UEW5 series intelligent air circuit breaker - EUROTRONIX · UEW5 series intelligent air circuit...
Transcript of UEW5 series intelligent air circuit breaker - EUROTRONIX · UEW5 series intelligent air circuit...
UEW5 series intelligent air circuit breaker UEW5 series intelligent air circuit breakers are applicable to the power distribution circuit under
the condition of AC50Hz/60Hz, rated working voltage 400V or 690V, rated current 630~6300A,
and take the role of distributing power and protecting wires and equipments from being damaged by
overload, under-voltage, short circuit and ground fault etc. The breakers with rated current below
1000A can also be used for the infrequent motor starting-up. The circuit breaker, with intelligent
protection function, precise selective protection, can improve reliability and safety and avoid
unnecessary power failure.
UEW5-
Rated frame current Number of poles Rated current Intelligent controller Installation method See Tablet 1
See Table 2 3P/4P See Table 2 L/M/H Table 1
Installation under voltage release Shunt release Pick up Auxiliary switch
Opening lock
Mechanical interlock
Frame
draw-out AC380V,220V AC380V,220V AC380V,220V4NO 4NC
one lock one key
horizontal interlock
draw-out
fixed instantaneous delay
1s,3s,5s DC220V,110V DC220V,110V
4NO 4NC
3 locks 2 keys
mechanical interlock
fixed
2000/ 4- 1250- M- Drawer type Accessories
AC400V,230V, DC220V,110V
Main specification Table 2
Type UEW5-2000 Rated frame current Inm(A) 2000 Rated current In(A) 630 800 1000 1250 1600 2000 Rated working voltage Ue(V) AC400/AC690 Rated insulation voltage Ui(V) AC690 Number of poles 3、4 3、4 3、4 3、4 3、4 3、4 Rated current of N pole IN(A) 50%或 100% In
AC400V 80 80 80 80 80 80 Rated ultimate short-circuit breaking capacity Icu(kA) (effective value) AC690V 50 50 50 50 50 50
AC400V 50 50 50 50 50 50 Rated service short-circuit breaking capacity Ics(kA) (effective value) AC690V 50 50 50 50 50 50
AC400V 176 176 176 176 176 176 Rated short circuit making capacity Icm(kA) (peak value) AC690V 105 105 105 105 105 105
AC400V 50 50 50 50 50 50 Rated short time withstand current (1s)Icw(kA) (effective value) AC690V 40 40 40 40 40 40 Full breaking time (without additional delay) (ms) 25~30 Closing time(ms) 70 at maximum
Basic ○ ○ ○ ○ ○ ○
Multi-functional ○ ○ ○ ○ ○ ○ Intelligent controller Communication ○ ○ ○ ○ ○ ○
Dielectric performance 50Hz AC 2500V 1min AC400V 500 500 500 500 500 500 Electrical life AC690V 500 500 500 500 500 500 Non-maintenance 9500 9500 9500 9500 9500 9500
Operational performance Mechanical life
Maintenance 20000 20000 20000 20000 20000 20000
Connection pattern horizontal vertical
horizontal vertical
horizontal vertical
horizontal vertical
horizontal vertical
horizontal vertical
Draw-out ○ ○ ○ ○ ○ ○ Pattern Fixed ○ ○ ○ ○ ○ ○
Draw-out 3P 395x362x323 Draw-out 4P 395x457x323 Fixed 3P 433x375x420
Externality dimensions
HxWxL(mm) Fixed 4P 433x470x420
Main specification Table 2
UEW5-3200 UEW5-4000 UEW5-6300 3200 4000 6300
2000 2500 2900 3200 3200 3600 4000 4000 5000 6300 AC400/AC690
AC690 3、4 3、4 3、4 3、4 3、4 3、4 3、4 3、4 3、4 3、4
50%或 100% In 100 100 100 100 100/110 100/110 100/110 120 120 120 65 65 65 65 75 75 75 75 75 75 80 80 80 80 80/85 80/85 80/85 100 100 100 65 65 65 65 65 65 65 65 65 65 220 220 220 220 220/242 220/242 220/242 264 264 264 143 143 143 143 165 165 165 165 165 165 80 80 80 80 80/85 80/85 80/85 100 100 100 50 50 50 50 65 65 65 65 65 65
25~30 70 at maximum
○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○ ○ ○ ○ ○ ○ ○
AC 2500V 1min 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
4500 4500 4500 4500 4500 4500 4500 2500 2500 2500 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
horizontal vertical
horizontal vertical
horizontal vertical
horizontal vertical horizontal horizontal horizontal horizontal horizontal horizontal
○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○
395x422x323 395x544x323 433x435x420 433x550x486 433x928x486 433x550x420 433x788x486 433x1043x486
UEM5 series molded case circuit breaker UEM5 Series Molded Case Circuit Breakers (MCCB for short) are
applicable to the electrical network under the condition of AC50Hz/60Hz,
rated working current 10A - 800A, rated insulation voltage 690V and rated
working voltage 400V or below with overload, short-circuit and
under-voltage protection performances, and can be used to protect the wires
and equipment from damage. Normally, the circuit breakers also take the
role of infrequent turn-on or turn-off and infrequent motor starting-up.
The circuit breakers are of characteristics of compact structure, small size and high breaking
capacity, which can be equipped with the accessories such as under-voltage release, shunt release,
auxiliary contact, alarm contact, motor-driven operation mechanism, turning operation handle and
etc.
This series of circuit breakers have a disconnecting function and the corresponding symbol is shown
as “ ”.
UEM5-
Installation pattern code
No code: wiring in front of the
board
H: wiring on back of the board
R: wiring by insertion
Number of poles
3: three poles
4: four poles
Rated Frame Current
Inm=63
Inm=100
Inm=225
Inm=400
Inm=800
Operation Pattern
No code: direct operation
P: motor-driven
Z: turning handle Application code
No code: for power
distribution protection
2: for motor protection
Short circuit breakers capacity
L: typical
M: second high breaking type
Rated current Code for release pattern and
internal accessories
Refer to the release pattern
and internal accessories
codes in detail
The N-pole of the four-pole
Refer to the release pattern
and internal accessories codes
in detail
100 M P / 80 3 300 2 A H
Main specification
Type Rated
current(A)
Pole
number
Rated
insulation
voltage Ui
(V)
Rated
working
voltage
Ue(V)
Rated ultimate/
service short-circuit
breaking capacity
Icu / Ics (kA)
Wiring in front
of board
Installation
dimension(mm)
UEM5-63L 10,16,20,25,
32,40,50,63 3/4 AC500 35/20
X Y
25 111
UEM5-100L 3 35/22
UEM5-100M
10,16,20,25,
32,40,50,63 3/4 50/35
X Y
25 132
UEM5-225L 3 35/25
UEM5-225M
100,125,140,
160 3/4 50/35
X Y
35 126
UEM5-225L 3 35/25
UEM5-225M 180,200,225
3/4 50/35
X Y
35 126
UEM5-400L 3 50/42
UEM5-400M
225,250,315,
350,400 3/4 65/50
X Y
44 194
UEM5-800L 3 50/50
UEM5-800M 400,500,630
3/4 65/50
X Y
70 243
UEM5-800L 3 50/50
UEM5-800M 700,800
3/4
AC690
AC400
65/50
X Y
70 243
UEM5L series molded case circuit breakers with residual current protection UEM5L Series molded case circuit breakers with residual current
protection (circuit breakers for short below) are applicable to the electrical
network under the condition of AC50Hz/60Hz, rated working current
16A~800A, rated insulation voltage 690V and rated working voltage 400V
or below, which can be used to protect human body and equipment from
electric shock and residual current, as well as to prevent from fire danger
due to earth-fault current caused by equipment insulation damage.
Normally, the circuit breakers also take the role of infrequent turn-on or turn-off and infrequent
motor starting-up.
The circuit breakers are of characteristics of compact structure, small size and high breaking
capacity, which can be equipped with the accessories such as under-voltage release, shunt release,
auxiliary contact, alarm contact, motor-driven operation mechanism, turning operation handle, etc.
This series of circuit breakers have a disconnecting function and the corresponding symbol is shown
as “ ”.
residual current circuit breakers
UEM5
Number of poles
3: three poles
4: four poles
Rated Frame Current
Inm=100
Inm=225
Inm=400
Inm=800
Operation Pattern
No code: direct operation
P: motor-driven
Z: turning handle
Installation pattern code
No code: wiring in front
of the board
H: wiring on back of the
board
R: wiring by insertion
Application code
No code: for power
distribution protection
2: for motor protection
Short circuit breaking capacity
L: typical
M: related high breaking type
Rated
current
Code for release pattern and internal
accessories
Refer to the release pattern and
internal accessories codes in detail
The N-pole of the four-pole
Refer to the release pattern
and internal accessories
codes in detail
L - 100 L P / 80 3 300 2 A H
Main specification
Type Rated
current(A)
Pole
number
Rated
insulatio
n voltage
Ui(V)
Rated
working
voltage
Ue(V)
Rated
residual
operating
current I n△
(mA)
Delay
time (s)
Rated ultimate/
service
short-circuit
breaking capacity
Icu / Ics (kA)
UEM5L-100L 3 35/22
UEM5L-100M
16,20,25,
32,40,50,
63,80,100 3/4 50/35
UEM5L-160L 3 35/25
UEM5L-160M
100,125,
140,160 3/4 50/35
UEM5L-225L 3 35/25
UEM5L-225M
180,200,22
5 3/4
30/100/300
adjustable
Non-time
delay/
0.1/0.3
adjustable
50/35
UEM5L-400L 3 50/42
UEM5L-400M
225,250,31
5,
350,400 3/4
100/300/500
adjustable
Non-time
delay
0.2/0.5
adjustable
65/50
UEM5L-630L 3 50/50
UEM5L-630M
400,500,63
0 3/4 65/50
UEM5L-800L 3 50/50
UEM5L-800M
630,700,80
0 3/4
AC690 AC400
300/500/1000
adjustable
Non-time
delay
0.5/1
adjustable 65/50
Remark: 3-pole units with residual current protection will be a special standard
UEM5Z1 series electronic molded case circuit breakers UEM5Z1 series electronic molded case circuit breakers (circuit breakers for short
below) are applicable to the electrical network under the condition of
AC50Hz/60Hz, rated working current 800A, rated insulation voltage 690V and
rated working voltage 400V or below, with overload long-delay definite time,
instantaneous short-circuit and under-voltage protection functions. Normally, the
circuit breakers also take the role of infrequent turn-on or turn-off and infrequent
motor starting-up.
The circuit breakers are of characteristics of compact structure, small size and high breaking
capacity, which can be equipped with the accessories such as under-voltage release, shunt release,
auxiliary contact, alarm contact, motor-driven operation mechanism, turning operation handle, etc.
This series of circuit breakers have a disconnecting function and the corresponding symbol is shown
as“ ”
intelligent over-current tripper (withour residual proction)
UEM5
Number of poles
3: three poles
4: four poles
Rated Frame Current
Inm=100
Inm=225
Inm=400
Inm=800
Operation Pattern
No code: direct operation
P: motor-driven
Z: turning handle
Installation pattern code
No code: wiring in front of
the board
H: wiring on back of the
board
R: wiring by insertion
Application code
No code: for power
distribution protection
2: for motor protection
Short circuit breaking capacity
L: typical
M: Related high breaking capacity type
Rated
current
Code for release pattern and internal
accessories
Refer to the release pattern and
internal accessories codes in detail
The N-pole of the four-pole
Refer to the release pattern
and internal accessories codes
in detail
Z1 - 100 L P / 80 3 300 2 A H
Main specification
Type
Rated
current
(A)
Setting
current
Ir1 (A)
Pole
number
Rated
insulation
voltage Ui
(V)
Rated
working
voltage
Ue(V)
Rated ultimate/
service
short-circuit
breaking capacity
Icu / Ics (kA)
Wiring in front
of board
Installation
dimension
UEM5Z1-100L 3 35/22
UEM5Z1-100M 32,100
10~32A
adjustable
40~100A
adjustable
3/4 50/35
X Y
30 132
UEM5Z1-225L 3 35/25
UEM5Z1-225M 225
100~225A
adjustable 3/4 50/35
X Y
35 126
UEM5Z1-400L 3 50/42
UEM5Z1-400M 400
200~400A
adjustable 3/4 65/50
X Y
44 215
UEM5Z1-800L 3 50/50
UEM5Z1-800M 630
400~630A
adjustable 3/4 65/50
X Y
70 243
UEM5Z1-800L 3 50/50
UEM5Z1-800M 800
600~800A
adjustable 3/4
AC690 AC400
65/50
X Y
70 243
UEM5Z2 series electronic MCCB with residual current protection UEM5Z2 Series electronic molded case circuit breakers with residual current
protection(circuit breakers for short below) are applicable to the electrical
network under the condition of AC50Hz/ AC60Hz, rated working current
800A, rated insulation voltage 690V and rated working voltage 400V or
below with overload long-delay inverse time, short-circuit short-delay inverse
time, short-circuit short-delay definite time, instantaneous short-circuit and
under-voltage protection. Normally, the circuit breakers also take the role in
infrequent turn-on or turn-off and infrequent motor starting-up.
The circuit breakers are of compact structure, small size and high breaking capacity, which can be
equipped with the accessories such as under-voltage release, shunt release, auxiliary contact, alarm
contact, motor-driven operation mechanism, turning operation handle, etc.
This series of circuit breakers have a disconnecting function and the corresponding symbol is shown
as“ ”.
intelligent over-current
tripper(residual proction)
UEM5
Number of poles
3: three poles
4: four poles
Rated Frame Current
Inm=100
Inm=225
Inm=400
Inm=800
Operation Pattern
No code: direct operation
P: motor-driven
Z: turning handle
Installation pattern code
No code: wiring in front of the
board
H: wiring on back of the board
R: wiring by insertion Application code
No code: for power
distribution protection
2: for motor protection
Short circuit breakers
capacity
L: typical
M: second high
breaking type
Rated
current
Code for release pattern and internal
accessories
Refer to the release pattern and
internal accessories codes in detail
The N-pole of the four-pole
Refer to the release pattern
and internal accessories codes
in detail
Z2 - 100 L P / 80 3 300 2 A H
Main specification
Type
Intelligent
Releasing
Rated
current(A)
Intelligent
Releaser
Setting
Current(A)
Pole
number
Rated
Insulation
Voltage
Ui(V)
Rated
working
Voltage
Ue(V)
Rated
Residual
Action
Current
IΔn(mA)
Delay
time(s)
Ultimate/
Service
short-circ
uit
breaking
capacity
Icu / Ics
(kA)
UEM5Z2-100L 3 35/22
UEM5Z2-100M 32,100
10~32A
Adjustable
40~100A
Adjustable
3/4 50/35
UEM5Z2-225L 3 35/25
UEM5Z2-225M 225
100~225A
Adjustable 3/4
30/100/300
Adjustable
Non-delay
/0.1/0.3
adjustable
50/35
UEM5Z2-400L 3 50/42
UEM5Z2-400M 400 200~400A
Adjustable 3/4
100/300/50
0
Adjustable
Non-delay
/0.2/0.5
adjustable65/50
UEM5Z2-800L 3 50/50
UEM5Z2-800M 630
400~630A
Adjustable 3/4 65/50
UEM5Z2-800L 3 50/50
UEM5Z2-800M 800
600~800A
Adjustable 3/4
AC690 AC400
300/500/10
00
Adjustable
Non-delay
/0.5/1
adjustable65/50
Remark: 3-pole units with residual current protection will be a special standard
UET5 series automatic transfer switching UET5 Series automatic transfer switching is applicable to the
double-circuit power supply (power distribution to power
distribution, or power distribution to generator), rated frequency
50HZ/60HZ, and rated voltage 400V. The power is shifted
automatically when one power breaks down, which ensures the reliability and safety of the power
supply and makes the power switch to achieve the intelligent unmanned operation and remote
control.
This device adopts a motor-driven operation mechanism with patent technique, providing with
multifunctional intelligent controllers to meet various market demands. This device conforms to
GB/T14048.11 standard.
UET5-□ □ □ /□ □ -□ □
Transfer mechanism: Y- Integrative F-Split
Power supply: A- power distribution –power distribution;
B-power distribution- generator
N-pole types for 4-pole circuit breaker Type A: N-pole without over-current release, it has been switch-on all along, and does not act as other three poles. Type B: N-pole without over-current release, it acts as other three poles. Type C: N-pole fixed with over-current release, it acts as other three poles. Type D: N-pole fixed with over-current release, it has been switch-on all
along, and does not act as other three poles.
Code of release pattern and accessories: 200-Electromagnetic release 300- Thermo/ electromagnetic release
Number of Pole: 2-two poles; 3-three poles; 4-four poles
Rated current of the breakers
Rated short circuit breaking capacity rating
Rated frame current of the breakers
Remark:UET5-63 only with Integrative Structure(Y), Power distribution-Power distribution
Structure.
Main specifications & Performance parameter
Type
Short circuit
breaking
capacity
Rated
Current (A)
Pole
number
Rated
Insulation
Voltage
Ui(V)
Rated
working
Voltage Ue
(V)
Ultimate/ working
short-circuit
breaking capacity
Icu / Ics (kA)
6
UET5-63
6,10,16,
20,25,32,
40,50,63
3/4 AC500 AC400 4.5
L 3 35/22
UET5-100 M
16,20,25,
32,40,50,
63,80,100 3/4 50/35
L 3 35/25
UET5-225 M
100,125,140,
160,180,200,
225 3/4 50/35
L 3 50/42 UET5-400
M
225,250,315,
350,400 3/4 65/50
L 3 50/50 UET5-800
M
400,500,630,
700,800 3/4
AC690 AC400
65/50
Remark: UET5-63 Series automatic transfer switches have been equipped with XMB0 series min.
circuit breaker.
UET6 series automatic transfer switching
UET6 series automatic transfer switching equipment
consists of switch main body and transfer controller.The
product adopts electromagnetic-driven, the transfer
controller adopts main and backup power supply of
working voltage AC 220V, which requires no additional
control power supply. The switch body has electric or mechanical switch-on indicator, which can be
used as an indicator for disconnect function.
This product is of compact size, simple structure, easy operation, quick transferring speed and long
usage life. The product conforms to GB/T14048.11-2002 standard.
UET6- □ □ □ □
2:Two-pole(Only for products below 125A) 3:Three-pole 4:Four-pole
Rated current
NA: Integrative styles ATS below 125 A
(non- generator starts function) C: Split style ATS below 125 A T: Rated current from 160A to 400A two sections
split ATS TN: Rated current from 160A to 400A three sections
split ATS M: Rated current from 630A to1600A two sections
split ATS
Rated frame current
Main Spec. and Performance Parameter
Endurance life(Cycle)
Type Rated
current(A)
Pole
number
Operating
current(A)
Rated
insulation
voltage Ui
(V)
Mechanical
life
Electrical
life
Operation
Frequency
UET6-32NA 16,20,25,32
UET6-125NA 40,50,63,
80,100,125
2,3,4
3.5 5 8000 3000
15s/cyc.
UET6-32C 16,20,25,32
UET6-125C 40,50,63,
80,100,125
2,3,4
3.5 5 8000 3000
15s/cyc.
3
UET6-400T
160,200,250
,
315,400 4
7 35 6000 2000
10s/cyc.
3 UET6-400TN 200,400
4
6 10 5000 1000
10s/cyc.
630 3,4 15 15s/cyc.
800 3,4 18 20s/cyc.
1000 3,4 20 25s/cyc.
1250 3,4 25 25s/cyc.
UET6-1600M
1600 3,4
16
32
2500 500
25s/cyc.
XMB0-63 series mini circuit breaker
Conform to standards GB10963.1 and IEC60898-1;
With protective functions of overload and short circuit;
Can be equipped with various accessories, such as residual release,
auxiliary contact, alarm contact, shunt release, under voltage release, bus
bar and so on;
Adopt any combination, the matched modular and modulus structure series;
Adopt TH35mm standard din rail, easy installation;
Rated working voltage: AC230 / 400V;
Rated working current: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A;
Releasing characteristic:
B type instantaneous releasing current: 3-5In, for non-inductance or tiny-inductance circuit.
C type instantaneous releasing current: 5~10In, for illumination distribution circuit
D type instantaneous releasing current: 10~20In, for industrial distribution system
The product is applicable to the lead wires which are 25mm² or below.
XMB0 – 63 □ □ / □
Pole number: 1P, 2P, 3P, 4P
Rated operating current:6, 10, 16,
20, 25, 32, 40, 50, 63
Instantaneous tripping characteristic
Type B: 3~5In
Type C: 5~10In
Type D: 10~20In
Rated frame current
XMB0 series high breaking capacity mini circuit breaker (MCB) XMB0 Series miniature circuit breaker is of high breaking capacity and
current-limiting characteristic, with power insulated function. Dual-use terminal
can connect with both bus bar and lead with optional insertion direction. MCB
can be assembled to the combined switches by multi accessories. MCB is used
to protect the circuit from overload and short circuit of AC 50Hz/60Hz, rated
Voltage 230/400V, rated current under 63A, and can be applicable to infrequent
turn-on and turn-off operation and electrical insulation. The products conform to
standards IEC60898 or GB10963.
XMB0 1 63 C
Pole number 1P,2P,3P,4P
Instantaneous characteristic types
B/C/D Rated current6,10,16,20,25, 32,40,50,63A
XMB0 series MCB with single-mould and dual-cutting Conform to the standards IEC60898 and GB10963.1
High breaking capacity 6kA
Rated voltage 230V
Small size, the width for one mould about 18mm
Wide current range, can reach up to 40A
Interruptible shunt, more reliable
High terminal connection capacity 1~16mm2
Protect the electric circuit from overload and short circuit
Applicable for protecting the civilian illumination and socket loop
XMB0 1 40 C N
Pole number1P+N
Rated current10,16,20,25, 32,40A
Instantaneous characteristic
types
C
Interruptible shunt
XMBL0-32 series residual protection circuit breaker
Conform to standards GB16917.1 and IEC61009-1;
With the all characteristics of XMB0-63 mini circuit breaker;
With protector of over load, short circuit and leakage;
Rated operating voltage:AC230 / 400V;
Rated operating current:6A, 10A, 16A, 20A, 25A, 32A,(40A),(50A);
Releasing characteristic: Type C instantaneous tripping current 5~10In,
applied in illumination distribution system;
Rated operating short circuit breaking capacity: 6KA;
The product is applicable to lead wires which are 10mm² or below.
X MBL0 – 32 C □ / □
Pole No.:1P+N,2P,3P,3P+N,4P
Rated operating current:6, 10, 16, 20, 25, 32,(40),(50)
Type C instantaneous tripping
Rated frame current
Notice: The special standard products for bracket
XMBL0 series dual mould residual circuit breaker (RCBO)
Conform to standards IEC61009 and GB16917.1
With residual, overload and short circuit protective function
Very high breaking capacity
Compact structure, small size(2 mould for 36mm width)
The N shunt with interruptible function, more reliable.
Double functioned terminal, better connection capacity
Wide rated current range, can be applied in the main switch for house
The surge protective current to 3000A
The circuit board past the 168 hours aging test
With contact status indicator
Optional line insertion
Ultimate breaking capacity 8kA
Rated voltage 230V.a.c
Rated current 6~40A
Frequency 50/60Hz
Rated residual operated current 30mA
Connected lead section max.25mm2
Standard installation din rail
XMBL0 1 40 C E
Notice: Can provide the over voltage protective products based on customer’s needs (280±5%V).
Pole number
2Poles with 1
protective pole
Rated
current
6,10,16,20,
25,32,40A
Instantaneous
characteristic
types
C/D
Electronic
XMG0 series insulated disconnector Applicable for industrial, commercial and civilian electric line as main disconnector.
Conform to standards IEC60947.3,GB14048.3
Rated voltage 230/400V.a.c
Frequency 50/60Hz
Application type: AC-22B
Double functioned terminal, high connection capability
Connect to lead section max.50mm2
With contact status indicator XMG0 1 40
Pole number 1P,2P,3P,4P
Rated current 40,63,80,100A
UES5 Series Surge Protector UES5 series surge protector, which conforms to standards IEC61643-1,GB18802.1, and is
applicable to various power supply systems of AC 50Hz/60Hz and rated voltage 380V. The product
has a lapsing-divorcement device and a reliable operating status indication, and the function of
remote communicated contact is available to achieve long-distance control; the response time is less
than 25 nanoseconds, and the product adopts 35mm electrical rail with safe use and easy
installation.
Pole 1,2,3,4 , Max. continuous working voltage
1+NPE,
2+NPE,
3+NPE
Norminal current In(kA) Remote signal Protection grade B,C,D
UES5 C/ - □- 20- 420- X
Type Conforming
standard
Rated working Voltage
Un
Rated discharge current
In(8/20us)
Max. discharge current
In(8/20us)
Responding time t(ns)
Protecting grade
accordance with IEC529
UES5D/□-10-140
UES5D/□-10-275
UES5D/□-10-320
UES5D/□-10-385
UES5D/□-10-420
140 275 320 385 420
5kA 10kA
UES5D/□-20-275
UES5D/□-20-320
UES5D/□-20-385
UES5D/□-20-420
275 320 85 420
10kA 20kA
UES5C/□-40-275
UES5C/□-40-320
UES5D/□-40-385
UES5D□-40-420
275 320 385 420
20kA 40kA
UES5C/□-60-275
UES5C/□-60-320
UES5C/□-60-385
UES5C/□-60-420
275 320 385 420
30kA 60kA
UES5B/□-80-275
UES5B/□-80-320
UES5B/□-80-385
UES5B/□-80-420
275 320 385 420
40kA 80kA
UES5B/□-100-320
UES5B/□-100-385
UES5B/□-100-420
320 385 420
50kA 100kA
UES5B/□-140-320
UES5B/□-140-385
UES5B/□-140-420
IEC61643-1 GB18802.1
320 385 420
70kA 140kA
Below 25 IP20
UEB-63 series
Miniature Circuit Breaker
- 1 -
UEB-63 Series Miniature Circuit Breaker
Overview and principle
UEB-63 series miniature circuit breaker (MCB) mainly used in the circuit of AC 50/60Hz, rated
voltage 230V/400V, rated current under 63A, to protect the circuit and electric equipments of building
and the similar places from over current, it’s also applicable for the infrequent opening and closing
operation.
Type nomenclature
Number of poles: 1P, 2P, 3P, 4P
Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A,
20A, 25A, 32A, 40A, 50A, 63A
Instantaneous tripping characteristic:
Type B: 3~5In
Type C: 5~10In
Type D: 10~20In
Breaking capacity: “H” for 10k A
Without code: 6kA
Frame current (A)
Miniature circuit breaker
Corporation code: Homer
Application condition
Ambient temperature: -5C~ +40C°;
Relative humidity 95% (under 20 )
Altitude 2000m;
Pollution degree: class 2;
The places no obvious vibration and shock.
UEB-63 series
Miniature Circuit Breaker
- 2 -
Conforming standard
Products features
Overload and short circuit protection;
Use the arc resistant material, high breaking capacity, long electrical life;
Use the safe wiring structure against the electrical shock;
The shelf and the parts use the imported high flame and stamping resistance plastic
Module structure for free combination;
Suitable for disconnecting, symbol is
Main specification
Rated voltage: AC230 / 400V;
Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A;
Instantaneous tripping characteristic
Type B: 3~5In,
Type C: 5~10In,
Type D: 10~20In;
Breaking capacity: 6kA, 10kA;
Number of poles: 1P, 2P, 3P, 4P
UEB-63 series
Miniature Circuit Breaker
- 3 -
Wiring capacity
35mm² and below
Dimension
Products selection table
UEB-63 seris
Pole
no.Type B Type C Type D
Rated
current
Breaking
capacity
UEB-63 series
Miniature Circuit Breaker
- 4 -
Pole
no.Type B Type C Type D
Rated
current
Breaking
capacity
UEB-63 series
Miniature Circuit Breaker
- 5 -
UEB-63H Series
Pole
no.Type B Type C Type D
Rated
current
Breaking
capacity
UEB-63 series
Miniature Circuit Breaker
- 6 -
UEB-63H series
Pole
no.Type B Type C Type D
Rated
current
Breaking
capacity
UEBL-63/40 H series
Residual current circuit breaker
UEBL-63/40(H) series residual current circuit breaker
Overview and principle
mainly used in the circuit
of AC 50/60Hz, rated voltage under 400V, rated current under 63A, to protect the circuit and electric
equipments of building and the similar places from over current, as well as providing the protection once
the over current equipment fault and the fire risk due to the ground current fault it’s also applicable for
the infrequent opening and closing operation.
Type nomenclature
- 7 -
Number of poles: 1P+N,2P,3P,3P+N,4P
Rated current(A): 6A,10A,16A,20A,25A,
32A,40A,50A,63A
Instantaneous tripping characteristic:
Type C: 5~10In
Type D: 10~20In
Rated breaking capacity: H: 10kA,
Without H: 6kA
Frame current: 63, 40
Residual current circuit breaker
Corporation code: Homer
UEBL-63/40 H series
Residual current circuit breaker
Conforming standard
Application condition
Ambient temperature: -5C~ +40C°
Relative humidity 95% (under 20 )
Altitude 2000m;
Pollution degree: class 2;
The places no obvious vibration and shock.
Products features
It’s of the all features of UEB-63 series MCB;
- 8 -
Overload, short circuit and residual current protection;
Protect the human from the indirect contact;
Provide the supplementary protection from the direct contact;
Provide the protection on insulation failure of electric equipment
(Such as electric fire);
Manual control: handle allows two kinds of reset mode
! Circuit breakers and residual current operated devices reset
at the same time
! Circuit breakers and residual current operated devices reset
individually, residual current operated device resets before the circuit breaker resets.
Prevent transient overvoltage (Lightening, state grid operation) caused
by the malfunction.
UEBL-63/40 H series
Residual current circuit breaker
Main specification
UEBL-63 series
! Rated voltage: AC230/400V;
! Rated current: 6A, 10A, 16A, 20A, 25A, 32A,, 40A, 50A, 63A;
! Instantaneous tripping characteristic:
Type C: 5~10In, applied in the distribution circuit illumination;
Type D: 10~20In, applied in the industrial distribution system;
! Breaking capacity: 6kA, 10kA;
! Rated residual operated current: 30mA
! Number of poles: 1P+N,2P,3P,3P+N,4P
UEBL-40(H) series
! Rated voltage: AC230;
! Rated current: Type C: 6A, 10A, 16A, 20A, 25A, 32A,, 40A;
Type D: 6A, 10A, 16A, 20A;
! Instantaneous tripping characteristic:
Type C: 5~10In, applied in the distribution circuit illumination;
Type D: 10~20In, applied in the industrial distribution system;
! Breaking capacity 8kA
! Rated residual operated current: 30mA
! Number of poles: 1P+N
Wiring capacity
! 35mm² and below(UEBL-40 series for 25mm2and below)
- 9 -
UEBL-63/40 H series
Residual current circuit breaker
Products selection table
UEBL-40 H series
Pole no. Type C Type D Rated
current
Breaking
capacity
- 11 -
UEBL-63/40 H series
Residual current circuit breaker
- 12 -
UEBL-63 series
Pole no. Type C Type D Rated
current
Breaking
capacity
UEBL-63/40 H series
Residual current circuit breaker
- 13 -
UEBL-63 series
Pole no. Type C Type D Rated
current
Breaking
capacity
UEBL-63/40 H series
Residual current circuit breaker
- 14 -
UEBL-63H series
Pole no. Type C Type D Rated
current
Breaking
capacity
UEBL-63/40 H series
Residual current circuit breaker
- 15 -
UEBL-63H series
Pole no. Type C Type D Rated
current
Breaking
capacity
UEG0-100 series disconnector
Disconnector
UEG0-100 series
Application
To make and break the circuit under the load condition, it’s of disconnecting
function, which can disconnect the circuit during inspection and maintenance.
Type nomenclature
Number of poles: 2P 3P 4P
Rated current: 40A 63A 80A 100A
Frame current
Corporation code: Homer
Products features
Applicable in the industrial, commercial and residential circuit as the main switch.
Conform to IEC60947.3,GB14048.3 standard
Rated voltage: AC230/400V
Frequency: 50/60Hz
Use type: AC-22B
Double function terminal, strong wiring capacity
Connection lead section area: max.50mm2
It’s of contact status indicator
16
UEG0-100 series disconnector
Disconnector
Products selection table
Max wiring
capacity (mm²)Pole no. Type
Rated
current
(A)Rated voltage
V
Width
mm
17
- 1 -
XMC0 Series Definite Purpose Contactors
Description HOMER XMC0 series high performance definite purpose contactors (1-Pole,
1-Pole+1Shunt, 1-Pole+1NC, 1-Pole+1NO, 2-Pole, 3-Pole,3-Pole+1NC and
3-Pole+1NO ,from 12A to 90A ) are ideal for(HVAC)air conditioning, refrigeration, heating, data
processing, welding, elevators, hoists & cranes, washing machine, lighting, pools & spas and food
service equipment. XMC0 series definite purpose contactors meet ARI 780 and UL508 standard
Features
1. Unique structure of amortization system eliminates contact bounce.
2. No tools required for snap-on accessories require that make modification quick and easy.
3. Various terminal options for specific application needs.
4. Easy to change coil.
5. Universal mounting plate allows easy replacement for other brands.
6. Heavy duty Silver Metal Oxide composition contacts ensure long electrical endurance.
7. Coils are Class F (155℃) temperature insulated with wide range of voltage and 50/60Hz ratings.
8. Double E Magnet Assembly provides optimal performance with reduced power consumption.
9. Effective dustproof structure.
10. UL, TÜV, CCC, CE approved.
Type model nomenclature - Ordering Information
XM C 0 - □ □ · □ □ □ □ □ □ □ 1 2 3 4 5 6 7 8 9 10 11 12
Number digit 1: Manufacturer’s code
XM – Xiamen Hongmei Electronic Co., Ltd.
Number digit 2: Product Type
C – Contactor
- 2 -
Number digit 3: Design Sequence Number – 0
Number digit 4: Full Load Amperes (FLA) – 12, 18, 20, 25, 32, 40, 50, 63, 75 or 90
Number digit 5: Number of Poles – 1,2, 2R, 3, 3A, 3B,3R, 5, 6, 7, 8 or 9
Number
digit 5 1 2* 2R 3 3A 3B
Number
of poles
1-pole+
1shunt 2-pole
2-pole
(1a1b) 3-pole
2-pole
(3pl frame)
3-pole
(small frame)
Number
digit 5 3R 5 6 7 8 9
Number
of poles
3-pole
(2a1b) 1-pole+1NC 1-pole+1NO 1-pole
3-pole+1NC
( small frame)
3-pole+1NO
(small frame)
Number digit 6: Coil Voltage – D, E, F, I, L, N, U
Number digit 6 D E F I J* L N U
50Hz 12V 24V 110-120V 208-220V 220V -- 380-415V 550-600V Coil
voltage 60Hz 12V 24V 110-120V 208-240V -- 277V 440-480V 550-600V
Number digit 7: Mounting plate – A, B
A – plastic base
B – metal plate
Number digit 8: Cover –A, B
A – long cover
B – short cover
Number digit 9: Terminal –A, B, C, D, E, F
A – screw w/quick connect
B – sems clamp w/quick connect
C – slotted & hex head washer w/ quick connect
D – box lug w/ quick connect
E –box lug w/quick connect (Line)
slotted&hex head washer w/quick connect (Load)
F –slotted&hex head washer w/quick connect (Line)
box lug w/quick connect (Load)
- 3 -
Number digit 10: Auxiliary contact blocks (for 3-pole) (Left & Right) side– 0, 1, 3, 4, 5, 6, 1P, 3P, 4P, 5P, 6P
Auxiliary contact block at left Auxiliary contact block at right
0- None (Standard type)
1- 1NC+1NO, pressure plate screws w/ quick connect
3- 1NC, pressure plate screws w/ quick connect
4- 1NO, pressure plate screws w/ quick connect
5- 2NC, pressure plate screws w/ quick connect
6- 2NO,pressure plate screws w/ quick connect
1P- 1NC+1NO, pressure plate screws
3P- 1NC, pressure plate screws
4P- 1NO, pressure plate screws
5P-2NC, pressure plate screws
6P-2NO, pressure plate screws
For example:
34P- 1NC pressure plate screws w/ quick connect at left and 1NO pressure plate screws at right
56- 2NC pressure plate screws w/ quick connect at left and 2NO pressure plate screws w/ quick connect at right
Number digit 11: Coil terminals– Blank, F
Blank – dual terminals without screws in 1-and 2- pole models and single terminals with screws in 3-pole models.
F-dual terminals with screws in 3- pole models.
Number digit 12: Power quick terminals– Blank, G, D, Q
Blank – quad terminals in 1-and 2- pole models.
dual terminals in 3-pole models.
G-without any terminals
D-dual terminals in 1-and 2- pole models
Q-dual terminals at the side near coil terminal and quad terminals at the other side in 3-pole models.
*If this will be the final digit(s) in selection, omit from model nomenclature.
- 4 -
Characteristics
Rated insulation voltage V 690
Conforming to standard IEC60947-4-1, GB14048.4, EN60947, ARI780
Approvals CCC UL CSA TÜV SEMKO EK CE
Protective treatment Total climate tropical use “TH”
Operating position Vertical ±5°
Operating altitude m 2000
operation ℃ -25℃~+70℃ Ambient temperature
storage ℃ -40℃~+70℃
Relative humidity 95% at 55℃
Pollution degree 3
contactor open g 6 Shock resistance 1/2 sine wave=11 ms contactor
closed g 15
contactor open g 2 Vibration resistance 5 to 300 Hz contactor
closed g 4
Performance
XMC0-
Poles 1 2 3 3A 3B 5 6 7 8 9
Rated insulation voltage V 690
Rated operating voltage V 480/277(60Hz) or 400/240(50Hz)600/345(60Hz)
Full load ampere(FLA) A 12 18 25 32 40 50 63 75 90
Resistive load ampere(RLA) A 20 25 35 40 50 63 75 95 120
Making capacity(230V cosφ0.45) A 12×FLA
Breaking capacity(230V cosφ0.45) A 10×FLA
Switching frequency op/h 360
Electrical endurance cycle 200,000
Mechanical endurance cycle 3,000,000
- 5 -
Pole Characteristics Locked Rotor amps Horsepower ratings Full
Load Amps
Resistive Amps Per
Pole 230
/277V 480V 600V 230V
1 Phase
480V 3
Phase
600V 3
Phase
Poles Catalog Number
3P XMC0 – 123 3P+1NC XMC0 – 128 12 20 72 60 48 1.5 3 5 3P+1NO XMC0 – 129 3P XMC0 – 183 3P+1NC XMC0 – 188 18 25 108 90 72 2 5 7.5 3P+1NO XMC0 – 189 1P+Shunt XMC0 – 251 2P XMC0 – 252 2P(1a1b) XMC0 – 252R 3P(at 40A frame) XMC0 – 253 2P(at 3P) XMC0 – 253A 3P(at 25A frame) XMC0 – 253B 3P(2a1b) XMC0 – 253R 1P+1NC XMC0 – 255 1P+1NO XMC0 – 256 1P XMC0 – 257 3P+1NC XMC0 – 258
25 35 150 125 100 3 7.5 10
3P+1NO XMC0 – 259 1P+Shunt XMC0 – 321 2P XMC0 – 322 2P(1a1b) XMC0 – 322R 3P XMC0 – 323 2P(at 3P) XMC0 – 323A 3P(2a1b) XMC0 – 323R 1P+1NC XMC0 – 325 1P+1NO XMC0 – 326
32 40 180 150 120 3 10 15
1P XMC0 – 327 1P+Shunt XMC0 – 401 2P XMC0 – 402 2P(1a1b) XMC0 – 402R 3P XMC0 – 403 2P(at 3P) XMC0 – 403A 3P(2a1b) XMC0 – 403R 1P+1NC XMC0 – 405 1P+1NO XMC0 – 406
40 50 240 200 160 5 15 20
1P XMC0 – 407 3P XMC0 – 503
50 63 300 250 200 5 20 25 2P(at 3P) XMC0 – 503A 3P XMC0 – 633
63 75 360 300 240 7.5 25 30 2P(at 3P) XMC0 – 633A 3P XMC0 – 753
75 95 450 375 300 15 40 50 2P(at 3P) XMC0 – 753A 3P XMC0 – 903
90 120 540 450 360 15 50 60 2P(at 3P) XMC0 – 903A
- 6 -
Auxiliary contacts block characteristics
Conventional thermal current (A) 10
Rated insulation voltage (V) 690
A600(AC-15) 230/380V
3/1.9 Rated operational current
(A) N600(DC-13) 11O/230V
2.2/1.1
Coil characteristics
Voltage Part number Inrushed
VA Sealed
VA Sealed Watts Pick-up Drop-out
XMC0-□1/5/6/7 40 7.5 2.5-3.5
XMC0-□2 45 8 2.5-4
XMC0-□3/3A/3R 90 16 3.5-5
XMC0-□3/3B/8/9 90 16 3.5-5
XMC0-503/633 145 20 5-7
XMC0-753/903 235 32 10-12
≤0.8Us ≥0.2Us
Dimensions
1-pole/1-pole+shunt/1p+1NC/1pole+1NO (plastic base, 25-40A)
- 1 -
XMCK Series Definite Purpose Contactors
Description HOMER XMCK series AC Contactors are applied for controlling of air conditioning, electric motor load under condition of frequency 50Hz/60Hz, rated insulation voltage ≤690V, rated current ≤40A. (IEC standard AC-8a,AC-8b), and can be used for the other home appliance and similar electric motor load. XMCK series AC contactors conform to ARI 780 and UL 508 standard.
Features 1. Low cost design project of contactor. 2. Solid configuration design, electric pure steel magnet.
3. Easy to change coil.
4. Compact size and configuration, universal mounting plate allows easy replacement of other brands.
5. Heavy duty Sliver Metal Oxide composition contacts ensure long electrical endurance.
6. Coils are Class F (155℃) temperature insulated with wide range of voltage and 50/60Hz ratings.
7. UL,KETI,TÜV and CCC approved.
Type model nomenclature - Ordering Information XM C K - □ □ □ □ 1 2 3 4 5 6 7
Number digit 1: Manufacturer’s code
XM – Xiamen Hongmei Electronic Co., Ltd.
Number digit 2: Product Type
C – Contactor
Number digit 3: Design number - K
Number digit 4: Resistive Load Ampere(RLA)– 25, 30, 40 or 50.
Number digit 5: Number of Poles – D, DN or 2.
Number digit 5 D DN 2
Number of poles 1-pole 1-pole+1shunt 2-pole
Number digit 6: Coil Voltage –024, 120, 240, 277
Number digit 6 024 120 240 277
60Hz 24V 110-120V 208-240V 277V Coil voltage
50Hz 24V 110-120V 208-240V ---
- 2 -
Number digit 7:Terminal –A, B, C, D, E, F
A – screw w/quick connect
B – sems clamp w/quick connect
C – slotted & hex head washer w/ quick connect
D – box lug w/ quick connect
E –box lug w/quick connect (Line)
slotted&hex head washer w/quick connect (Load)
F –slotted&hex head washer w/quick connect (Line)
box lug w/quick connect (Load)
Characteristics Rated insulation voltage V 690
Conforming to standard IEC60947-4-1, GB14048.4, ARI780, UL508
Approvals UL/CUR SEMKO KETI CCC
Operating position Vertical ±5°
Operating altitude m 2000
operation ℃ -25℃~ +70℃ Ambient temperature
storage ℃ -40℃~ +70℃
Relative humidity 90-95%RH
Pollution degree 3
Performance
XMCK-
Poles D DN 2
Rated insulation voltage V 690
Rated operating voltage V 480/277,60Hz
Or 400/230,50Hz; 600/345,60Hz
Full load ampere(FLA) A 20 25 30 40
Resistive load ampere(RLA) A 25 30 40 50
Making capacity(230V cosφ0.45) A 12×FLA
Breaking capacity(230V cosφ0.45) A 10×FLA
Switching frequency op/h 360
Electrical endurance(ARI 780) cycle 100,000
Mechanical endurance(ARI 780) cycle 500,000
- 3 -
Pole Characteristics
Locked Rotor amps Power Full Load Amps
Resistive Amps Per
Pole 230
/277V 480V 600V 230V 1 Phase
480V 3 Phase
600V 3 Phase
Poles Catalog Number
1P XMCK – 25D
1P+Shunt XMCK – 25DN 20 25 120 100 80 2 5 7.5
2P XMCK – 252
1P XMCK – 30D
1P+Shunt XMCK – 30DN 25 30 150 125 100 3 7.5 10
2P XMCK – 302
1P XMCK – 40D 150 75 50 1P+Shunt XMCK – 40DN 30 40
180 150 120 3 10 15
2P XMCK – 402
1P XMCK – 50D
1P+Shunt XMCK – 50DN 40 50 240 200 160 5 15 20
2P XMCK – 502
Coil characteristics
Voltage Part number Inrushed
VA Sealed
VA Sealed Watts Pick-up Drop-out
XMCK-□D
XMCK-□DN 32 6 2-4
XMCK-□2 40 7 2.5-4.5
≤0.8US ≥0.2US
- 1 -
XMC2 Series AC Contactors
Description HOMER XMC2 series contactors are developed by Hongmei Electronic
according to customer’s requirements for high performance,
high reliability. It is of wider range coil voltage, better contact operating
ability, higher thermal-resistance class and better performance in anti-shock and vibration than same level product. It
is applied for controlling of air conditioning electric motor load under condition of 50HZ/60HZ, rated insulation voltage
≤690V, rated current ≤32A. (IEC criterion AC-8a, AC-8b). It also can be used in power supply system for long
distance making and breaking circuit, controlling electric motor load (IEC category: AC-3, AC-4). It can work with
thermal relays to be a magnet starter assembly to protect circuit from over- load current.
XMC2 series contactors not only can meet the high requirements for Air conditioning compressor and freezing
container but also can be used for all kinds of power system. It’s flexible to attach auxiliary contact to meet all
customers’ requirements and providing various contact arrangements: 3P, 3P+1NC, 3P+1NO, 2NO+2NC, 4P .
XMC2 series conform to IEC60947, GB/T14048 and ARI 780/790 standards.
Features 1. The structure of amortization system is unique, which eliminated contact bounce.
2. Heavy duty Silver Metal Oxide composition contacts ensure long electrical endurance.
3. Various contact arrangements meet different customer requirements.
4. Interface available for Auxiliary contact and protection module, easy to assemble.
5. The maximum ambient temperature can approach +80 ℃
6. Excellent performance on anti- shock and vibration (acceleration 0~20G&40Hz no failure.)
7. Coils are Class H (180 ) temperature insulated with wide range of voltage and 50/60Hz ratings.℃
8. Two types of coil terminal: double coil terminal and triple coil terminal and easy to change.
9. Easy to change coil.
10. Universal mounting plate, easily replace other brands’ contactors.
11. Double E Magnet Assembly provides optimal performance with reduced power consumption.
12. Effective dustproof structure.
- 2 -
Type model nomenclature - Ordering Information
XM C 2 - □ □ □· □ □ 1 2 3 4 5 6 7 8
Number digit 1 : Manufacturer’s code
XM – Xiamen Hongmei Electronics Co. Ltd.
Number digit 2 : Product Type
C – Contactor
Number digit 3 : Design Sequence Number – 2.
Number digit 4 : Full Load Amperes (FLA) –12, 18, 30, 32, 40, 50
Number digit 5 : Number of Poles – 3 , 2R, 4, 8 or 9.
Number digit 5 3 2R 4 8 9
Number of poles 3-pole 4-pole (2a2b) 4-pole 3-pole+1NC 3-pole+1NO
Number 6 : coil terminal type:— P , S
P:Double coil terminal(Standard type, can be omitted)
S:Triple coil terminal
Number digit 7 : Coil Voltage –D,E,F,G,I,L,N,U
Number digit 7 D E F I L N
60Hz 12V 24V 110-120V 208-240V 277V 440-480V Coil voltage
50Hz 12V 24V 110V 208-220V 230V 380-415V Remark:Lis common type, it can be removed in regular production.
数字 8:3pole auxiliary contact block -00, 1L, L1, 2L, L2, 1R, R1, 2R, R2, 10, 01, RL,11
00*- None(Standard type, can be omitted)
1L- 1NC at left L1- 1NO at left, 2L- 2NC at left, L2- 2NO at left 1R- 1NC at right, R1- 1NO at right, 2R- 2NC at right, R2- 2NO at right 10- 1NC+1NO at left 01- 1NC+1NO at right RL- 1NO at left, 1NC at right 11- 1NO+1NC at both sides
- 3 -
Characteristics Rated insulation voltage V 690
Conforming to standard IEC60947-4-1, GB/T14048.4, EN60947-4, ARI780/790
Approvals CCC
Protective treatment TH
Operating position Vertical ±5°
Operating altitude m 2000
operation ℃ -25 ~ +70 ℃ ℃ Ambient temperature
storage ℃ -40 ~ +70℃ ℃
Relative humidity 95% at 55 ℃
Pollution degree 3
contactor open g 30 Shock resistance 1/2 sine wave=11 ms contactor closed g 30
contactor open g 10 Vibration resistance 5 to 60 Hz
contactor closed g 15
Performance
XMC2- Poles 3 4 2R 8 9
Rated insulation voltage V 690
Rated operating voltage V 480/277(60Hz) or 400/230(50Hz)
Full load ampere(FLA) A 12 18 30 32 40 50
Resistive load ampere(RLA) A 20 25 32 40 50 63
Making capacity(400V cos 0.45φ ) A 12×FLA
Breaking capacity(400V cos 0.45φ ) A 10×FLA
Switching frequency op/h 360
Electrical endurance(ARI 780) cycle 200,000
Mechanical endurance cycle 10,000,000
- 4 -
Pole Characteristics
Locked Rotor amps Power Full Load Amps
Resistive Amps
Per Pole 230/277V 480V 600V 230V
1 Phase480V
3 Phase600V
3 PhasePoles Part Number
3P XMC2 – 123 3P+1NC XMC2 – 128 3P+1NO XMC2– 129
12 20 72 60 48 1.5 3 5
4P(2a2b) XMC2 – 122R 3P XMC2– 183 3P+1NC XMC2 – 188 3P+1NO XMC2 – 189
18 25 108 90 72 2 5 7.5
4P(2a2b) XMC2– 182R 3P XMC2 – 303 3P+1NC XMC2 – 308 3P+1NO XMC2 – 309
30 32 150 125 100 3 7.5 10
4P(2a2b) XMC2 – 302R 3P XMC2 – 323 3P+1NC XMC2 – 328 3P+1NO XMC2 – 329
32 40 180 150 120 3 10 15
4P(2a2b) XMC2– 322R 3P XMC2 – 403 3P+1NC XMC2 – 408 3P+1NO XMC2 – 409
40 50 240 200 160 5 15 20
4P(2a2b) XMC2 – 402R 3P XMC2– 503 3P+1NC XMC2 – 508 3P+1NO XMC2 – 509
50 63 300 250 200 5 20 25
4P(2a2b) XMC2 – 502R
Auxiliary contacts block characteristics
Conventional thermal current (A) 10
Rated insulation voltage (V) 690
A600(AC-15) 230/380V 3/1.9 Rated operational current (A)
N600(DC-13) 110/230V 2.2/1.1
Coil characteristics
Voltage Part number Inrushed
VA Sealed
VA Sealed Watts Pick-up Drop-out
XMC2-12~32 25 5 0.45-0.9
XMC2-40~50 40 6 2.5-4.5 ≤0.8US ≥0.3US