Not for Reproduction ComAp, spol s.r.o. Kundratka 2359/17 180 00, Praha 8 Czech Republic InteliNano-NT MRS, SW version 1.4, ©ComAp March 2013 1 InteliNano-NT-MRS-1.4-Fast User Guide.pdf CAN INTERFACE GENERATOR VOLTAGE MEASUREMENT T16 = Neutral T17 = Phase 1 T18 = Phase 2 T19 = Phase 3 USB interface L COM H INTPUT TERMINALS T10 = COM for analog inputs T11 = binary input T12 = binary input T13 = binary/analog input – Low Fuel Level T14 = binary/analog input – Coolan Temperature T15 = binary/analog input – Oil Pressure OUTPUT TERMINALS T04 = binary output – Starter (6A) T05 = binary output - Fuel Solenoid (6A) T06 = binary output (500 mA) T07 = binary input/output (500 mA) POWER SUPPLY, D+ T01 = BATT - T02 = D+ T03 = BATT + G ECU DIESEL / GASOLINE ENGINE GENERATOR LOAD Fuel Solenoid Battery Sarter Fuel Level Analog Coolant Temperature Analog Oil Pressure Analog D+ - + Alarm Ready To Load Fuel Solenoid Starter COM Remote Start And Load Emergency Stop CAN L COM H USB Battery + Battery - D + PC L1 L2 L3 N InteliNano NT MRS Fast User Guide Typical wiring diagram Accessing the setup mode Ensure the engine is stopped and the controller is in Manual mode (green LED above button Auto is turned off). If you have not configured the custom initialization (init) screen then press and hold Stop button, then briefly press button and then Auto . If you have already created your own init screen then press and hold Stop button and then briefly press , the custom init screen will appear, keep holding the Stop button. Then press to switch LCD to default init screen, and then press AutoTo move up and down in the setup menu use and buttons. Press Start button to select or Stop button for exit. Basic settings Input settings Engine parameters and protections ECU setting Generator protections Info Output settings Outputs and inputs Output code Output source Type Terminal assignment O00 Not Used binary T04, T05, T06, T07 O01 Starter binary T04 O02 Fuel Solenoid binary T04, T05, T06, T07 O03 Stop Solenoid binary T04, T05, T06, T07 O04 Alarm binary T04, T05, T06, T07 O07 Ready To Load binary T04, T05, T06, T07 O08 Prestart binary T04, T05, T06, T07 O09 ECU Power Relay binary T04, T05, T06, T07 O10 Choke binary T04, T05, T06, T07 O11 Glow Plugs binary T04, T05, T06, T07 Normally Open Contact output Normally Open Contact - input button Normally Closed Contact output Normally Closed Contact input button User curves I21 I23 I25 VDO Level % VDO 5 Bar VDO 40-120 °C Datcon Level % VDO 10 Bar VDO 50-150 °C Datcon 5 Bar Datcon High °C Datcon 7 Bar Datcon Low °C Datcon 10 Bar Not selected Not selected Not selected Input code Input source Type Terminal assignment I00 Not Used binary T07, T11, T12, T13, T14, T15 I01 Emergency Stop binary T07, T11, T12, T13, T14, T15 I02 Remote Start/Stop binary T11 I03 Remote Start And Load binary T11 I04 Access Lock binary T07, T11, T12, T13, T14, T15 I07 GCB Feedback binary T07, T11, T12, T13, T14, T15 I10 External Warning 1 binary T07, T11, T12, T13, T14, T15 I11 External Warning 2 binary T07, T11, T12, T13, T14, T15 I12 External Warning 3 binary T07, T11, T12, T13, T14, T15 I13 External Shutdown 1 binary T07, T11, T12, T13,T14, T15 I14 External Shutdown 2 binary T07, T11, T12, T13, T14, T15 I15 External Shutdown 3 binary T07, T11, T12, T13, T14, T15 I20 Low Fuel Level binary T07, T11, T12, T13, T14, T15 I21 Fuel Level Analog analog T13, T14, T15 I22 Low Oil Pressure binary T07, T11, T12, T13, T14, T15 I23 Oil Pressure Analog analog T13, T14, T15 I24 High Coolant Temperature binary T07, T11, T12, T13, T14, T15 I25 Coolant Temperature Analog analog T13, T14, T15 Dimensions Case dimensions: 118mm x108mm x 40mm Panel Cutout: 96mm x 96mm WARNING! If D+ is not used, connect this terminal to battery positive! 80018963

Transcript of Typical wiring diagram T12 = binary input PC Not for ...

Page 1: Typical wiring diagram T12 = binary input PC Not for ...

Not for

Rep

roduc

tion

ComAp, spol s.r.o.Kundratka 2359/17 180 00, Praha 8 Czech Republic

InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013 1 InteliNano-NT-MRS-1.4-Fast User Guide.pdf

CAN INTERFACE

GENERATOR VOLTAGE MEASUREMENT

T16 = NeutralT17 = Phase 1T18 = Phase 2T19 = Phase 3

USB interface

LCOM

H

INTPUT TERMINALST10 = COM for analog inputsT11 = binary inputT12 = binary inputT13 = binary/analog input – Low Fuel LevelT14 = binary/analog input – Coolan TemperatureT15 = binary/analog input – Oil Pressure

OUTPUT TERMINALST04 = binary output – Starter (6A)T05 = binary output - Fuel Solenoid (6A)T06 = binary output (500 mA)T07 = binary input/output (500 mA)

POWER SUPPLY, D+T01 = BATT -T02 = D+T03 = BATT +

GECU

DIESEL / GASOLINE ENGINE GENERATOR

LOAD

Fue

l Sole

no

id

Batte

ry

Sarter

Fue

l Leve

l An

alog

Co

olan

t Tem

pe

rature

An

alog

Oil P

ressu

re A

nalo

g

D+

-+

Alarm

Re

ady To

Load

Fue

l Sole

no

idStarte

r

CO

MR

em

ote

Start An

d Lo

adEm

erge

ncy Sto

p

CA

NL C

OM

HUSB

Batte

ry +

Batte

ry -D

+

PC

L1

L2

L3

N

InteliNano NT MRS Fast User Guide

Typical wiring diagram

Accessing the setup mode

Ensure the engine is stopped and the controller is in Manual mode (green LED above button Auto is turned off). If you have not configured the custom initialization (init) screen then press and hold Stop button, then briefly press ▲ button and then Auto .If you have already created your own init screen then press and hold Stop button and then briefly press ▲, the custom init screen will appear, keep holding the Stop

button. Then press ▼ to switch LCD to default init screen, and then press Auto.To move up and down in the setup menu use ▲ and ▼ buttons. Press Start button to select or Stop button for exit.

Basic settings Input settings

Engine parameters and protections ECU setting

Generator protections Info

Output settings

Outputs and inputs

Output code

Output source Type Terminal assignment

O00 Not Used binary T04, T05, T06, T07 O01 Starter binary T04 O02 Fuel Solenoid binary T04, T05, T06, T07 O03 Stop Solenoid binary T04, T05, T06, T07 O04 Alarm binary T04, T05, T06, T07 O07 Ready To Load binary T04, T05, T06, T07 O08 Prestart binary T04, T05, T06, T07 O09 ECU Power Relay binary T04, T05, T06, T07 O10 Choke binary T04, T05, T06, T07 O11 Glow Plugs binary T04, T05, T06, T07

Normally Open Contact – output Normally Open Contact - input button

Normally Closed Contact – output Normally Closed Contact – input button

User curves

I21 I23 I25

VDO Level % VDO 5 Bar VDO 40-120 °C

Datcon Level % VDO 10 Bar VDO 50-150 °C

Datcon 5 Bar Datcon High °C

Datcon 7 Bar Datcon Low °C

Datcon 10 Bar

Not selected Not selected Not selected

Input code

Input source Type Terminal assignment

I00 Not Used binary T07, T11, T12, T13, T14, T15I01 Emergency Stop binary T07, T11, T12, T13, T14, T15I02 Remote Start/Stop binary T11 I03 Remote Start And Load binary T11 I04 Access Lock binary T07, T11, T12, T13, T14, T15 I07 GCB Feedback binary T07, T11, T12, T13, T14, T15I10 External Warning 1 binary T07, T11, T12, T13, T14, T15I11 External Warning 2 binary T07, T11, T12, T13, T14, T15I12 External Warning 3 binary T07, T11, T12, T13, T14, T15I13 External Shutdown 1 binary T07, T11, T12, T13,T14, T15I14 External Shutdown 2 binary T07, T11, T12, T13, T14, T15I15 External Shutdown 3 binary T07, T11, T12, T13, T14, T15I20 Low Fuel Level binary T07, T11, T12, T13, T14, T15I21 Fuel Level Analog analog T13, T14, T15 I22 Low Oil Pressure binary T07, T11, T12, T13, T14, T15I23 Oil Pressure Analog analog T13, T14, T15 I24 High Coolant Temperature binary T07, T11, T12, T13, T14, T15I25 Coolant Temperature Analog analog T13, T14, T15

Dimensions

Case dimensions: 118mm x108mm x 40mmPanel Cutout: 96mm x 96mm

WARNING!

If D+ is not used, connect this terminal to battery positive!

80018963

Page 2: Typical wiring diagram T12 = binary input PC Not for ...

Not for

Rep

roduc

tion

ComAp, spol s.r.o. Kundratka 2359/17 180 00, Praha 8 Czech Republic

InteliNano-NT MRS, SW version 1.4, ©ComAp – March 2013 2 InteliNano-NT-MRS-1.4-Fast User Guide.pdf

Setpoints

Use ▲ and ▼ buttons to move or change value. Start button to select setpoint or confirm changes and Stop button to go back.

Basic settings

Setpoint code

Setpoint name

B01 Nominal Voltage Ph-N 80 – 480 V

B02 Nominal Voltage Ph-Ph 80 – 600 V

B03 Nominal Frequency 50 Hz (1), 60 Hz (2)

B04 Connection Type Mono Phase (1), SplitPhase (2), 3Ph3Wire (3), 3Ph4Wire (4)

B05 Units Format Metric unit format (1), US unit format (2)

B07 Zero Power Mode Delay 0-360 min

B08 Light Tower Mode Disable (1), Enable (2)

B09 Nominal RPM 100-4000

Engine parameters and protections

Setpoint code

Setpoint name

E01 Prestart Time 0-600 s

E02 Maximum Cranking Time 0-60 s

E03 Cooling Time 0-3600 s

E04 Oil Pressure Shutdown 0-10 Bar E05 Coolant Temperature Shutdown 0 -150 °C E06 Battery Undervoltage 8 – 40 V

E07 Warning Maintenance 0 – 10000 h

E08 Oil Pressure Starter Disengagement Disable (1), Enable (2) E09 Choke Time 0 – 3600 s

E10 Minimal Stabilization Time 1 – 300 s

Generator protections

Setpoint code

Setpoint name

G01 Generator Overvoltage Shutdown G02 – 200 % G02 Generator Undervoltage Shutdown 0 - G01 % G03 Generator Overfrequency Shutdown G04 – 130 % G04 Generator Underfrequency Shutdown 0 – G03 %

To apply all changes return to the main setup menu and restart the controller by pressing the Stop button.

Alarms and Events

Events

Manual Start

Remote Start

Manual Stop

Remote Stop

Auto On

Auto Off

Power On

Island Operation

Warnings

Warning Maintenance

Low Battery

Low Fuel Level

External Warning 1

External Warning 2

External Warning 3

ECU Communication Error

Shutdowns

Emergency Stop

Overspeed

Underspeed

Low Oil Pressure

High Coolant temperature

External Shutdown 1

External Shutdown 2

External Shutdown 3

GCB Fail

Generator Overvoltage

Generator Undervoltage

Generator Overfrequency

Generator Underfrequency

Generator CCW Rotation

Start Fail

Stop Fail

Battery Flat

ECU

For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide. Technical data

Power supply range 6-36 VDC Power supply drop-out immunity 100 ms Power consumption 35 – 295 mA Zero Power Mode consumption 52 - 344 µA

Operating temperature -20... 70 °C Operating humidity 95% non-condensing (IEC/EN 60068-2-30)

Protection degree (front panel) IP65 with GASKET 4x405 only IP50 without gasket

Storage temperature -30... 80 °C

Binary outputs (up to 4) Low current outputs (2) 500 mA High current output (2) 6 A (long term) / 10 A (short term) Total output current 10 A (long term) / 16 A (short term)

Binary inputs (up to 6) Input resistance 1,5 kΏ Closed contact voltage <2 V Open contact voltage >3,5 V

Analog inputs (up to 3) Galvanic insulation Not insulated Electrical range 0 - 2500 kΏ Resolution 0,1 Ώ Precision 2 % ± 3 Ώ

Charging alternator preexcitation circuit Excitation current 100 mA Charging fail threshold 80 %

Generator/Mains measurements Measurement input 3ph generator voltage Measurement type True RMS Voltage range 480 V Ph-Ph (277 V Ph-N) Max. measured voltage 340 V Ph-N Voltage accuracy 1% Frequency range 40 – 70 Hz Frequency accuracy 1 %

Page 3: Typical wiring diagram T12 = binary input PC Not for ...

Not for

Rep

roduc

tion

ComAp, spol s.r.o. Kundratka 2359/17 180 00, Praha 8 Czech Republic

InteliNano-NT MRS, SW version 1.1, ©ComAp – February 2012 1 InteliNano-NT-MRS-1.1-Fast User Guide.pdf

GECU

DIESEL / GASOLINE ENGINE GENERATOR

LOAD

Fue

l Sole

no

id

Batte

ry

Sarter

Fue

l Leve

l An

alog

Co

olan

t Tem

pe

rature

An

alog

Oil P

ressu

re A

nalo

g

D+

-+

Alarm

Re

ady To

Load

Fue

l Sole

no

idStarte

r

CO

MR

em

ote

Start An

d Lo

adEm

erge

ncy Sto

p

CA

NL C

OM

HUSB

Batte

ry +

Batte

ry -D

+

PC

L1

L2

L3

N

INTERFAZ CAN

MEDIDA DE TENSION DE GENERADOR

T16 = NeutroT17 = Fase 1T18 = Fase 2T19 = Fase 3

Interfaz USB

LCOM

H

TERMINALES DE ENTRADAST10 = COM para entradas analógicasT11 = entrada binariaT12 = entrada binariaT13 = Entrada bin./anal. – Bajo nivel de combT14 = Entrada bin./anal. – Temperatura motorT15 = Entrada bin./anal. – Presion aceite

TERMINALES DE SALIDAST04 = salida binaria – Arranque (6AT05 = salida binaria - Solenoide comb (6A) T06 = salida binaria (500 mA)T07 = entrada/salida binaria (500mA)

ALIMENTACIÓN, D+T01 = BAT -T02 = D+T03 = BAT +

InteliNano NTMRS

Guia rápida de usuario

Esquema típico

Accediendo al modo programación

Asegurese de que el motor está parado y en controlador en modo Manual (el LED verde sobre el botón Auto está apagado). Si no ha configurado la pantalla inicial personalizada, mantenga presionado el botón Stop, pulse brevemente el botón ▲ y entonces pulse Auto.

Si ha creado su popia pantalla inicial, mantenga presionado el botón Stop y entonces pulse brevemente ▲, aparecerá la pantalla personalizada, mantenga presionado el botón Stop. Entonces pulse ▼ para cambiar a la pantalla por defecto, y por último presione Auto.

Para desplazarse por el menú utilice los botones ▲ y ▼. Pulse Start para seleccionar o Stop para salir.

Basic settings (Parámetros básicos) Input settings (Ajustes de entradas)

Engine parameters and protections (Parámetros y protecciones

de motor) ECU setting (Ajustes ECU)

Generator protections (Protecciones de generador) Info (Información)

Output settings (Ajuste de salidas)

Entradas y salidas

Salidas código

Fuente de la salida Tipo Asignación del terminal

O00 No Usado binario T04 , T05, T06, T0 O01 Arranque binario T04 O02 Solenoide combustible binario T05 O03 Solenoide parada binario T05 O04 Alarma binario T04, T05, T06, T07 O07 Preparado para meter carga binario T04, T05, T06, T07 O08 Prearranque binario T04, T05, T06, T07 O09 Relé de Potencia ECU binario T04, T05, T06, T07

Contacto NC – salida Contacto NA - entrada

Contacto NA – salida Contacto NC – entrada

User curves

I21 I23 I25

VDO Nivell % VDO 5 Bar VDO 40-120 °C

Datcon Nivel % VDO 10 Bar VDO 50-150 °C

Datcon 5 Bar Datcon High °C

Datcon 7 Bar Datcon Low °C

Datcon 10 Bar

No seleccionado No seleccionado No seleccionado

Input code

Input source Type Terminal assignment

I00 Not Used binary T07, T11, T12, T13, T14, T15 I01 Emergency Stop binary T07, T11, T12, T13, T14, T15 I02 Remote Start/Stop binary T11 I03 Remote Start And Load binary T11 I04 Access Lock binary T07, T11, T12, T13, T14, T15 I07 Estado GCB binary T07, T11, T12, T13, T14, T15 I10 Aviso Externo 1 binary T07, T11, T12, T13, T14, T15 I11 Aviso Externo 2 binary T07, T11, T12, T13, T14, T15 I12 Aviso Externo 3 binary T07, T11, T12, T13, T14, T15 I13 Parada Externa 1 binary T07, T11, T12, T13,T14, T15 I14 Parada Externa 2 binary T07, T11, T12, T13, T14, T15 I15 Parada Externa 3 binary T07, T11, T12, T13, T14, T15 I20 Bajo Nivel de Combustible binary T07, T11, T12, T13, T14, T15 I21 Nivel de Combustible Analog. analog T13, T14, T15 I22 Baja Presión de Aceite binary T07, T11, T12, T13, T14, T15 I23 Presión de Aceite Analog. analog T13, T14, T15 I24 Alta Temperatura Refrigerante binary T07, T11, T12, T13, T14, T15 I25 Temperatura Refrig. Analog analog T13, T14, T15

Dimensiones Dimensiones de caja:118mm x108mm x40mm

Corte panel: 96mm x 96mm

AVISO! Si no se utilize el D+, conectar este terminal al positivo de batería!

Page 4: Typical wiring diagram T12 = binary input PC Not for ...

Not for

Rep

roduc

tion

ComAp, spol s.r.o. Kundratka 2359/17 180 00, Praha 8 Czech Republic

InteliNano-NT MRS, SW version 1.1, ©ComAp – February 2012 2 InteliNano-NT-MRS-1.1-Fast User Guide.pdf

Setpoints

Utillice los pulsadores ▲ y ▼ para moverse o cambiar valores. El pulsador Start para seleccionar el parámetro o confirmar los cambios y el Stop para salir.

Basic settings

Ajuste código

Nombre parámetro

B01 Tension Nominal F-N 80 – 480 V

B02 Tensión Nominal F-F 80 – 600 V

B03 Frecuencia Nominal 50 Hz (1), 60 Hz (2)

B04 Tipo Conexión Monofásica (1),Doble delta (2), 3F3Hilos (3), 3F4Hilos (4)

B05 Formato Unidades Formato Metrico (1), formato US (2)

B07 Retardo Modo Zero Consumo 0-360 min

Engine parameters and protections

Ajuste código

Nombre parámetro

E01 Tiempo Prearranque 0-600 s

E02 Máximo Tiempo Arranque 0-60 s

E03 Tiempo Enfriamiento 0-3600s

E04 Parada Presion Aceite 0-10 Bar E05 Parada Temperatura Refrigerante 0 -150 °C E06 Baja tension Batería 8 – 40 V

E07 Aviso Mantenimiento 0 – 10000 h

E08 Detección de arranque por presión Disable (1), Enable (2)

Generator protections

Ajuste código

Nombre parámetro

G01 Parada Sobretensión de generador G02 – 200 % G02 Parada Baja tension de generador 0 - G01 % G03 Parada Sobrefrecuencia de generador G04 – 130 % G04 Parada Baja frecuencia de generador 0 – G03 %

Para que se apliquen todos los cambios, vuelva a la manu principal de programación y reinicie el controlador pulsando el botón Stop.

Alarmas y Eventos

Events

Arranque Manual

Arranque Remoto

Parada Manual

Parada Remota

Auto On

Auto Off

Encendido

Operación en Isla

Warnings

Aviso Mantenimiento

Batería Baja

Bajo Nivel Combustible

Aviso Externo 1

Aviso Externo 2

Aviso Externo 3

ECU Error Comunicación

Shutdowns

Parada Emergencia

Sobrevelocidad

Baja velocidad

Baja presión de Aceite

Alta Temperatura motor

Parada Externa 1

Parada Externa 2

Parada Externa 3

Fallo GCB

Sobretensión Generador

Baja Tensión Generador

Alta frecuencia Generador

Baja frecuencia Generador

Sentido Giro Generador

Fallo de Arranque

Fallo de Parada

Batería descargada

ECU

Para la configuración ECU utilice el software para PC NanoEdit. Para más detalles vea ‘InteliNano AMF Reference Guide’. Información Técnica

Rango de alimentación 6-36VDC Inmunidad caida de tensión 100ms Consumo 35 – 295mA Consumo en modo Zero Consumo 52 - 344 µA

Temperatura de funcionamiento -20... 70°C Humedad de funcionamiento 95% no-condensado (IEC/EN 60068-2-30) Grado de protección (frente panel) IP65 Temperature almacenamiento -30... 80°C

Salidas binarias (hasta 4) Salidas de bajo corriente (2) 500mA Salidas de alta corriente (2) 6A (permanente) / 10A (puntual) Corriente de Salida Total 10A (permanente) / 16A (puntual)

Entradas binarias (hasta 6) Resistencia de Entrada 1,5 kΏ Tensión contacto cerrado <2V Tensión contacto abierto >3,5V

Entradas Analógicas (hasta 3) Aislamiento Galvánico No aislado Rango eléctrico 0 - 2500kΏ Resolución 0,1 Ώ Precisión 2% ± 3Ώ

Circuito de preexcitación del Alternador Cargabaterías Corriente de Excitación 100mA Umbral fallo de carga 80%

Medidas Generador/Red Medida entrada Tension de generador 3f, tensión de red 3f Tipo medición RMS verdadero Rango de tensión 480V F-F (277V F-N) Max. tension medida 340V F-N Preción de tensión 1% Rango de frecuencia 40 – 70 Hz Precisión de frecuencia 1%