UL EX-4510 4-1-05 Page 1-4 - Suppression...The 24 VDC electric actuator is required to electrically...

1
System Components UL EX-4510 4-1-05 Page 1-4 REV. 1 The 24 VDC electric actuator is required to electrically actu- ate the tank valve. An electric signal is required from the AUTOPULSE Control panel which operates the solenoid in the actuator. This causes the actuator to open the tank valve and discharge the agent. On multiple tank systems, only one actuator is required, on the master valve. The remaining tanks will be actuated pneumatically through 1/4 in. stainless steel hose and a pneumatic actuator installed on the top of each tank valve. The actuator draw is 0.2A. Note: Composite cap attached to actuator is used as the reset tool. To reset actuator, put cap in place and turn knurled swivel coupling until cap threads are completely engaged. A small “click” will be heard while resetting. Note: Actuator has a 10-year shelf life. Electric Actuator – 24 VDC TYCO SAFETY PRODUCTS, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003186-1 © 2005 Ansul Incorporated Litho in U.S.A. ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates. Shipping Assembly Part No. Description 570537 Electric Actuator Thread Component Material Type Approvals Electric Body: Steel 1 in. UL Listed Actuator Swivel Nut: BSPP ULC Listed Brass FM Approved Actuation Pin: Stainless Steel 006763 1.8 IN. (45 mm) 3.3 IN. (85 mm) 1 IN. BSP

Transcript of UL EX-4510 4-1-05 Page 1-4 - Suppression...The 24 VDC electric actuator is required to electrically...

Page 1: UL EX-4510 4-1-05 Page 1-4 - Suppression...The 24 VDC electric actuator is required to electrically actu-ate the tank valve. An electric signal is required from the AUTOPULSE Control

System ComponentsUL EX-4510 4-1-05 Page 1-4

REV. 1

The 24 VDC electric actuator is required to electrically actu-ate the tank valve. An electric signal is required from theAUTOPULSE Control panel which operates the solenoid inthe actuator. This causes the actuator to open the tankvalve and discharge the agent. On multiple tank systems,only one actuator is required, on the master valve. Theremaining tanks will be actuated pneumatically through1/4 in. stainless steel hose and a pneumatic actuatorinstalled on the top of each tank valve.

The actuator draw is 0.2A.

Note: Composite cap attached to actuator is used as thereset tool. To reset actuator, put cap in place and turnknurled swivel coupling until cap threads are completelyengaged. A small “click” will be heard while resetting.

Note: Actuator has a 10-year shelf life.

Electric Actuator – 24 VDC

TYCO SAFETY PRODUCTS, MARINETTE, WI 54143-2542 715-735-7411 Form No. F-2003186-1 ©2005 Ansul Incorporated Litho in U.S.A.

ANSUL and SAPPHIRE are trademarks of Ansul Incorporated or its affiliates.

Shipping AssemblyPart No. Description

570537 Electric Actuator

ThreadComponent Material Type Approvals

Electric Body: Steel 1 in. UL ListedActuator Swivel Nut: BSPP ULC Listed

Brass FM ApprovedActuation Pin:StainlessSteel

006763

1.8 IN.(45 mm)

3.3 IN.(85 mm)

1 IN. BSP