UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED STATE OF ELECTRICITY DISTRIBUTION ASSETS INSPECTION REPORT FOR QUARTERS THREE & FOUR OF 2015 DECEMBER 2015

Transcript of UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium...

Page 1: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

UGANDA ELECTRICITY

DISTRIBUTION COMPANY LIMITED

STATE OF ELECTRICITY DISTRIBUTION

ASSETS

INSPECTION REPORT FOR

QUARTERS THREE & FOUR OF 2015

DECEMBER 2015

Page 2: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

ii

REPORT PREPARATION AND APPROVAL FOR CIRCULATION

Compilation & Drafting:

DATE NAME DESIGNATION SIGNATURE

Checking and proof-reading:

DATE NAME DESIGNATION SIGNATURE

Approval for Circulation:

DATE NAME DESIGNATION SIGNATURE

Page 3: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

iii

CONTENTS

ABBREVIATIONS .................................................................................................... iv

1 SUMMARY .......................................................................................................... 6

2 INTRODUCTION ............................................................................................... 8

3 OBJECTIVE OF THE INSPECTION ................................................................................ 9

4 METHODOLOGY .................................................................................................. 9

5 CHALLENGES .................................................................................................... 10

6 KEY FINDINGS FROM THE FIELD INSPECTION .................................................. 11

6.1 Substations ............................................................................................................. 11

6.2 Medium and Low Voltage Lines ...................................................................... 11

6.3 Other Distribution Assets ..................................................................................... 12

7 CONCLUSION ................................................................................................... 14

8 RECOMMENDATIONS .......................................................................................... 15

9 REFERENCES ..................................................................................................... 16

10. FIELD INSPECTION FINDINGS .......................................................................... 17

10.1 SUBSTATIONS ...................................................................................................... 17

10.2 DISTRIBUTION LINES ........................................................................................... 50

10.3 OFFICE BUILDINGS .......................................................................................... 105

10.4 FLEET .................................................................................................................... 111

Page 4: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

iv

ABBREVIATIONS

ABC: Aerial-Bundled conductor

ABS: Air Break Switch

CAPEX: Capital Expenditure

DO: District Office

ERA: Electricity Regulatory Authority

FDI: Foreign Direct Investment

GoU: Government of Uganda

HV: High Voltage

KV: Kilo Voltage

KVA: Kilo Volt-Ampere

LAA: Lease and Assignment Agreement

LV: Low Voltage

MVA: Mega Volt Ampere

MV: Medium Voltage

REA: Rural Electrification Agency

R & R: Restoration and Rehabilitation

SHE: Safety, Health and Environment

UEDCL: Uganda Electricity Distribution Company Limited

Page 5: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

v

UGX: Uganda Shillings

VFM: Value for Money

VHF: Very High Frequency

VM:

O&M:

Vegetation Management

Operations and Maintenance

Page 6: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

6

1 SUMMARY

Clauses 2.16 (a) & (b) of the LAA obl igates UEDCL, as lessor/owner

of the Distr ibution System to continuously monitor the restoration

and reinforcement (R & R); repair and maintenance; instal lations,

retirement, and modifications carried out by Umeme Limited, as

the concessionaire, on the assets making up the Distr ibution

System. UEDCL carr ies out quarterly inspections of the network

and reports on the state of maintenance.

Inspections for Third and Fourth Quarters of 2015 were carried out

in August/September and November 2015, respectively, to assess

the state of the Distr ibution Assets with regard to the afore-

mentioned.

The inspection found that appreciable amount of maintenance

activities have been carried out on the MV network but the level of

rehabilitation of the LV network doesn’t match up. This could create an

absorption problem when the proposed generation plants, currently under

construction, eventually come on line. A comprehensive programme needs

to be put in place to raise the LV network to acceptable level of

maintenance.

That notwithstanding, quality of materials and quality of workmanship needs

to be monitored carefully as they are affecting the useful lives of the assets,

hence value for money (VFM) accrued to consumers who pay for these

assets. These include quality of poles and conductors; poorly rammed poles;

poorly installed stay assemblies; incomplete structures, e.g. missing or

undersize bolts, missing cross-arm struts; poor conductor joints – especially at

LV; etc.

Page 7: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

7

Due attention should also be given to non-network assets like land and

buildings, to ensure they are fully utilised and properly maintained. Otherwise,

as stipulated in the Lease and Assignment Agreement (LAA) they should be

formally handed back to UEDCL to either use them or dispose them off as the

case may be.

With the increased rainfall, effective vegetation management (VM) was

found lacking in many areas. This affects the reliability of the network and

increases maintenance costs, e.g. on replacing conductors and insulators

broken by tree branches.

Aris ing from the inspection f indings, it is recommended that

Umeme undertakes the fol lowing:

a) As provided for in Section 2.16 of the LAA, and in order to maintain the

integrity of the Asset Register, Umeme should notify UEDCL of all

additions, modifications, transfers of assets on the distribution network;

b) Shares with UEDCL its Annual Maintenance Schedules for improved

monitoring and evaluation activities, hence keep copies of

maintenance logs in the substations highlighting actions done on the

respective apparatus;

c) Non-functional equipment on the distribution network that are not

serving their purpose, yet are part of the asset base, should either be

made fully functional or retired and disposed of;

d) Non-network assets like land and buildings should also be properly

utilised and kept at acceptable level of maintenance according to

good utility practice;

e) Preserve the integrity of the way leave corridor by improving on the

quality and frequency of vegetation clearance.

Page 8: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

8

2 INTRODUCTION

The Government of Uganda (GoU) privatized UEDCL through a 20 year

concession by bringing on board private investors in the electricity distribution

and supply business in order to:

Attract Foreign Direct Investment (FDI);

Improve the quality of service;

Rehabilitate, upgrade and expand the distribution network; and

Increase the electricity access to other customers in the country.

The electricity distribution and supply business was subsequently transferred to

Umeme on 1st March 2005 after signing a Lease and Assignment Agreement

(LAA) that leased the distribution assets to Umeme to carry out electricity

distribution and supply business.

The agreement specifically stipulates investment obligations by Umeme

during the initial period and the first five years of the concession. As part of

the agreement, Umeme was obligated to make an investment of a minimum

of USD 5 Million during the initial period and a minimum of USD 65 Million in the

first 5 years in system rehabilitation and reinforcement. This obligation was full

filled but a lot needs to be done on the electricity distribution network to

further enhance its efficiency.

The supply and distribution license to Umeme provides for an exclusive right

to supply electricity in an area up to one kilometer radial distance from the

existing distribution lines, and an obligation to provide service within the area

of exclusivity. However, network extensions have been carried out beyond

the initial scope due to lines added through REA and UEDCL.

With reference to Clauses 2.16(a) & (b) of the LAA that provide for rights of

access to the assets as Lessor to observe the Restoration and Reinforcement,

Page 9: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

9

repair and maintenance, installations and retirement plus modifications,

UEDCL personnel inspected the Distribution System to establish the status of

the assets for the period ending December 2015.

3 OBJECTIVE OF THE INSPECTION

The objectives of inspecting the electricity distribution assets were to assess

and report on the following:

Current state of the distribution assets including electricity distribution lines,

integrity of the way leave corridor, substations, office buildings, fleet and

their impact on system reliability;

Observance of Prudent Utility Practices in the Operation and

Maintenance of the electricity distribution network as provided for in

Electricity (Primary Grid Code) Regulations, 2003.

Asses the distribution system for the requirements in the Electricity

(Transmission and Distribution) Investments Approval and Verification

guidelines, hence provision of accurate and complete information as a

means of making the investment plans more streamlined, targeted and

agreeable to stakeholders.

4 METHODOLOGY

A substantial part of the distribution network was inspected in Central,

Eastern, Western and Northern regions of the country. The focus was to

establish the asset management practices on the distribution system, their

conformity to prudent utility practices and adherence to the provisions of the

Lease and Assignment Agreement as a result of Repair and Maintenance

activities of substations, MV and LV Lines, way leave corridor, vegetation

Page 10: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

10

management, office buildings, storage yards, fleet management and

including the effects to the environment. Note was also taken of any on-

going grid-extension works or modifications.

The approach for obtaining relevant information was physical inspection by

technical personnel and interaction with technical staff in the respective

areas. Snapshots were also taken to accompany the technical description of

the findings, some of which have been included in the last part of this report.

5 CHALLENGES

UEDCL is not regularly updated and/or notified of extensions to the

distribution network, sometimes carried out by third parties, making it difficult

to keep track of the full extent of the network.

Sharing of relevant information such as the annual substation maintenance

plans, network modifications is not realized hence making it hard to

accurately track the progress of changes made.

Adverse weather conditions and deteriorating roads make some parts of the

network not easily accessible, e.g. in mountainous areas.

Page 11: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

11

Vandalism of stay

wires!!

6 KEY FINDINGS FROM THE FIELD INSPECTION

6.1 SUBSTATIONS

a) The main 33/11 kV substations continued to be rehabilitated and

improved. Subject to confirmation, about 50% of the substations have

now been fully rehabilitated. Others are still work-in-progress or partially

rehabilitated;

b) There is need for sustained and regular substation housekeeping,

storage; hygiene; drainage and vegetation management; which was

under looked in many substations;

c) Availability of SCADA was reported to be unreliable in many of the

substations. Apart from Kampala area substations where SCADA was

fully available, all the upcountry stations reported problems with

SCADA, attributed largely to breaks in the communication link;

d) Detailed findings of the inspected substations are in Section 10.1.

6.2 MEDIUM AND LOW VOLTAGE LINES

a) The medium voltage distribution lines (33kV,

11kV) and Low voltage lines in some areas

require urgent rehabilitation to improve on

their reliability. The poles in several areas are

leaning either due to bad plumbing or lack of right anchoring,

broken/vandalised stay wires, removed stay rods, or being rotten. While

considerable work has been done or ongoing to rehabilitate the lines,

some other lines, as detailed in the appendix, require urgent attention;

Page 12: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

12

b) Low voltage (LV) lines in most of the outlying areas of the distribution

network require rehabilitation in order to improve on safety and

reliability;

c) As already highlighted in previous inspection reports, issues of quality of

materials, and suspected quality of workmanship, are persisting and still

need to be further investigated and addressed. Many poles continue

to be replaced without all the necessary accessories like pole caps

thus shortening their service life. Other shortcomings like installing

distribution transformers, either without or poorly positioned, surge

arrestors and arcing horns, are quite common. If you add in poor

earthing, it contributes to the high turnover of the distribution

transformers;

d) It is quite evident that unprofitable lines, as well as outlying lines far from

urban areas are still not receiving the requisite attention.

e) Details of MV and LV lines inspected are in Section 10.2.

6.3 OTHER DISTRIBUTION ASSETS

a) Most office buildings and substation plant houses were in fair state of

maintenance. Structures in Masindi and Fort portal are in need of total

rehabilitation and/ or redesign;

b) Incidences of plots of land not

being properly secured, e.g. by

fencing off, hence being prone

to encroachers, are still

persisting, e.g. in Kapchorwa,

Mbale, and Mubende. Also of

note are plots of land on hilltops

Page 13: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

13

around the country, where VHF radio stations were formerly located,

that have not been secured and/or utilised by Umeme for some time,

hence some of them have been claimed by encroachers;

c) Details of other distribution assets inspected are in Sections 10.3

(Buildings) & 10.4 (Fleet)

Page 14: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

14

7 CONCLUSION

A lot of maintenance work has been carried out on the MV network but the

level of rehabilitation of the LV network doesn’t match up. This could create

a power absorption problem when the proposed generation plants, currently

under construction, eventually come on line. A comprehensive programme

needs to be put in place to raise the LV network to acceptable level of

maintenance and readiness to absorb power from generating plants being

developed.

That notwithstanding, quality of materials and quality of workmanship needs

to be monitored carefully as they are affecting the useful lives of the assets,

hence value for money (VFM) accrued to consumers who pay for these

assets. These include quality of poles and conductors; poorly rammed poles;

poorly installed stay assemblies; incomplete structures, e.g. missing or

undersize bolts, missing cross-arm struts; poor conductor joints – especially at

LV; poorly protected distribution transformers; etc.

Due attention should also be given to non-network assets like land and

buildings, to ensure they are fully utilised and properly maintained. Otherwise

they should be formally handed back to UEDCL to either use them or dispose

them off as the case may be.

With the increased rainfall, effective vegetation management (VM) was

found lacking in many areas. This affects the reliability of the network and

increases maintenance costs, e.g. on replacing conductors and insulators

broken by tree branches.

Page 15: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

15

8 RECOMMENDATIONS

Based on the field findings and in l ine with the requirements of the

LAA and prudent Uti l i ty Practices, it is recommended that Umeme

considers the fol lowing:

a) As provided for in Section 2.16 of the LAA, and in order to maintain the

integrity of the Asset Register, Umeme should notify UEDCL of all

additions, modifications, transfers of assets on the distribution network;

b) Shares with UEDCL its Annual Maintenance Schedules for improved

monitoring and evaluation activities, hence keep copies of

maintenance logs in the substations highlighting actions done on the

respective apparatus;

c) Non-functional equipment on the distribution network that are not

serving their purpose, yet are part of the asset base, should either be

made fully functional or retired and disposed of;

d) Non-network assets like land and buildings should also be properly

utilised and kept at acceptable level of maintenance according to

good utility practice;

e) Preserve the integrity of the way leave corridor by improving on the

quality and frequency of vegetation clearance.

Page 16: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

16

9 REFERENCES

This report should be read in conjunction with:

Report on State of Distribution Assets as at December 2014;

Umeme Investment Plan for 2014;

Lease And Assignment Agreement(LAA);

Electricity (Primary Grid Code) Regulations 2003;

Electricity (Transmission and Distribution) Investments Approval and

Verification guidelines 2013

Page 17: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

17

10. FIELD INSPECTION FINDINGS

10.1 SUBSTATIONS

10.1.1 CENTRAL

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Motor Mart Switching Station Switchgear and ground mounted

500kVA/11kV auxiliary transformer in

good working condition

The station is at a risk, left without space

for possible future expansion and

maintenance works, with a possibility of

encroachment due to ongoing

construction works by HBT Investments

that have encircled the station

Issues raised in previous

inspections still remain

outstanding

Queensway1(Old) Substation-

{2x15/20 MVA 33/11kV Aichi

transformers (S/N:912254902)

&

(S/N:912254901)}

Transformers in good condition of O&M;

operating in parallel; substation fence

intact & well-guarded

Drainage issues exist with running water

over flooding the drainage channels

leaving some and some structures

(behind the guard house) in the middle

of stagnant water. This has been

worsened by works on the new

substation site; Temporary portable

toilet used by security guards in poor

state, raising sanitation issues ; Kisugu &

Kampala South 1 feeders not labelled

Drainage needs

improvement; newly

constructed pit latrine

should be completed to

solve the sanitation

issues

Page 18: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

18

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Queensway2(New)

Substation-

{2x15/20 MVA 33/11kV

Crompton transformers

(S/N:ET10327/2) &

(S/N:ET10327/1)}

The installed power transformers in good

working condition; fence intact, plant

house looks elegant

Reports of malfunctioning of the newly

installed Siemens switchgear during

Opening/Closing, Isolating & Earthing

sequences (e.g. Kisenyi & Katwe 11kV

feeders; covers for cable trenches in the

plant house loosely put overlapping the

floor, not properly aligned with the

trench dimensions & likely to cause an

accident to the operators; labelling

requires improvement; drainage lacking

& causing flooding situations at the old

substation site

Proposed Nabugabo

Road & Namirembe

Road 11kV feeders(Bays

K02 & K03 respectively)

not yet fed by the

substation; quality of

works and integrity of

installed apparatus

require close scrutiny,

especially during

investment verification;

Works yet to be verified

Kitante Substation-

{2x10/14MVA 33/11kV Power

transformers

(S/N:113020)&(S/N:112120)}

Power transformers & ABB switchgear in

good condition; fence intact; lights

working; guard available; substation

found locked

2 manhole covers for the cable trench

in front of the plant house not replaced

after cable works for new Queensway

substation; Cable trench besides the

33kV panels inside the plant house

found uncovered; Labelling for Lugogo

Incomer 2 & Queensway Interconnector

require improvement; No toilet; No tap

water; No guard house; temporary

shelter used by the security guard

Though there exists

space constraints, there

is need for proper

sanitation facilities for

personnel working at

the substation

Page 19: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

19

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Lugogo 132/33/11kV

Substation-UETCL (33/11kV

Switchgear Inspected)

Substation drawing available; Labelling

for all panels in place; SCADA

functionality okay; rubber mats(2)

available for operational safety;

substation logbook available; 2x9 kg

serviced fire extinguishers available;

Air Conditioners working

Key cabinet missing; some lights inside

the plant house not functional(thus light

insufficient)

Siemens switchgear in

good condition of

O&M; non-functioning

lights should be

maintained

Kampala North 132/33/11kV

Substation-UETCL (33/11kV

Switchgear Inspected)

Rubber mats(2) available for operational

safety; AC working; Lights working; Key

cabinet available

Status Indicator for Ntinda 33kV feeder

faulty; Namungona 33kV Bay

completely burnt &not in use; Status

indicator(earth switch) faulty; Kawala

Spare 33kV bay completely burnt;

Nakasero 33kV Bay found open; Fire

extinguishers missing; Cable trench

besides Acacia Mall 11kV panel not

covered; No substation drawing; No

keys in the key cabinet

Switchgear has serious

signs of burning and

quite untidy

Kawanda Substation –

{1 x5MVA(S/N:112520),

1x10/14MVA (S/N:112121)

33/11kV power transformers}

Drainage worked on; Security guards

found on duty; Gravel improved;

concrete foundation put at the base of

the metallic fence/enclosure; water on

site; pit latrine available; Outdoor

switchgear in good condition; Power

transformers in good condition; Standard

padlock used on the access to the

substation; Auxilliary supply transformer

that had blown replaced;1 of 3 security

Illegal connection exists with a service

cable taping from the first transformer,

buried underground round the

substation fence to supply a metallic

kiosk placed just next to the substation

towards the road; Metallic pole for the

security light at the substation entrance

found broken; AC needed

servicing(supplying hot air);

100kVA/33kV transformer just outside

Replacement of the

broken security light

pole and servicing the

non-working ones

required; servicing of

the air conditioning;

Capacity issues likely on

the 5MVA transformer

dedicated to Kakiri 11kV

feeder;

Page 20: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

20

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

light working the substation directly connected

without MV protection & with poorly

terminated LV wiring; Some weed

starting to grow within the substation

yard; Only 1x9kg fire extinguisher

available-insufficient(second one taken

during servicing and not returned

yet);Breached fence for the storage

area;1 of 3 security light behind the

guard house not working; Unterminated

fibre cable lying within the substation

yard; fence knocked and damaged by

a speeding vehicle besides the

substation entrance; offcuts of materials

and timber kept behind the guard

house-hose keeping! Kakiri 11kV feeder

not remotely monitored

Waligo Substation –

{ 2x10/14MVA 33/11kV

Crompton transformers

(S/N:ET10126/2) &

(S/N:ET10126/1)}

Fence, gravel in good condition; power

transformers working perfectly and in

parallel; External Alstom switchgear

functional;25kVA/11kV/415V

S/N:EJ27047/1 Ampcontrol auxiliary

transformer well maintained; Rubber mat

available on the 11kV switchgears; ABB

Indoor switch gear in good condition;

Drainage channel at the substation

entrance rubbish in it likely to block

runoff water flow;4x9kg fire extinguishers

had expired on 24th October 2014 as on

4th March 2015;No substation diagram

available; Nangabo 107 Bay wrongly

named“Mangabo”;Katalemwa 109 Bay

wrongly labelled, technically known as

“Ugachick” on the system operation

diagram; Air conditioning not working;

surge arrestors on “Ugachick” 11kV

feeder cable across the road not

connected;

Issues noted in previous

inspections still need

addressing

Page 21: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

21

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Namungona 132/11kV

Substation -UETCL(33/11kV

Switchgear Inspected)

The Aichi 11kV switchgear is operating

perfectly with no reported anomalies;

new labels on 11kV panels;

Buildings constructed under first spans of

Nansana 11kV feeder; foundation for

first structure of Nakulabye 11kV feeder

threatened by brick laying works;

Nansana 11kV feeder has its first

structure wrongly labeled

“Nansana/Kawala(NAM/NSN/11/1)”

inconsistent with Panel labeling, besides

the feeder label is jus placed standing

besides the structure and can easily be

taken away(needs fixing onto the

structure)

Aichi 33kV switchgear is

not in use since no 33kV

feeders exist

Mutundwe 132/33/11kV

Substation-UETCL (33/11kV

Switchgear Inspected)

3x 9kg fire extinguishers available &

serviced; Rubber mats(x2) available for

operational safety; Air Conditioner

working; lights in the plant house working

Substation drawing not available;

First structure on Mityana 33kV feeder

has vandalized stays and without a

feeder label

Substation was found

generally okay, though

issues noted in previous

inspections hadn’t been

addressed.

Page 22: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

22

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Gaba Substation-

{ 2x10/14MVA 33/11kV Power

transformers (S/N:120521) &

(S/N:112619)}

New battery bank installed; Key cabinet

available & well labeled; Air conditioning

working though in need of service;

50kVA auxiliary transformer well

maintained;

Fence, gravel, access gates & lights in

good condition; security guard found on

site; transformers in good condition and

working in parallel; substation drawing &

rubber mats available

Lugogo Bay Bus Bar extended and its

mode of operation needs revision;

Remote operation of Kansanga 11kV

Circuit breaker not functional; Lugogo &

Portbell 33kV panels operated

manually(rather than electrically) for

isolation and earthing functions; Bay 303

reportedly with operational issues & not

in use(its mode of operation needs

improvement);Water borne toilet

blocked & not in use; AC unit still

discharging condensed water inside the

plant house onto the apparatus; plant

house paint starting to peel off; No

means of communication at the

substation(e.g. telephone handset,

radio call); Metering Unity on Gaba

Water Works 3 faulty & isolated; No

water at the substation; fire

extinguishers had expired in October

2015 as on 9th February 2015

Noted issues in previous

inspections hadn’t been

addressed.

Page 23: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

23

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kisugu Substation-

{ 1x10/14MVA 33/11kV Power

transformer (S/N:120421)}

Aichi outdoor switchgear in good

condition of maintenance;1 of 2 security

light working; Power transformer in good

state of maintenance

Only 1of 2 security light working; No fire

extinguishers; No means of

communication at the substation;

SCADA functionality unreliable;

Except for noted issues,

all other issues observed

in previous inspections

had been handled and

s/s was okay

Page 24: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

24

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kampala South Substation-

{ 1x15/20MVA 33/11kV

Crompton Greaves

transformer

(S/N: ET10047/1)}

Aichi outdoor switchgear in good

condition and remotely operated; Front

part of the yard partitioned for materials

storage; Security lights working;2x9kg fire

extinguishers available & serviced

No standard padlock at the main

access to the substation yard;110V DC

battery bank(batteries) had 10 open

covers exposing the battery solution; No

substation drawing; labeling for

“Kisubi(Entebbe 1)” 33kV inconsistent

with the labeling as “Lubowa 1” on the

first structure; Substation yard gravel

insufficient requiring re-enforcement

(worsened during cable installation

works/ non restoration of its original

integrity); poor drainage/channels

blocked with silted soil; open man holes

exist around the recovered transformer

plinth(unsafe);plumbing for the toiled

leaking

Another layer of gravel

needs to be added.

Considering that a

corner of the substation

was being used as

storage area (meters,

cables, etc) safety

considerations needed

to be beefed up e.g.

demarcation between

storage & substation

areas should be more

robust using high

metallic fence, and

access to switchgear to

be securely padlocked

Page 25: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

25

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Lubowa Substation-

{ 2x10/14MVA 33/11kV

Crompton Greaves

transformers (S/N:ET10126/3) &

(S/N:ET10126/4)}

ABB switchgear in good condition and

power transformers in good condition

Air conditioner leaking water onto the

DC panels inside the plant house; No

substation drawing; drainage on the

upper part of the substation blocked by

rubbish from neighbours

Substation still new &

generally in good

condition

Kajjansi Substation-

{ 1x5MVA 33/11kV Aichi

Electric transformer (S/N:

9422337)}

Power transformer & all installed NULEC

circuit breakers in good condition

Substation Metering Unit(on Nakilagala

& Lubowa 11kV feeders) leaking oil;

New pit latrine not used, temporally one

used); no water at the substation;

Storeyed building under construction

below Kampala South, Entebbe 1&2

feeders just besides the substation

Station generally okay,

though needs a touch

of refurbishment,

especially strengthening

the boundary wall

Page 26: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

26

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Entebbe Substation –

{2 x10/14MVA 33/11kV (S/N:

1901010602),(S/N:

1901010601)}

Tap water available at the substation; 9

of 11 lights in the plant house working

&sufficient; Substation rubber mat

available for operational safety; All

feeders labeled;

SCADA functionality available/ based on

wireless network; Fence/substation

enclosure intact; All security lights

working; Gate to the main substation

yard to the substation locked with a

standard padlock; Transformers in good

state of maintenance & operating in

parallel; Switchgear functioning properly

with no reported/visible anomalies

No fire extinguishers found at the

substation;

Guard house paint peeling off; 2 of 11

lights in the plant house not working;

One side of the access gate to guard

partition broken;

Communication for remote operation

of the substation not reliable; Air

conditioning system leaking water inside

the plant house that eventually flows

towards the RTU

While the substation is in

generally good state of

maintenance, some

issues had not yet been

addressed, e.g. fire

protection, operation of

air-conditioning, etc

Kisubi Substation –

{1 x5MVA 33/11kV (S/N:

68277)}

Power transformer & outdoor JICA

switchgear in good state of

maintenance; DC working normally; All

feeders labeled; Pit latrine & guard

house in good order;

Security guard found on duty; 2x9kg fire

extinguishers available & serviced;

SCADA functional depending on the

availability of communication;

Drainage at the entrance of the

substation is poor, requiring a trench so

that running water from the main road

does not wash the soil into the

substation; Access road to the

substation is washed away with open &

dip trenches; Cable trench at the

transformer position/33kV cable side not

covered; piped water turned off due to

a leakage in the pipe within the

substation access;

The drainage issue had

been largely addressed

and the substation was

generally okay.

Page 27: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

27

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Port bell Substation –

Observed from Outside

{2x5MVA 33/11kV (S/N:68278),

(S/N:68280)}

Main access gate had a standard

padlock; All feeders well labeled; Guard

house has a window under repair; aerial

earth installed over the power

transformers

Weed growth visible in the yard around

the transformers; Loose materials within

the substation yard; Timber workshop

operated besides the substation under

Kitintale 11kV feeder has damaged the

fence. Safety of the public & feeder

cable compromised; Roofing/iron

sheets for the pit latrine damaged and

almost blown off by wind; No tap water;

Paint for the pit latrine peeling off;

external perimeter fence(enclosure for

the substation land) old & broken on

several spots requiring

maintenance/replacement

Same situation prevails

when compared to the

previous inspection

hence 2014 status

report findings still

relevant. Especially the

substation fence needs

to be worked on and

strengthened

Page 28: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

28

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kireka Substation –

{2 x10/14MVA 33/11kV

Emirates transformers

(S/N:19010719/01)

& (S/N:19010719/04)}

New Siemens 33kV Panels installed for

Namanve,Lugogo 2 & Transformer No.2

Bays; New Digital Siemens relays installed

on Kyambogo,Namugongo,Mandela

Stadium,Tx Bay 303/104,Bus Section(Bay

105),Port bell(Bay 107), Seeta (Bay 108)

panels;2 of 4 security lights working; All

lights in the plant house working; Rubber

mats available for operational safety; DC

in good condition; Substation drawing &

logbook available;1x9kg serviced fire

extinguisher available; Power transformers

well maintained and running in parallel;

Fence/enclosure intact with no forced

entries; Security guard available; Most

feeders labeled; Plant house in good

condition;

Access to the substation locked with a

standard padlock

A number of maintenance issues raised

in previous inspections had not yet

been addressed

All concerns raised

require urgent attention

to put the substation in

desired state of

operation and

maintenance

Page 29: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

29

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Ntinda Substation –

{1x 10/14MVA (S/N: 68268),

1x 5MVA(S/N: 68273)

33/11kV Energo Invest

transformers}

Air Break Switches on Waligo & Kampala

North 33kV Incomers replaced &

motorized; Metering Unit reportedly

installed on Kyanja 11kV feeder from

Waligo substation in preparation for load

transfer from Ntinda substation;1 of 2

flood light working; Signs to install a new

battery charger & DC assembly exist with

materials already at the substation &

execution of works expected in March

2015; All feeders labeled; Substation

fence/enclosure intact; Security guards

found on duty

No surge arrestors or aerial earth

installed on the 10/14MVA transformer

for its protection; 11kV Cable for

Kiwatule 11kV feeder from Tx No.1

terminate onto the 11kV bus bar instead

of the 11kV circuit breaker under normal

configuration-possibly due to a faulty

circuit breaker, which is risky; Capacity

issues exist for Tx.No.2 (5MVA) currently

dedicated to Kiwatule 11kV feeder

apparently with a Maximum Demand of

about 4.9MVA;

Drainage issues still evident in case of

heavy rains; Stones/gravel in the yard

insufficient; Pit latrine engulfed in a bush

environment; Man holes besides Tx.No.1

open; SCADA not working,

communication cable reportedly

damaged around Ntinda Stretcher;1 of

2 flood light not working; No fire

extinguishers at the substation; Trees

within the neighboring school

compound growing towards the 33kV

bus bar; First wooden structure for

Kyambogo 11kV feeder rotten; Open

trenched besides Tx.No.2

Some emergency work

was done in this

substation to address

capacity and drainage

issues; additional

comprehensive works

are being planned

Page 30: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

30

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mukono Substation -

{1x10/14 MVA 33/11kV

(S/N:ET10046/2)}

NOTE

Other transformers {5MVA,

S/No: 113022,

1MVA,S/No.X1317/1, 5MVA,

S/No.942024301 whose status

could not easily be

established still exist in the

storage space besides the

substation

Switchgear and power transformer

maintained on 11th February 2015;GEC

Alsthom Switchgear (Circuit Breaker) for

Mpoma 11kV feeder initially with

operational difficulties during isolation

reportedly worked on(though not tested);

Substation rubber mats available for

operational safety; Lights in the plant

house working; Works ongoing on the 1st

structure of Seeta 11kV feeder, Metering

Unit yet to be installed on it; Rotten poles

in the yard being replaced progressively;

gravel re-enforced; Old Isolator(Alpha

Switzerland) next to the auxiliary

transformer replaced; coat of metallic

paint added onto the substation fence; 2

existing security lights working; Pit latrine in

good condition; security guard available;

aerial earth installed for transformer

protection; All feeders labeled;

SCADA functionality working properly for

most of the apparatus

Substation guard available; Access gate

to the substation found with a standard

padlock

Circuit Breaker Isolator for the

transformer Bay faulty with broken

insulators and by passed; Air conditioner

not working; Battery bank still inside the

plant house with the switchgear;

communication to ensure remote

operation of the substation not reliable

just like SCADA functionality for Mbalala

33kV feeder; recovered control units

boxes stored inside the substation yard;

3rd security light behind the

communication antenna not working;

external fence on the upper side of the

substation damaged by civil works on

the neighbouring building; No tap

water; No electricity connection in the

guard house; drainage channel in front

of the substation blocked with silt and

required unblocking

Work was found going

on to install a second

transformer. Excavations

around live MV cables

highlighted the need to

create proper cable

trenches in the

substation hence

reorder the cables

properly through them.

Page 31: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

31

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Nakifuma Substation -

{1x2.5MVA 33/11kV

Crompton Parkinson

transformer of 1936

(S/N:79539)}

SCADA functionality reportedly okay;

Wooden structures still new; All feeders

well labeled; Security lights working; The

tap exists but no water in the entire area,

worsened by the dry season; Guard

house & toilet in good state; Gate to the

substation locked with a standard lock

Signs of oil leakage through the power

transformer tap changer and gasket still

exist; Old Reyrolle circuit breaker still

exists; Multiple forced entries exist within

the fence(besides Ntenjeru 11kV &

Mukono 33kV feeder structures);

Drainage poor & likely to worsen during

the rainy season; No fire extinguishers at

the substation; Battery cubicle heavily

affected by dust from the road

Security guards were

available but station

needs refurbishment for

operational safety. A

drainage issue was

developing with rain

run-off finding its way

into the substation and

displacing the stone

chippings.

Page 32: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

32

10.1.2 WESTERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mityana Substation - Wabigalo

{2x2.5MVA 33/11kV ABB

transformers

(Tx1 S/N: 57.235)&

(Tx2 S/N: 57.231)}

The substation is generally in a fair

condition of maintenance with the yard

well taken care of; Tap changer for

transformer No.2 worked on by

replacement of the motor

Isolator & Earth Switch(on Mutundwe

33kV Incomer Bay) on the same structure

without interlocks, a safety risk for

operational staff;

Spring charging for Mutundwe 33kV

Incomer CB can only be charged

manually. The motor is faulty; Substation

diagram not available; Labeling of the

33kV Panels just scribbled; Transformer

No.1 GEC Alsthom circuit breaker old

and sometimes malfunctions; Circuit

breakers charged manually. SCADA

would remotely operate the apparatus if

the circuit breakers were not being

charged manually; Signs of water

leakage through the guard house roof

and through the openings within the

wall; Signs of the security guards cooking

close to the substation apparatus exist at

the entrance of the substation(Untidy)

Separation of the

Isolator and Earth

switch/or provision of

interlocks is essential in

ensuring the safety of

the operators;

Mubende Substation

{1x2.5 MVA 33/11kV Brush

transformer (S/N:77123)}

Fire extinguishers available and serviced;

Substation access gate in good

condition & kept locked; Yard stones in

good order; Security guard present;

Circuit Breaker for Kakumiro 33kV feeder

is still the Old Reyrolle OCB and not

remotely monitored; Transformer tap

changer faulty, reportedly vandalized,

Issues highlighted need

attention, most

importantly the faulty

tap changer,

Page 33: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

33

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Guard house in good condition; All

apparatus; substation logbook in place;

substation drawing exists; DC for

Mubende Town 11kV circuit breaker

worked on

thus no automatic voltage regulation for

quality supply; Substation fence is

damaged(with a wide open forced

entry) on the rear side besides the pit

latrine wall; 1 of 2 security lights not

working not working; A ladder kept within

the substation yard; Remote operation

not possible for Nkonge 33kV Incomer CB

at Mubende substation, relies on Nkonge

substation circuit breaker; Nkonge 33kV

line has a faulty isolator that requires

repair on the yellow phase; weeding

required on the rear side of the

substation; wiring for the auxiliary supply

transformer needs improvement

replacement of

outdated Reyrolle OCB,

automation of

switchgear operations

& safety concerns; signs

of encroachment on s/s

land - boundaries need

to be secured.

Rugombe Substation

{1x5MVA 33/11kV

Energo Invest

transformer(S/N:68276)}

All outdoor switchgear, plant house, pit

latrine, guard house, fence in good

condition; Power Transformer is well

maintained; All apparatus labelled; 2 of

3 security lights working;2x9kg fire

extinguishers available & substation

guarded; main access gate worked on;

Drainage, water tank and plant house

worked on

Mwenge 11kV feeder Circuit Breaker

faulty, Mwenge 11kV & Mukunyu 11kV

feeders linked together & sharing same

CB meant for Mukunyu. Requires

restoring the faulty CB and subsequent

separation of the two feeders; Battery

bank inside the plant house with the

switchgear; Links instead of proper fuses

used for auxiliary transformer HT

protection

Operational status of

Mwenge 11kV feeder

Circuit breaker should

be restored

Fort portal Substation

{1x5MVA, 1X2.5MVA 33/11kV

Power & Brush transformers

respectively(S/N: 112019 &

76026 respectively)}

Substation is generally well maintained

inclusive of the Power Transformers; Fire

extinguishers (5),apparatus labelling,

availability of a rubber mat for

operational safety, security lights, tap

water and presence of security guards

The fence is damaged at the rear end,

cats or dogs and people can easily get

into the substation & storage area; The

coat of paint on the Plant house is

peeling off; Switchgear between

Nkenda 33kV Incomer and Mpanga

Same condition as in

Q1,2 & 3 of 2015

Page 34: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

34

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

33kV needs maintenance or

replacement to a better one;Rugombe

33kV feeder Metering Unit faulty;

Substation mostly operated manually

due to unreliable SCADA system; Battery

bank housed in the plant house with the

switchgear; stores structure leaks through

the roof; cracks have developed in the

internal wall of the stores building; broken

main entrance gate & now tied with

binding wire; breached fence behind

the guard house due to

offloading/loading of poles stored there;

stores building has openings on the side

of the substation & water passes through

to flood the inside; drainage needs

improvement

Kasese Central Substation

{1x2.5MVA 33/11kV Brush

transformer

(S/N:51750/2)}

The following issues well taken care of:-

Auxiliary transformer, guard house, toilet,

feeder labelling,2x9kg fire extinguishers,

tap water availability, guards &

availability of security lights.

Yard stones insufficient and cab stones

affected by construction works, these

need to be re-done; Fence foundation

damaged on the rear side besides

Kabale 33kV line; Guards available,

though with no access control register for

proper documentation; Vegetation

noticed in the substation yard; 2 security

lights working & permanently switched

on, require maintenance; Air break

switch between Kabale & Nkenda 33kV

lines faulty; First air break switch(ABS) on

Kabale 33kV line bypassed; Damaged

cab stones along the inside access way

Same situation as in

Q1,2 & 3 of 2015 still

prevails

Page 35: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

35

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

to substation yard; Drainage channel at

substation gate needs maintenance

Ishaka Substation {1x5MVA

33/11kV Power

transformer(S/N:111211)}

Substation stone cover have been

maintained appropriately;

The substation is guarded all the time;

Partitioning created to cater for material

storage; Feeder labels in place; DC

supply in good order; security guards

found at the substation; 1of 2 security

lights working; Substation fence in good

condition; Substation access restricted

by use of standard padlock;

Bees have settled onto the main access

gate support pillars; Isolators on the

incomer 33kV lines from Mbarara North &

Kasese worn out; Cab stones inside the

substation are broken; Some materials

(half drum of conductor found kept

inside the substation yard just like in

November 2014,March,June &

September 2015; Substation lacks tap

water, hence staff cannot clean their

hands after using the

toilet(SHE);substation gravel insufficient

as you access the substation yard; 1 of 2

security light not working; Auxiliary

transformer has links rather than standard

fuses for HT protection; Nulec CBs

located external to the substation(across

the road) vulnerable to illegal operation;

Access door to material storage area

always open allowing free entry,

because the toilet is housed within the

same partition, hence exposing materials

to possible theft; No fire extinguishers at

the substation;

All operational, safety

issues noted require

intervention; Ishaka

Town 11kV feeder

should be split into two

with the Tea Estate t-off

originating directly from

the substation

busbar,thus relocating

its CB to the substation

Total reconstruction of

the substation with two

new transformers, plant

house, indoor

switchgear in plan

Page 36: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

36

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kabale Substation {1x5MVA

33/11kV Energo Invest

transformer

(S/N:68271)}

The access gate, stones/gravel,

transformer tap changer,gantries,poles

and signage,metering,SCADA

functionality, guard house,

security/lights, DC supply, fire prevention

& protection(4x9kg serviced fire

extinguishers available),plant house

condition,Safety,Health &

Environment(SHE) in good condition.

Signs of oil leakage from the conservator

tank exist; Silica gel needed changing;

Status indicators needed correction on

some circuit breakers such as Kabale

West 11kV feeder Earth switch, thus

unsafe during operation; The batteries

are located in the plant house with the

switchgear; No updated substation

operational drawing; Kabale East 11kV

bay redundant; substation fence

showing signs of damage due to storage

of poles besides the guard house

Urgent need to relocate

the battery bank from

inside the plant house,

where the switch gear is

housed; the leakage on

the conservator tank

should be cured and

silica gel changed;

generally the power

transformer should be

maintained

Rukungiri Substation

{1x2.5MVA 33/11kV Energo

Invest transformer

(S/N:68282)}

Faulty tap changer motor worked on;

Auxiliary transformer well protected with

CBs installed; Surge arrestors for the pole

mounted circuit breaker for the Incomer

Ishaka 33kV line replaced; Optic fiber

cable extended to the substation &

office building; Aerial earth exists for

enhanced substation protection;

Signage largely in place except that

Kagogo 11kV feeder label is wrongly

written as “Kagogoro”; Substation fence

in good condition, except that the lower

side needed a retaining wall as well; The

substation stone cover in good

condition; Guard house and pit latrine

enclosed off the substation;

Some switchgear worn out requiring

maintenance such as the faulty &

bypassed transformer isolator; The pole-

mounted nulec circuit breaker for

Kanungu 33kV line has two faulty surge

arrestors isolated thus not protected

against lightening, earth wire broken &

illegally operated due to its location

outside the substation; SCADA system

only allows for visibility but cannot

remotely operate the apparatus, hence

substation manually operated; No oil

sump for the power transformer, oil goes

direct into the gravel & environment;

Labeling for Kagogo 11kV feeder

wrongly written as “Kagogoro”; All the 2

Worn-out isolators,

faulty accessories like

surge arrestors on

Kanungu 33kV nulec

circuit breaker, SCADA

functionality and

lighting among others

should be addressed;

The old redundant

building besides the

substation yard could

be renovated & utilised

as part of the offices

Page 37: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

37

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

available security lights not working,

insufficient light; A redundant Metering

Unit exists on Kanungu 33kV feeder

structure & not connected, should be

recovered; No fire extinguishers at the

substation for fire prevention and control;

An old & redundant structure/building

exists besides the substation yard,

occasioned by floods whenever it rains

due to poor drainage & lack of

maintenance

Mbarara Central Substation

{2x5MVA 33/11kV Aichi

transformers(S/N:942024303 &

942024302 for Tx 1 & 2

respectively)}

The transformers and switchgears are

well maintained; battery room is

separate from the Control room;

Substation earthing improved by

installation of aerial earth across the

transformers; Guard available; All

feeders labeled; Tap water available;

Substation drawing available; Substation

lighting okay; Substation rubber mats(x2)

available; All H-pole structures inside the

substation replaced, The two

interconnectors from Mbarara North are

terminated on different sections of the

33kV bus for improved supply reliability;

Substation gate found locked with a

standard padlock; Container removed

from the substation yard

The 11kV bus coupler is open &

accordingly the two transformers do not

share load, leading to TX-1 being

overloaded at peak hours while TX-2 is

only about 50% loaded; Perimeter fence

damaged with several openings; Very

big tree just outside the substation fence

& a redundant rotten 3-phase terminal

LV pole within the yard besides Tx

No.1.They are likely to fall and damage

the Plant-house or the power

transformer, if not removed early

enough; Guard house, toilet & its

plumbing in a poor state with paint

peeling off; Some recovered

materials(mostly disc insulators kept

inside the substation) making it untidy;

Drainage issues exist at the substation

with the channel in front of the old store

structure damaged and blocked; Weed

Land between s/s and

main road taken over

by unknown person

who demands

relocation of 11KV

feeders on it (Ishaka,

Karamurani, Ntare,

Kakoba);

The substation

environment requires

complete refurbishment

and partitioning to

utilize the available

space.

Page 38: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

38

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

growth was evident; Old and

abandoned concrete pole rack behind

the old store building needs to be

covered up & entire substation floor

covered with stone pitch; Old poles on

Masaka West 33kV feeder first structure

not decommissioned; Station supply

transformer labeling wrong indicating

“50kVA” yet the installed capacity is

“160kVA/11kV”; An old Siemens Panel

labeled “Mukwano” & possibly

recovered from another substation found

positioned next to Kakoba 11kV feeder

Masaka Central Substation

(1x10/14MVA

33/11kV{S/N:19010719/02})

Aerial earth installed for enhanced

substation transformer protection

against lightening; Substation fence and

plant house are in good condition; New

operating carpet at the 11kV bay

provided; Battery bank & DC supply in

good condition; Substation drawing

available; Lights working both inside the

plant house and yard; Power & Auxiliary

transformers in good state of

maintenance; fence, stone pitch well

maintained, substation access secured

with a standard padlock

Reports of a heavy flash from the

overhead line conductors of Lower Ring

11kV feeder first structure whenever it

rains developing into heavy flames exist;

Drainage channel towards the road side

on the upper part of the substation

prone to silting due to soil erosion; Lack

of tap water at the substation for staff

sanitation; Incomers-first structures for

Mitala Maria & Masaka West 33kV

feeders not labeled; Drainage works

partially handled excluding the upper

part where the poles are stored, some

civil works still required around the pole

bed; loose wires & a ladder kept behind

the guard house

Drainage issues still

prevailing aggravated

by additional silt

washing down the

slope and blocking the

drainage; the source of

heavy flames around

Lower Ring 11kV first

overhead structure

conductors should be

investigated

Page 39: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

39

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kiriri Substation

{1x2.5 MVA 33/11kV Pauwels

transformer(S/N: 85.40668)}

Substation apparatus fairly maintained;

transformer tap changer replaced; All

security lights working;

Weed growth exists within the substation

yard; reports of operational failure of the

newly replaced tap changer; No pole

cap on one of the newly replaced poles

on the first Kiriri 11kV feeder H-structure;

Kibibi 11kV feeder not individually

metered(No metering unit & meter

installed);No fire extinguishers in place for

fire prevention; Poor terminations on CB

& Metering Unit for 11kV side of the

power transformer; Links used for HT

protection on the transformer isolator;

33kV/100kVA auxiliary supply transformer

lacks HT protection(directly

connected);No source of water for use

at the substation; no electricity in the

guard house; Labelling for “Mitala Maria”

33kV incomer required changing to

“Masaka Central” 33kV to match the

operational system diagram

Issues raised require

attention

Busunju Substation {1x2.5 MVA

33/11kV, 1x5MVA 33/33kV

Energo Invest & Pauwels Auto

transformers(S/N:68284

&00.2.4026 respectively)}

Power transformer, DC

supply,fencing,drainage,lights,stone

pitch well maintained; Power

transformer maintenance done; All

energy metered; fire extinguishers

available and serviced;

Main access gate to substation found

unlocked; weed exists on the rear side of

the substation; stone pitch not restored

between Kiziba & Jesa Farm 11kV

feeder; Power transformer overloaded;

No label on Kawanda 33kV incomer;

Circuit breaker for Hoima 33kV feeder

not stable-initially graded for dispatching

to Hoima rather than receiving supply

from Buseruka; There are reports of

voltage synchronization issues when

Same status as in the

previous inspections of

Q1,2 & 3 of 2015;

Capacity issues, all

substation apparatus

visibility, protection for

Kawanda 33kV line and

voltage profiles(on

Buseruka 33kV incomer

& Kiziba 11kV feeder)

need urgent attention,

Page 40: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

40

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

supply is got from Buseruka 33kV

line;5MVA/33kV Auto transformer

overloaded & sometimes leaks oil; The

auto transformer reportedly trips on

overload; Surge arrestors on the nulec CB

for Katera 11kV feeder not terminated;

Surge arrestor on Red phase for

Katera11kV cable supplying the bus bar

not terminated; No surge arrestor on Red

phase for Jesa Farm 11kV cable; No

surge arrestor on Yellow phase of the

Auto transformer circuit breaker; some

switchgear lacks operational padlocks;

No circuit breaker installed for the

Kawanda 33kV Incomer to the

substation, hence no protection; The

2.5MA transformer is having capacity

issues with maximum demand currently

at 2.37MVA. Remote operation of

Mityana 33kV line circuit breaker

through SCADA not working; “Jesa Farm”

11kV labelling requires changing to

“Mulwana” 11kV feeder to match the

operational system diagram; 1 of 2

security light working and permanently

on; No substation drawing; No source of

water at the substation; No security

guard found at the substation from

1030hours to 1158hours on 18/11/2015;An

anthill likely to damage one side of the

substation fence

in addition to

addressing the

operational safety

concerns

Page 41: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

41

10.1.3 NORTHERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Hoima Substation

{1x5MVA 33/11kV

(S/N:68279),

1x1MVA 33/11kV

(S/N:68288),

1x5MVA 33/33kV

(S/N:9920254)}

New Air Break Switches installed on all

the first overhead structures from the

substation (i.e. Hoima Town 11kV

x1,Busunju 33kV x2,Buseruka

33kVx1,Munteme 33kV x1,Masindi 33kV

x2); Standard padlocks used on

substation apparatus; Old Reyrolle

Circuit Breaker on Busunju 33kV Incomer

decommissioned; New cables installed

on 33kV side of Tx 1&2;Cable gantries

installed on both Tx1&2; Fencing &

substation access/gate are in good

condition & found locked; DC Supply

found in good condition;

All feeders labelled; 2 of 3 security lights

working; Outdoor switchgear

maintained & functional; Pole caps

installed on all the poles within the yard;

Security guard found on site

Munteme 33kV feeder shifted from the

Auto transformer & now picks supply

directly from the bus bar; Tap changer for

the 1MVA Power transformer removed,

taken for repair & not returned yet, hence

no voltage regulation;33kV Circuit

Breaker supplying the 1MVA power

transformer non-operational, motor blew;

Stone pitch not well maintained-large

sized stones allow weed growth;

Substation environment had weed

growth, a sign of lack of regular weed

control;SCADA not reliable; Poles stored

on ground besides the substation as in all

previous inspections; Pit latrine paint

peeling off;3x9kg fire extinguishers had

expired; 1 of 3 security light not

working;5MVA 33/33kV Auto transformer

is by-passed by two feeders;

Weeding and storage of

poles still remains a problem

but substation generally

okay.

Page 42: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

42

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Masindi Substation

{2x2.5 MVA 33/11kV

(S/N:68281) & (85.4066)}

Fencing & gates are in good condition;

Yard stones are still good order; Security

guards are available and in control;

Guard house is in good state;

Transformers in good state of

maintenance; Isolators exist on Lira

Main and Hoima 33kV lines close to the

substation; All feeders labelled;2 0f 3

security lights working; Surge arrestors

replaced on 11kV side of Power

transformer No.1;

Need for regular weed control; 11kV

feeders lack isolators on first structures

from the substation; Transformer No.2

operating in a fixed tap (2); No SCADA

functionality at the substation for more

over a year; Capacitor bank set not

operational; Battery bank housed in the

plant house with switch gear; Only

available 1x9kg fire extinguisher had

expired; Guard house still lacks a lighting

source;1 of 3 security light not working; No

substation drawing on site; No tap water

at the substation

Weeding still remains a

problem but station

generally okay.

Kinyara Substation

{1x5MVA 33/11kV

(S/N:19010720/.01)}

Security and fire control measures in

place at the substation;2 security lights

working; Safety improved by cutting of

trees formerly close to Budongo &

Kinyara 11kV feeders; Budongo Line

diverted for the first 2 spans to improve

clearance for bagasse from the sugar

factory; Substation logbook available

at the substation; Guard available

Yard full of grown up weed & without a

stone pitch; No label & No isolator on

Masindi 33kV line; One security light

faulty; No label on Kinyara Sugar Works

11kV feeder; One H-structure formerly for

a metering unit left redundant; Station

supply transformer has links for MV

protection instead of fuses; Silica Gel cap

missing from the transformer; No

substation drawing

Substation yard still

overgrown by weeds.

URGENT Need for stone

pitching and to create

SEPARATE access for the

substation without having to

go through the Kinyara

factory access gate.

Page 43: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

43

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Gulu Substation

{2x5MVA 33/11kV

(S/N:57.234 & 57.232)}

Substation was still in generally good

state of maintenance

Some weak aspects observed March

2015 had not yet been worked on, e.g.

isolators for incoming/outgoing lines

Toilet now okay. Faulty

indications on some

switchgear panels, e.g. Gulu

Hospital, probably due to

faulty transducers – need to

be addressed

Lira Spinning Mill

Substation {1x5MVA

33/11kV

(S/N:942016401/

942016402)}

Substation still in generally good state of

maintenance.

Deficiencies observed in March 2015 are

still pertaining

Work in progress to refurbish

the substation and increase

transformer capacity.

Expected to be completed

by Dec 2015.

Kitgum Substation

{1x1MVA 33/11kV

(S/N:62468)}

Substation still okay after the general

refurbishment.

Issues noted in March 2015 still pertaining,

e.g. Still shows signs of not being regularly

weeded & menace of traders hanging

wares on the substation fence still remains

Substation generally okay.

Rapid growth of vegetation

needs to be addressed.

Bombo Substation

{2x5MVA 33/11kV

(S/N:68275)& (S/N:68272)}

Auxiliary transformer in good state of

maintenance; All Air break switches

locked; Main gate in good condition &

access restricted; Yard stones are still

good order with no grass is growing

therein; Plant house, Guard house &

toilet in good state; Fire extinguisher

available; All apparatus labeled;New

circuit breaker installed for Luwero 11kV

feeder; 2x9kg fire extinguishers

available and serviced

In previous inspection, it was found that:-

No SCADA installation/functionality for

remote visibility; 4 of 4 security lights not

working; transformers operating

independently/not in parallel; Old Cooke

& Ferguson Indoor switchgear &

associated DC supply not in use, though

still intact; Guard house has no light;

Substation fence damaged during

offloading of poles & a big opening exists

on the front corner; Most of the Isolators

are faulty and bi-passed; New 11kV bus

bar H-structures have no stays and

SUBSTATION NOW

UNDERGOING MAJOR

REHABILITATION: New Plant

House; cable trenches; civil

works; fencing & gates

Page 44: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

44

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

already leaning; Poles littered

everywhere in an unorderly manner as

one accesses the substation making it

untidy; access road to the substation

washed away with deep trenches; first

access gate to substation premises

broken

Lumpewe Substation

{1x2.5 MVA

33/11kV(S/N:9920252)}

Yard/gravel in good condition; Fence

new & intact; Tap changer working

properly; All apparatus labeled;DC

Supply in good condition; All security

lights working; Plant house,

guard house & toilet in good state; All

feeders have Air break switches

installed & functional; Security guards

are available and in control; All feeders

have operational circuit breakers

Power transformer requires a coat of

metallic paint to improve its appearance;

SCADA installation/functionality not in

place; No light source in the guard's

house; No tap water at the substation,

fetched from the borehole in trading

centre

The substation is generally in

a good status;

Wabigalo Auto

Substation -Observed

from Outside (1x3MVA

33/33kV)

Substation fence earthed; Yard stones

are adequate and in good condition;

Fence & main access intact and

secured with standard padlock; All

feeders well labelled; Guard

house/container improved by adding

two windows with glasses fixed

(improved ventilation), painting and

roofing; Toilet in good condition.

Nakasongola & Migyera 33kV feeders

sharing the same Circuit Breaker; No line

isolators on all first structures from the

substation; No SCADA functionality;

Security lights(x3) are all faulty; lack of tap

water at the substation

A separate Circuit Breaker

should be provided for

Migyera 33kV feeder; SCADA

should be installed & Line

isolators installed on all

feeders to/from the

substation. Due to its

remoteness from the office,

there is urgent need to install

remote monitoring and

operation functionality in this

auto-transformer substation.

Page 45: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

45

10.1.4 EASTERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mbale Substation

{2x10/14 MVA

33/11kV(S/N:19010873/01

-on soak)&

(S/N:19010719/03)}

Substation still maintained OK as was

observed in March 2015. A new battery

charger in place; but the old one is also

still in operation.

Faulty lights had not yet been fixed from

the last inspection and SCADA

performance was intermittent. Cracks

developing on the guard-house had not

yet been fixed. The transformer

automatic tap changer keeps tripping at

tap 9 leading to failure of the process

frequently.

Faulty lights and the guard-

house need to be fixed. The

tripping of the tap changer

should be cured to mitigated

voltage compliance. The

entire substation land needs

to be fenced off.

Bubulo Substation

{1x5 MVA

33/11kV(S/N:Not

available)}( Very old

Ferranti transformer

relocated from Lira

spinning Mill s/s)

Substation still generally okay. The tap changer is not automated. The remote control of this

substation should be

improved.

Kumi Substation

{1x1 MVA

33/11kV,energo invest

(S/N:68287)}

Substation generally okay. Oil spillage

retention has been improved.

The old cook Ferguson 11Kv switchgear

acting as a bus should be replaced.

SCADA not efficient.

The remote control of this

substation should be

improved. The 11Kv old

switchgear in the plant

house should be replaced.

Soroti Substation

{1x5 MVA 33/11kV JICA

Aichi Transformer;

(S/N:942233602)}

Substation generally okay after

renovation.

SCADA not efficient. The remote control of this

substation should be

improved.

Serere Substation Substation generally okay after No guard, exposing s/s to vandalism; No The remote control of this

Page 46: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

46

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

{1x1MVA 33/11kV Jica

Aichi transformer

renovation and upgrading from 0.5 to

1MVA.

SCADA substation should be

improved,

Especially due to its

remoteness. A guard should

be deployed else CCTV

remote monitoring be

introduced.

Bulangira Substation

{1x5MVA 33/11kV

(S/N:57.230)}

Substation still generally okay The security lights were reported faulty by

the security guards. No operational

SCADA

The remote control of this

substation should be

improved.

Iki-Iki Substation

{1x2.5MVA 33/11kV

(S/N:77122)}

Substation generally okay The security lights were reported faulty by

the security guards. No operational

SCADA

The remote control of this

substation should be

improved

Opuyo Substation-UETCL All the 33KV outgoing feeders are back

indoor. Scada functionality restored.

Sharing the plant house with UETCL.; this

can led to an operational risk.

Isolation challenges on the

33KV bays need to be

addressed for safety reasons.

Tororo Rock Substation

{1x5MVA(S/N:68274),

1x2.5MVA (S/N:68285)

33/11kV}

Substation still maintained well. A new

battery charger in place; but the old

one is also still in operation.

SCADA performance was still

intermittent..

The entire substation land

needs to be fenced off.

Tororo Main Substation-

UETCL

The 33kV Switchgear in good working

condition; All feeders labelled

The decommissioned 33KV indoor

switchgear still in location.

The decommissioned

Jacobson switchgear should

be removed and disposed

of.

Page 47: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

47

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Nagongera Substation

{1x2.5 MVA 33/11kV

(S/N:51750/1)} from Soroti

Substation

Substation still okay. No significant weakness as the restoration

was recently done.

Restored substation still okay

Magamaga Substation

{1x2.5MVA,33/11kV

(S/N:9422335)}

Substation still generally okay. . Observed deficiencies of March 2015 still

pertaining. No provision for security. A

guard house and a toilet are planned for

construction.

There is need for provision of

security personnel at the

substation, improved SHE

management on highlighted

issues.

Jinja Industrial Substation

{1x10/14MVA

(S/N:98.2.4067)&

1x10/14MVA , 33/11kV }

Substation still generally okay. A new

1x10/14MVA, 33/11kV} is being installed.

New battery banks in place. SCADA

operations have substantially improved.

Deficiencies of March 2015 still there .e.g.

Bat infestation in the plant house. Firm

capacity needs to be restored as soon as

possible.

There is need to address the

drainage issue in front of the

substation yard/plant house,

Grain Milling Switching

Station

The containerized ABB switchgear has

no reported anomalies

No significant weaknesses, apart from no

remote controllability. No security

provision.

Appropriate conventional

switchgear should be

introduced.

Njeru Substation

{1x10/14MVA, 33/11KV)

(S/N:ET10046/1)

Substation still in good working

condition & properly maintained

No more Standby transformer in place for

improved supply reliability. 5MVA

transformer (S/N:942233602) formerly on

standby removed

The substation should have a

firm capacity, to ensure

supply reliability; given that it

is supplying an essential load.

Nile Breweries Substation

- 1x10/14MVA 33/11kV }

The 10/14MVA transformer is in good

state of maintenance

No free access by Umeme staff. Free access should be

allowed to Umeme staff to

improve on safety and the

Transformer should be

Page 48: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

48

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

efficiently utilized.

Kaliro Substation-

1x2.5MVA 33/11kV

Substation generally okay. The outdoor

33KV bus and auto-reclosure was

replaced with new indoor Siemens

8DJH36-L GIS switchgear and new MV

cables installed.

Some deficiencies still there, except the

blown part of the roof still temporarily

fixed, on the 11KV side the cable and bus

are still low but barricaded. A flood prone

entry to the substation.

Low lying 11 KV bus bar

should be raised for

operational safety, provision

of a water source for

improved hygiene still

needed. Drainage at

substation entry should be

improved.

Iganga Substation

{1x5MVA

33/11kV(S/N:1901010701)}

Substation generally okay Structures in substation, e.g. for Bugiri

feeder are rotten and required

replacement. SCADA reported to be

partially operational – station can be

monitored but not operated. Existing plant

house where communication equipment

are installed is quite congested. Storm

water control in substation needed. The

alternate access to substation was

blocked by a developer.

Deficiencies should be

addressed and a way should

be found to keep away the

cats which could precipitate

faults on the transformer. The

remote control of this

substation should be

improved

Lugazi Substation –

UETCL,66/11kV{2x10/14M

VA 66/11kV}

11KV Switchgear at substation was

found generally okay

There is a persistent low gas alarm. The

transformer will be overloaded soon.. the

MD is now 21MVA.

Switchgear still remains to be

officially vested to UEDCL

from UETCL so as to be

included on the leased asset

base. There is steady load

growth due to Tembo steel

works.

Page 49: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

49

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kamuli Substation

{1x2.5MVA

33/11kV(S/N:57233)}

Apart from awkwardly placed

guardhouse (behind substation!) the

substation was generally okay. All the

rotten substation structures replaced.

Flooding of substation by mud

overflowing from blocked drainage

along the road still occurs.

Battery banks should be

housed separately,

substation rubber mat

provided for operational

safety of staff & the MV

cable touching the fins

removed to avoid a possible

short circuit.

Drainage needs serious

improvement.

Kayunga Substation

{1x5MVA 33/11kV

(S/N:942233601)}

Substation generally okay. Vegetation

well controlled and good security in

place.

SCADA performance was still intermittent. Station well maintained.

Page 50: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

50

10.2 DISTRIBUTION LINES

10.2.1 CENTRAL

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kitante s/s – Motor Mart

11kV Interconnector

Interconnector switched off due to

damaged underground MV cable

around Kitgum House

The damaged cable needs

maintenance to restore the

integrity of the interconnector

Kitante s/s – Dewinton

Road 11kV feeder

Umeme team found on site carrying out

the repairs

Underground MV feeder cable found

damaged at Centenary Park by a

tractor doing excavation

Cable reportedly damaged

around the same place more

than once

Kitante s/s – Lugogo 2

11kV feeder

The feeder is not in use The feeder should be put to

use

Kampala North s/s –

Kololo 11kV feeder

Poles and conductors largely in good

condition

VM required. Vertical Section structure

with eroded foundation due to run off

water, support wires inclusive & likely to

fall exists in Kamwokya just above

Tufnell Drive opposite a makeshift

canteen

VM required on most parts of

the feeder

Waligo s/s - Ugachick

11kV feeder

The rest of the line is in good state of

maintenance

Surge arrestors on the feeder cable not

connected, possibly faulty. First

structure across the road not labelled

The faulty cables should be

replaced & first structure

labelled

Page 51: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

51

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kampala North s/s –

Nakulabye 11kV feeder

Most poles are in good condition Terminal transformer at Kawaala, Good

Shepherd P/S has three (3) surge

arrestors not connected/faulty hence

no MV protection against over voltage.

Structures around Nakulabye round

about leaning towards the road

The feeder is largely in good

condition

Mutundwe s/s – Budo

11kV feeder

Entire feeder refurbished by replacing all

rotten poles, MV conductors, putting ABC

conductors on LV and introducing

prepayment system

Mutundwe Hill Police post transformer

had two(x2) surge arrestors not

connected & transformer leaking oil

The entire feeder is in a

satisfactory state; improved

maintenance of the

apparatus recommended

Mutundwe s/s – Kabusu

11kV feeder

All rotten poles replaced & MV

conductor is largely 100sqmm SCA

Some portions still have 50sqmm SCA

hence non uniformity of the conductor

size. Naiga road t-off at Rubaga road

roundabout has 25sqmm conductor;

Poorly done MV line diversion at TAL

Cottages compound/gardens & in

need of re-design/modifications

The feeder is in good

condition except that portions

with 50sqmm should be

upgraded to 100sqmm SCA

conductors

Mutundwe s/s – Natete

11kV feeder

Entire feeder refurbished by replacing all

rotten poles, MV conductors, putting ABC

conductors on LV and introducing

prepayment system

The entire feeder is in a

satisfactory state

Page 52: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

52

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mutundwe s/s –

Bunamwaya 11kV

feeder

Some rotten poles replaced in certain

areas during system improvement of

some transformer zones. System

improvement carried out in Mutundwe

Village No.3 (Ngobe Village) by injection

of a 200kVA/11kV transformer-Handled

by KSHydro – Umeme Contractor

Some poles require replacement;

Nyanama t-off has steel

conductors;Kitebi H/C(town) t-off of

about 1km has 25sqmm SCA

conductor;Ngobe t-off to Jomayi

estate has 25sqmm conductor & with a

big load; Workmanship for system

improvement scheme in Ngobe Village

poor with a leaning transformer

structure(newly constructed),poor

wiring on LV,old poles not

decommissioned, poor conductors on

LV circuits worked on & with

many(poor) joints; poles not dressed on

LV where combined construction is

involved, low sagging LV conductors &

at worst leaking transformer despite

being new. Injected Kina

Kwekulakulanya 200kVA transformer

had three(x3) surge arrestors not

connected; Old Kina Kwekulakulanya

transformer had no surge arrestors at

all.

Poor parts of the network

should be scoped so that

intervention measures are put

in place; need for improved

prudent utility practices like

installation of surge arrestors

on transformers for over

voltage protection among

others

Mutundwe s/s –

Nakawuka 11kV feeder

Entire feeder refurbished by replacing all

rotten poles, MV conductors, putting ABC

conductors on LV and introducing

prepayment system

Kikajjo T/C 200kVA/11kV transformer

had all the three(x3) surge arrestors

disconnected, implying no over

voltage protection. Transformer wiring

was also burnt with Circuit Breakers by-

passed

Whereas the feeder was

refurbished, there is need to

adhere to prudent utility

practices while operating the

apparatus

Page 53: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

53

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mutundwe s/s – Mityana

33kV feeder

All rotten poles changed; load break

switches installed

MV conductors sagging low across the

Entebbe Express Highway(road

crossing) under construction between

Mityana road & Masanafu

Underground MV cable would

be better for improved safety

of the road users

Queensway s/s – Katwe

2 11kV feeder

The entire feeder generally has poor

conductors, yet serves commercial and

heavily congested areas like Kibuye.

Open point at Total Fuel Station had

jumpers instead of an isolator

Need for upgrading of the

conductors for improved

safety & reduced technical

losses on the feeder

Kampala North s/s –

Down Town 11kV feeder

VM required along Aki Bua road(for

example U/G Cable T-off for a

630MVA/11kV ground mounted

transformer near South African High

Commission residence where

Vegetation is covering up to LV & MV

conductors

The feeder heavily loaded

and frequently goes off,

offering unreliable supply

around Nakasero road

Gaba s/s – Kansanga

11kV feeder

All t-offs have steel/poor conductors

such as Gaba landing site, Tank hill

among others

Poor steel conductors on the t-

offs need upgrading to a

better conductor size

Kampala South s/s –

Kigo Road 11kV feeder

Refurbished by replacement of all rotten

poles and changing the conductor to

100sqmm SCA

Page 54: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

54

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kampala South s/s –

Najjanankumbi 11kV

feeder

Poles and conductors in a good

condition

Line in a satisfactory state of

maintenance

Kampala South s/s –

Salaama Road 11kV

feeder

Poles and conductors in a good

condition

Line in a satisfactory state of

maintenance

Kampala South s/s –

Kabowa 11kV feeder

Poles and conductors in a good

condition

Entire feeder gets its supply from

Mutundwe substation, open point at

the cable bracket structure

Line in a satisfactory state of

maintenance

Lubowas s/s – Kigo 11kV

feeder

Line in good condition Line in a satisfactory state

Lubowas s/s –

Bunamwaya 11kV

feeder

Line in good condition Line in a satisfactory state

Lubowa s/s – Ndejje

11kV feeder

Line in good condition Line in a satisfactory state

Lubowa s/s – Roofings

33kV feeder

Line new, short and in sound condition Line in satisfactory condition

Page 55: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

55

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kajjansi s/s – Nakigalala

11kV feeder

Poles in good condition Line has muliti-jointed steel conductor

that is worn out

Need to upgrade the

conductor to at least 50sqmm

Kajjansi s/s – Lubowa

11kV feeder

Line in good condition Line in a satisfactory state

Mukono s/s – Mbalala

Industrial 33kV feeder

Line in a satisfactory condition Line in a satisfactory condition

Mukono s/s - Nakifuma

33kV feeder

The conductor on the main line

satisfactory(100sqmm)

Most MV structures rotten (approx.70%),

with some leaning

Line requires major

refurbishment works

Mukono s/s – Seeta

11kV feeder

Replacement of rotten poles and worn

out conductors ongoing including T-offs

Most poles rotten with worn-out and

mixed conductors;T-offs poor, not fused

thus affecting the reliability of the main

line

The line under refurbishment

Mukono s/s – Mpoma

11kV feeder

A few poles replaced by the district

under the O&M

Most poles rotten (about 70%), no

isolation point on the entire line and

with a mixture of conductor sizes

(25,50sqmm& copper)

The line needs total

revamping

Page 56: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

56

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mukono s/s – Katosi 11kv

feeder

Line in satisfactory state; Katosi landing

site LV network converted to ABC from

bare conductor

T-offs poor with multi-jointed

steel/25sqmm conductors, not fused

thus affecting the reliability of the main

line; newly replaced MV pole without x-

arm struts and leaning at

Ntenjeru(8.5km to Katosi landing

site);11/19788/315kVA transformer

along Albert Cook road had

unconnected surge arrestor on red

phase

Line in satisfactory state.

Maintenance of transformer

installations requires

improvement

Namanve s/s – Mukono

1 33kV feeder

Poles and conductors in a good state Underground Cables (150sqmm) right

from the gantries faulty with too many

multiple joints

Replacement/up rating of the

cable required

Namanve s/s – Mukono

2 33kV feeder

Poles and conductors in a good state Underground Cables (150sqmm) right

from the gantries faulty with too many

multiple joints.

Replacement/up rating of the

cable required

Page 57: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

57

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Nakifuma s/s – Ntenjeru

11kV feeder

The line is fairly okay with a few rotten

poles replaced by O&M teams

Some badly rotten poles exist(such as

one at 200M Black Spot Warning Sign at

Nagalama near Martins SS,eaten up by

termites)

The identified rotten poles

should be scoped to have

them replaced with

installation of sufficient

isolation points along the line

Kireka s/s - Lugogo 1

33kV Incomer

Line in a satisfactory condition Line in a satisfactory condition

Kireka s/s – Lugogo 2

33kV Interconnector

Line in a satisfactory condition

Line in a satisfactory condition

Kireka s/s – Port bell

33kV feeder

Line in a relatively good condition except

the second structure

Encroachment on the line corridor at

the second structure exists with stay

supports enclosed in ones wall fence;

unsafe for public settlement too

Need to restore the way

leaves integrity of the line

corridor

Kireka s/s – Namugongo

11kV feeder

Line in a relatively good condition except

the first structure

Encroachment on the line corridor exists

with the first structure built into; unsafe

for public settlement too

Need to restore the way

leaves integrity of the line

corridor

Kireka s/s – Port bell

11kV feeder

Line in good condition after

refurbishment works

Line in good condition

Page 58: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

58

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kireka s/s – Kyambogo

11kV feeder

Line has most of the poles rotten with

some attacked by termites; Some parts

of the feeder have poor

conductors(steel) such as Banda area;

earth wire on first structure damaged;

First H-structure from the substation very

rotten; Feeder label poorly fixed on to

the structure; Encroachment on the line

corridor at the second structure exists

with stay supports enclosed in ones wall

fence; unsafe for public settlement

too;500kVA/11kV ground mounted

transformer below Nanziri stressed &

leaking oil; Vegetation on the network

around Kyambogo University(above

the Mosque,Kyambogo College &

former polytechnic side); 2 surge

arrestors un terminated on MV cable

feeding 11/13030/315kVA ground

mounted polytechnic Tx with burnt

cable terminations on both LV & MV;

No surge arrestors installed on

11/8124/315kVA Transformer at

Department of Agriculture, Kyambogo

University

Issues raised require attention,

given the fact that the feeder

serves the Kyambogo

University among others

Kireka s/s – Mandela

11kV feeder

(Underground)

Line in a satisfactory condition Circuit breaker for this feeder is faulty The circuit breaker operational

status should be re-established

rather than relying on the RMU

Ntinda s/s – Kampala

North 33kV Incomer

Line in a satisfactory condition; Faulty air

break switch replaced & motorized

First span going over the school

compound, thus unsafe for the school

Line in satisfactory condition.

Page 59: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

59

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Ntinda s/s – Bukoto 11kV

feeder

Line in a satisfactory condition

Line in a satisfactory condition

Ntinda s/s – Kyambogo

11kV feeder

The line is in a fair state

Some poles rotten such as the first one

from the substation

Rotten poles should be

identified and replaced

Ntinda s/s – Waligo 33kV

Line

Line in a satisfactory condition, Faulty air

break switch replaced & motorized

Line in a satisfactory condition

Ntinda s/s – Kisasi 11kV

feeder

Line in a satisfactory condition

Line in a satisfactory condition.

Ntinda s/s – Kiwatule

11kV feeder

Line in a satisfactory condition Feeder cable terminated directly onto

the bus bar rather than through the

circuit breaker

Line in a satisfactory condition

LV network in Naguru

Entire LV network poor with rotten,

leaning poles and worn out

conductors; Vegetation growing into

the network

Complete overhaul of the LV

network necessary

Port bell s/s – Gaba

33kV Line

Line in a relatively stable condition Lugogo-Kireka-Portbell-Gaba 33kV ring

reportedly has capacity constraints,

especially Portbell-Gaba leg that seems

to have a high resistance path thus

hindering load balancing on the ring

Operational issues should be

addressed to ensure an

alternative source of supply to

the substation in the event of

Kireka 33kV feeder being off

Page 60: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

60

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Port bell s/s – Kitintale

11kV feeder

Line in a satisfactory condition

Air Break Switch at Total ,Luzira T/C still

locally operated

Line in a satisfactory state but

automation of the ABSs

essential

Port bell s/s – Butabika

11kV feeder

Most structures in good condition

MV conductor is a mixture of 25 &

50sqmm with several

joints;11/18608/100kVA transformer at

Red Chilli Restaurant-Butabika installed

without all the surge arrestors

Re-conductoring with a

uniform conductor size

necessary

Port bell s/s – Breweries

11kV feeder

Line in a satisfactory condition

Line in a satisfactory condition

Port bell s/s – Kireka

11kV feeder

Line largely in a satisfactory condition First ABS structure(current open point)

rotten requiring replacement

First ABS structure should be

replaced; feeder currently

used for training purposes

Page 61: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

61

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Entebbe s/s – Botanical

11kV feeder

Most poles in good condition Poor cable/jumper terminations exist at

most points along the line, with most

cable sections having

unconnected/faulty surge arrestors for

example Aero Beach off Circular road,

Kigungu and across the runway; Broken

concrete MV structure still exists

opposite Ministry of Agriculture Sign Post

along Botanical road; Some

transformers not protected on HT such

as at Tx No.413434 at Vet Offices

enroute Kigunga

Poor structures should be

identified & immediately

improved; A tie line should be

provided between Botanical

& Airport 11kV feeders to offer

an alternative supply to the

Airport

Entebbe s/s – Kisubi

11kV feeder

Line recently refurbished Line in satisfactory condition

Entebbe s/s – Entebbe

Airport 11kV feeder

Most poles are rotten requiring

replacement, conductor requires

upgrading; Only source of supply to the

airport

Plans under way to have all

rotten poles replaced and

conductor upgraded; Another

standby line would be

necessary given the sensitivity

of the airport

Entebbe s/s – State

house 11kV feeder

Line in a satisfactory condition Vegetation noticed on some LV poles

at the rear entrance of State house

towards Airport flats

Line in a satisfactory condition

Page 62: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

62

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Entebbe s/s – Entebbe

Township 11kV feeder

Line recently refurbished and in

satisfactory condition

Airport flats 200kVA/11kV transformer

requires improved protection on

LV(Red phase had no fuse, burnt wiring,

loose binding used instead)

Line in good condition,

improvement on transformer

maintenance practices

inevitable

Kisubi s/s – Kisubi Mission

11kV feeder

Line in a satisfactory condition Line in a satisfactory condition

Kisubi s/s - Sisa 11kV

feeder

Line refurbishment completed by

replacing of rotten poles & re-

conductoring to 100sqmm SCA

Line in good condition

Namungona s/s –

Masanafu 11kV feeder

Largely in a fair condition Some t-offs have worn out and mixed

conductors-25&50sqmm(such as t-offs

from Lugala t/c to Masanafu & Busega

areas)

Poor t-offs should be re-

conductored with a better

conductor size to minimize

technical losses

Namungona s/s –

Nansana 11kV feeder

T-Offs rehabilitated Rotten poles & worn-out conductors on

the t-offs; newly extended line to a

50kVA/11kV transformer at Kigoma TC

with leaning poles, lacks drop-out fuse

isolator & circuit breaker enclosures

Snags on Kigoma TC scheme

should be corrected

Page 63: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

63

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Namungona s/s –

Nakulabye 11kV feeder

Most parts of the MV line in a fair state Some leaning structures still evident in

Nakulabye T/C; Conductor is a mixture

of 25&50sqmm SCA;Transformer at

Nakulabye round about is almost in the

road & can easily be knocked

Re-conductoring required on

the affected parts of the line.

The leaning structures require

redesign due to limited space

Kawanda s/s – Kakiri

11kV feeder

Most parts of the main line in a good

condition

Mixed & worn-out conductor of 25, 50&

100sqmm size; Rotten poles especially

on the t-offs; Not operated remotely

Refurbishment of the poor t-

offs & their fusing should be

carried out;SCADA

functionality should be

restored

Kawanda s/s –

Namulonge 11kV feeder

Namalele,Namavundu & Nakasajja t-

offs have rotten poles & worn-out

conductors

Namalele,Namavundu &

Nakasajja t-offs should be

rehabilitated with a suggestion

to introduce ABC conductors

on the LV network

Kawanda s/s – Bombo

Industrial Park 33kV Line

Line extends to Semuto and Kapeeka

areas

Wrong pilot spindles initially used were

all being replaced by the contractor-

Cablesult

New line under construction to

provide supply to Bombo

Industrial Park

10.2.2 WESTERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Page 64: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

64

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kassanda 33kV feeder

from Mityana s/s

Refurbishment works expected to

commence on 24/11/2015 to have all

the rotten poles replaced and

conductor upgraded to 100sqmm sca

on main line and 50sqmm on t-offs-

Cluster Umeme contractor to handle;

Line strength stands at about 70% due

to weakened & aged MV poles; line

conductor poor.

Line extension by REA Scheme

by about 55km with 24

transformers(as a t-off) to

Lusarira & Banda areas

expected to be commissioned

Mityana Town 11kV

feeder from Mityana s/s

All poles & hardware on first 5km in good

condition after replacement as part of

the REA scheme to extend power to

Lusarira &Banda areas

Majority of the MV and LV poles along

this feeder are rotten. The MV

conductors have numerous joints

(25sqmm/stranded), and very old

wooden cross arms along Katakala

spur.

Major refurbishment required

despite replacement of some

poles by the district teams

Mityana s/s - Kiriri 33kV

Interconnector

The line is very old with multiple rotten

poles, bent cross-arms and poor

conductors

Line is in a sorry state just like it

was in Q1,2 & 3 of 2015

Mubende - Kakumiro

33kV feeder

Line relatively okay after recent pole

replacements

Conductor poor with multiple joints in

some portions of the line;

Same status as in Q1,2 & 3 of

2015

Kaweri Coffee

Plantation 33kV Line

T-off in good condition with all the

rotten poles replaced & conductor

changed to 50sqmm ACSR

T-Off in good condition

Nkonge s/s - Mubende

33kV feeder

All poles in good condition; 100sqmm

ACSR exists between Mubende

substation and Kubiri Trading Centre

Lusarira air break switch faulty &

bypassed; no operational line circuit

breaker at Mubende substation; Kubiri

T/C to Nkonge substation network

though with 150sqmm conductor, has

multiple damages; Lack of

operational& sufficient number of

At least 3 functioning Isolators

required at Kakonyoga T-Off,

Kasambya & Lusarira

Page 65: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

65

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

isolators

Mubende 11kV Town

feeder from Mubende

s/s

Most poles are in good condition;

Kisindizi water pump transformer zone

submitted as part of major works; LV

network in Mubende town had been

proposed for second quarter 2015

inclusive of prepayment & refurbishment;

40% of the distribution transformers that

neither had no drop-out fuse nor Lucy

cut-outs/CBs or bypassed have been

handled;

Circuit Breaker charging system for this

feeder not working and draining the

battery; Power transformer Circuit

breaker used instead to operate the

line, thus doubling as line and

transformer protection; A number of LV

poles in Mubende town are rotten

Same status as in Q1,2 & 3; LV

network requires major works

Kiriri substation –

Kabulasoke 11kV feeder

Line in good condition after recent

refurbishment by replacing all rotten

poles and upgrading the conductors to

50sqmm ACSR

Line in good condition

Fort portal 11kV Town

feeder from Fort portal

s/s

The feeder in good condition including t-

off from Shell up to Holy cross Noviate

through Mt of the Moon University,t-off to

Bundibugyo road up to Kichwamba

Technical Institute; MV line has a good

conductor 100sqmm SCA from the

substation to Mpanga market

Some parts of the line are poor such as

Kagoote areas,St Lious t-off(rotten

poles,25sqmm/steel, wooden x-

arms),Bwamba road(25sqmm/multi-

jointed conductors),Kamwenge

road(25sqmm/steel conductor &

wooden x-arms),leaning x-arms along

the t-off just before Karago

market(Legal Aid offices signpost),use

of 1 x-arm strut on some poles along

Same situation as in Q1,2 & 3

of 2015; replacement of some

rotten structures by District

teams continue; conductor

upgrade in the town centre

required since its largely a

mixture of 25&50sqmm SCA so

as to facilitate reduction in

technical losses & improved

quality of supply

Page 66: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

66

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Bundibugyo road(Karago&Katebe

T/Cs,directly connected Katebe t-off,

broken 3ph LV pole at F/portal church

of Christ & no Lucy cut-outs on one

circuit of Western Youth Centre terminal

100kVA/11kV Tx past Lisieux guest

centre,Booma. Fuses just fixed onto the

transformer wiring lugs

Kijura 33kV feeder from

Fortpotal s/s

Poles and 50sqmm SCA conductor in

good condition

A few post insulators bent due to weak

fabricated x-arms; T-off at Ibonde has

the first two structures with 1 cross-arm

each thus compromising the structural

stability of the line

Same state as in previous Q1,2

& 3 of 2015 inspections; Line in

good condition though

changing the conductor to

100sqmm may be considered

due to forecasted load

growth from tea factories

Mabale 11kV feeder

from Rugombe s/s

Some of worst structures replaced Very old line with multiple rotten poles;

leaning x-arm around Mukunyu T/C.VM

requires constant attention around

Mpanga National Park

Same status as in previous

Q1,2 & 3 of 2015;urgent

intervention required to have

the line worked on

Mwenge 11kV feeder

from Rugombe

substation

Line in good condition all the way to

Kyarushozi and Kirinda hospital areas

In good condition as before

Mpanga 11kV feeder

from Fortpotal s/s

A number of poles replaced by district

teams

Very old line with multiple rotten poles;

T-off to Kiko along Kamwenge road

equally old with rotten poles; No caps

on boundary structure poles(boundary

between Mabale & Mwenge 11kV

feeders); jumpers rather than an isolator

at this point

Q1,2 & 3 of 2015 status still

prevails

Page 67: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

67

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Nkenda 33kV feeder at

Fortpotal s/s

Line in good condition after its

rehabilitation some years back

Two T-offs serving individual transformers

isolated without transformers on the

structures after they faulted at Rwenzori

Mining Plant & Mubuku areas; Musunga

T-off at Gweri has worn-out conductors

yet it is not fused(first termination) off

the main line, likely to cause feeder

faults; need for replacement of

shattered disc insulators; need for

replacement of bypassed ABS’s.

Musunga t-off is still not fused.

Drop-out fuse isolators should

be installed at t-off to King

Oyo

Rugombe 33kV feeder

from Fortpotal s/s

Substantial number of poles are rotten

with several section structures broken

and leaning

Same status as in Q1,2 3 of

2015 prevailing

Hima -1 & Hima -2 33kV

feeders from Nkenda s/s

In good condition Hima -2 has relatively small size poles,

hence facing the challenge of

withstanding strong winds; Long bolts

used with post insulators, hence the

challenge of withstanding the heavy

conductors

A number of poles require

replacement & considering

the strategic nature of these

feeders, serious consideration

to convert the structures to

steel is required

Kasese 11kV Town

feeder from Kasese s/s

Line still in good condition with most

rotten MV & LV poles replaced

LV conductors not upgraded; Some of

the stressed transformers include

Nyakasanga,Kamaiba & Oil installation

LV re-conductoring required

Kasese 33kV feeder from

Nkenda s/s

Most of the structures in good condition Multi-jointed and worn-out 25sqmm

ACSR conductors exist

Previous inspection findings still

relevant

Kabale 33kV feeder from

Nkenda s/s

Line partly in good condition with sound

MV poles between Nkenda and

Katunguru bridge including T-off to

Network from Katunguru bridge to

Ishaka S/S has many rotten poles,

especially in the National Park, worn-out

Same status in Q1, 2 & 3 of

2015 still existing; Some

sections of the line in the

Page 68: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

68

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Katwe/Mweya Safari Lodge; Capacitor

bank at Kyamuhunga operational

knife blade links at Kyamuhunga Tech

Institute T-off; Some transformer

networks stressed such as

Nyakasharu,Bururuma and Ndekye

national Park leaning badly

and need wind stays; Despite

surveying and marking the

poles for replacement a while

ago, no further action has

been taken

Ishaka - Kagamba –

Kashenyi-Rukungiri 33kV

Line

Ishaka – Kagamba 33kV portion has

newly replaced poles and 100sqmm

SCA conductor installed; New capacitor

bank installed at Kanyamabona;

Kashenyi T-Off has most of the MV

structures rotten standing at about 60%

( Poles rotten, wooden x-arms

burnt/hanging/completely missing such

as at Omukarambiro TC, Kyeibare

swamp,kashenyi

market,nyamushebeya village along

mitooma-Kabira road ),nyarubira

hill,buharambo,nyakatete parish; all air

break switches faulty at

Rwamabondo,Kimwanyi & Nyakibare);

Previously isolated & abandoned

capacitor bank at Kashenyi T/C

decommissioned & recovered; A

substantial number of T-offs not

protected; wrongly specified pilot

spindles used during refurbishment

works leading to leakages & burning of

poles since the jumpers are too close to

the poles causing voltage flashover;

Kashenyi T/C Tx found recovered;

Kashenyi T-off H-structure has worn-out

drop-out fuse isolators & found isolated

due to a fault; incomplete replacement

of poles at Nyakateete; Leaning H-

Feeder performance worse

after partial refurbishment due

to dominance of shattered pin

insulators. The quality of

insulators used are suspected

to have been of poor quality

besides non replacement of

others that could have been

worn out; Quality of Kashenyi

Kashenyi T-Off found isolated

with a permanent through

fault that tripped the

substation & circuit breaker

back at Mbarara North,

eventually burning the trip coil

in the process; The entire line is

not protected & introduction

of some load break switches

would improve its reliability;

Kashenyi T-Off is in a very sorry

Page 69: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

69

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

structure at Bitoma Voc S.S state & should be refurbished;

faulty ABS’s replaced & more

installed at convenient

locations

Mbarara North -

Bushenyi 33kV Line

All rotten poles replaced from Mbarara

North S/S to Ishaka S/S; Vegetation

management satisfactory

Some pin insulators worn out/shattered

and re-used during refurbishment,

causing frequent faults on the line due

to leakages; Isolators/load break

switches required at convenient

locations on the line for improved

flexibility and protection; Line Isolators

worn-out/by-passed on the

incoming/outgoing 33kV lines to Ishaka

substation; Some t-offs directly

connected

Line diverted at Mbarara

University due to 220/132kV

UETCL substation works;

Air break switches/Load break

switches required at

convenient locations;

Ishaka 11kV town feeder

from Ishaka s/s

A few poles replaced by the district

teams

Most MV & LV poles are rotten, worn-

out/mixed conductors (25/50sqmm)

resulting in numerous breakdowns

during rainy seasons. MV poles along

Mashonga Tea factory spur have been

infested with bees; MV H-structure past

Kyamuhunga found re-inforced with

metal bars to increase its

height;Kibutamo(from rwentuha),

bugongi(from nyamufumura) t-offs

have rotten poles; Bweranyangi Girls' &

Nyakabirizi T-off have steel conductors

Q1, 2 & 3 of 2015 status still

existing; The line in dire need

of rehabilitation. The tea

estate t-off just after the

substation could be turned

into a second feeder

considering the load,

protection & area of

coverage

Kisoro - Kyanika 33kV line Insignificant number of poles replaced;2

schemes expected for system

Metering Unit & four ABS H-Pole

structures at Kyanika border on the

Same status as in Q1,2 & 3 of

2015; Entire line (about 35km)

Page 70: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

70

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

improvement verge of collapsing, Rutare(Chai S/C)

poles,Kyakabande T/C(Mutolere

Junction) poles,Kamonyi ABS &

Transformer structures along Mutolere

road badly rotten; Nulec CB at Kyanika

locally operated

needs urgent rehabilitation

LV network in Kisoro area A significant number of LV poles

replaced in Kisoro town

Entire LV network outside Kisoro town in

a very poor state with badly rotten

poles such as around Kisoro Youth

Development Association & Uganda

Prisons Kisoro opposite Army Barracks

Same status as in Q1,2 & 3 of

2015 prevails

Mbarara North - Kabale

33kV Line

Mbarara-Ntungamo portion in good

condition with sound poles & better

conductor 200sqmm SCA-characterised

by a number of MV extensions;

Ntungamo-Kagamba portion worked on

with all rotten poles replaced;

Ntungamo-Kabale portion under

refurbishment by replacement of rotten

poles & 100sqmm SCA conductor on

poor portions-snags pending clearance;

Formerly isolated surge arrestors on

Rwahi transformer noted replaced

Capacitor bank at Kirigime AIC got

burnt-isolated from supply; Poor sags

across the swamp at Nyabiteme; worn

out drop-out fuse isolators(Yellow

phase) on Karegyeya MTN T-off-found

burning with serious flames; Nulec auto

reclosure on Rubaya T-off at Katuna

border faulty/by-passed; Several Air

break switches & knife blade links at

Buteraniro and Ntungamo not

functional, insufficient too

A number of functional Air

break/load break switches

necessary to improve its

reliability; all the t-offs should

be fused

Rukungiri - Kanungu

33kV feeder

Well maintained structures at

Nyakagyeme boundary with ferdsult

network; Line still relatively new with little

operational problems

Six(6) structures rotten; Isolator

necessary at the previous Metering Unit

structure at Rukungiri substation; nulec

circuit breaker next to the substation

illegally operated by non-staff &

requires relocation for operational

safety; faulty surge arrestors & broken

Same status as in Q1, 2 & 3 of

2015;

Page 71: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

71

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

earth wire exist on this same breaker;

Redundant metering unit on second

structure from the substation;

Kinyasanao Girls S.S transformer with

broken MV stay wire-hanging & likely to

short with LV

conductors;33/16204/100kVA

transformer on Omukatoma t-off missing

circuit breakers on one of the circuits,

surge arrestor on yellow shattered &

abnormally hissing; very low sagging

ABC conductor across the road;

Leaning terminal MV H-structure at

Rushasha T/C due to vandalism of one

of the stays

Rukungiri - Kagogo 11kV

feeder

The line is short with most MV poles in

good condition

MV conductor poor 25sqmm;Shell

Rukungiri ABS faulty; MV required on

some portions of the network; Cable

section(about 250m) between Shell &

Sena supermarket difficult to maintain

due to developments along the cable

route.

Same status as in Q1,2 & 3 of

2015 exists; Overhead MV line

could be constructed along

the existing LV route to avoid

the cable that is hard to

maintain in event of a fault

Rukungiri LV network A few of the poles replaced by the

district teams

Majority of the LV poles in Rwashaimire,

Rukungiri town, Kebisoni, Nyamunuka

and surroundings are rotten

Q1,2 & 3 of 2015 status still

exists; LV system improvement

required in the areas

mentioned

Page 72: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

72

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kabale s/s - Kabale

Town 11kV feeder

A few of the poles replaced by the

district teams; Extension of HV & injection

of three transformer done in Bugongi

and Nyakibugwe;1 scheme expected in

Kaharo-Kabale;

Substantial number of MV & LV poles

are rotten due to old age with the

conductor size small for the growing

load. T-off to Butobere has rotten poles,

worn-out/jointed conductors & Air

break switch by-passed; Line extended

by a REA scheme for a reasonable

distance despite its poor state;

Rugarama leg has steel conductors and

LV network in a bad shape

On-going road construction

works affecting the integrity of

the line, causing relocations

Mbarara Central -

Kakoba 11kV feeder

Line in satisfactory condition after recent

replacement of most rotten MV poles,

reconductoring of the main line to

100sqmm, t-offs to 50sqmm & installation

of 3 ABS’s; Kizungu, Kisenyi and

Rwebikoona areas improved with

introduction of ABC

Main line runs too close to the road

between BOU and 2 Miles and

occasionally the poles continue to be

knocked down by speeding vehicles;

Alliance T-off has poor and leaning

structures with transformer structures(x2)

very rotten. Terminal 50kVA/11kV

transformer at Alliance T/C had a

broken MV jumper on Blue Phase

Alliance t-off should be

rehabilitated to the same

status as the rest of the line

Mbarara Central s/s -

Ntare 11kV feeder

Very few poles replaced due to system

breakdown.

Entire line of R/L 15.8km characterised

by rotten MV/LV poles(over 70%),multi-

jointed conductor of steel & 25sqmm;All

isolators faulty & by-passed; Multiple

incidences of broken MV conductors

common making the line unreliable &

unsafe (e.g. MV conductor broke on

the 11/09/2015 night at University Inn

rendering the entire line off supply for

over 12hours)

Q1,2 & 3 of 2015 status still

exists; Entire line requires

refurbishment by replacement

of rotten poles, upgrading the

conductor to at least

100sqmm,installation of

sufficient number of isolators &

creating a Tie-Line with

Kakoba 11kv feeder between

Andrews Inn & Tuwereza

Bakery t-off to provide an

Page 73: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

73

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Feeder conductors are a mixture of

25sqmm SCA and steel; Over 70% of MV

& LV poles rotten & infested with bees;

All isolators faulty

alternative route for improved

supply reliability in the town

centre

Mbarara Central s/s -

Karamurani 11kV feeder

Very few poles replaced due to system

breakdown; MV extension & installation

of a transformer privately executed at

Creameries though not yet

commissioned

Over 60% of MV poles are rotten with

some infested with bees; worn-out and

multi-jointed conductors(steel) on Mwizi

t-off

Q1, 2 & 3 of 2015 inspection

status still stands. Complete

rehabilitation required

Mbarara Central s/s –

Ishaka 11kV feeder

Very few poles replaced due to system

breakdown

VM required where the line passes

through the forests; Only one ABS

functional/insufficient; Insulators worn

out; Line poorly maintained, standing at

about 70% rotten; Some of the wooden

X-arms on Ryakasinga T-off are broken

with conductors worn-out; Most

transformer structures are rotten;

Kabwohe Tree Shade 200kVA/11kV

Transformer zone stressed with single

phase lines covering over 2km to areas

of Nyabishera where low voltage supply

is experienced;

Kabwohe Tree Shade 200kVA/11kV

Transformer zone stressed with single

phase lines covering over 2km to areas

of Nyabishera where low voltage supply

is experienced

Line diversion done at

Mbarara University to pave

way for the 220/132kV UETCL

S/S under construction.11kV

Metering Unit & ABS to be

relocated & sections of

underground

cables(185sqmm,Cu)

introduced

Otherwise Q1,2 &3 of 2015

status still remains with an

additional risk of affecting the

interconnector where same

structures are shared along

Mbarara- Kasese road

Page 74: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

74

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Line requires complete

refurbishment to improve its

reliability by replacement of

rotten poles, upgrading the

conductor to at least

100sqmm SCA & installation of

sufficient number of

isolators/LBS’s

Mbarara Central s/s -

Masaka West 33kV Line

All poles on the main line and major t-

offs(Rushere/Rwakitura,Mateete,

Mbirizi,Sembabule)

Rushere-Rwakitura t-off (15km) has a

poor conductor (steel) that breaks

down so often, creating outages to His

Excellence the President’s home;

Portion at 71km mark between

Kyazanga and Lyantonde(opposite pile

plantation) has worn out & multi-jointed

conductors that require replacement;

First H-structure at Mbarara central

substation though newly replaced

during feeder refurbishment has old

poles not decommissioned; Dropout

fuse isolators at Mbirizi not sufficient for

Matete-Sembalule t-off-a circuit

breaker preferred in light of the

extended network to UEDCL territory in

Lwemiyaga

Same status as in Q1,2 & 3 of

2015 still remains;

Rushere-Rwakitura portion of

about 15km requires a better

conductor;

Masaka West -Mbirizi-Matete-

Sembabule line reportedly

unreliable despite the recent

replacement of poles. As a

result an alternative feed from

Nkonge 33kV line is currently

used to supply the UEDCL

territory in Lwemiyaga and

Kazo, with the ABS(Open

point) at Sembabule open

Page 75: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

75

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mbarara Central s/s -

Kikagati 33kV feeder

The feeder is quite strong;3 system

improvement schemes handled in

Nyamitanga areas

Line tremendously extended courtesy of

REA schemes, linked with Rakai 33kV

line from Masaka & Kabale 33kV line at

Ntungamo; These extensions are likely

to affect its reliability

Still in good condition

Mbarara Central -

Mbarara North 1 33kV &

Mbarara Central -

Mbarara North 2 33kV

interconnectors

The two interconnectors are in good

status

A few poles are rotten on the two

interconnectors; T-off with a 5MVA

33/11kV substation at Nile Breweries

Mbarara plant constructed & tapped

from Mbarara North-Mbarara Central 2

33kV interconnector, compromising its

primary objective; No functional Isolator

at the connection point rather than the

drop-out fuses, now bypassed because

they could not support the load;VM

required along the interconnectors &

Nile Breweries t-off

Still largely OK; Few rotten

poles on the interconnector

should be replaced before the

situation worsens; An isolator

should be installed at the t-off

to Nile Breweries plant

Mbarara North - Ibanda

33kV feeder

Line in good condition up to Ibanda with

two t-offs serving UEDCL territories at

Igorora and Nyabuhikye; Vegetation

well maintained;1 system improvement

handled in Ibanda town by extension of

MV line and installation of a transformer

Portion from Ibanda to Kamwenge has

50sqmm conductors that would require

upgrading to at least 100sqmm SCA in

light of interconnecting the new

Mpanga grid s/s to Mbarara North; Only

one isolator exists on the entire line of

about 169.4km; Burnt MV pole& leaning

cross arm exists at Rwenzaza;

construction under the line noted at

Rubindi T/Insufficient number of

isolators(only one worn-out knife blade

links at Ibanda) on the line; Old t-off of

1km at Igorora has 50sqmm SCA

Need to promptly replace the

few rotten/leaning poles and

upgrade the conductor for

about 50km from Ibanda to

Kamwenge before they

become a crisis; More isolators

and load break switches

required;

New MV network extensions

noticed at Bugarama &

Page 76: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

76

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

conductor insufficient for the extended

UEDCL network to Kazo-upgrading it to

at least 100sqmm SCA would suffice;

Non decommissioned old pole, non-

transfer of hardware, with a new pole

erected and the two tied together

instead at Kamwenge Taxi Park

Kigarama Trading Centres;

Ongoing roadworks affecting

the network integrity in

Kamwenge town with

relocations inevitable

Masaka West s/s -

Masaka Central 33kV

interconnector

Interconnector in good condition after

recent refurbishment

Some distribution transformers exist on

the interconnector

Existence of distribution

transformers compromise its

reliability

Masaka Central s/s -

Upper Ring 11kV feeder

Line in good condition up to Nabinene-

Kyotera road/Kyabakuza-Mbarara road

with sound poles & better conductor

100sqmm SCA;

After Kyabakuza along mbarara road,

the conductors which are mainly

25sqmm SCA have multiple joints; The

following t-offs have poor conductors:-

Ssaza, Kyanamukaka, Bwala Hill, Bukoto,

Ssemya, Kabwoko & Mirambi; LV

network has many rotten poles and

poor conductors, reports of illegal

connections & thus a safety hazard

Similar situation as in Q1,2 & 3

of 2015;

The affected t-offs and the

portion beyond Kyabakuza

should be considered for re-

conductoring. LV network

needs similar attention as the

MV;

Line significantly extended into

Rakai areas;

Its recommended that part of

the load on this feeder be

shifted to Lower ring 11kV

Page 77: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

77

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

feeder, with prior

reconductoring of Lower ring

current network

Masaka Central s/s -

Kalungu 11kV feeder

Line in good condition with sound poles

and 100sqmm SCA conductor up to

Lwabenge T/C

Incidences of stays’ vandalism noticed

at Kitante(Kyirikiti-Kyamulibwa road)

Same good condition still

stands

Masaka Central s/s -

Lower Ring 11kV feeder

All rotten poles replaced during

refurbishment of Mitala Maria 33kV

feeder

Entire portion has poor conductors

(steel) considering the town load

Same situation as in previous

Q1,2 & 3 of 2015 inspections;

Re-conductoring of this

portion required to ensure

reduced technical losses &

improved quality of supply

Masaka West s/s - Rakai

33kV feeder

Line refurbishment works ongoing to

replace all rotten MV poles and

upgrading the backbone conductor to

150sqmm sca; faulty circuit breaker

replaced at the substation

T-offs excluded in the scope of ongoing

refurbishment works

Quality of works to be

monitored to ensure value for

money

Masaka Central s/s -

Mitala Maria 33kV

feeder

Poles in sound condition Re-conductoring required; first structure

at Masaka Central s/s not labelled

Same status as in Q3 of 2015

T-off from Mitala Maria

to Kiriri s/s 33KV

This portion is in poor condition Same status as in Q3 of 2015

Page 78: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

78

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kiriri s/s - Kibibi 11kV

feeder

This feeder has 25sqmm SCA

conductors which are burnt in a

number of sections, with multiple joints;

hence high resistance; Road

construction works ongoing and

affecting the line corridor and some

structures

Situation still as it was in

2014,Q1,2 & 3 of 2015

Kiriri s/s - Kabulasoke

11kV feeder

Line in good condition with sound

poles,100sqmm SCA & 50sqmm SCA

conductors on the main line & t-offs

respectively

Q3 of 2015 status still remains

Busunju s/s - Katera 11kV

feeder

Feeder has very old poles overdue for

replacement; some poles completely

broken & supported by temporary wind

stays tied on tree stamps like at

Kikandwa sub county(55km mark);

Kateera TC 300kVA/11kV ground

mounted transformer had signs of oil

leakage, not enclosed & with exposed

unsafe wiring

Q3 of 2015 status still remains

Busunju s/s - Kiziba 11kV Line refurbishment works ongoing and

about 60% complete to replace all

rotten MV poles and upgrading the

conductor to 100sqmm sca on the main

line & 50sqmm sca on the t-offs-

PODITECH Umeme contractor handling

Busunju s/s - Mityana

33kV Line

Line largely strong and reliable Some few structures need replacement Q3 of 2015 status still remains

Page 79: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

79

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mutundwe s/s - Mityana

33kV Line

All structures in good condition due to

recent refurbishment; 3 Load break

switches installed at convenient

locations on the line such as

Nakuwadde T-off

Conductor requires an upgrade to at

least 100sqmm sca required; Load

break switch at Mudduma can only be

closed locally NOT electrically

up-grading the conductor

essential for improved supply

reliability

Mutundwe s/s – Mitala

Maria 33kV Line

MV line in sound condition with newly

replaced poles and conductors

including major t-offs at Mpigi and

Kamengo

Poor/multi-jointed LV conductors with

rotten poles on along Kamengo- Butoro

T-Off; T-off to Kampiringisa has very long

& low sagging & multijointed LV network

due to combined construction with MV

without installation of intermediate LV

poles. Part of this network is illegal; VM

poor along this t-off

Q3 of 2015 status still remains

Mityana s/s – Namataba

11kV feeder

T-offs fused by the District maintenance

team

Line conductor steel and multi-jointed

with mostly rotten poles

Line in poor state of

maintenance requiring urgent

attention

10.2.3 NORTHERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Page 80: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

80

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Busunju s/s - Hoima

33kV Line

Entire line in good condition with recent

replacement of the previously rotten poles

and changing of conductors to 100sqmm

SCA; and handling most of the worst

structures on the t-offs (e.g.

Kyankwanzi,Ntwete) & installation of 5 air

break switches & a load break switch at

Lwamata

Line still in satisfactory

condition

Hoima - Masindi

33kV Line

Some MV poles continue to be replaced by

district teams

No functioning isolators on the entire

line, several intermediate structures

have one X-arm strut each such as at

Kinyara out growers; Some X-arms

leaning down the poles as a result;

Vegetation poor on some portions of

the line

A number of leaning poles

noted after Bwijanga,

especially in the sugar fields.

Vegetation management

needs to be beefed up with

increasing rains.

Page 81: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

81

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Hoima s/s -

Munteme 33kV

feeder

Line conductor largely okay with some

rotten poles replaced by district teams

Most poles rotten and require

replacement; Check Metering Unit at

Munteme faulted & recovered; all the 3

Isolators working; Line

conductor(75sqmm) replaced with a

smaller size(50sqmm) whenever it

breaks(e.g. at Buhimba Police Post

area); LV poles for new REA Schemes at

Buhimba erected under/close to 33kV

line, burning as a result even before

commissioning, leading to breakage of

main line conductors; vegetation

clearance poor for most parts of the line

Vegetation management

issues. Line generally okay.

Hoima s/s - Hoima

Town 11kV feeder

Some poles continue to be replaced

The line conductor is poor with a mixture

of 25, 50,100sqmm and steel and with

multiple joints; Kiryantete areas still have

poor LV network; Line is criss- crossed,

multiple times by Buseruka 33kV feeder

operated by Hydromax, making it very

unsafe for the operational teams;

Shrubs exist along the line touching MV

conductors like at East African Crane

areas

A number of bad poles have

been replaced and the

feeder is generally okay

clearance required

Page 82: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

82

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kinyara s/s –

Budongo 11kV

feeder

Most of the MV poles rotten with

incidences of over 5 poles falling at ago

in some worst portions; conductor

largely 25sqmm ACSR and multi-

jointed;Nyabyeya Forestry College

11/18154/100kVA transformer had links

for MV protection and poor/burnt

transformer wiring; Vegetation

clearance required; Structures with

broken/badly leaning X-arms exist

This feeder is now in a bad

state, especially in the sugar

fileds.

Masindi s/s -

Nyamigisa 11kV

feeder

Line still in a fair condition Line has no isolator on first structure from

the substation; has poor & multi-jointed

conductors-mixture of

steel/25/50/100sqmm ACSR; some

rotten poles; Installed Capacitor bank

at the playground disconnected from

supply

Isolator required next to the

substation; Installed capacitor

bank should be restored to

service; Reconductoring

required for reduced

technical losses and improved

voltage quality

Masindi s/s – Masindi

Town 11kV feeder

Line in a fair state of maintenance Some rotten poles and worn out

conductors exist

Ever since it underwent major

rehabilitation this feeder is still

okay

Page 83: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

83

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Masindi - Apac - Lira

33kV Interconnector

Most structures in good state of

maintenance. Some poles replaced and

conductor changed to 150sqmm ACSR from

Masindi substation to Apac; Some major T-

Offs in Apac reconductored with 50sqmm

ACSR

LV network in Apac Town is still in a bad

state with examples of badly broken

poles on Apac Hospital transformer

zone; Some rotten/broken MV poles

noticed along the line(e.g. Structure

No.433 after Kungu Port); Some few

poles not replaced during recent works

close to Lira substation due to

unresolved long standing wayleaves

issues

Issues of insulators breaking off

on the main line have been

addressed by changing to

two-bolt insulators. Same

needs to be done on Bweyale

leg. Many of the insulators

have only one bolt installed!

Situation of strands of

conductor breaking and

unwinding still needs to be

addressed; reported

continuous breakage of

conductors on towers crossing

R Nile needs to be addressed

too

Gulu s/s - Gulu

Hospital 11kV feeder

The line has a mixture of 25sqmm and

steel despite continuous load growth

Status still the same as was in

March 2015

Gulu s/s - Layibi 11kV

feeder

Parts where system improvements were

done are okay

Remaining parts of the feeder not

scoped as part of system improvements

have many rotten poles and poor

conductors on both the MV and LV

Preparations were underway

to rehabilitate the feeder –

replacing poles and

conductors.

Page 84: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

84

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Lira s/s - Gulu s/s

33kV Line

Line still generally okay after stringing new

conductors, and regular maintenance

Increasing numbers of the newly

installed poles are rotting and requiring

replacement

Structures reported rotting

especially in Aboke area; line

continues to suffer lightening

damage in Koro & Bobi areas;

section of aerial earth wire

found missing after Palenga

towards Gulu

Lira Spinning s/s -

Boroboro 11kV

feeder

Nulec circuit breaker faulty; No

functional isolator on the first structure

from the substation.

Need to repair/replace faulty

switchgear & install isolators on

the line to avoid direct

connection to the bus bar.

Substaion under major

rehabilitation though ALL

feeders are temporarily served

by ONE breaker raising serious

reliability issues

Lira Spinning s/s -

Spinning Mill 33kV

feeder

75sqmm acsr conductor on the line still

sufficient

Most of the poles are rotten Rehabilitation of the entire line

is necessary being just about

4km.

Page 85: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

85

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Lira Spinning s/s -

Ngetta 11kV feeder

Some of the worst structures replaced but

the situation still remains bad

Still many leaning poles and associated

LV networks are in very poor state, and

seemingly dangerous in some of the

areas. Situation has worsened from

what was observed in March 2015

Vegetation management

should be improved on this

feeder, all rotten poles

replaced and re-

conductoring done for

improved safety and reduced

technical losses and supply

reliability

Lira s/s - Kitgum s/s

33kV line

Most of the worst structures and sections of

the line have been worked on and is now

relatively stable

Some insulators and cross-arms still need

attention along the line. Integrity of

structures in water at River Aswa

crossing needs addressing

Consider re-designing the line

where the base of poles are

submerged in water in River

Aswa. Consider using four-

member structures on higher

ground on both sides of the

river to ease monitoring and

replacement work.

Lira s/s - Lake

Kwania 33kV feeder

A few poles have been replaced as they

break

The line continues to deteriorate by the

day and many poles are now leaning

and about to fall

Rehabilitation of line

underway.

Lira - Anai 11kV

feeder

Most poles are rotten, worn out and low

sagging multi jointed conductors(e.g.

Anai transformer zone) & poor VM

This short feeder has been left

to deteriorate for unclear

reasons. Could contemplate

constructing combined 33kV

and 11kV line where the 11kV

is at present hence deal with

the way leaves problems

Page 86: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

86

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

being faced by the 33kV line

in the Anai area.

Lira Town MV and LV

network

Rotten poles have continued to be replaced

under O&M, plus conversion of LV to ABC

Most poles replaced have no caps

which shortens their lifespan.

Town network still remains

relatively okay, though rapid

deterioration of poles needs to

be investigated

Kitgum s/s - Padibe

11kV feeder

Nearly all poles on the line were replaced

and still okay

Line still in a good condition

Kitgum s/s - Padibe

11kV feeder (Lamwo

t-off)

Poor poles were used on the line initially

and have continued to rot at a high

rate

Cause of rapid decay in poles

needs to be investigated and

addressed

Kitgum s/s - Ayulu

11kV feeder

The feeder has many bad structures

with seemingly 25sqmm conductor that

should be considered for upgrading to

help control technical losses

Same situation from previous

inspections still prevailing

MV and LV network

in and around

Kitgum Town

Considerable work is still visible on

replacement of bad MV structures in Kitgum

Town

Airfield transformer stressed and needs

attention.LV system within Kitgum town

needs improvement

Same situation as in March

2015 inspection

Bombo s/s -

Kawanda 33kV

Incomer

Main 33kV line is in a good state

Most T-Offs are in very bad state with

rotten poles and poor conductors (such

as Namalele & Kitungwa t-offs); Most air

break switches at open points faulty &

bi-passed such as at Matugga &

Kitungwa

While the MV system is largely

okay, the LV network needs

addressing

Page 87: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

87

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Bombo s/s -

Wabigalo 33kV

feeder

Most structures still in a good condition, with

some of the worst structures worked on

around Kakooge swampy area

T-off to Kaweweta-Ngoma at Katugo

T/C not fused, though new and very

long; Circuit breaker required on the t-

off to offer HT protection in light of the

big load that cannot be sustained by

the ordinary fuses

A few leaning structures noted

especially around Kakooge

and Katuugo that need to be

rectified.

Bombo s/s -

Namulonge 11kV

feeder

Entire MV line fully refurbished by

replacement of all rotten poles & re-

conductoring T-offs with ACSR50sqmm from

ACSR25sqmm mixed with steel; 2 ABS

operational

More air break switches

required at convenient

locations

Bombo s/s - Ndejje

11kV feeder

Over 60% of poles are rotten, with some

replaced by O&M teams such as

around Nandere Secondary School);

conductor largely steel with a small

portion covered by 25sqmm conductor;

Some structures have X-arm strut each

leading to structural instability in the line

& eventually leaning poles; despite

extension of the line to areas of

Wambale P/S by REA, the first portion of

the feeder remains poor

Line still remains in a poor state

of O&M as was in November

2014.Frequent earth faults are

currently experiences due to

breaking of conductors.

Introduction of ABC and

prepaid metering suggested

controlling technical losses

estimated at about 50% in

addition to improved safety

being predominantly schools.

Page 88: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

88

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Bombo s/s - Luwero

11kV feeder

Main line refurbished by replacement of all

rotten poles & re-conductoring with

ACSR100 on main line from Bombo town to

Wobulenzi and 50sqmm on Bamunanika &

Nakaseke t-offs from ACSR25sqmm

conductor

LV network a poor with examples of

Low sagging, worn-out, multi jointed

conductors touching vegetation at

Bbowa & leaning poles around

Semuyungu T/C; Naluvule College T-off

has steel conductors

MV line and t-offs still okay but

the associated LV networks still

remain in poor state.

Lumpewe s/s -

Luwero 11kV feeder

Line structures in good condition after recent

refurbishment works

Line Circuit Breaker faulty Faulty Circuit Breaker requires

maintenance to make it

operational so that an

alternative source of supply to

parts of Nakaseke t-off is

provided

Wabigalo Auto s/s -

Bombo 33kV

Incomer

All overhead structures still good As observed for Bombo – 33 –

Wabigalo feeder

Wabigalo Auto s/s -

Mijera 33kV feeder

Most structures still in a good state Lacks a functional circuit breaker at the

substation

Separate operational Circuit

Breaker required at the

substation

Wabigalo Auto s/s -

Nakasongola 33kV

feeder

Line in good condition Need for a circuit breaker at

Nakasongola Army Barracks

Line in good condition

Page 89: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

89

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Bombo stressed

distribution

transformers

Gayaza T/C, Kasangati T/C, Luwero

Town, Wobulenzi

Town,Nakanaku,Nakasongola Town

transformers stressed and require system

improvement

These transformer zones

require system improvement

10.2.1 EASTERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Nakifuma - Kayunga

s/s – 33kV

Interconnect

Line had marginal pole replacements. The line still had several rotten & leaning

poles, especially on Kasawo T-off

While Umeme maintenance

teams work to replace the

worst structures, total

refurbishment is required

Page 90: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

90

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kayunga s/s –

Kayunga Town 11kV

feeder

The line is still relatively okay A few rotten poles are being replaced

under O&M as and when identified

Line is in a sound state

Kayunga s/s – Baale

33kV feeder

The line in a fairly good condition A few rotten poles are being replaced

under O&M as and when identified

While the line is in relatively

sound state it has been

observed that there many

still poles needing

replacement and regular

line clearance needed..

Kayunga s/s –

Kangulumira 11kV

feeder

Remedial Refurbishment of the line

completed in October 2014. Voltage

regulation improved by installation of

900Kvar Capacitor banks at Nateta.

Poles in swampy areas need better

anchoring.

Still generally okay after

refurbishment

LV lines in Kayunga

area

Vegetation clearance handled LV network is generally poor with a few

poles and conductors replaced under

O&M

LV refurbishment still required

in most parts & continuous

vegetation clearance

Owen falls s/s - Jinja

Industrial 1,2&3 33kV

Lines

These lines are in good condition having

been refurbished

Stays are still being vandalized,

especially on line No:3

All Jinja Industrial lines still in

good condition

Owen falls s/s -

Mulco 33kV Lines

Line generally okay Few rotten poles 60% of the Rotten poles

replaced. All potential rotten

poles need to be replaced

before further deterioration

Page 91: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

91

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Owen falls s/s -

Nyanza 1&2 33kV

Lines

Nyanza 1 on steel structures; Nyanza 2

(Upper Industrial) is a new construction

The diversions due to road construction

are still temporary.

Both lines okay

Jinja Industrial s/s –

Iganga 33kV feeder

Refurbishment works on Kakira T-off were

completed. 600Kvar Capacitor bank

installed.

Vegetation management (VM) needs

to be carried out regularly

Some rotten poles still need urgent

replacement

Vegetation management

handled regularly

Complaints of abnormal

voltage drop, e.g. 26KV at

Iganga needs addressing.

T-off from Musita to

Mayuge-Ikulwe-

Buyemba

80% of the main line was rehabilitated and

conductor re-enforced from 50mm2 to

100mm2 between Musita and mayuge /

Buluba.

Vegetation management (VM) needs

to be carried out regularly. Between

Mayuge and Buyemba; 60% rotten

poles still need urgent replacement

20% of the line still needs

extensive refurbishment.

T-off from Tembo

Steel mill to Kiyunga

Line still new; constructed by REA in 2013. Lack of automated line isolation Line still in good condition;

however an auto-reclosure is

urgently needed just after

Tembo steel mills

Jinja Industrial s/s –

Kamuli 33kV Line

feeder

Main line performing well after refurbishment

works in 2012. The Nile ply forest was fully

cleared away from the line,

Line affected by un-rehabilitated t-offs.

Faulty isolators like the one at just next

to Kamuli s/s need replacement. Poor

line anchoring in swampy areas.

Continuous vegetation

clearance is needed and

improvement on stays.

Page 92: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

92

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Jinja Industrial s/s –

Kamuli 33kV Line

(Buwenge to

kiyunga/Mbulamuti

T-Off)

Provides alternate supply to Mbulamuti

areas

The T-off has continued to deteriorate There is increasingly urgent

need to refurbish this T-off

Kamuli s/s –

Namasagali 11KV

50% pole replacements done. Many rotten and worn out, multi-jointed

25/50sqmm SCA conductors

T-offs should be fully

rehabilitated.

Kamuli s/s –

Namasagali 11KV ,

T-Off to Mbulamuti)

Many rotten and worn out, multi-jointed

25/50sqmm SCA conductors. Only 10%

pole replacements done.

T-offs should be fully

refurbished.

Jinja Industrial s/s –

Steel Rolling 33kV

feeder

80% of the rotten poles replaced. Many rotten poles Line still needs marginal

rehabilitation

Jinja Industrial s/s –

BIDCO 11 33kV

feeder

900Kvar Capacitor banks installed No significant weaknesses Line still ok

Jinja Industrial s/s –

Kakira (1+2) 33kV

feeders

Lines are generally okay Affected by vandalism. Vegetation

management is regularly needed as

well as pole realignment

Need to devise ways of

managing the vandalism.

Continuous vegetation

management needed in the

sugar plantation areas.

Jinja Industrial s/s -

Walukuba 11kV

feeder

Refurbishment of poles and conductors

completed

Evidence of vandalisation of stay

assemblies

Line is now in a good state

after completion of the

rehabilitation works

Page 93: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

93

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Jinja Industrial s/s –

Mutai 11kV feeder

Line relatively okay Line has some leaning/rotten poles &

mixed conductors

Total refurbishment and re-

conductoring required.

Jinja Industrial s/s –

Town 11kV feeder

Line relatively okay Line has some leaning/rotten poles &

mixed conductors

Line still needs minor works

done.

Jinja Industrial s/s –

Ring South 11kV

feeder

O&M teams working on the worst structures Rampant vandalism of feeder pillars in

areas where the network is

underground (cables)

Need to manage the

vandalism and either restore

or recover vandalised feeder

pillars

LV Lines in Jinja area More LV refurbishment still required in

most areas. Regular Vegetation

management is needed.

Ground-mounted distribution boxes

often vandalised in town area

While the main town area is

relatively okay, the outlying

areas like Bugembe,

Wanyange, etc still need

urgent rehabilitation.

Njeru s/s – Ring North

11kV feeder

Line generally okay VM being hindered by resistance from

Municipal Authorities who have refused

to authorize trimming of tress, e.g. in

Magwa area. T-off to Kimaka in Bad

state with many rotten poles and poor

conductors.

Feeder needs urgent

rehabilitation

Page 94: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

94

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Njeru s/s – Lugazi

11kV feeder

Rehabilitation works by Inter-Tek contractors

completed.

The link with line from Lugazi network still

needs to be restored to provide an

alternative source of supply.

Associated LV system is bad

and not included in the

scope of ongoing

rehabilitation works. Only

one span needed to link with

the line from Lugazi 11KV.

Njeru s/s – Kayunga

33kV feeder

Line still in moderate state & line clearance

handled

About 20% rotten poles still exist. Line in good state of

maintenance, though

regular line clearance and

replacement of 20% poles

needs to be done before

line deteriorates further

Kamuli s/s – Kasolwe

11kV feeder

This feeder is still in a good condition. The line

now stops at Balawuli TC

Regular vegetation clearance required The line is still in a good

condition. The Balawuli to

Kasolwe portion was

vandalized and customers

shifted to the Bukungu 33KV

line

Kamuli s/s –

Namwendwa 11kV

feeder

The line has continued to deteriorate,

including T-offs. The worst part is

between Namwendwa and Bulogo with

several with several joints of 25mm2 and

steel.

District trying to work on the

worst structures but line

needs total refurbishment.

Page 95: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

95

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kamuli s/s –Bulopa

11kV feeder

The line has continued to deteriorate,

including T-offs. 80% poles still need

replacement. Conductors with several

joints of 25mm2 and steel exist.

District trying to work on the

worst structures but line

needs total refurbishment.

LV lines in Kamuli

area

District carrying out emergency repairs Nawansaso & Namwendwa T/Cs have

poor networks

General rehabilitation of the

LV network is required.

Iganga s/s – Kaliro

33kV feeder

90% of the rotten poles have been replaced

and the conductor re-enforced from

100mm2 ASCR to 150mm2 AAAC from

Iganga to Kaliro.

This particular feeder cannot be

operated remotely through the SCADA

system. Some t-offs cause outages on

the main line.

SCADA functionality should

be improved for this feeder

Iganga s/s – Kaliro

33kV feeder

(Kawete T-off)

Many poles have been replaced under

O&M on this T-off but it’s not sustainable as

they continue to rot at a very fast rate.

70% of poles (MV & LV) are rotten

barely five years after the T-off was

constructed in 2009

The T-off should be scoped

for complete rehabilitation

before if fully breaks down.

Issue of quality of poles

needs to addressed by all

concerned stakeholders. An

auoto-reclosure needed at

T-off to Kawete from main

line.

Iganga s/s – Kaliro

33kV feeder

(Busembatya T-Off)

Many poles have been replaced under

O&M but it’s not sustainable as they

continue to rot at a very fast rate. A nulec

auto-reclosure installed at start of the T-off.

Most poles are rotten and require

immediate replacement, otherwise they

pose a safety risk

The T-off should be scoped

for complete rehabilitation

before if fully breaks down

Page 96: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

96

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Iganga s/s – Bugiri

33kV feeder

Some of the identified rotten poles have

been replaced under O&M

The line has several leaning poles

especially around swampy areas.

Waka Waka T-off still has several leaning

poles. Conductors have many joints

that are non-homogeneous. All the

swampy locations of the line need

special attention. The conductors on

the REA extension from Naluwerere to

Namutere keep breaking due to

resonance. The ABS at Namasere needs

repair.

Total rehabilitation is urgently

needed.

Iganga s/s – Iganga

Town 11kV feeder

The line is in good condition No serious issues with this line

LV network in

Iganga

70% of the network rehabilitated and 12 new

substations injected

As in all other areas, LV network in

Iganga is in generally poor state. About

25% conductor re-enforcement

required.

Continuous improvement of

the LV network should be

done.

Page 97: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

97

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kaliro s/s – Kaliro

Town 11kV feeder

The line is in generally good condition The 11KV T-off to Ivukula needs urgent

revamping (many poles and a sizable

length of conductor needs

replacement)

A new 33KV generator line

has been added on the

same structures to evacuate

power from Sugar & Allied

Industries at Bwayuya - Co-

generation to feed bus bars

at Kaliro s/s. Isolation of

Ivukula / Bulumba T-offs

needs to be improved to

ease operations

Kaliro s/s – SAIL 33kV

line

The line of 10KM of 150mm2 AAAC is new

and generally in good condition. i

The new 33KV co-generation line has

been added on the same structures to

evacuate power from Sugar & Allied

Industries at Bwayuya - Co-generation

to feed bus bars at Kaliro s/s with. It’s

not clear who is responsible for the

ownership, O&M of this new line.

Isolation of Ivukula / Bulumba T-offs

needs to be improved to ease

operations. A combined 11KV and 33KV

lines on one structure my cause

disruptions during maintenance of

either lines,

An O & M agreement needs

to be concluded with SAIL.

The line should be planned

to be on a separate

exclusively co-generation

line.

Page 98: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

98

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kaliro s/s – Kiyunga

11kV feeder

The line is in generally good condition. 24 KM

of 11KV and 12 transformers added.

A good length of Aluminium conductors

was vandalised and upon replacement

different sizes were used; leading to

non-homogeneous setup.

Vandalism is still persisting

LV Lines in Kaliro

areas

O&M teams working to replace the worst

structures. 30% of poles replaced and 2 new

transformers injected.

70 % of need replacement Continuous replacement of

poles is required.

(Nagongera s/s –

Nagongera 11KV)

formerly Tororo Rock

s/s – Town Ring 11kV

feeder

Refurbishment done up to Busolwe. Line re-

enforced to 100mm2 ASCR.

Portion from Busolwe onwards has not

yet been handled.

Need to complete

refurbishment of Busolwe,

Butaleja & Budumba T-offs

(Nagongera s/s –

Town 11KV) formerly

Tororo Rock s/s –

Town Ring 11kV

feeder

Refurbishment done all the way back to

Tororo Town

No significant weaknesses Line still ok

Tororo Rock s/s –

Town Via Quarry

11kV feeder

Line infrastructure is in a fair condition. Vegetation management needs to be

regular.

Line in a fair condition and

bad poles had been

replaced.

Tororo s/s – Petrol

Station 11kV feeder

Line infrastructure is in a satisfactory

condition

Vegetation management needs to be

regular

Line in a satisfactory

condition

Page 99: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

99

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Tororo Municipality

LV network affected

by road works

The LV network of about 31 poles along

Bazaar, Parkside & Rock view P/S streets from

3 Transformers on Town Ring 11kV feeder

that had been excavated was relocated

No significant weaknesses Vegetation management

needs to be regular.

Tororo Main s/s –

Bugiri 33kV feeder

Line in a satisfactory condition

Some few poles leaning due to missing

wind stays at mile eight.

Line in a satisfactory

condition; but wind stays

need re installation in some

places.

Tororo Main s/s –

Busia 33kV feeder

Line still in good condition after rehabilitation

of 51km from Tororo Main s/s to lumino by

pole replacements & conductor re-enforced

to 100sqmm SCA.

The portion from Lumino T.C to

Majanji/Sangalo still remains in bad

state

Rehabilitation of the portion

between Lumino and

Majanji TC/ Sangalo beach

should be handled, fusing of

all the directly connected t-

offs and improvement of

transformer maintenance

practices

Tororo main s/s – TCI

33kV Line

The entire line with PB steel structures is in a

satisfactory condition

No weaknesses identified Line in a satisfactory

condition

Tororo Main s/s -

Tororo Ring 1 33kV

feeder

Line is in generally good state after total

rehabilitation

No weaknesses identified Line in a satisfactory

condition after total

Replacement of rotten

structures.

Page 100: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

100

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Tororo Main s/s –

Mbale 1 33kV Line

Refurbishment works was completed Some replaced structures are already

leaning;Rampant vandalism of stay

assemblies

Rehabilitation of T-offs

improgress

Tororo Main s/s –

Mbale 2 33kV Line

Refurbishment works was completed

Rampant vandalism of stay assemblies Line in a satisfactory

condition

Mbale s/s – Iki Iki

33kV feeder

90% of the Line still remains in a bad

state; structures on the first 5 spans

outside Mbale 33Kv s/s were leaning

badly

Urgent need to rehabilitate

the entire line

Mbale s/s – Kumi

33kV feeder

Refurbishment works were completed Some few leaning poles were observed Remaining snags on line still

need to be cleared by

contractor

Mbale s/s – Industrial

11kV feeder

Line is generally okay Some poles are rotten and leaning

especially in areas traversing the

swamps.

Pole replacement was going

on. The conductor needs

uprating from 50sqmm to

100sqmm SCA due to

growing load reaching 200A

at peak. Procedures of

erecting poles in swamps

should be followed

Mbale s/s – Mbale

Ring 2 11kV feeder

Line still generally okay

Some poles are rotten and require

replacement.

Line experiencing vandalism by cutting

down of poles almost weekly

Ways need to be found to

manage the vandalism

Page 101: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

101

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mbale s/s – Mbale

Ring 1 11kV feeder

The Main Line is in a satisfactory condition

after recent refurbishment

T-Offs still remain in a very bad state

and affected by vandalism.

Quality of poles used, e.g. on Sironko T-

off still remains outstanding

All T-offs in a bad state

require complete

refurbishment to the same

status as the main line

Mbale s/s – Bugema

11kV feeder

The main line conductor is in a fair condition Several poles rotten & leaning such as

at Nyondo PTC T-off. Some t-offs have

worn out conductors. Some open points

are jumpers with no isolators provided

for

Though some pole

replacement was still going

on, problematic T-offs need

to be handled as well.

T-Off at Kachumbala

to Kapchorwa 33kV

Line via Kolir

Refurbishment was completed. Switching station at Kapchorwa with

rotten structures and completely

abandoned

T-offs worked on as well. Vandalism of

stay assemblies & and rampant theft of

power (hooking!), especially in

Bulambuli district was noted

Way forward needs to be

found for Kapchorwa

substation/switching station.

T-offs need to be worked on

as well

Mbale Municipality

LV/MV networks

Line relocations completed. LV & MV networks need continuous

vegetation management.

Regular line clearance

needed.

Iki-Iki s/s – Kakoro

11kV feeder

Some emergency replacements had been

done by O&M teams

Line has several leaning poles Leaning poles should be re-

plumbed/replaced following

the right procedures of

planting poles in swamps

Page 102: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

102

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Iki-Iki – Bulangira

33kV Line

70% of the Line still remains in a bad

state; many structures were leaning

badly

Urgent need to rehabilitate

the entire line

Bulangira s/s – Pallisa

11kV feeder

Few of the worst structures had been worked

on by O&M team

Akadoti T-Off has rotten and leaning

poles. 90% of the poles need

replacement on the main line.

General refurbishment of the

line is urgently required

Bubulo S/S T-Off on

Tororo - Mbale 1

33kV Line

T-off is still in a bad state 50% poles

need replacement and conductor re-

enforcement.

This T-Off requires immediate

rehabilitation, installation of

a circuit breaker and

replacement of the worn-out

Knife Blade Links

Bubulo s/s – Bududa

Hospital 11kVfeeder

Most poles are rotten and leaning with

some t-offs directly connected. The

conductor is a mixture of 25 & 50sqmm

SCA

Refurbishment of the entire

feeder is required.

Bubulo s/s – Bududa

Hospital 11kVfeeder

(Bududa T-Off)

Some structures are rotten such as

Mulatsi Transformer structure that is also

leaning & sinking

This T-off requires routine

maintenance to keep the

integrity of the distribution

network

Kumi s/s – Serere

33kV feeder

Line was fully refurbished and is okay LV networks along the line were not

addressed

The faulty apparatus on the

line should be replaced &

sufficient number of isolators

Page 103: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

103

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

installed for flexibility of the

network

Kumi s/s –

Mukongoro 33kV

feeder

Line has many leaning poles all the way

through

Leaning poles need re-

plumbing. 80% poles need

replacement.

LV Lines in Mbale

areas

ABC installed and transformer injected at

Bugema military barracks

LV lines are in very poor state. Rampant

illegal connections in outlying areas of

Mbale town.

Most isolation points in Mbale are faulty,

creating safety hazards

A strategy of restoring sanity

of the LV network is urgently

required, otherwise it is

totally unsafe and a source

of both commercial and

technical losses Opuyo s/s – Kumi

33kV feeder

Refurbishment completed. Long line needs ABS to ease isolation

and sectionalisation. The swampy

section at Awoja needs special

attention.

Line in a satisfactory

condition ; however the line

needs about 5 ABS

installed.

Opuyo s/s – Soroti

33kVfeeder

Refurbishment completed. Some 5 poles already leaning due to

need of wind stays

Line in a satisfactory

condition ; however the line

needs about 2 ABS installed Serere s/s – Serere

Town 11kV feeder

Formerly stopping in Serere Town, line

extended by REA about 4 years ago for

about 35km

Line extension already rotten. The load

Break Switch installed at the same time

is also faulty

The fast deterioration of this

line points to the quality of

materials used. The 35km

portion of the line should be

rehabilitated and faulty

apparatus maintained

Page 104: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

104

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Soroti s/s – Atirir 33kV

feeder

Existing portion of line has deteriorated

further and now most of it is rotten and

affecting power supply to UEDCL areas

in Kaberamaido, Dokolo & Amolatar.

Rampant theft of HV UG cable at 132

KV crossing.

Rotten/leaning poles should

be replaced and cable theft

at 132 KV crossing should be

checked.

Soroti s/s – North

Ring 11kV feeder

Most poles in good condition Line has worn out conductors(25sqmm

SCA)

Some transformers & their LV networks

are stressed

MV Line needs a better

conductor for improved

safety, voltage quality &

reduced technical losses

Soroti s/s – South

Ring 11kV feeder

Line is generally okay MV Line in a satisfactory

condition

LV network in Soroti

areas

ABC installed in Mukura and Asuret areas Many areas still require system

improvement

System improvement

interventions in these areas

should be considered

Page 105: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

105

10.3 OFFICE BUILDINGS

10.3.1 WESTERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mityana District

Office

Office and back office building

rehabilitated; Rear compound floor

improvement and shelves for

storage expected

Some poles on ground besides the office

rear gate

Office now looks better

Mubende District

Office

Office and outside yard

maintained well, with floor hard

pressed with marram

Only one container used as the office; The

uniport store sits on low ground with Rain

water flowing into it; Drainage is poor at

the office yard; Noticeable encroachment

of UEDCL land around the

substation/offices; Umeme plans to shift the

office operations to the town centre in

January 2016

Status-quo hasn't changed from

2014, Q1, 2 & 3 of 2015. Need to

consider constructing a proper

office on available space in front

of substation; Need to re-survey the

land where the substation/office sit

to eliminate possible

encroachment

Fort Portal District

Office

The office yard is used by Umeme

as a night parking yard

The building itself is dilapidated and not in

use, and continues to be unsightly amid

developments in the neighbourhood. The

building is now enclosed with iron sheets

typical of unsafe environment.

The building has deteriorated

further and is now an eyesore in

the town. Decision should quickly

be made on what to do with the

plot before Municipal Authorities

step in!

Page 106: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

106

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kasese District Office Office building still looks elegant,

with its interior set up offering a

good image; Sufficient space is

offered

One toilet upstairs completely closed out

with a warning of out of order; Upstairs

offices require rehabilitation with repair of

some flash toilet handles; materials store

needs to be organised in shelves

Upstairs offices require revamping

to the same level as the down stair

offices

Kabale District

Office

The interior of the ground level

offices is kept well; Bats infestation

cleared; Office building painted;

rear gate maintained, with more

works to beautify the premises &

drainage improvement on the rear

side expected

Housekeeping & storage of materials in the

yard behind the office building requires

improvement

More works to further improve the

building, drainage & flowering was

expected within Quarter 3, 2015.

Rukungiri District

Office

Office building and signage offer a

fair external appearance due to a

coat of paint that was applied

The foundation and floor of the building

also need plastering and tiles respectively;

Only pit latrine almost full; The verandah of

the office building falling off in pieces;

Drainage around the office building poor;

multiple old structures exist besides the

main office premises

Status-quo hasn't changed from

2014, Q1, 2 &3 of 2015. Complete

redesign & refurbishment of entire

office premises required

Mbarara District

Office

Office environment well

maintained

The offices seem to be congested with

increasing staff, customer numbers and

accommodation of two containers

containing stores materials; a damage

Office still in good shape

Page 107: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

107

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

exists at the access gate foundation

Masaka District

Office

The interior surfaces of the lower

offices maintained quite well; Work

was expected on the ceiling

Cabs for the floor gardens in front of the

parking damaged; The perimeter wall has

wide cracks and not maintained with a

weakened foundation; Most of the upper

offices housing the technical personnel

experience heavy leakages during rains

with the ceiling cardboards visibly damp

and broken. On an early morning

inspection after a previous night’s heavy

downpour, the O&M Engineer’s office had

flooded with all the computers, desks &

documents wet!

Despite several repairs done on the

office building, leakages on the

upstairs’ offices have persisted;

Situation hasn't changed from

what was reported in 2014, Q1, 2 &

3 of 2015. Upstairs offices need

renovating the same way the lower

offices have been done

Kisoro District Office Front compartment of the office in

a fair condition after recent

painting,partitioning,blocking of

some leakages on the roof,

unblocking of the sewerage lines,

working on the plumbing, gate at

the back side and sign post

Reports of leakages in some parts of the

building still exist, windows with broken

glasses on the front are evident, old doors

requiring replacement & the rear

compartment still poorly maintained &

unutilized

Besides some cosmetic work done

on the building, a lot more is still

pending in order to improve its

overall appearance and lifetime.

Page 108: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

108

10.3.2 NORTHERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Hoima District Office Downstairs offices descent. Entire building needs full renovation;

Upstairs offices’ ceiling infested with bats!

Office coat of paint is faded and peeling

off; Some plumbing broken down

Status-quo hasn't changed from

November 2014; Building

earmarked to be in the road

reserve by Hoima Town Council,

reportedly want it demolished &

reconstructed off the road reserve.

Kikwite Military

Hill,Hoima

Site taken over by a retired Lawyer Yesero

Mugyenyi who has enclosed off the entire

land; former radio room extended and

used as a rearing place for chicken

Intervention required to secure the

UEDCL land formerly hosting the

VHF radio

Masindi District

Office

Some minor painting done at the

toilet; Old Radio Antenna still intact

within the office compound; Tap

water available for improved

hygiene; security guard available

In bad state of maintenance; Ceiling still

infested with bats; Stores buildings in poor

state of maintenance;

Poles stores in the compound (on ground)

besides a pole rack; Perimeter fence is

broken down; Insufficient security lights at

the office premises; Septic tank overflowing

with sewerage

These buildings have become

inhabitable and have been

abandoned by Umeme who have

rented new office space in town!

Page 109: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

109

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Gulu District Office Building still in fairly good condition. Maintenance issues cited in March 2015

need to be handled.

Building was found undergoing

rehabilitation.

Lira District Office Lira office still in a fair condition. Road work expansion has broken up part

of the pavement in front of the building

Building still relatively.

Plumbing/water issues need

addressing.

Bombo District

Office

Bombo Office still in a satisfactory

condition.

Big crack exists on the wall besides the exit

opposite the cash office; broken window

glass next to front access door

Building still okay

10.3.3 EASTERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Kamuli District Office Building in generally good

condition

Drainage channel in front of the office

covered by eroded soil due to ongoing

road construction works

Upstairs rooms need to be

rehabilitated as well and put to use

Iganga District

Office

Building in generally good

condition

One of the toilets reportedly floods when it

rains. Concrete ceiling beginning to peel

off in some rooms

Remedial maintenance needs to

be carried out

Jinja District Office Building in generally good Building still in good condition

Page 110: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

110

condition

Mbale District Office Building in generally good

condition

Showing some signs of deterioration, e.g.

toilet ceiling

Remedial maintenance needs to

be carried out

Soroti District Office Building in generally good

condition

Upstairs rooms need to be

rehabilitated as well and put to use

Tororo District Office Building in generally good

condition

Drainage channel in front & sides of the

office covered by eroded soil due to

ongoing road construction works. Water

stagnates. Signs of rainwater infestation in

upstairs rooms

Upstairs rooms need to be

rehabilitated as well

10.3.4 CENTRAL

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Mukono District

Office

Office building looks descent; yard

worked on and now partly used for

parking

Pit latrine requires paint Building generally okay. Some work

had been done to improve the

sanitary facilities

Entebbe District

Office

Office building had a poor appearance

and requires major rehabilitation works;

signs of leakage on the surface plumbing

exist on the rear side

Some rehabilitation work had been

undertaken to improve the

appearance of the building, including

improving the rear gate and

improving sanitary facilities

Page 111: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

111

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Metro Office Building recently worked on and

offers an elegant appearance

In a good condition of maintenance

10.4 FLEET

10.4.1 WESTERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Masaka Fleet Most fleet in a fair condition Cranes for self-loader trucks UAL 158L and

UAJ 077U faulty and were removed

The cranes should be restored to

facilitate lifting of loads that are

characteristic of customer service

Mbarara Fleet Most of the fleet in good working

condition

Pick-Up UAJ316F experiencing frequent

breakdowns

Requires replacement

Kasese Fleet Pick-Ups UAH 269X and UAJ321F in poor

mechanical condition with the later

unable to start

These grounded vehicles should be

maintained to make them operational

or disposed off

Page 112: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

112

10.4.2 NORTHERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Hoima Fleet Most fleet found in good

mechanical condition

Pick up UAJ633D not mechanically

sound, despite pushing, it still fails to hard

start-possible issues with the injector

pump

Routine maintenance essential to

sustain operational fleet

Masindi Fleet Only pickup and truck UAA 069E in

operational state

Motorcycle UDG 530L had faulted and

abandoned requiring new sprockets and

clutch plates

A number of old motor cycles still

remain packed, unused at the parking

lot

Gulu Fleet Gulu fleet in good mechanical

condition

Need to sustain the routine servicing &

repair of the fleet, to sustain

operations

Lira Fleet Available vehicles found in

relatively good condition and all

working.

Troublesome vehicles had been sent to

Kampala for disposal.

The general status of the Lira fleet

points to a poor culture of repair and

maintenance leading to its total

breakdown.

Kitgum Fleet Available vehicle & motor cycle

found in relatively good condition

Need to sustain the routine servicing &

repair of the fleet, to sustain

Page 113: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

113

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

and all working. operations.

Bombo Fleet Most of the available vehicles in

good working condition

One pick up was unreliable (UAJ322F) &

two motorcycles broken down &

abandoned in the parking yard i.e.

UDQ006A,UAC478U

Need to sustain the routine servicing &

repair of the fleet, to sustain

operations. Its inadequate as well

10.4.3 EASTERN

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

Iganga/ Kamuli Fleet Same vehicles still existing, one lent

to Kamuli

One pickup (UAG 659L) had been

effectively grounded due to frequent

breakdowns

Update needs to be provided on

boarded-off vehicles that had been

transferred to Lugogo for disposal, in

order to update Distribution Network

Asset Register

Tororo Fleet Same vehicles as from March 2015

inspection still existing and running

Mbale & Soroti Fleet Fleet still running Update needs to be provided on

boarded-off vehicles that had been

transferred to Lugogo for disposal, in

Page 114: UGANDA ELECTRICITY DISTRIBUTION COMPANY LIMITED · 6.2 MEDIUM AND LOW VOLTAGE LINES a) The medium voltage distribution lines (33kV, 11kV) and Low voltage lines in some areas require

114

Asset Description Observed Strong Aspects Observed Weak Aspects Remarks

order to update Distribution Network

Asset Register

Kayunga Fleet Only Pick-Up (UAJ 668D) still

running, albeit looking bad

Jinja Fleet still running Update needs to be provided on

boarded-off vehicles that had been

transferred to Lugogo for disposal, in

order to update Distribution Network

Asset Register