Replace board

699 20733 USynFreeze_CCI8

CCI8. Synchronous Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaADCFreezeMon Further steps: - Replace board

700 20734 USynAllLost_CCI8

CCI8. Synchronous Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Converter Alarm Related parameters: Prot_Protection \ UsynEnaAllLostMon

Page 313: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

313 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling

701 20735 SelfTrip_CCI8

CCI8. Link Fault detected by CCI Possible reasons: - Optical link cabling to CCI interrupted (OM2 Link 1) Default reaction: - Converter Trip Related parameters: ---- Further steps: - Check optical link cabling to AC 800PEC

702 20736 AdvFuseBlow_CCI8

CCI8. Advanced fuse blow procedure detected faulty branch. Fault clearing by Fire all pulses Possible reasons: - Internal short circuit at a TWIN configuration (Cold Standby) Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ EnableColdStandby EnableAdvancedFuseBlown Further steps: - Check thyristors - Check fuses

Page 314: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

314 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

703 20737 IConvOpCeil_CCI8

CCI8. Converter Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaADCFreezeMon Further steps: - Replace board

704 20738 IConvFreeze_CCI8

CCI8. Converter Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Converter TRIP Related parameters: Prot_Protection \ IconvEnaOpAmpCeilMon Further steps: - Replace board

Page 315: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

315 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

705 20739 CoolingFailure_CCI8

CCI8. Cooling failure Possible reasons: - The configured cooling system does not work sufficiently - Pressure sensor defective - Dirty filters Default reaction: - Converter TRIP Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord Further steps: - Replace fan(s) - Clean air inlet filters - Replace pressure sensor

706 20740 Fan1Supply1Flt_CCI8

CCI8. Fan 1 Supply 1 fault Possible reasons: - Fan 1 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters

Page 316: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

316 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace pressure sensor

707 20741 Fan1Supply2Flt_CCI8

CCI8. Fan 1 Supply 2 fault Possible reasons: - Fan 1 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

Page 317: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

317 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

708 20742 Fan2Supply1Flt_CCI8

CCI8. Fan 2 Supply 1 fault Possible reasons: - Fan 2 defective - Supply 1 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

709 20743 Fan2Supply2Flt_CCI8

CCI8. Fan 2 Supply 2 fault Possible reasons: - Fan 2 defective - Supply 2 missing - Pressure sensor defective - Dirty filters Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps:

Page 318: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

318 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace fan - Check supply voltage (HW-schematic page 410) - Clean air inlet filters - Replace pressure sensor

710 20744 MCB1Fault_CCI8

CCI8. Fan Supply Miniature Circuit Breaker 1 fault Possible reasons: - Fan 1 defective Default reaction: - Converter Redundancy fault Related parameters: Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

711 20745 MCB2Fault_CCI8

CCI8. Fan Supply Miniature Circuit Breaker 2 fault Possible reasons: - Fan 2 defective Default reaction: - Converter Redundancy fault Related parameters:

Page 319: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

319 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Conv_ConverterSystem1 \ CoolingTypeConfigWord CoolingSupplyTypeConfigWord Further steps: - Replace fan (HW-schematic page 410) - Re-check cabling

712 20746 ThyrTemp1Lev1Fl_CCI8

CCI8. Thyristor Rp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 320: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

320 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

713 20747 ThyrTemp2Lev1Fl_CCI8

CCI8. Thyristor Tn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

714 20748 ThyrTemp3Lev1Fl_CCI8

CCI8. Thyristor Sp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 321: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

321 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

715 20749 ThyrTemp4Lev1Fl_CCI8

CCI8. Thyristor Rn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 322: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

322 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

716 20750 ThyrTemp5Lev1Fl_CCI8

CCI8. Thyristor Tp Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

717 20751 ThyrTemp6Lev1Fl_CCI8

CCI8. Thyristor Sn Case Temperature above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 323: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

323 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

718 20752 AirTemp1Lev1Flt_CCI8

CCI8. Air Temperature 1 ( Thyristor Cooler Input ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

Page 324: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

324 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

719 20753 AirTemp2Lev1Flt_CCI8

CCI8. Air Temperature 2 ( Air outlet chimney ) above alarm level (Alarm level = Fault level -10°K) Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

720 20754 ThyrTemp1SensFl_CCI8

CCI8. Thyristor Rp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps:

Page 325: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

325 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Re-check sensor circuit

721 20755 ThyrTemp2SensFl_CCI8

CCI8. Thyristor Tn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 326: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

326 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

722 20756 ThyrTemp3SensFl_CCI8

CCI8. Thyristor Sp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - re-check sensor circuit

723 20757 ThyrTemp4SensFl_CCI8

CCI8. Thyristor Rn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 327: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

327 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

724 20758 ThyrTemp5SensFl_CCI8

CCI8. Thyristor Tp Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

725 20759 ThyrTemp6SensFl_CCI8

CCI8. Thyristor Sn Case Temperature Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Re-check sensor circuit

Page 328: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

328 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

726 20760 AirTemp1SensFlt_CCI8

CCI8. Air Temperature 1 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

727 20761 AirTemp2SensFlt_CCI8

CCI8. Air Temperature 2 Sensor fault Possible reasons: - Sensor circuit open >156°C - Sensor circuit shorten < -13°C Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Re-check sensor circuit

Page 329: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

329 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

728 20762 SnubberSwiFlt_CCI8

CCI8. Snubber Switch fault Possible reasons: - IGBT Switch defective - Optical snubber command/feedback mismatch Default reaction: N-1 - Converter alarm TWIN - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterTypeConfigWord Further steps: - Re-check sensor circuit

729 20763 SnubberFuseFlt_CCI8

CCI8. Snubber Fuse fault Possible reasons: ---- Default reaction: ---- Related parameters: ---- Further steps: ----

Page 330: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

330 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

730 20764 ThyristorFuseFl_CCI8

CCI8. Thyristor Fuse fault Possible reasons: - Digital input for fuse supervision activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Check and replace faulty thyristors - Check and replace blown fuses

731 20765 DoorFlt_CCI8

CCI8. Converter cabinet Door fault Possible reasons: - Digital input for open door activated Default reaction: - Converter alarm Related parameters: ---- Further steps: - Close converter cabinet door

732 20766 VersionFlt_CCI8

CCI8. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Converter Trip Related parameters: ----

Page 331: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

331 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Download required software version

733 20767 NegConvFault_CCI8

CCI8. NegConvFault_CCI8 Possible reasons: - The DI 12 signal of Converter I/O does not match converter configuration Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ConverterNegCurrConfigWord Further steps: - Re-check HW input

734 20768 PulseBlockFault_CCI8

CCI8. PulseBlock_CCI8 by hardware Possible reasons: - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive Default reaction: - Converter Trip Related parameters: ---- Further steps: - Re-check HW input

735 20769 TestPosition_CCI8

Page 332: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

332 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

736 20770 Event2_31_CCI8

737 20771 ThyrTemp1Lev2Fl_CCI8

CCI8. Thyristor Rp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

738 20772 ThyrTemp2Lev2Fl_CCI8

CCI8. Thyristor Tn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature

Page 333: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

333 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

fault of the other converters (n-1) - Clean air inlet filters

739 20773 ThyrTemp3Lev2Fl_CCI8

CCI8. Thyristor Sp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 334: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

334 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

740 20774 ThyrTemp4Lev2Fl_CCI8

CCI8. Thyristor Rn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

741 20775 ThyrTemp5Lev2Fl_CCI8

CCI8. Thyristor Tp Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1)

Page 335: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

335 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

742 20776 ThyrTemp6Lev2Fl_CCI8

CCI8. Thyristor Sn Case Temperature above trip level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter Trip Related parameters: Conv_ConverterSystem1 \ ThyrCaseTempFaultLevel EnableThyrCaseTempMeas Conv_ConverterModule1 \ EnaThyrTempMeas Further steps: - Reduce excitation current immediately to prevent overtemperature fault of the other converters (n-1) - Clean air inlet filters

Page 336: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

336 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

743 20777 AirTemp1Lev2Flt_CCI8

CCI8. Air Temperature 1 ( Thyristor Cooler Input ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp1FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level - Clean air inlet filters

744 20778 AirTemp2Lev2Flt_CCI8

CCI8. Air Temperature 2 ( Air outlet chimney ) above fault level Possible reasons: - Insufficient cooling - High ambient temperature - Snubber control not working Default reaction: - Converter alarm Related parameters: Conv_ConverterSystem1 \ AirTemp2FaultLevel EnableAirTempTempMeas Conv_ConverterModule1 \ EnaCabinetTempMeas Further steps: - Reduce excitation current to prevent overtemperature fault level

Page 337: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

337 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Clean air inlet filters

745 20779 Event3_08_CCI8

746 20780 Event3_09_CCI8

747 20781 Event3_10_CCI8

748 20782 Event3_11_CCI8

749 20783 Event3_12_CCI8

750 20784 Event3_13_CCI8

751 20785 Event3_14_CCI8

752 20786 Event3_15_CCI8

753 20787 Event3_16_CCI8

754 20788 Event3_17_CCI8

755 20789 Event3_18_CCI8

756 20790 Event3_19_CCI8

757 20791 Event3_20_CCI8

758 20792 Event3_21_CCI8

759 20793 Event3_22_CCI8

760 20794 Event3_23_CCI8

761 20795 Event3_24_CCI8

762 21000 Event3_25_CCI8

Page 338: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

338 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

763 21001 Event3_26_CCI8

764 21002 Event3_27_CCI8

765 21003 Event3_28_CCI8

766 21004 Event3_29_CCI8

767 21005 Event3_30_CCI8

768 21006 Event3_31_CCI8

769 21007 OvrCurrInstFlt

Field Current instantaneous overcurrent fault Possible reasons: - Short circuit either on converter AC or DC-side Default reaction: - Trip Related parameters: ProtOvercurrentMon \ Ifskal Ifinst InstDelay Further steps: ----

770 21008 OvrCurrInvFlt

Field Current inverse time Overcurrent fault Possible reasons: - Overload either on AC or DC-side Related parameters: ProtOvercurrentMon / Ifskal Ifstart SelCurve k FixInvDelay ThermalDownTime Further steps:

Page 339: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

339 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

----

771 21009 PQProtFlt

P/Q Protection fault Possible reasons: - Loss of Excitation - FCB Tripped from external Default reaction: - Trip Related parameters: Prot_PQMon \ Characteristic_QP10 Characteristic_QP08 Characteristic_QP06 Characteristic_QP04 Characteristic_QP02 Characteristic_QP00 DelayTime Further steps: ----

Page 340: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

340 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

772 21010 VHzProtFlt

V/Hz Protection fault Possible reasons: - The machine voltage was higher than the V/Hz protection characteristic Default reaction: - Trip Related parameters: Prot_VHzMon \ Gradient Vfn ThermalDownTime DelayTime DelayFuncSelect DelayFactor Further steps: ----

773 21011 DCSCTrip

External short-circuit Trip: Short-circuit on converter DC side Possible reasons: - Short circuit on DC side which was not possible to clear due to a 200ms pulse blocking period Default reaction: - Trip Related parameters: Prot_ConvFaultDetect \ ExtSCIfFaultLevel ExtSCUfFaultLevel ExtSCIfClearingFaultLevel ExtSCUfClearingFaultLevel ExtSCReleaseFaultClearing TFCDthreshold Prot_Protection \ EnableIConvMon

Page 341: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

341 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

EnableConvFaultDetection Further steps: ----

774 21012 S800Watchdog

S800 Watchdog Possible reasons: - Connection to optional I/O of S800 module (OM1 Link 5) Default reaction: - Alarm Related parameters: Prot_protection \ EnableS800Mon Further steps: - Check optical link

775 21013 OtherCHHWFlt

Other Channel Hardware fault Possible reasons: - Powerfail or FPGA freeze on other Channel detected Default reaction: - Immediate changeover to this channel Related parameters:

Page 342: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

342 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: - Check power supply - Replace hardware

776 21014 BUHWFlt

Backup Channel Hardware fault Possible reasons: - Powerfail or FPGA freeze on other Channel detected Default reaction: - Changeover to back-up channel blocked Related parameters: ---- Further steps: - Check power supply - Replace hardware

777 21015 OtherCHLinkFlt

Other Channel Link fault detected by AC 800PEC Possible reasons: - Optical link cabling to other AC 800PEC interrupted (OM1 Link 1&2) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Alarm Related parameters: ---- Further steps:

Page 343: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

343 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Check optical links cabling to other AC 800PEC

778 21016 BUCHLinkFlt

CCM Backup Channel Link fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCM Backup Channel interrupted (OM1 Link 3) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Channel to back-up link loss Related parameters: ---- Further steps: - Check optical link cabling to CCM

Page 344: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

344 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

779 21017 CCMLinkFlt

CCM Link fault detected by AC 800PEC Possible reasons: - Optical link cabling to CCM interrupted (OM1 Link 4) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Channel fault Related parameters: ---- Further steps: - Check optical link cabling to CCM

780 21018 OtherCHVerFlt

Other Channel Software version fault Possible reasons: - Wrong Channel SW version in other regulator channel Default reaction: - Alarm Related parameters: ---- Further steps: - Download required software version

Page 345: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

345 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

781 21019 BUCHVersionFlt

Backup Channel Software version fault Possible reasons: - Wrong SW version in back-up channel Default reaction: - Alarm Related parameters: ---- Further steps: - Download required software version

782 21020 CCMVersionFlt

CCM Software version fault Possible reasons: - Wrong SW version in CCM measuring board Default reaction: - Alarm Related parameters: ---- Further steps: - Download required software version

783 21021 OtherCHAddrErr1

Other Channel Redundant Link 1 Address Error Link fault detected by AC 800PEC Possible reasons: - Optical link cabling to other AC 800PEC connected to wrong optical port (Link 1 to Link 1 ) - CCM Hex switch setting not correct Default reaction: - Alarm

Page 346: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

346 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: ---- Further steps: - Check optical link cabling to other channel

784 21022 OtherCHAddrErr2

Other Channel Redundant Link 2 Address Error Link fault detected by AC 800PEC Possible reasons: - Optical link cabling to other AC 800PEC connected to wrong optical port (OM1 Link 2 to OM1 Link 2 ) - CCM Hex switch setting not correct Default reaction: - Alarm Related parameters: ---- Further steps: - Check optical link cabling to other channel

785 21023 BUCHAddressErr

Backup Channel Address Error Possible reasons: - Wrong HEX Switch setting at back-up CCM Default reaction: - Channel fault Related parameters: ----

Page 347: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

347 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

786 21024 CCMAddressErr

CCM Address Error Possible reasons: - Wrong HEX Switch setting at CCM Default reaction: - Channel fault Related parameters: ---- Further steps: ----

787 21025 OtherCHDevType1

Other Channel Device Type Error on Redundant Link 1 Device Type Error detected by AC 800PEC Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 1) - Wrong installer archive loaded to other AC 800PEC Default reaction: - Alarm Related parameters: ---- Further steps: ----

Page 348: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

348 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

788 21026 OtherCHDevType2

Other Channel Device Type Error on Redundant Link 2 Device Type Error detected by AC 800PEC Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 2) - Wrong installer archive loaded to other AC 800PEC Default reaction: - Alarm Related parameters: ---- Further steps: ----

789 21027 BUDevTypeErr

Backup Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 3) - Wrong installer archive loaded to CCM BU Default reaction: - Channel to back-up link loss - Alarm Related parameters: ---- Further steps: ----

Page 349: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

349 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

790 21028 CCMDevTypeErr

CCM Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM1 Link 4) - Wrong installer archive loaded to CCM 1 Default reaction: - Channel fault Related parameters: ---- Further steps: ----

791 21029 PowerFail

Power fail Possible reasons: - Internal power fail on AC 800PEC - Both power supply inputs are missing Default reaction: - channel fault, if possible channel transfer Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 350: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

350 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

792 21030 BURedPwrFail1

Backup CCM Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

793 21031 CCMRedPwrFail1

CCM Redundant Power 1 fail Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

794 21032 BURedPwrFail2

Backup CCM Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply

Page 351: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

351 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling and power supply

795 21033 CCMRedPwrFail2

CCM Redundant Power 2 fail Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

796 21034 BUPrciPwrFail

BU Precision Power fail Possible reasons: - Internal power fail on CCM - BU - Both power supply inputs are missing Default reaction: - BU channel HW-Fault Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 352: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

352 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

797 21035 CCMPrciFail

CCM Precision Power fail Possible reasons: - Internal power fail on CCM - Both power supply inputs are missing Default reaction: - Channel Fault Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

798 21036 CPUWatchdog

CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Channel Fault Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

Page 353: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

353 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

799 21037 BUCPUWatchdog

Backup Channel CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Back-up channel HW-fault Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

800 21038 CCMCPUWatchdog

CCM CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Channel fault Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

Page 354: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

354 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

801 21039 CCI1Trip

CCI1 Trip: Pulses Blocked on CCI1 Possible reasons: - Optical link cabling to CCI1 interrupted (OM2 Link 1) - CCI1 CPU failure - Internal power fail on CCI1 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI1 - Wrong HEX Switch setting at CCI1 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match converter configuration Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 355: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

355 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

802 21040 CCI2Trip

CCI2 Trip: Pulses Blocked on CCI2 Possible reasons: - Optical link cabling to CCI2 interrupted (OM2 Link 1) - CCI2 CPU failure - Internal power fail on CCI2 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI2 - Wrong HEX Switch setting at CCI2 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 2 signal of Converter I/O does not match to converter configuration Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 356: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

356 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

803 21041 CCI3Trip

CCI3 Trip: Pulses Blocked on CCI3 Possible reasons: - Optical link cabling to CCI3 interrupted (OM2 Link 1) - CCI3 CPU failure - Internal power fail on CCI3 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI3 - Wrong HEX Switch setting at CCI3 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 357: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

357 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

804 21042 CCI4Trip

CCI4 Trip: Pulses Blocked on CCI4 Possible reasons: - Optical link cabling to CCI4 interrupted (OM2 Link 1) - CCI4 CPU failure - Internal power fail on CCI4 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI4 - Wrong HEX Switch setting at CCI4 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 358: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

358 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

805 21043 CCI5Trip

CCI5 Trip: Pulses Blocked on CCI5 Possible reasons: - Optical link cabling to CCI5 interrupted (OM2 Link 1) - CCI5 CPU failure - Internal power fail on CCI5 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI5 - Wrong HEX Switch setting at CCI5 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 359: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

359 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

806 21044 CCI6Trip

CCI6 Trip: Pulses Blocked on CCI6 Possible reasons: - Optical link cabling to CCI6 interrupted (OM2 Link 1) - CCI6 CPU failure - Internal power fail on CCI6 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI6 - Wrong HEX Switch setting at CCI6 - Insufficient converter cooling - Overtemerature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 360: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

360 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

807 21045 CCI7Trip

CCI7 Trip: Pulses Blocked on CCI7 Possible reasons: - Optical link cabling to CCI7 interrupted (OM2 Link 1) - CCI7 CPU failure - Internal power fail on CCI7 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI7 - Wrong HEX Switch setting at CCI7 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 361: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

361 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

808 21046 CCI8Trip

CCI8 Trip: Pulses Blocked on CCI8 Possible reasons: - Optical link cabling to CCI8 interrupted (OM2 Link 1) - CCI8 CPU failure - Internal power fail on CCI8 - Wrong device connected to AC 800PEC (OM2 Link 1) - Wrong installer archive loaded to CCI8 - Wrong HEX Switch setting at CCI8 - Insufficient converter cooling - Overtemperature in converter module (Heat sinks and/or in/outlet air) - Defective current measuring - Fuse blown (only with cold stand-by systems) - Thyristor not conducting (only with cold stand-by systems) - Pulse blocking via DI 6 - Pulse blocking via DI 5 not alive - The DI 12 signal of Converter I/O does not match to converter configuration Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 362: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

362 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

809 21047 CCI1RedFault

CCI1 Redundancy fault Possible reasons: - Power supply fault at CCI1 input 1 (X1:1-2) - Power supply fault at CCI1 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps - See individual events

810 21048 CCI2RedFault

CCI2 Redundancy fault Possible reasons: - Power supply fault at CCI2 input 1 (X1:1-2) - Power supply fault at CCI2 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps - See individual events

Page 363: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

363 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

811 21049 CCI3RedFault

CCI3 Redundancy fault Possible reasons: - Power supply fault at CCI3 input 1 (X1:1-2) - Power supply fault at CCI3 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps - See individual events

812 21050 CCI4RedFault

CCI4 Redundancy fault Possible reasons: - Power supply fault at CCI4 input 1 (X1:1-2) - Power supply fault at CCI4 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps - See individual events

Page 364: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

364 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

813 21051 CCI5RedFault

CCI5 Redundancy fault Possible reasons: - Power supply fault at CCI5 input 1 (X1:1-2) - Power supply fault at CCI5 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps - See individual events

814 21052 CCI6RedFault

CCI6 Redundancy fault Possible reasons: - Power supply fault at CCI6 input 1 (X1:1-2) - Power supply fault at CCI6 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps - See individual events

Page 365: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

365 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

815 21053 CCI7RedFault

CCI7 Redundancy fault Possible reasons: - Power supply fault at CCI7 input 1 (X1:1-2) - Power supply fault at CCI7 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps - See individual events

816 21054 CCI8RedFault

CCI8 Redundancy fault Possible reasons: - Power supply fault at CCI8 input 1 (X1:1-2) - Power supply fault at CCI8 input 2 (X2:3-4) - Fuse blown (only with N-1 systems) - Thyristor not conducting (only with N-1 systems) - Fan fault Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps - See individual events

Page 366: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

366 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

817 21055 CCI1Alarm

CCI1 Alarm Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

818 21056 CCI2Alarm

CCI2 Alarm Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version Default reaction: - Redundancy Fault

Page 367: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

367 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

819 21057 CCI3Alarm

CCI3 Alarm Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 368: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

368 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

820 21058 CCI4Alarm

CCI4 Alarm Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

821 21059 CCI5Alarm

CCI5 Alarm Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version Default reaction: - Redundancy Fault

Page 369: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

369 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: Verify the listing together with the individual events Further steps: - See individual events

822 21060 CCI6Alatm

CCI6 Alarm Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version Default reaction: - Redundancy Fault Related parameters: Verify the listing together with the individual events Further steps: - See individual events

Page 370: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

370 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

823 21061 CCI7Alarm

CCI7 Alarm Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air) - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version Default reaction: - Redundancy Fault Related parameters: Verify the listing together with the individual events Further steps: - See individual events

824 21062 CCI8Alarm

CCI8 Alarm Possible reasons: - Usyn measurement fail - Uf measurement fail - Temperature sensor fault - Overtemperature (alarm level) in converter module (Heat sinks and/or in/outlet air - Snubber switch fault (N-1) - Snubber fuse fault (N-1) - Converter cabinet door open - Wrong SW version Default reaction: - Redundancy Fault

Page 371: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

371 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: Verify the listing together with the individual events Further steps: - See individual events

825 21063 PTMonInPhaseFlt

Generator Voltage measurement failure Possible reasons: - One Phase of the AC-connection lost Default reaction: - Auto fault Related parameters: Prot_Protection \ PTEnaInPhaseMon Further steps: - Check cabling

826 21064 PTMonOpampCeil

Generator Voltage measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Auto fault Related parameters: Prot_Protection \ PTEnaOpAmpCeilMon

Page 372: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

372 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Replace board

827 21065 PTMonADCFreeze

Generator Voltage measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Auto fault Related parameters: Prot_Protection \ PTEnaADCFreezeMon Further steps: - Replace board

828 21066 PTMonAllLost

Generator Voltage measurement failure Possible reasons: - Two or all three connections lost Default reaction: - Auto fault Related parameters: Prot_Protection \ PTEnaAllLostMon Further steps: - Check cabling

Page 373: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

373 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

829 21067 CTMonSumFault

Generator Current measurement failure Possible reasons: - One or two connections lost Default reaction: - Auto fault Related parameters: Prot_Protection \ CTEnaSumMon Further steps: - Check cabling

830 21068 CTMonOpampCeil

Generator Current measurement failure Possible reasons: - Operation amplifier blocked at ceiling level Default reaction: - Auto fault Related parameters: Prot_Protection \ CTEnaOpAmpCeilMon Further steps: - Replace board

831 21069 CTMonADCFreeze

Generator Current measurement failure Possible reasons: - Operation amplifier blocked (frozen) - ADC failure Default reaction: - Auto fault Related parameters: Prot_Protection \ CTEnaADCFreezeMon

Page 374: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

374 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Replace board

832 21070 CTMonParaphase

Generator Current measurement failure Possible reasons: - One connection lost (if only two CT-measurement circuits are used) Default reaction: - Auto fault Related parameters: Prot_Protection \ EnableMaschineMeasCTMon PTEnaParaPhaseMon Further steps: - Check cabling

833 21071 CIO1Trip

CIO1 Trip Possible reasons: - Optical link cabling to CIO1 interrupted (Link 1) - CIO1 CPU failure - Internal power fail on CIO1 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO1 - Wrong HEX Switch setting at CIO1 Default reaction: - Redundancy Fault Related parameters:

Page 375: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

375 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Verify the listing together with the individual events Further steps: - See individual events

834 21072 CIO2Trip

CIO2 Trip Possible reasons: - Optical link cabling to CIO2 interrupted (Link 3) - CIO2 CPU failure - Internal power fail on CIO2 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO2 - Wrong HEX Switch setting at CIO2 Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 376: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

376 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

835 21073 CIO3Trip

CIO3 Trip Possible reasons: - Optical link cabling to CIO3 interrupted (Link 1) - CIO3 CPU failure - Internal power fail on CIO3 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO3 - Wrong HEX Switch setting at CIO3 Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

836 21074 CIO4Trip

CIO4 Trip Possible reasons: - Optical link cabling to CIO4 interrupted (Link 3) - CIO4 CPU failure - Internal power fail on CIO4 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO4 - Wrong HEX Switch setting at CIO4 Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 377: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

377 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

837 21075 CIO5Trip

CIO5 Trip Possible reasons: - Optical link cabling to CIO5 interrupted (Link 1) - CIO5 CPU failure - Internal power fail on CIO5 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO5 - Wrong HEX Switch setting at CIO5 Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

838 21076 CIO6Trip

CIO6 Trip Possible reasons: - Optical link cabling to CIO6 interrupted (Link 3) - CIO6 CPU failure - Internal power fail on CIO6 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO6 - Wrong HEX Switch setting at CIO6 Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 378: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

378 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

839 21077 CIO7Trip

CIO7 Trip Possible reasons: - Optical link cabling to CIO7 interrupted (Link 1) - CIO7 CPU failure - Internal power fail on CIO7 - Wrong device connected to AC 800PEC (Link 1) - Wrong installer archive loaded to CIO7 - Wrong HEX Switch setting at CIO7 Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

840 21078 CIO8Trip

CIO8 Trip Possible reasons: - Optical link cabling to CIO8 interrupted (Link 3) - CIO8 CPU failure - Internal power fail on CIO8 - Wrong device connected to AC 800PEC (Link 3) - Wrong installer archive loaded to CIO8 - Wrong HEX Switch setting at CIO8 Default reaction: - Redundancy Fault Related parameters: - Verify the listing together with the individual events Further steps: - See individual events

Page 379: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

379 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

841 21079 CIO1RedFault

CIO1 Redundancy fault Possible reasons: - Power supply fault at CIO1 input 1 (X1:1-2) - Power supply fault at CIO1 input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

842 21080 CIO2RedFault

CIO2 Redundancy fault Possible reasons: - Power supply fault at CIO2 input 1 (X1:1-2) - Power supply fault at CIO2 input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

843 21081 CIO3RedFault

CIO3 Redundancy fault Possible reasons: - Power supply fault at CIO3 input 1 (X1:1-2) - Power supply fault at CIO3 input 2 (X2:3-4) Default reaction: - Redundancy Fault

Page 380: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

380 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

844 21082 CIO4RedFault

CIO4 Redundancy fault Possible reasons: - Power supply fault at CIO4 input 1 (X1:1-2) - Power supply fault at CIO4 input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

845 21083 CIO5RedFault

CIO5 Redundancy fault Possible reasons: - Power supply fault at CIO5 input 1 (X1:1-2) - Power supply fault at CIO5 input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

Page 381: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

381 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

846 21084 CIO6RedFault

CIO6 Redundancy fault Possible reasons: - Power supply fault at CIO6 input 1 (X1:1-2) - Power supply fault at CIO6 input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

847 21085 CIO7RedFault

CIO7 Redundancy fault Possible reasons: - Power supply fault at CIO7 input 1 (X1:1-2) - Power supply fault at CIO7 input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

848 21086 CIO8RedFault

CIO8 Redundancy fault Possible reasons: - Power supply fault at CIO8 input 1 (X1:1-2) - Power supply fault at CIO8 input 2 (X2:3-4) Default reaction: - Redundancy Fault

Page 382: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

382 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

849 21087 CIO1Alarm

CIO1 Alarm Possible reasons: - Wrong SW version on CIO1 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800) Default reaction: - Alarm Related parameters: Meas_CIO1 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq Further steps: ----

Page 383: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

383 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

850 21088 CIO2Alarm

CIO2 Alarm Possible reasons: - Wrong SW version on CIO2 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800) Default reaction: - Alarm Related parameters: Meas_CIO2 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq Further steps: ----

Page 384: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

384 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

851 21089 CIO3Alarm

CIO3 Alarm Possible reasons: - Wrong SW version on CIO3 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800) Default reaction: - Alarm Related parameters: Meas_CIO3 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq Further steps: ----

Page 385: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

385 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

852 21090 CIO4Alarm

CIO4 Alarm Possible reasons: - Wrong SW version on CIO4 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800) Default reaction: - Alarm Related parameters: Meas_CIO4 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq Further steps: ----

Page 386: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

386 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

853 21091 CIO5Alarm

CIO5 Alarm Possible reasons: - Wrong SW version on CIO5 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800) Default reaction: - Alarm Related parameters: Meas_CIO5 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq Further steps: ----

Page 387: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

387 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

854 21092 CIO6Alatm

CIO6 Alarm Possible reasons: - Wrong SW version on CIO6 - Temperature sensor fault at CIO temperature input 1,2 or 3 (X800) Default reaction: - Alarm Related parameters: Meas_CIO6 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq Further steps: ----

Page 388: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

388 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

855 21093 CIO7Alarm

CIO7 Alarm Possible reasons: - Wrong SW version on CIO7 - Temperature sensor fault at CIO temerature input 1,2 or 3 (X800) Default reaction: - Alarm Related parameters: Meas_CIO7 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq Further steps: ----

Page 389: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

389 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

856 21094 CIO8Alarm

CIO8 Alarm Possible reasons: - Wrong SW version on CIO8 - Temperature sensor fault at CIO temerature input 1,2 or 3 (X800) Default reaction: - Alarm Related parameters: Meas_CIO8 \ EnaTempSens1FaultDetection EnaTempSens2FaultDetection EnaTempSens3FaultDetection AnaInTemp1_Type AnaInTemp2_Type AnaInTemp3_Type EnableFilt4 EnableFilt5 EnableFilt6 AnaInTemp1_Filter_Freq AnaInTemp2_Filter_Freq AnaInTemp3_Filter_Freq Further steps: ----

857 21095 SmallIODev_CH

Small IO deviation between Channel 1 and Channel 2 Possible reasons: - Defective I/O section on CCM Board - Wiring faults Default reaction: - Alarm Related parameters: ----

Page 390: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

390 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check wiring - Replace device

858 21096 SmallIODev_BU

Small IO deviation between this Channel and Backup Channel Possible reasons: - Defective I/O section on CCM Board - Wiring faults Default reaction: - Alarm Related parameters: ---- Further steps: - Check wiring - Replace device

859 21097 OtherCHChannlFl

Other Channel Channel fault Possible reasons: - Other channel has a channel fault event Default reaction: - Alarm Related parameters: ---- Further steps:

Page 391: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

391 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Check other channel

860 21098 BUChannelFlt

Back-up Channel Channel fault Possible reasons: - Back-up channel has a channel fault event Default reaction: - Alarm Related parameters: ---- Further steps: - Check Back-up channel

861 21099 CHXferFlt

Automatic channel transfer occurred. (Channel transfer not forced by the user) Possible reasons: - CCM link fault - CCM Address error - CCM device type error - AC 800PEC Power fail - CCM Power fail - CCM CPU watchdog - AC 800PEC CPU watchdog - CCM link fault - CIO config word fault - Manual fault in manual mode - Auto and manual mode fault

Page 392: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

392 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Default reaction: ---- Related parameters: ---- Further steps: - According to individual event documentation

862 21100 Event3_29 863 21101 Event3_30 864 21102 Event3_31

865 21103 EFRStage1Flt

Earth Fault Relay Stage 1 fault Possible reasons: - Resistance to ground too low Default reaction: - Alarm Related parameters: Prot_EarthFaultMon \ Level1ResponseValue SelectIRDH275 SelectCIO Prot_Protection \ EnaEarthFaultMon Further steps: ----

Page 393: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

393 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

866 21104 EFRStage2Flt

Earth Fault Relay Stage 2 fault Possible reasons: - Resistance to ground too low Default reaction: - Trip Related parameters: Prot_EarthFaultMon \ Level2ResponseValue SelectIRDH275 SelectCIO Prot_Protection \ EnaEarthFaultMon Further steps: ----

867 21105 EFRCommFlt

Earth Fault Relay Communication fault Possible reasons: - Serial link to device IRDH275 is disturbed - Link to selected CIO failed Default reaction: - Alarm Related parameters: Prot_EarthFaultMon \ SelectIRDH275 SelectCIO Prot_Protection \ EnaEarthFaultMon Further steps: ----

Page 394: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

394 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

868 21106 FFTimeout

Field-flashing timeout Possible reasons: - Field Flashing breaker was closed for a longer time than expected Default reaction: - Emergency stop Related parameters: SM-StateMashine \ FieldFlashTimeout Further steps: ----

869 21107 ExcOnTimeout

Excitation-on timeout Possible reasons: - The overall excitation starting time was longer than the supervision time - Converter electronics was not able to fire thyristors Default reaction: - Emergency stop Related parameters: SM_StateMashine \ ExcOnTimeout FireAllTimeout FieldFlashTimeout Further steps: ----

Page 395: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

395 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

870 21108 OVFlt

Synchronous voltage over-voltage fault level reached Possible reasons: ---- Default reaction: - Trip Related parameters: Prot_Pretecion \ Enable OverVoltageMon Prot_OverVoltageMon \ OVDetectionLevel FaultOnDelayTime Further steps: ----

871 21109 ParSaveFlt

Parameter save fault Possible reasons: - Flash defective Default reaction: - Alarm Related parameters: ---- Further steps: - Replace AC 800PEC

Page 396: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

396 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

872 21110 AuxNotReadyFlt

One or more auxiliaries are not ready Possible reasons: - Aux not ready input (CIO1 DI09 activated) - Aux ready input (CIO3 DI06 not activated) Default reaction: - Alarm - Start-up inhibit Related parameters: ---- Further steps: - Check inputs

873 21111 ConfigWordFlt

CIO configuration word is not valid Possible reasons: - Wrong CIO Configuration Default reaction: - Channel fault - Start-up inhibit Related parameters: MeasCIOConfig \ CIOConfigWord Further steps: - Check configuration

Page 397: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

397 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

874 21112 FieldBusExtTrip

Field Bus External Trip Possible reasons: - Trip via fieldbus. Fieldbus control word Bit 2 (Bits 0…15) - Bit 2 is logic zero Default reaction: ---- Related parameters: ---- Further steps: ----

875 21113 ConvRed1Flt

Converter Redundancy Stage fault level 1 More thyristors in the same branch as defined with stage level parameter are not conducting Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors - Blocked CCI Default reaction: - Alarm Related parameters: Conv_ConverterSystem1 \ FaultStage1Level Further steps: ----

Page 398: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

398 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

876 21114 ConvRed2Flt

Converter Redundancy Stage fault level 2 More thyristors in the same branch as defined with stage level parameter are not conducting Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors - Blocked CCI Default reaction: - Alarm Related parameters: Conv_ConverterSystem1 \ FaultStage2Level Further steps: ----

877 21115 ConvRed3Flt

Converter Redundancy Stage fault level 3 More thyristors in the same branch as defined with stage level parameter are not conducting Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors - Blocked CCI Default reaction: - Alarm Related parameters: Conv_ConverterSystem1 \ FaultStage3Level

Page 399: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

399 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

878 21116 ConvRed4Flt

Converter Redundance Stage fault level 4 More thyristors in the same branch as defined with stage level parameter are not conducting Possible reasons: - Defective Thyristors - Defective branch fuses - Defective CCI's - Defective pulse amplifiers - Blocked Thyristors - Blocked CCI Default reaction: - Trip Related parameters: Conv_ConverterSystem1 \ FaultStage4Level Further steps: ----

Page 400: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

400 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

879 21117 PTFailExcOn

PT fail during excitation on sequence Possible reasons: - PT's not connected - CCM defective Default reaction: - Auto Fault Related parameters: Prot_Protection \ EnaUgExcOnMon Further steps: - Check PT circuit - Check CCM

880 21118 CrowbarFlt

Crowbar fault Possible reasons: - Crowbar not conducting when opening fieldbreaker Default reaction: - Alarm Related parameters: ---- Further steps: ----

Page 401: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

401 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

881 21119 CrowbarOVFlt

Crowbar Over-voltage detection Possible reasons: - The field overvoltage protection (crowbar) was responding to a positive or negative field overvoltage - Negative field overvoltage occurs if an interruption occurs in the power supply or field circuit Default reaction: - Trip Related parameters: ---- Further steps: - Check whether there is (or has been) a problem with the generator. If not, report the problem to ABB. - Check the function of the field breaker at the input or output of the converter. - Check connection line and insulation resistance of the field winding. - Check Positive field overvoltage, this error is usually caused by a generator fault, which induces negative field current, such as pole slip, short circuit at the generator terminals etc.

Page 402: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

402 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

882 21120 RotTempFlt1

Rotor Temperature level 1 fault Possible reasons: - UNITROL® 6000 monitors the rotor temperature, which is calculated from the excitation current, excitation voltage and the resulting field resistance. Alarm is triggered if this value exceeds the set temperature. Default reaction: - Alarm Related parameters: Prot_Protection \ EnableRotTempMon Prot_RotTempMon \ RotTempFaultLevel1 R1 T1 T0 SelectMode BrushVDrop CurrDepVDrop Further steps: - Check whether the rotor has been overloaded for a long time and whether the rotor cooling system is working properly.

Page 403: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

403 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

883 21121 RotTempFlt2

Rotor Temperature Level 2 fault Possible reasons: - UNITROL® 6000 monitors the rotor temperature, which is calculated from the excitation current, excitation voltage and the resulting field resistance. Alarm is triggered if this value exceeds the set temperature. Default reaction: - Alarm Related parameters: Prot_Protection \ EnableRotTempMon Prot_RotTempMon \ RotTempFaultLevel2 R1 T1 T0 SelectMode BrushVDrop CurrDepVDrop Further steps: - Check whether the rotor has been overloaded for a long time and whether the rotor cooling system is working properly.

884 21122 Event4_19 885 21123 Event4_20 886 21124 Event4_21 887 21125 Event4_22 888 21126 Event4_23

Page 404: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

404 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

889 21127 LocalCTOPCFlt

Local CT OPC Communication fault Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working Default reaction: - Alarm Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT

890 21128 RemCT1OPCFlt

Remote CT1 OPC Communication fault Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective Default reaction: - Alarm Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime Further steps: - Check wiring - Check OPC server

Page 405: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

405 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT

891 21129 RemCT2OPCFlt

Remote CT2 OPC Communication fault Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective Default reaction: - Alarm Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT

Page 406: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

406 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

892 21130 RemCT3OPCFlt

Remote CT3 OPC Communication fault Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective Default reaction: - Alarm Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime Further steps: - Check wiring - Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT

893 21131 RemCT4OPCFlt

Remote CT4 OPC Communication fault Possible reasons: - Ethernet cable to ECT unplugged - Ethernet switch not working - OPC-Server not working - Optical electrical ethernet converter defective Default reaction: - Alarm Related parameters: OpSel_Local \ EnableCommMom SlowCommMonTimeoutTime Further steps: - Check wiring

Page 407: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

407 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Check OPC server - Doublecheck if parameter "SlowCommMonRamp" is written correctly in ECT

894 21132 BlockStartUpFlt

Block Startup Possible reasons: - Digital input activated (Default not used) Default reaction: - Startup blocked Related parameters: ---- Further steps: ----

895 21133 ManFailExcOn

PT fail during excitation on sequence Possible reasons: - Converter CTs not connected - CSI defective - CCI defective Default reaction: - Manual Fault Related parameters:

Page 408: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

408 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_Protection \ EnaIfExcOnMon Further steps: - Check CT circuit - Check CCI

896 21134 FBCommFlt

Field Bus Communication fault Possible reasons: - Fieldbus connection disturbed Default reaction: - Alarm - Release of the Fieldbus operation request Related parameters: OpSel_Fieldbus \ EnableCommMon ComFaultTime Further steps: ----

897 21135 ExcTrTmpFlt1

Excitation Transformer Temperature Level 1 fault Possible reasons: - Insufficient cooling of the excitaion transformer Default reaction: - Alarm Related parameters: ExcTrafoMon \ TempFaultLevel1 EnableExcTrafoMon SelectPT100

Page 409: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

409 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

EnaTemp1 EnaTemp2 EnaTemp3 Further steps: ----

898 21136 ExcTrTmpFlt2

Excitation Transformer Temperature Level 2 fault Possible reasons: - Insufficient cooling of the excitation transformer Default reaction: - Trip Related parameters: ExcTrafoMon \ TempFaultLevel2 EnableExcTrafoMon SelectPT100 EnaTemp1 EnaTemp2 EnaTemp3 Further steps: ----

Page 410: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

410 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

899 21137 ExcTrSensorFlt

Excitation Transformer Temperature Sensor fault Possible reasons: - Circuit to sensor open - Level 2 picked up without level 1 alive - Level 1 and 2 picked up within 100 ms Default reaction: - Alarm Related parameters: ExcTrafoMon \ dTdtDetectLevel EnableExcTrafoMon EnaTemp1 EnaTemp2 EnaTemp3 Further steps: ----

900 21138 ExcTrOilMinFlt

Excitation Transformer Oil minimum Level fault Possible reasons: - Digital input "Oil Level in excitation transformer below limit" activated Default reaction: - Alarm Related parameters: ExcTrafoMon \ EnableExcTrafoMon Further steps: ----

Page 411: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

411 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

901 21139 ExcTrOilMaxFlt

Excitation Transformer Oil maximum Level fault Possible reasons: - Digital input "Oil Level in excitation transformer above limit " activated Default reaction: - Alarm Related parameters: ExcTrafoMon \ EnableExcTrafoMon Further steps: ----

902 21140 ExcTrOilTmpFlt1

Excitation Transformer Oil Temperature Level 1 fault Possible reasons: - Digital input "Oil temperature in excitation transformer above limit 1" activated Default reaction: - Alarm Related parameters: ExcTrafoMon \ EnableExcTrafoMon Further steps: ----

903 21141 ExcTrOilTmpFlt2

Excitation Transformer Oil Temperature Level 2 fault Possible reasons: - Digital input "Oil temperature in excitation transformer above limit 2" activated Default reaction: - Trip Related parameters: ExcTrafoMon \ EnableExcTrafoMon

Page 412: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

412 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

904 21142 ExcTrBuchFlt1

Exictation Transformer Buchholz fault 1 Possible reasons: - Digital input "Excitation Transformer Buchholz fault 1" activated Default reaction: - Alarm Related parameters: ExcTrafoMon \ EnableExcTrafoMon Further steps: ----

905 21143 ExcTrBuchFlt2

Exictation Transformer Buchholz fault 2 Possible reasons: - Digital input "Excitation Transformer Buchholz fault 2" activated Default reaction: - Alarm Related parameters: ExcTrafoMon \ EnableExcTrafoMon Further steps: ----

Page 413: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

413 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

906 21144 PSU1ICU1Src1Flt

Power Supply Unit 1 Input Coupling Unit +ER-V80 Source 1 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1ICU1 \ SourceConfigWord Further steps: ----

907 21145 PSU1ICU1Src2Flt

Power Supply Unit 1 Input Coupling Unit +ER-V80 Source 2 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1ICU1 \ SourceConfigWord Further steps: ----

Page 414: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

414 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

908 21146 PSU1ICU1Src3Flt

Power Supply Unit 1 Input Coupling Unit +ER-V80 Source 3 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1ICU1 \ SourceConfigWord Further steps: ----

909 21147 PSU1ICU1SigFlt

Power Supply Unit 1 Input Coupling Unit +ER-V80 Signal Fault Possible reasons: - Hardware defective - Monitoring line to I/O board interrupted Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1ICU1 \ SourceConfigWord Further steps: ----

Page 415: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

415 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

910 21148 PSU1APD12APDFlt

Power Supply Unit 1 APD 1-2 Fault Possible reasons: - See corresponding hardware diagram - APD +ER-Q801 or +ER-Q802 defective - Monitoring line to I/O board interrupted Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1APDGrp1 \ Enable Further steps: ----

911 21149 PSU1ICU2Src1Flt

Power Supply Unit 1 Input Coupling Unit +ER-V81 Source 1 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1ICU2 \ SourceConfigWord Further steps: ----

Page 416: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

416 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

912 21150 PSU1ICU2Src2Flt

Power Supply Unit 1 Input Coupling Unit +ER-V81 Source 2 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1ICU2 \ SourceConfigWord Further steps: ----

913 21151 PSU1ICU2Src3Flt

Power Supply Unit 1 Input Coupling Unit +ER-V81 Source 3 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1ICU2 \ SourceConfigWord Further steps: ----

Page 417: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

417 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

914 21152 PSU1ICU2SigFlt

Power Supply Unit 1 Input Coupling Unit +ER-V81 Signal Fault Possible reasons: - Hardware defective - Monitoring line to I/O board interrupted Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1ICU2 \ SourceConfigWord Further steps: ----

915 21153 PSU1APD34APDFlt

Power Supply Unit 1 APD 3-4 Fault Possible reasons: - See corresponding hardware diagram - APD +ER-Q801 or +ER-Q802 defective - Monitoring line to I/O board interrupted Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU1APDGrp2 \ Enable Further steps: ----

Page 418: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

418 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

916 21154 PSU2ICU1Src1Flt

Power Supply Unit 2 Input Coupling Unit +EE-V80 Source 1 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2ICU1 \ SourceConfigWord Further steps: ----

917 21155 PSU2ICU1Src2Flt

Power Supply Unit 2 Input Coupling Unit +EE-V80 Source 2 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2ICU1 \ SourceConfigWord Further steps: ----

Page 419: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

419 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

918 21156 PSU2ICU1Src3Flt

Power Supply Unit 2 Input Coupling Unit +EE-V80 Source 3 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2ICU1 \ SourceConfigWord Further steps: ----

919 21157 PSU2ICU1SigFlt

Power Supply Unit 2 Input Coupling Unit +EE-V80 Signal Fault Possible reasons: - Hardware defective - Monitoring line to I/O board interrupted Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2ICU1 \ SourceConfigWord Further steps: ----

Page 420: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

420 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

920 21158 PSU2APD12APDFlt

Power Supply Unit 2 APD 1-3 Fault Possible reasons: - See corresponding hardware diagramm - APD +EE-Q801 or +EE-Q802 or +EE-Q803 defective - Monitoring line to I/O board interrupted Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2APDGrp1 \ Enable Further steps: ----

921 21159 PSU2ICU2Src1Flt

Power Supply Unit 2 Input Coupling Unit +EE-V81 Source 1 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2ICU2 \ SourceConfigWord Further steps: ----

Page 421: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

421 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

922 21160 PSU2ICU2Src2Flt

Power Supply Unit 2 Input Coupling Unit +EE-V81 Source 2 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2ICU1 \ SourceConfigWord Further steps: ----

923 21161 PSU2ICU2Src3Flt

Power Supply Unit 2 Input Coupling Unit +EE-V81 Source 3 Fault Possible reasons: - See corresponding hardware diagram Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2ICU2 \ SourceConfigWord Further steps: ----

Page 422: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

422 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

924 21162 PSU2ICU2SigFlt

Power Supply Unit 2 Input Coupling Unit +EE-V81 Signal Fault Possible reasons: - Hardware defective - Monitoring line to I/O board interrupted Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2ICU2 \ SourceConfigWord Further steps: ----

925 21163 PSU2APD34APDFlt

Power Supply Unit 2 APD 4-6 Fault Possible reasons: - See corresponding hardware diagram - APD +EE-Q811 or +EE-Q812 or +EE-Q813 defective - Monitoring line to I/O board interrupted Default reaction: - Alarm Related parameters: Prot_Protection \ EnablePowerSupplyMon Prot_PSU2APDGrp2 \ Enable Further steps: ----

Page 423: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

423 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

926 21164 CITVersionFlt

CIT software version fault Possible reasons: - The downloaded CIT software version is not compatible with M/S software version Default reaction: - Alarm Related parameters: ---- Further steps: ----

927 21165 ColdgasAnaInFlt

ColdgasAnaInFlt Possible reasons: - One or both analog input signals for the DE/NDE temperature signals are below the supervision level Default reaction: - Alarm Related parameters: Reg_ColdGas \ SelectAnaInputType EnableAnaInFaultDetection Further steps: ----

Page 424: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

424 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

928 21166 LCIAnaInFlt

ColdgasAnaInFlt Possible reasons: - One or both analog input signals for the DE/NDE temperature signals are below the supervision level Default reaction: - Alarm Related parameters: Reg_ColdGas / SelectAnaInputType EnableAnaInFaultDetection Further steps: ----

929 21167 PreSelectionFlt

Channel Preselection fault Possible reasons: - Channel 1 and Channel 2 are indicated as the active one after start-up Default reaction: - Alarm - none channel is starting as the active one Related parameters: Sys_ExcitationSystem \ PreSelChannel1 PreSelChannel2 Further steps: ----

Page 425: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

425 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

930 21168 DCSCDetected

External Short-Circuit detected Possible reasons: - Short-circuit on converter dc side is detected Default reaction: - Alarm Related parameters: Prot_Protection \ EnableConvFaultDetection EnableExtSCMon Prot_ConvFaultDetect \ ExtSCIfFaultLevel ExtSCUfFaultLevel ExtSCIfClearingFaultLevel ExtSCUfClearingFaultLevel TFCDthreshold Further steps: ----

931 21169 DCSCBlockPulses

External Short-Circuit clearing: Pulse block activated Possible reasons: - Short-circuit on converter dc side is detected Default reaction: - Alarm Related parameters: Prot_Protection \ EnableConvFaultDetection EnableExtSCMon Prot_ConvFaultDetec \ ExtSCIfFaultLevel ExtSCUfFaultLevel ExtSCIfClearingFaultLevel ExtSCUfClearingFaultLevel

Page 426: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

426 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

TFCDthreshold ExtSCReleaseFaultClearing Further steps: ----

932 21170 IntSCAlphaMin

Internal Short-Circuit clearing: Alpha min activated Possible reasons: ---- Default reaction: - Alarm Related parameters: Prot_Protection \ EnableConvFaultDetection EnableIntSCMon Prot_ConvFaultDetect \ TFCDthreshold IntSCReleaseFaultClearing Further steps: ----

Page 427: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

427 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

933 21171 IntSCTrip

Internal Short-Circuit Possible reasons: ---- Default reaction: - Trip Related parameters: Prot_Protection \ EnableConvFaultDetection EnableIntSCMon Prot_ConvFaultDetect \ TFCDthreshold IntSCReleaseFaultClearing Further steps: ----

934 21172 GenSC3Phase

Generator 3-Phase Short-Circuit detected Possible reasons: - All 3 Phases measure less than 5% voltage and at the same time more than 140% current Default reaction: - Alarm Related parameters: ---- Further steps: ----

Page 428: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

428 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

935 21173 GenSC2Phase

Generator 2-Phase Short-Circuit detected Possible reasons: - One or two Phases measure less than 5% voltage and at the same time more than 140% current Default reaction: - Alarm Related parameters: ---- Further steps: ----

936 21174 DistantSC3Phase

Distant 3-Phase Short-Circuit detected Possible reasons: - All 3 Phases measure less than 80% voltage and at the same time more than 120% current Default reaction: - Alarm Related parameters: ---- Further steps: ----

Page 429: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

429 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

937 21175 DistantSC2Phase

Distant 2-Phase Short-Circuit detected Possible reasons: - One or two Phases measure less than 80% voltage and at the same time more than 120% current Default reaction: - Alarm Related parameters: ---- Further steps: ----

938 21176 AnySC

Any Short-Circuit deteced This signal is followed by a signal of the range 21165 . . .21168 to get better information Possible reasons: - High current and at the same time a low voltage detected Default reaction: - Alarm Related parameters: ---- Further steps: ----

939 21177 Event6_10

Page 430: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

430 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

940 21178 CTOvercurrent

Generator Current measurement fault: Current out of measurable range Possible reasons: - Sensing current > 1,53 A (7.65A) 1.53% Default reaction: - Alarm - Blocking of single phase CT-Monitoring Related parameters: Prot_Protection \ EnableMaschineMeasCTMon Further steps: ----

941 21179 ActiveCHFlt

Active Channel fault Possible reasons: - The active channel is faulty and there is no possibility to transfer to another channel Default reaction: - Trip Related parameters: ---- Further steps: ----

942 21180 MANFltinMAN

Manual fault in manual mode: Possible reasons: - There is a Manual Fault while the Unit is running in Manual Mode Default reaction: - Channel fault Related parameters:

Page 431: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

431 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: ----

943 21181 AUTOandMANFlt

Auto and Manual fault: Possible reasons: - Auto Mode as well as Manual Mode of the same channel are faulty Default reaction: - Channel fault Related parameters: ---- Further steps: ----

944 21182 NegFieldCurrFlt

Negative bridge fault while applying negative current Possible reasons: - Check the Event List regarding event numbers 20700 to 20795 Default reaction: - Trip Related parameters: ---- Further steps: ----

Page 432: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

432 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

945 21183 ConverterCfgFlt

Converter configuration fault Possible reasons: - ConverterSystemConfigWord <1 or >8 - ConverterSystemConfigWord not equal to 2 and parameter EnableColdStandby = True - ConverterNegCurrConfigWord =1 and parameter EnableColdStandby = True Default reaction: - All pulses blocked Related parameters: Conv_ConverterSystem1 \ ConverterSystemConfigWord ConverterNegCurrConfigWord EnableColdStandby Further steps: ----

946 21184 ChannelCfgFlt

Channel configuration fault: Possible reasons: - ChannelConfigWord <1 or >3 Default reaction: - System deadlocked Related parameters: Sys_ExcitationSystem \ ChannelConfigWord Further steps: ----

Page 433: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

433 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

947 23409 IOCfgFlt

IO configuration fault Possible reasons: - CIOConfigWord <1 or >32767 Default reaction: - Alarm Related parameters: Meas_CIOConfig \ CIOConfigWord Further steps: ----

948 23410 IntSCDet

Internal Short-Circit detected. Possible reasons: - Defective Thyristor Default reaction: - Alarm Related parameters: Prot_Protection \ EnableConvFaultDetection EnableIntSCMon Prot_ConvFaultDetect \ TFCDthreshold IntSCReleaseFaultClearing Further steps: ----

Page 434: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

434 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

949 21188 OtherCHLink1Flt

Other Channel Redundant Link 1 Fault. Possible reasons: - Opt cabling interrupted - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Alarm Related parameters: ---- Further steps: - Check optical link cabling to other channel

950 21189 OtherCHLink2Flt

Other Channel Redundant Link 2 Fault. Possible reasons: - Opt cabling interrupted - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - Alarm Related parameters: ---- Further steps: - Check optical link cabling to other channel

Page 435: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

435 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

951 21190 OtherCHCPUWD

Other Channel CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - Other channel HW-fault Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

952 21191 OtherCHPwrFail

Other Channel Power Fail Possible reasons: - Internal power fail on AC 800PEC of other channel - Both power supply inputs are missing Default reaction: - Other channel HW-fault Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 436: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

436 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

953 21192 ExternalTrip

External Trip Possible reasons: - CCM I/O DI5 activated Default reaction: - Trip Related parameters: ---- Further steps: ----

957 21193 HotStartUpFlt

Hot-startup fault. Channel started after: Channel fault, reset manual as soon as the Regulator deviation between channel 1 and channel 2 is zero Possible reasons: - Default reaction: - Related parameters: ---- Further steps: ----

958 21194 CHFltStandbyCH

Hardware Fault on this channel detected by the Other Channel or the Backup Channel Possible reasons: - Default reaction: - Related parameters:

Page 437: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

437 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: ----

959 21195 OtherCHHWFltBU

Hardware Fault on the Other Channel detected by the Backup Channel Possible reasons: - Default reaction: - Related parameters: ---- Further steps: ----

960 21196 PassiveCHTrip

Channel is not active and has a Trip Possible reasons: - Default reaction: - Related parameters: ---- Further steps: ----

Page 438: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

438 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

961 21197 FCB1Off1CoilFlt

Field Circuit Breaker 1 Off-Coil 1 Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Alarm Related parameters: Brk_FieldBreaker1 \ EmaxOff1Off2DelayTime Further steps: ----

962 21198 FCB1Off2CoilFlt

Field Circuit Breaker 1 Off-Coil 2 Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Alarm Related parameters: Brk_FieldBreaker1 \ EmaxOff1Off2DelayTime Further steps: ----

Page 439: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

439 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

963 21199 FCB1AntivalFlt

Field Circuit Breaker 1 Status Antivalency Fault Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time Default reaction: - Alarm Related parameters: Brk_FieldBreaker1 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime Further steps: ----

964 21200 FCB1TurnOnFlt

Field Circuit Breaker 1 Turn-On Fault Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldBreaker1 \ FCBOnDelayTime Further steps: ----

Page 440: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

440 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

965 21201 FCB1TurnOffFlt

Field Circuit Breaker 1 Turn-Off Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Trip Related parameters: Brk_FieldBreaker1 \ FCBOffDelayTime Further steps: ----

966 21202 FCB1ManOffFlt

Field Circuit Breaker 1 Manual-Off Fault Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil) Default reaction: - Trip Related parameters: ---- Further steps: ----

Page 441: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

441 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

967 21203 Iso1lTurnOnFlt

Isolator 1 Turn-On Fault Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldIsolator1 \ IsolatorOnDelayTime Further steps: ----

968 21204 Iso1lTurnOffFlt

Isolator 1 Turn-Off Fault Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldIsolator1 \ IsolatorOffDelayTime Further steps: ----

Page 442: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

442 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

969 21205 Iso1lAntivalFlt

Isolator 1 Status Antivalency Fault Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time Default reaction: - Alarm Related parameters: Brk_Fieldisolator1 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime Further steps: ----

970 21206 Iso1OnLdOffFlt

Isolator 1 On-Load Open Fault Possible reasons: - The Isolator was opened manually when it was on-load Default reaction: - Trip Related parameters: ---- Further steps: ----

Page 443: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

443 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

971 21207 FCB2Off1CoilFlt

Field Circuit Breaker 2 Off-Coil 1 Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Alarm Related parameters: Brk_FieldBreaker2 \ EmaxOff1Off2DelayTime Further steps: ----

972 21208 FCB2Off2CoilFlt

Field Circuit Breaker 2 Off-Coil 2 Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Alarm Related parameters: Brk_FieldBreaker2 \ EmaxOff1Off2DelayTime Further steps: ----

Page 444: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

444 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

973 21209 FCB2AntivalFlt

Field Circuit Breaker 2 Status Antivalency Fault Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time Default reaction: - Alarm Related parameters: Brk_FieldBreaker2 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime Further steps: ----

974 21210 FCB2TurnOnFlt

Field Circuit Breaker 2 Turn-On Fault Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldBreaker2 \ FCBOnDelayTime Further steps: ----

Page 445: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

445 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

975 21211 FCB2TurnOffFlt

Field Circuit Breaker 2 Turn-Off Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Trip Related parameters: Brk_FieldBreaker2 \ FCBOffDelayTime Further steps: ----

976 21212 FCB2ManOffFlt

Field Circuit Breaker 2 Manual-Off Fault Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil) Default reaction: - Trip Related parameters: ---- Further steps: ----

Page 446: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

446 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

977 21213 Iso2lTurnOnFlt

Isolator 2 Turn-On Fault Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldIsolator2 \ IsolatorOnDelayTime Further steps: ----

978 21214 Iso2lTurnOffFlt

Isolator 2 Turn-Off Fault Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldIsolator2 \ IsolatorOffDelayTime Further steps: ----

Page 447: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

447 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

979 21215 Iso2lAntivalFlt

Isolator 2 Status Antivalency Fault Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time Default reaction: - Alarm Related parameters: Brk_Fieldisolator2 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime Further steps: ----

980 21216 Iso2OnLdOffFlt

Isolator 2 On-Load Open Fault Possible reasons: - The Isolator was opened manually when it was on-load Default reaction: - Trip Related parameters: ---- Further steps: ----

Page 448: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

448 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

981 21217 FCB3Off1CoilFlt

Field Circuit Breaker 3 Off-Coil 1 Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Alarm Related parameters: Brk_FieldBreaker3 \ EmaxOff1Off2DelayTime Further steps: ----

982 21218 FCB3Off2CoilFlt

Field Circuit Breaker 3 Off-Coil 2 Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Alarm Related parameters: Brk_FieldBreaker3 \ EmaxOff1Off2DelayTime Further steps: ----

Page 449: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

449 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

983 21219 FCB3AntivalFlt

Field Circuit Breaker 3 Status Antivalency Fault Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time Default reaction: - Alarm Related parameters: Brk_FieldBreaker3 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime Further steps: ----

984 21220 FCB3TurnOnFlt

Field Circuit Breaker 3 Turn-On Fault Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldBreaker3 \ FCBOnDelayTime Further steps: ----

Page 450: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

450 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

985 21221 FCB3TurnOffFlt

Field Circuit Breaker 3 Turn-Off Fault Possible reasons: - OFF command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Trip Related parameters: Brk_FieldBreaker3 \ FCBOffDelayTime Further steps: ----

986 21222 FCB3ManOffFlt

Field Circuit Breaker 3 Manual-Off Fault Possible reasons: - Fieldbreaker was opened without command from the fieldbreaker control module (either manually or by trip command, given directly to the OFF coil) Default reaction: - Trip Related parameters: ---- Further steps: ----

Page 451: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

451 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

987 21223 Iso3lTurnOnFlt

Isolator 3 Turn-On Fault Possible reasons: - ON command not executed within the set parameter time "is On" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldIsolator3 \ IsolatorOnDelayTime Further steps: ----

988 21224 Iso3lTurnOffFlt

Isolator 3 Turn-Off Fault Possible reasons: - ON command not executed within the set parameter time "is Off" feedback signal is missing. Default reaction: - Emergency Stop Related parameters: Brk_FieldIsolator3 \ IsolatorOffDelayTime Further steps: ----

Page 452: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

452 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

989 21225 Iso3lAntivalFlt

Isolator 3 Status Antivalency Fault Possible reasons: - There is a wrong position indication of the breaker Feedback "is ON" and "is OFF" are both true or false at the same time Default reaction: - Alarm Related parameters: Brk_Fieldisolator3 \ AntivalencyCheckDisabled AntivalencyFaultOnDelayTime Further steps: ----

990 21226 Iso3OnLdOffFlt

Isolator 3 On-Load Open Fault Possible reasons: - The Isolator was opened manually when it was on load Default reaction: ---- Related parameters: ---- Further steps: ----

991 21227 FCBNotChgdFlt Field Circuit Breaker not charged fault

Page 453: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

453 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

992 21228 FireAllTrip

Trip while system running with fire all Possible reasons: - Too high synchronous voltage, generator voltage or field current while excitation start with fire all thyristors Default reaction: - Emergency stop Related parameters: Prot_Protection \ EnableFireAllTripDet Further steps: ----

993 21229 Event8_00 994 21230 Event8_01 995 21231 Event8_02 996 21232 Event8_03 997 21233 Event8_04 998 21234 Event8_05 999 21235 Event8_06 1'000 21236 Event8_07 1'001 21237 Event8_08 1'002 21238 Event8_09 1'003 21239 Event8_10 1'004 21240 Event8_11 1'005 21241 Event8_12 1'006 21242 Event8_13 1'007 21243 Event8_14 1'008 21244 Event8_15 1'009 21245 Event8_16 1'010 21246 Event8_17 1'011 21247 Event8_18 1'012 21248 Event8_19 1'013 21249 Event8_20 1'014 21250 Event8_21 1'015 21251 Event8_22 1'016 21252 Event8_23 1'017 21253 Event8_24 1'018 21254 Event8_25 1'019 21255 Event8_26 1'020 22000 Event8_27 1'021 22001 Event8_28 1'022 22002 Event8_29 1'023 22003 Event8_30 1'024 22004 Event8_31

Page 454: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

454 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'025 22005 LinkFault_CIO1

CIO1. Link Fault Possible reasons: - Optical link cabling to CIO interrupted (OM2 Link 5) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'026 22006 RedPwrFail1_CIO1

CIO1. Redundant Power fail 1 Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

1'027 22007 RedPwrFail2_CIO1

CIO1. Redundant Power fail 2 Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters:

Page 455: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

455 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

1'028 22008 PrciPwrFail_CIO1

CIO1. Precision Power fail Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

1'029 22009 CPUWatchdog_CIO1

CIO1. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - CIO Trip Related parameters: ---- Further steps:

Page 456: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

456 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Reboot device - Download installer archive - Replace board

1'030 22010 VersionFlt_CIO1

CIO1. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - CIO Trip Related parameters: ---- Further steps: - Download required software version

1'031 22011 AddressErr_CIO1

CIO1. Address Error Possible reasons: - Wrong HEX Switch setting at CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check Hex-Switch setting on CIO

Page 457: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

457 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'032 22012 DevTypeErr_CIO1

CIO1. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 5) - Wrong installer archive loaded to CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'033 22013 SigConsistFlt_CIO1

CIO1 Digital IO deviation between IO's of Channel 1 and Channel 2 Possible reasons: - Defective I/O section on CIO Board - Wiring faults Default reaction: - Alarm Related parameters: ---- Further steps: - Check wiring - Replace device

Page 458: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

458 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'034 22014 Temp1SnsFlt_CIO1

CIO1. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'035 22015 Temp2SnsFlt_CIO1

CIO1. Temperature Sensor 2 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

Page 459: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

459 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'036 22016 Temp3SnsFlt_CIO1

CIO1. Temperature Sensor 3 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'037 22017 Event1_12_CIO1

1'038 22018 Event1_13_CIO1

1'039 22019 Event1_14_CIO1

1'040 22020 Event1_15_CIO1

1'041 22021 Event1_16_CIO1

1'042 22022 Event1_17_CIO1

1'043 22023 Event1_18_CIO1

1'044 22024 Event1_19_CIO1

1'045 22025 Event1_20_CIO1

1'046 22026 Event1_21_CIO1

1'047 22027 Event1_22_CIO1

1'048 22028 Event1_23_CIO1

1'049 22029 Event1_24_CIO1

1'050 22030 Event1_25_CIO1

1'051 22031 Event1_26_CIO1

1'052 22100 Event1_27_CIO1

1'053 22101 Event1_28_CIO1

Page 460: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

460 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'054 22102 Event1_29_CIO1

1'055 22103 Event1_30_CIO1

1'056 22104 Event1_31_CIO1

1'057 22105 LinkFault_CIO2

CIO2. Link Fault Possible reasons: - Optical link cabling to CIO1 interrupted (OM6 Link 3) - PowerLink Watchdog (>3 Link cycles (100 us) no telegram received) - PowerLink Frame Error (4 consecutive telegrams corrupt) Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'058 22106 RedPwrFail1_CIO2

CIO2. Redundant Power fail 1 Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

Page 461: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

461 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'059 22107 RedPwrFail2_CIO2

CIO2. Redundant Power fail 2 Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

1'060 22108 PrciPwrFail_CIO2

CIO2. Precision Power fail Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 462: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

462 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'061 22109 CPUWatchdog_CIO2

CIO2. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - CIO Trip Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

1'062 22110 VersionFlt_CIO2

CIO2. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - CIO Trip Related parameters: ---- Further steps: - Download required software version

Page 463: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

463 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'063 22111 AddressErr_CIO2

CIO2. Address Error Possible reasons: - Wrong HEX Switch setting at CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check Hex-Swtich setting on CIO

1'064 22112 DevTypeErr_CIO2

CIO2. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'065 22113 SigConsistFlt_CIO2

CIO2. Digital IO deviation between IO's of Channel 1 and Channel 2 Possible reasons: - Defective I/O section on CIO Board - Wiring faults Default reaction: - Alarm Related parameters: ----

Page 464: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

464 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check wiring - Replace device

1'066 22114 Temp1SnsFlt_CIO2

CIO2. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'067 22115 Temp2SnsFlt_CIO2

CIO2. Temperature Sensor 2 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ----

Page 465: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

465 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

1'068 22116 Temp3SnsFlt_CIO2

CIO2. Temperature Sensor 3 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'069 22117 Event1_12_CIO2

1'070 22118 Event1_13_CIO2

1'071 22119 Event1_14_CIO2

1'072 22120 Event1_15_CIO2

1'073 22121 Event1_16_CIO2

1'074 22122 Event1_17_CIO2

1'075 22123 Event1_18_CIO2

1'076 22124 Event1_19_CIO2

1'077 22125 Event1_20_CIO2

Page 466: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

466 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'078 22126 Event1_21_CIO2

1'079 22127 Event1_22_CIO2

1'080 22128 Event1_23_CIO2

1'081 22129 Event1_24_CIO2

1'082 22130 Event1_25_CIO2

1'083 22131 Event1_26_CIO2

1'084 22200 Event1_27_CIO2

1'085 22201 Event1_28_CIO2

1'086 22202 Event1_29_CIO2

1'087 22203 Event1_30_CIO2

1'088 22204 Event1_31_CIO2

1'089 22205 LinkFault_CIO3

CIO3. Link Fault Possible reasons: - Optical link cabling to CIO interrupted (OM2 Link 6) Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'090 22206 RedPwrFail1_CIO3

CIO3. Redundant Power fail 1 Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ----

Page 467: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

467 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling and power supply

1'091 22207 RedPwrFail2_CIO3

CIO3. Redundant Power fail 2 Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

1'092 22208 PrciPwrFail_CIO3

CIO3. Precision Power fail Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 468: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

468 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'093 22209 CPUWatchdog_CIO3

CIO3. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - CIO Trip Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

1'094 22210 VersionFlt_CIO3

CIO3. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - CIO Trip Related parameters: ---- Further steps: - Download required software version

Page 469: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

469 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'095 22211 AddressErr_CIO3

CIO3. Address Error Possible reasons: - Wrong HEX Switch setting at CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check Hex-Swtich setting on CIO

1'096 22212 DevTypeErr_CIO3

CIO3. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM2 Link 6) - Wrong installer archive loaded to CIO3 Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'097 22213 SigConsistFlt_CIO3

CIO3. Digital IO deviation between IO's of Channel 1 and Channel 2 Possible reasons: - Defective I/O section on CIO Board - Wiring faults Default reaction: - Alarm Related parameters:

Page 470: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

470 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: - Check wiring - Replace device

1'098 22214 Temp1SnsFlt_CIO3

CIO3. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'099 22215 Temp2SnsFlt_CIO3

CIO3. Temperature Sensor 2 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ----

Page 471: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

471 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

1'100 22216 Temp3SnsFlt_CIO3

CIO3. Temperature Sensor 3 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'101 22217 Event1_12_CIO3

1'102 22218 Event1_13_CIO3

1'103 22219 Event1_14_CIO3

1'104 22220 Event1_15_CIO3

1'105 22221 Event1_16_CIO3

1'106 22222 Event1_17_CIO3

1'107 22223 Event1_18_CIO3

1'108 22224 Event1_19_CIO3

1'109 22225 Event1_20_CIO3

Page 472: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

472 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'110 22226 Event1_21_CIO3

1'111 22227 Event1_22_CIO3

1'112 22228 Event1_23_CIO3

1'113 22229 Event1_24_CIO3

1'114 22230 Event1_25_CIO3

1'115 22231 Event1_26_CIO3

1'116 22300 Event1_27_CIO3

1'117 22301 Event1_28_CIO3

1'118 22302 Event1_29_CIO3

1'119 22303 Event1_30_CIO3

1'120 22304 Event1_31_CIO3

1'121 22305 LinkFault_CIO4

CIO4. Link Fault Possible reasons: - Optical link cabling to CIO3 interrupted (OM6 Link 3) Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'122 22306 RedPwrFail1_CIO4

CIO4. Redundant Power fail 1 Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ----

Page 473: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

473 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling and power supply

1'123 22307 RedPwrFail2_CIO4

CIO4. Redundant Power fail 2 Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

1'124 22308 PrciPwrFail_CIO4

CIO4. Precision Power fail Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 474: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

474 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'125 22309 CPUWatchdog_CIO4

CIO4. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - CIO Trip Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

1'126 22310 VersionFlt_CIO4

CIO4. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - CIO Trip Related parameters: ---- Further steps: - Download required software version

1'127 22311 AddressErr_CIO4

CIO4. Address Error Possible reasons: - Wrong HEX Switch setting at CIO Default reaction: - CIO Trip Related parameters:

Page 475: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

475 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: - Check Hex-Swtich setting on CIO

1'128 22312 DevTypeErr_CIO4

CIO4. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'129 22313 SigConsistFlt_CIO4

CIO4. Digital IO deviation between IO's of Channel 1 and Channel 2 Possible reasons: - Defective I/O section on CIO Board - Wiring faults Default reaction: - Alarm Related parameters: ---- Further steps: - Check wiring

Page 476: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

476 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

- Replace device

1'130 22314 Temp1SnsFlt_CIO4

CIO4. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'131 22315 Temp2SnsFlt_CIO4

CIO4. Temperature Sensor 2 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ----

Page 477: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

477 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

1'132 22316 Temp3SnsFlt_CIO4

CIO4. Temperature Sensor 3 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'133 22317 Event1_12_CIO4

1'134 22318 Event1_13_CIO4

1'135 22319 Event1_14_CIO4

1'136 22320 Event1_15_CIO4

1'137 22321 Event1_16_CIO4

1'138 22322 Event1_17_CIO4

1'139 22323 Event1_18_CIO4

1'140 22324 Event1_19_CIO4

1'141 22325 Event1_20_CIO4

Page 478: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

478 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'142 22326 Event1_21_CIO4

1'143 22327 Event1_22_CIO4

1'144 22328 Event1_23_CIO4

1'145 22329 Event1_24_CIO4

1'146 22330 Event1_25_CIO4

1'147 22331 Event1_26_CIO4

1'148 22400 Event1_27_CIO4

1'149 22401 Event1_28_CIO4

1'150 22402 Event1_29_CIO4

1'151 22403 Event1_30_CIO4

1'152 22404 Event1_31_CIO4

1'153 22405 LinkFault_CIO5

CIO5. Link Fault Possible reasons: - Optical link cabling to CIO interrupted (OM3 Link 5) Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'154 22406 RedPwrFail1_CIO5

CIO5. Redundant Power fail 1 Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ----

Page 479: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

479 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling and power supply

1'155 22407 RedPwrFail2_CIO5

CIO5. Redundant Power fail 2 Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

1'156 22408 PrciPwrFail_CIO5

CIO5. Precision Power fail Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 480: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

480 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'157 22409 CPUWatchdog_CIO5

CIO5. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - CIO Trip Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

1'158 22410 VersionFlt_CIO5

CIO5. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - CIO Trip Related parameters: ---- Further steps: - Download required software version

1'159 22411 AddressErr_CIO5

CIO5. Address Error Possible reasons: - Wrong HEX Switch setting at CIO Default reaction: - CIO Trip Related parameters: ----

Page 481: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

481 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check Hex-Swtich setting on CIO

1'160 22412 DevTypeErr_CIO5

CIO5. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM3 Link 5) - Wrong installer archive loaded to CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'161 22413 SigConsistFlt_CIO5

CIO5.Digital IO deviation between IO's of Channel 1 and Channel 2 Possible reasons: - Defective I/O section on CIO Board - Wiring faults Default reaction: - Alarm Related parameters: ---- Further steps: - Check wiring - Replace device

Page 482: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

482 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'162 22414 Temp1SnsFlt_CIO5

CIO5. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'163 22415 Temp2SnsFlt_CIO5

CIO5. Temperature Sensor 2 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

Page 483: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

483 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'164 22416 Temp3SnsFlt_CIO5

CIO5. Temperature Sensor 3 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'165 22417 Event1_12_CIO5

1'166 22418 Event1_13_CIO5

1'167 22419 Event1_14_CIO5

1'168 22420 Event1_15_CIO5

1'169 22421 Event1_16_CIO5

1'170 22422 Event1_17_CIO5

1'171 22423 Event1_18_CIO5

1'172 22424 Event1_19_CIO5

1'173 22425 Event1_20_CIO5

1'174 22426 Event1_21_CIO5

1'175 22427 Event1_22_CIO5

1'176 22428 Event1_23_CIO5

1'177 22429 Event1_24_CIO5

1'178 22430 Event1_25_CIO5

1'179 22431 Event1_26_CIO5

1'180 22500 Event1_27_CIO5

1'181 22501 Event1_28_CIO5

Page 484: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

484 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'182 22502 Event1_29_CIO5

1'183 22503 Event1_30_CIO5

1'184 22504 Event1_31_CIO5

1'185 22505 LinkFault_CIO6

CIO6. Link Fault Possible reasons: - Optical link cabling to CIO5 interrupted (OM6 Link 3) Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'186 22506 RedPwrFail1_CIO6

CIO6. Redundant Power fail 1 Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ---- Further steps: - Check cabling and power supply

Page 485: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

485 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'187 22507 RedPwrFail2_CIO6

CIO6. Redundant Power fail 2 Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

1'188 22508 PrciPwrFail_CIO6

CIO6. Precision Power fail Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 486: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

486 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'189 22509 CPUWatchdog_CIO6

CIO6. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - CIO Trip Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

1'190 22510 VersionFlt_CIO6

CIO6. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - CIO Trip Related parameters: ---- Further steps: - Download required software version

Page 487: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

487 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'191 22511 AddressErr_CIO6

CIO6. Address Error Possible reasons: - Wrong HEX Switch setting at CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check Hex-Swtich setting on CIO

1'192 22512 DevTypeErr_CIO6

CIO6. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'193 22513 SigConsistFlt_CIO6

CIO6. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at senor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm

Page 488: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

488 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Related parameters: ---- Further steps: ----

1'194 22514 Temp1SnsFlt_CIO6

CIO6. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'195 22515 Temp2SnsFlt_CIO6

CIO6. Temperature Sensor 2 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ----

Page 489: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

489 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

1'196 22516 Temp3SnsFlt_CIO6

CIO6. Temperature Sensor 3 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'197 22517 Event1_12_CIO6

1'198 22518 Event1_13_CIO6

1'199 22519 Event1_14_CIO6

1'200 22520 Event1_15_CIO6

1'201 22521 Event1_16_CIO6

1'202 22522 Event1_17_CIO6

1'203 22523 Event1_18_CIO6

1'204 22524 Event1_19_CIO6

1'205 22525 Event1_20_CIO6

Page 490: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

490 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'206 22526 Event1_21_CIO6

1'207 22527 Event1_22_CIO6

1'208 22528 Event1_23_CIO6

1'209 22529 Event1_24_CIO6

1'210 22530 Event1_25_CIO6

1'211 22531 Event1_26_CIO6

1'212 22600 Event1_27_CIO6

1'213 22601 Event1_28_CIO6

1'214 22602 Event1_29_CIO6

1'215 22603 Event1_30_CIO6

1'216 22604 Event1_31_CIO6

1'217 22605 LinkFault_CIO7

CIO7. Link Fault Possible reasons: - Optical link cabling to CIO interrupted (OM3 Link 6) Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'218 22606 RedPwrFail1_CIO7

CIO7. Redundant Power fail 1 Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ----

Page 491: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

491 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling and power supply

1'219 22607 RedPwrFail2_CIO7

CIO7. Redundant Power fail 2 Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

1'220 22608 PrciPwrFail_CIO7

CIO7. Precision Power fail Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 492: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

492 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'221 22609 CPUWatchdog_CIO7

CIO7. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - CIO Trip Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

1'222 22610 VersionFlt_CIO7

CIO7. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - CIO Trip Related parameters: ---- Further steps: - Download required software version

Page 493: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

493 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'223 22611 AddressErr_CIO7

CIO7. Address Error Possible reasons: - Wrong HEX Switch setting at CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check Hex-Swtich setting on CIO

1'224 22612 DevTypeErr_CIO7

CIO7. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM3 Link 6) - Wrong installer archive loaded to CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'225 22613 SigConsistFlt_CIO7

CIO7. Digital IO deviation between IO's of Channel 1 and Channel 2 Possible reasons: - Defective I/O section on CIO Board - Wiring faults Default reaction: - Alarm Related parameters:

Page 494: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

494 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: - Check wiring - Replace device

1'226 22614 Temp1SnsFlt_CIO7

CIO7. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'227 22615 Temp2SnsFlt_CIO7

CIO7. Temperature Sensor 2 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ----

Page 495: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

495 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

1'228 22616 Temp3SnsFlt_CIO7

CIO7. Temperature Sensor 3 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'229 22617 Event1_12_CIO7

1'230 22618 Event1_13_CIO7

1'231 22619 Event1_14_CIO7

1'232 22620 Event1_15_CIO7

1'233 22621 Event1_16_CIO7

1'234 22622 Event1_17_CIO7

1'235 22623 Event1_18_CIO7

1'236 22624 Event1_19_CIO7

1'237 22625 Event1_20_CIO7

Page 496: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

496 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'238 22626 Event1_21_CIO7

1'239 22627 Event1_22_CIO7

1'240 22628 Event1_23_CIO7

1'241 22629 Event1_24_CIO7

1'242 22630 Event1_25_CIO7

1'243 22631 Event1_26_CIO7

1'244 22700 Event1_27_CIO7

1'245 22701 Event1_28_CIO7

1'246 22702 Event1_29_CIO7

1'247 22703 Event1_30_CIO7

1'248 22704 Event1_31_CIO7

1'249 22705 LinkFault_CIO8

CIO8. Link Fault Possible reasons: - Optical link cabling to CIO7 interrupted (OM6 Link 3) Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'250 22706 RedPwrFail1_CIO8

CIO8. Redundant Power fail 1 Possible reasons: - Power supply fault at input 1 (X1:1-2) Default reaction: - Redundancy Fault Related parameters: ----

Page 497: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

497 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: - Check cabling and power supply

1'251 22707 RedPwrFail2_CIO8

CIO8. Redundant Power fail 2 Possible reasons: - Power supply fault at input 2 (X2:3-4) Default reaction: - Redundancy Fault Related parameters: Prot_PowerSupplyMon \ EnableRedundantSupply Further steps: - Check cabling and power supply

1'252 22708 PrciPwrFail_CIO8

CIO8. Precision Power fail Possible reasons: - Internal power fail on CIO - Both power supply inputs are missing Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check cabling and power supply - Replace board

Page 498: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

498 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'253 22709 CPUWatchdog_CIO8

CIO8. CPU Watchdog Possible reasons: - CPU failure - Simulink application not running Default reaction: - CIO Trip Related parameters: ---- Further steps: - Reboot device - Download installer archive - Replace board

1'254 22710 VersionFlt_CIO8

CIO8. Software Version fault Possible reasons: - Wrong converter interface SW version Default reaction: - Alarm Related parameters: ---- Further steps: - Download required software version

Page 499: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

499 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'255 22711 AddressErr_CIO8

CIO8. Address Error Possible reasons: - Wrong HEX Switch setting at CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check Hex-Swtich setting on CIO

1'256 22712 DevTypeErr_CIO8

CIO8. Device Type Error Possible reasons: - Wrong device connected to AC 800PEC (OM6 Link 3) - Wrong installer archive loaded to CIO Default reaction: - CIO Trip Related parameters: ---- Further steps: - Check optical link cabling to CIO

1'257 22713 SigConsistFlt_CIO8

CIO8. Digital IO deviation between IO's of Channel 1 and Channel 2 Possible reasons: - Defective I/O section on CIO Board - Wiring faults Default reaction: - Alarm Related parameters:

Page 500: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

500 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: - Check wiring - Replace device

1'258 22714 Temp1SnsFlt_CIO8

CIO8. Temperature Sensor 1 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'259 22715 Temp2SnsFlt_CIO8

CIO8. Temperature Sensor 2 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ----

Page 501: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

501 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

1'260 22716 Temp3SnsFlt_CIO8

CIO8. Temperature Sensor 3 fault Possible reasons: PT100 PTC - Short circuit at sensor cabling < 82.5 Ohm < 20 Ohm - Open circuit at sensor cabling > 181.6 Ohm > --- Ohm Default reaction: - Alarm Related parameters: ---- Further steps: ----

1'261 22717 Event1_12_CIO8

1'262 22718 Event1_13_CIO8

1'263 22719 Event1_14_CIO8

1'264 22720 Event1_15_CIO8

1'265 22721 Event1_16_CIO8

1'266 22722 Event1_17_CIO8

1'267 22723 Event1_18_CIO8

1'268 22724 Event1_19_CIO8

1'269 22725 Event1_20_CIO8

Page 502: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

502 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'270 22726 Event1_21_CIO8

1'271 22727 Event1_22_CIO8

1'272 22728 Event1_23_CIO8

1'273 22729 Event1_24_CIO8

1'274 22730 Event1_25_CIO8

1'275 22731 Event1_26_CIO8

1'276 23000 Event1_27_CIO8

1'277 23001 Event1_28_CIO8

1'278 23002 Event1_29_CIO8

1'279 23003 Event1_30_CIO8

1'280 23004 Event1_31_CIO8

1'281 23005 ChannelFault

Channel Fault - Group alarm Possible reasons: - One or more events which are assigned to "Channel Fault" has (have) occurred - The signal was forced by the command "Force Channel Fault" Default reaction: - Single channel -> Trip - Redundant system -> Channel transfer Related parameters: ---- Further steps: - According to individual event description

Page 503: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

503 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'282 23006 AutoFault

Auto Fault - Group alarm Possible reasons: - One or more events which are assigned to "Auto Fault" has (have) occurred - The signal was forced by the command "Force Auto Fault" Default reaction: - Single channel -> Transfer to "Manual Mode" - Redundant system -> Channel transfer, own channel transfer to "Manual Mode" Related parameters: ---- Further steps: - according to individual event description

1'283 23007 ManualFault

Manual Fault - Group alarm Possible reasons: - One or more events which are assigned to "Manual Fault" has (have) occurred - The signal was forced by the command "Force Manual Fault" Default reaction: - Single channel -> Trip - Redundant system -> Channel transfer Related parameters: ---- Further steps: - According to individual event description

Page 504: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

504 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'284 23008 OtherCHHWFault

Other Channel Hardware Fault - Group alarm Possible reasons: - One or more events which are assigned to "Other Channel Hardware Fault" has (have) occurred - The signal was forced by the command "Force Other Channel Hardware Fault" Default reaction: - Blocking of channel transfer ability to "Other Channel" Related parameters: ---- Further steps: - According to individual event description

1'285 23009 BUCHHWFault

Backup Channel Hardware Fault - Group alarm Possible reasons: - One or more events which are assigned to Auto Fault has (have) accured - The signal was forced by the command "Force Auto Fault" Default reaction: - Single channel -> Transfer to "Manual Mode" - Reduadant system -> Channel transfer, own channel transfer to "Manual Mode" Related parameters: ---- Further steps: - According to individual event description

Page 505: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

505 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'286 23010 CHtoBULinkLoss

Channel to Backup Link Loss - Group alarm Possible reasons: - One or more events which are assigned to Channel to Backup Link Loss has (have) occurred - The signal was forced by the command "Channel to Backup Link Loss" Default reaction: - Blocking of channel transfer ability to Backup Channel Related parameters: ---- Further steps: - According to individual event description

1'287 23011 EmergencyStop

Emergency Stop - Group alarm Possible reasons: - One or more events which are assigned to "Emergency Stop" has (have) occurred - The signal was forced by the command "Emergency Stop" Default reaction: - Excitation is swiched off - Fieldbreaker is opened Related parameters: ---- Further steps: - According to individual event description

Page 506: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

506 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'288 23100 Trip1

Trip 1 - Group alarm Possible reasons: - One or more events which are assigned to "Trip 1" has (have) occurred - The signal was forced by the command "Trip 1" Default reaction: - Trip command given to Plant Protection - Excitation is swiched off - Fieldbreaker is opened Related parameters: ---- Further steps: - According to individual event description

1'289 23101 Trip2

Trip 2 - Group alarm Possible reasons: - One or more events which are assigned to "Trip 2" has (have) occurred - The signal was forced by the command "Trip 2" Default reaction: - Trip request given to Plant Protection - If accepted - Excitation is swiched off - Fieldbreaker is opened Related parameters: ---- Further steps: - According to individual event description

Page 507: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

507 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'290 23102 StartupInhibit

Startup Inhibit - Group alarm Possible reasons: - One or more events which are assigned to "Startup Inhibit" has (have) occurred - The signal was forced by the command "Force Startup Inhibit" Default reaction: - Blocking of Fieldbreaker Close command - Blocking of Excitation On command Related parameters: ---- Further steps: - According to individual event description

1'291 23103 RedundancyFault

Redundancy Fault - Group alarm Possible reasons: - One or more events which are assigned to "Redundancy Fault" has (have) occurred - The signal was forced by the command "Redundancy Fault" Default reaction: ---- Related parameters: ---- Further steps: - According to individual event description

Page 508: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

508 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'292 23104 Alarm

Alarm - Group alarm Possible reasons: - One or more events which are assigned to "Alarm" has (have) occurred - The signal was forced by the command "Alarm" Default reaction: ---- Related parameters: ---- Further steps: - According to individual event description

1'293 23105 ForceChannelFault

Force Channel Fault Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Channel Fault" Default reaction: ---- Related parameters: ---- Further steps: ----

Page 509: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

509 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'294 23106 ForceAutoFault

Force Auto Fault Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Auto Fault" Default reaction: ---- Related parameters: ---- Further steps: ----

1'295 23107 ForceManualFault

Force Manual Fault Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Manual Fault" Default reaction: ---- Related parameters: ---- Further steps: ----

1'296 23108 ForceOtherCHHWFault

Force Other Channel Hardware Fault Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Other Channel Hardware Fault" Default reaction: ---- Related parameters:

Page 510: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

510 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: ----

1'297 23109 ForceBUCHHWFault

Force Backup Channel Hardware Fault Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Backup Channel Hardware Fault" Default reaction: ---- Related parameters: ---- Further steps: ----

1'298 23110 ForceCHtoBULinkLoss

Force Channel to Backup Link Loss Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Channel to Backup Link Loss" Default reaction: ---- Related parameters: ---- Further steps:

Page 511: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

511 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

----

1'299 23111 ForceEmergencyStop

Force Emergency Stop Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Emergency Stop" Default reaction: ---- Related parameters: ---- Further steps: ----

1'300 23200 ForceTrip1

Force Trip 1 Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

Page 512: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

512 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'301 23201 ForceTrip2

Force Trip 2 Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "conditional Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'302 23202 ForceStartupInhibit

Force Startup Inhibit Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Startup Inhibit" Default reaction: ---- Related parameters: ---- Further steps: ----

1'303 23203 ForceRedundancyFault

Force Redundancy Fault Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Redundancy Fault" Default reaction: ---- Related parameters:

Page 513: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

513 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: ----

1'304 23204 ForceAlarm

Force Alarm Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "Alarm" Default reaction: ---- Related parameters: ---- Further steps: ----

1'305 23205 ForceCCI1Trip

Force CCI1 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI1 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

Page 514: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

514 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'306 23206 ForceCCI2Trip

Force CCI2 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI2 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'307 23207 ForceCCI3Trip

Force CCI3 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI3 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'308 23300 ForceCCI4Trip

Force CCI4 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI4 Trip" Default reaction: ---- Related parameters:

Page 515: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

515 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: ----

1'309 23301 ForceCCI5Trip

Force CCI5 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI5 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'310 23302 ForceCCI6Trip

Force CCI6 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI6 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

Page 516: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

516 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'311 23303 ForceCCI7Trip

Force CCI7 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI7 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'312 23304 ForceCCI8Trip

Force CCI8 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CCI8 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'313 23305 ForceCIO1Trip

Force CIO1 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO1 Trip" Default reaction: ---- Related parameters:

Page 517: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

517 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: ----

1'314 23306 ForceCIO2Trip

Force CIO2 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO2 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'315 23307 ForceCIO3Trip

Force CIO3 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO3 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

Page 518: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

518 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'316 23400 ForceCIO4Trip

Force CIO4 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO4 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'317 23401 ForceCIO5Trip

Force CIO5 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO5 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'318 23402 ForceCIO6Trip

Force CIO6 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO6 Trip" Default reaction: ---- Related parameters:

Page 519: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

519 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

---- Further steps: ----

1'319 23403 ForceCIO7Trip

Force CIO7 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO7Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

1'320 23404 ForceCIO8Trip

Force CIO8 Trip Possible reasons: - The signal was forced by the manually given command. Typically activated to test the System / Plant behavior to a "CIO8 Trip" Default reaction: ---- Related parameters: ---- Further steps: ----

Page 520: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

520 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'321 23405 Reset

Reset Possible reasons: - A Reset command was given to the Excitation System Default reaction: ---- Related parameters: ---- Further steps: ----

1'322 23406 AuxReady

AuxReady State Possible reasons: - The Excitation System reached the "AuxReady" main state Default reaction: ---- Related parameters: ---- Further steps: ----

1'323 23407 AuxOn

AuxOn State Possible reasons: - The Excitation System reached the "AuxOn" main state Default reaction: ---- Related parameters: ----

Page 521: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

521 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

Further steps: ----

1'324 23408 Ready

Ready State Possible reasons: - The Excitation System reached the "Ready" main state Default reaction: ---- Related parameters: ---- Further steps: ----

1'325 21186 Operation

Operation State Possible reasons: - The Excitation System reached the "Operation" main State Default reaction: ---- Related parameters: ---- Further steps: ----

Page 522: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

522 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'326 23411 ManualControl

Manual Control Active Possible reasons: - The Excitation System changed to "Manual" Mode Default reaction: ---- Related parameters: ---- Further steps: ----

1'327 21187 ChannelActive

Channel Active Possible reasons: - The Excitation System changed the control to "this Channel" Default reaction: ---- Related parameters: ---- Further steps: ----

Page 523: UN6800 (Excitation)Alarm and Event List

ABB

Events Nr ID Name Description

523 3BHS258033 E01 Rev. A Unitrol 6800 Alarm and Event list

1'328 23412 TRTrig

Transient Recorder Trigger Possible reasons: - The Transient Recorder in the Excitation System was triggered either by a - Trip - Channel Fault - Auto Fault - Manual Fault or - manually Default reaction: ---- Related parameters: ---- Further steps: ----

1'329 23413 ChannelStartup

Channel Startup Possible reasons: - The channel hardware was powered up Default reaction: ---- Related parameters: ---- Further steps: ----

1'330 23414 ActUfMeasFlt

1'332 23415 Event6_27

1'340 20173 Event3_09_CCI2