Page 1: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

UL2248 Marina Fueling Systems ProjectUL2248 Marina Fueling Systems Project

Page 2: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

MARINA FUELING SYSTEMSPROJECT

MARINA FUELING SYSTEMSPROJECT

Maggie Carroll - Project Manager

Paul Lloret - Standards Development

Susan Stene - Piping

Greg Okada - General Systems

Phil York - Tanks

Wendy Winter - Technical Support

Maggie Carroll - Project Manager

Paul Lloret - Standards Development

Susan Stene - Piping

Greg Okada - General Systems

Phil York - Tanks

Wendy Winter - Technical Support

Page 3: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

UL’s RoleUL’s Role

• Standards Writing Body– NOT responsible for standards adoption or

enforcement• Obtain input from

– Authorities Having Jurisdiction (AHJ’s)– Product Manufacturers– Users (Marina Owners/Associations,

Contractors)– Other Interested Parties

• Maintain UL’s Safety Mission

• Standards Writing Body– NOT responsible for standards adoption or

enforcement• Obtain input from

– Authorities Having Jurisdiction (AHJ’s)– Product Manufacturers– Users (Marina Owners/Associations,

Contractors)– Other Interested Parties

• Maintain UL’s Safety Mission

Page 4: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Scope of StandardScope of Standard

• “These requirements apply to marina fuelingsystems intended for temporary storage (tanksystem), transporting (piping system fromtank to dispensing systems) and dispensing(dispensing system) of flammable orcombustible liquids, such as gasoline ordiesel fuel, on waterways serviced by landbased marinas intended to service floatingvessels.”

• “These requirements apply to marina fuelingsystems intended for temporary storage (tanksystem), transporting (piping system fromtank to dispensing systems) and dispensing(dispensing system) of flammable orcombustible liquids, such as gasoline ordiesel fuel, on waterways serviced by landbased marinas intended to service floatingvessels.”

Page 5: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

UL2248UL2248

Page 6: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

ExclusionsExclusions

• Fuel Delivery to Vessels

• Fuel Delivery to Tank System

• Fueling Practices or Procedures

• Submerged or Floating Tanks• Tank Foundation

• Anchoring of primary tank to pier or pier to shore

• Construction/Stability of Pier

• ADA Requirements

• Fuel Delivery to Vessels

• Fuel Delivery to Tank System

• Fueling Practices or Procedures

• Submerged or Floating Tanks• Tank Foundation

• Anchoring of primary tank to pier or pier to shore

• Construction/Stability of Pier

• ADA Requirements

Page 7: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Consistent with Current CodeRequirements

Consistent with Current CodeRequirements

• NFPA• UFC

• IFC• OSHA• CCR - California Code of Regulations

• CFR - Code of Federal Regulations

• NFPA• UFC

• IFC• OSHA• CCR - California Code of Regulations

• CFR - Code of Federal Regulations

Page 8: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Potential Hazards AddressedPotential Hazards Addressed

• Public Safety– Fire Hazards

– Electrical Hazards– Environmental Hazards

• Leak Prevention and Detection

– Other Hazards (Mechanical)

• Public Safety– Fire Hazards

– Electrical Hazards– Environmental Hazards

• Leak Prevention and Detection

– Other Hazards (Mechanical)

Page 9: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

GeneralGeneral

• Ease in Determining Compliance withRequirements

• Address Environmental, Tidal andSituational Issues

• Consideration to Marina Owners

• Ease in Determining Compliance withRequirements

• Address Environmental, Tidal andSituational Issues

• Consideration to Marina Owners

Page 10: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Overall System RequirementsOverall System Requirements

• Secondary Containment

• Continuous Monitoring for Leakage

• Audible and Visual Alarms

• Secondary Containment

• Continuous Monitoring for Leakage

• Audible and Visual Alarms

Page 11: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Tank SystemTank System

• All tanks secondarily contained

• Tank Capacity per NFPARequirements

–12K gal. (individual) (15K ifvaulted)

–40K gal. Aggregate Capacity

• All tanks secondarily contained

• Tank Capacity per NFPARequirements

–12K gal. (individual) (15K ifvaulted)

–40K gal. Aggregate Capacity

Page 12: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Aboveground Storage TanksAboveground Storage Tanks

• Meet UL2085 Requirements• Protected Tank - “An aboveground atmospheric

tank with secondary containment and an insulationsystem intended to reduce the heat transferred tothe primary tank when the tank is exposed to ahydrocarbon pool fire and provided withprotection from physical damage”

• Optional Projectile Protection• If vaulted, must comply with UL2245

Requirements

• Meet UL2085 Requirements• Protected Tank - “An aboveground atmospheric

tank with secondary containment and an insulationsystem intended to reduce the heat transferred tothe primary tank when the tank is exposed to ahydrocarbon pool fire and provided withprotection from physical damage”

• Optional Projectile Protection• If vaulted, must comply with UL2245

Requirements

Page 13: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Underground Storage TanksUnderground Storage Tanks

• Comply with Existing Requirementsper:–UL58 (Steel Tanks)–API Specification 12B–UL1316 (Fiberglass Reinforced)–Flood Areas – Additional NFPA 30

requirements may apply

• Comply with Existing Requirementsper:–UL58 (Steel Tanks)–API Specification 12B–UL1316 (Fiberglass Reinforced)–Flood Areas – Additional NFPA 30

requirements may apply

Page 14: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Additional Tank IssuesAdditional Tank Issues

• Secondary Containment and Tank Supports• Fill connection, Gauges, other openings

• Venting (Normal and Emergency)• Flexible Connectors

– Less than 8 feet

– Comply with UL 2405• Piping, Valves and Fittings

• Secondary Containment and Tank Supports• Fill connection, Gauges, other openings

• Venting (Normal and Emergency)• Flexible Connectors

– Less than 8 feet

– Comply with UL 2405• Piping, Valves and Fittings

Page 15: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Distribution SystemDistribution System

• Aboveground Piping shallcomply with UL2405

• All Piping SystemComponents shall besecondarily contained

• Continuous Audible andVisual Alarm

• Pier Piping Secured andProtected

• Installed on pier –opposite side of electricalwiring

• Aboveground Piping shallcomply with UL2405

• All Piping SystemComponents shall besecondarily contained

• Continuous Audible andVisual Alarm

• Pier Piping Secured andProtected

• Installed on pier –opposite side of electricalwiring

Page 16: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

ValvesValves

• Block Valves – Isolate Tank and Piping• Upstream of basic equipment – Prevent

release of Product• Solenoid Valve

– Tank and Pier

– Every 40 feet of Distribution Piping

• Block Valves – Isolate Tank and Piping• Upstream of basic equipment – Prevent

release of Product• Solenoid Valve

– Tank and Pier

– Every 40 feet of Distribution Piping

Page 17: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

EmergencyEmergency

• Emergency Shut off Valves– Fire Valve – Approach to Pier

• Double–Poppeted Breakaway– All product lines– Directly Upstream from Pier

• Emergency Shut off Valves– Fire Valve – Approach to Pier

• Double–Poppeted Breakaway– All product lines– Directly Upstream from Pier

Page 18: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

SumpsSumps

• Secondary Containment– “When used as secondary containment,

sumps shall have a volume adequate tocapture all fuel in the system from thesolenoid valve directly before the sump tothe point of exit from the sump.”

• Secondary Containment– “When used as secondary containment,

sumps shall have a volume adequate tocapture all fuel in the system from thesolenoid valve directly before the sump tothe point of exit from the sump.”

Page 19: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Distribution SystemDistribution System

• Pipe Joints, Compounds and Gaskets• Piping Materials

– Steel, Nodular Iron, Malleable Iron Brass,Bronze, Stainless Steel

– Exception: Non-metallic materials maybe used when comply with UL971,UL2405 as applicable

• Pipe Joints, Compounds and Gaskets• Piping Materials

– Steel, Nodular Iron, Malleable Iron Brass,Bronze, Stainless Steel

– Exception: Non-metallic materials maybe used when comply with UL971,UL2405 as applicable

Page 20: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Leak DetectionLeak Detection

• Earliest possible detection• Lesser of:

– Detecting 3 g/hr at 10 psi within onehour, or

– 25% of the lower flammable liquid stored

• 95% probability of detection, false alarmless than 5%

• Earliest possible detection• Lesser of:

– Detecting 3 g/hr at 10 psi within onehour, or

– 25% of the lower flammable liquid stored

• 95% probability of detection, false alarmless than 5%

Page 21: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Secondary ContainmentSecondary Containment

• Contain 100% of usable capacity of primarycontainment system

• For multiple primaries in single secondary- whichever is greater:– 150% of the volume of the largest primary

container

– 10% or aggregate internal volume of allprimary containers within the secondary system

• Contain 100% of usable capacity of primarycontainment system

• For multiple primaries in single secondary- whichever is greater:– 150% of the volume of the largest primary

container

– 10% or aggregate internal volume of allprimary containers within the secondary system

Page 22: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Dispensing SystemDispensing System

• UL87 Dispenser• UL330 Hose and Hose Assemblies

• UL1238 Control Equipment• UL109 Fittings and Tubing• UL25 Meters

• UL87 Dispenser• UL330 Hose and Hose Assemblies

• UL1238 Control Equipment• UL109 Fittings and Tubing• UL25 Meters

Page 23: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Dispensing System RequirementsDispensing System Requirements

• Length 18 ft. or less unless protected fromdamage when not in use

– Rack, reel, retriever• Automatic Closing• Shall not have latch open capability

• Length 18 ft. or less unless protected fromdamage when not in use

– Rack, reel, retriever• Automatic Closing• Shall not have latch open capability

Page 24: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Electrical SystemElectrical System

• Per NEC Requirements– Corrosion Resistant

– Wet Locations– Grounding Requirements– Opposite Side of Pier from Flammable

Liquid Piping– Emergency Disconnect

• Per NEC Requirements– Corrosion Resistant

– Wet Locations– Grounding Requirements– Opposite Side of Pier from Flammable

Liquid Piping– Emergency Disconnect

Page 25: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

UL2405 –Aboveground Secondarily-contained Piping For Flammable Liquids

UL2405 –Aboveground Secondarily-contained Piping For Flammable Liquids

• RequirementsSeparated fromUL2248

• UL971 (Non-metallicUnderground Piping)

• ASTM A53, A106,A135, B31.3(Metallic)

• RequirementsSeparated fromUL2248

• UL971 (Non-metallicUnderground Piping)

• ASTM A53, A106,A135, B31.3(Metallic)

Page 26: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Scope of StandardScope of Standard

• “These requirements cover primarycarrier pipe, secondary containmentpipe, secondary containment pans,outer protective pipe and fittingsintended for use aboveground in thedistribution of petroleum-basedflammable and combustible liquids,alcohols, and alcohol-blended fuels.”

• “These requirements cover primarycarrier pipe, secondary containmentpipe, secondary containment pans,outer protective pipe and fittingsintended for use aboveground in thedistribution of petroleum-basedflammable and combustible liquids,alcohols, and alcohol-blended fuels.”

Page 27: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Other ConsiderationsOther Considerations

• Corrosion Protection

• Permeability:• Primary – 2.05x10-5 lb/ft2/day• Secondary – 4.92x10-3 lb/ft2/day

• Corrosion Protection

• Permeability:• Primary – 2.05x10-5 lb/ft2/day• Secondary – 4.92x10-3 lb/ft2/day

Page 28: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Test ProgramTest Program

• Per Table 9.1• Per Table 9.1

Page 29: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Flammability Testing (1/4)Flammability Testing (1/4)

Page 30: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Flammability Testing (2/4)Flammability Testing (2/4)

Page 31: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Flammability Testing (3/4)Flammability Testing (3/4)

Page 32: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Flammability Testing (4/4)Flammability Testing (4/4)

Page 33: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Verification of ComplianceVerification of Compliance

• UL2405 – Product Marking• UL2248 – Certificate Program

• UL2405 – Product Marking• UL2248 – Certificate Program

Page 34: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

UL2248 Certificate Program(Preliminary)

UL2248 Certificate Program(Preliminary)

• Initial Inspection Certificate• State Documents

• Ongoing Inspections by State

• Initial Inspection Certificate• State Documents

• Ongoing Inspections by State

Page 35: UL2248 Marina Fueling Systems Project - · PDF fileAboveground Storage Tanks • Meet UL2085 Requirements • Protected Tank - “An aboveground atmospheric tank with secondary containment

Where are we going?Where are we going?

• Comments on Current Draft Due by JULY22, 2002.

• First Edition Published• National Standard• ANSI

• Living Document, Ongoing Support

• Comments on Current Draft Due by JULY22, 2002.

• First Edition Published• National Standard• ANSI

• Living Document, Ongoing Support