Types KIR-60, KIR-75, and KIR-11Current Transformers5 - 15 kV; 60, 75, & 110 kV BIL; IndoorProduct Bulletin 1VAP429141-DB

Page 2: Types KIR-60, KIR-75, & KIR-11 Current Transformers€¦ ·  · 2010-12-01Types KIR-60, KIR-75, and KIR-11 Current Transformers 5 - 15 kV; 60, 75, & 110 kV ... IEEE test reports

- 2 -

Product Features

• 5 - 15 kV Indoor• 60, 75, and 110 kV BIL• 60 Hertz

• Primary Amperes: 5 - 1200

• Mechanical Rating:Refer to Selection Guide

• Thermal Rating:Refer to Selection Guide

• IEEE Metering Accuracy:All ratings 0.3B-1.8

• IEEE Relaying Accuracy:KIR-60 & KIR-75All ratings T100KIR-11All ratings T200

• UL Recognized Components;File No. E96461

ApplicationThe KIR-60, KIR-75, and KIR-11 indoor current transformers aredesigned for relaying and metering applications.

Construction FeaturesPrimary and secondary windings are assembled around a distributedgap core and attached to a support frame. Each coil is insulated withmylar film to provide a high dielectric strength between layers. The coilsand core are combined to create a complete winding structure that isassembled to a support frame. The entire assembly is vacuum cast inpolyurethane for added insulation and protection.

Secondary TerminalsThe secondary terminals are compression-type and can accommodate#14 through #1 wire. Terminal screws are slotted hex-head type andare easily accessible.

BaseplateThe baseplate is constructed of corrosion-resistant aluminum and issecured to the encapsulated base support.

MountingThe KIR-60, KIR-75, and KIR-11 can be mounted in upright, cantilever, or upside-down positions.

Test ReportsIEEE test reports are stored electronically and can be e-mailed invarious formats at the time of shipment.

StandardsThese units meet all applicable IEEE and NEMA standards.

UL Recognized Component

Page 3: Types KIR-60, KIR-75, & KIR-11 Current Transformers€¦ ·  · 2010-12-01Types KIR-60, KIR-75, and KIR-11 Current Transformers 5 - 15 kV; 60, 75, & 110 kV ... IEEE test reports

- 3 -

Note: Metric dimensions are displayed in [mm].

Unit Dimensions

Type KIR-60

Type KIR-75

3.56[91]

1.00[25]

.50[13]

.75 [19]

2.75[70]

4.00[102]

2.38[60]

.13 [3]

B

5.75[146]

8.06[205]

6.13 [156]

3.06[78]

3.06[78]

7.00 [178]

15.00 [381]

9.25 [235]2.88[73]

2.88[73]

H1

8.63 [219]

3.56[91]

2.12[54]

5.50[140]

2.38[60]

2.50[64]

1.08[28]

7.00 [178]

.44 X 2.10 [11 X 53]

SLOT IN BASE 4-TOTAL

Ø.56 [14] HOLE2-TOTAL

Ø.44 [11] HOLE

.56 X 1.31[14 X 33]LG SLOT2-TOTAL

A

NAMEPLATE

RATING DECAL

SECONDARYPOLARITYMARKER

COMPRESSION TYPE SECONDARY TERMINALFOR #14 TO #1 WIRE - SECONDARYTERMINALS ARE SHIPPED SHORT CIRCUITED

PRIMARYPOLARITYMARKER

3.56[91]

1.00[25]

.50 [13]

.75 [19]

1.08[28]2.50[64]

2.75[70]

2.88[73]

10.25 [260] 2.88[73]

3.94[100]

3.94[100]

1.75[44]

.13 [3]

8.00[203]

B

5.75[146]

8.06[205]

2.25[57]

.13 [3]1.28

[33]

5.50 [140]

1.28[33]

2.75[70]

10.31[262]

6.13 [156]

3.06[78]

3.06[78]

2.75[70]

H1

X2

X1

8.63 [219]4.31[110]

3.56[91]

2.12[54]

5.50[140]

2.38[60]

5.13 [130]

16.00 [406]

7.50 [191]7.50 [191]

PRIMARY POLARITYMARKER

COMPRESSION TYPE SECONDARY TERMINALSFOR #14 TO #1 WIRE - SECONDARYTERMINALS ARE SHIPPED SHORT CIRCUITED

SECONDARY POLARITYMARKER

NAMEPLATE

RATING DECAL

Ø.44 [11] HOLE4-TOTAL

.56 x 1.31[14 x 33]LG SLOT2-TOTAL

Ø.56 [11] HOLE2-TOTAL

A

.44 X 2.10[11 X 53]

SLOT IN BASE4-TOTAL

Page 4: Types KIR-60, KIR-75, & KIR-11 Current Transformers€¦ ·  · 2010-12-01Types KIR-60, KIR-75, and KIR-11 Current Transformers 5 - 15 kV; 60, 75, & 110 kV ... IEEE test reports

- 4 -

Note: Metric dimensions are displayed in [mm].

Baseplate Dimensions

Style

PrimaryAmpereRating

Unit Dimensions

Weight(lbs)

A B C D

(in) (mm) (in) (mm) (in) (mm (in) (mm)

KIR-605-200 1.5 38 0.25 6 14.0 356 15.0 381 35.5

300-800 2.0 51 0.375 10 14.0 356 15.0 381 38.0

KIR-755-200 1.5 38 0.25 6 15.0 381 16.0 406 35.0

300-800 2.0 51 0.375 10 15.0 381 16.0 406 38.5

KIR-115-200 1.5 38 0.25 6 22.0 559 23.0 584 56.0

300-800 2.0 51 0.375 10 22.0 559 23.0 584 61.0

Type KIR-11

H1

X1

X2

3.38[86]

6.76[172]

9.89[251]

9.01[229]

H1

H2

23.03 [585]

11.51 [292]

3.04 [77]

.50 [13] 1.00

[25].75 [19]

6.01 [153]

4.82 [122]

4.82 [122]

5.26 [134]

10.51 [267]

2.57 [65] 5.13

[130]

2.13 [54]

B

SECONDARYPOLARITY

MARKER

H2NAMEPLATE

RATING DECAL

CLAMP TYPE SECONDARY TERMINALSFOR #14 TO #1 WIRE. SECONDARY TERMINALSARE SHIPPED SHORT CIRCUITED.

3.00 [76]

.44 X 2.10[11 X 53]SLOT IN BASE4-TOTAL

PRIMARY POLARITYMARKER

.56 X 1.31[14 X 33]2-TOTAL

Ø.44 [11] HOLE4-TOTAL

A

Ø.56 [14] HOLE2-TOTAL

Unit Dimensions

7.13 [181]

8.63 [219]

.75 [19]

4.75 [121]

.38 [10]

5.50 [140]

1.66 [42]

5.00 [127]

1.81 [46]

4.25 [108]

Types KIR-60 and KIR-75

9.63[245]

.44[11]

10.50[267]

5.13[130]

.44[11]2.75

[70]

1.66[42]

5.00[127]

.87[22]

4.25[108]

6.00[152]

Type KIR-11

Page 5: Types KIR-60, KIR-75, & KIR-11 Current Transformers€¦ ·  · 2010-12-01Types KIR-60, KIR-75, and KIR-11 Current Transformers 5 - 15 kV; 60, 75, & 110 kV ... IEEE test reports

Selection Guide

Additional styles available upon request. Contact your ABB Sales Representative or call +1-252-827-3212 for more information.

- 5 -

Primary

Ampere

Rating

Rating

Factor

Mechanical

Rating

Thermal

Rating

Style Number

KIR-60 KIR-75 KIR-11

5 1.5 150 100 7524A01G01 7524A02G01 7524A03G01

10 1.5 150 100 7524A01G02 7524A02G02 7524A03G02

15 1.5 150 100 7524A01G03 7524A02G03 7524A03G03

20 1.5 150 100 7524A01G04 7524A02G04 7524A03G04

25 1.5 150 100 7524A01G05 7524A02G05 7524A03G05

30 1.5 150 100 7524A01G06 7524A02G06 7524A03G06

40 1.5 150 100 7524A01G07 7524A02G07 7524A03G07

50 1.5 150 100 7524A01G08 7524A02G08 7524A03G08

75 1.5 150 100 7524A01G09 7524A02G09 7524A03G09

100 1.5 150 100 7524A01G10 7524A02G10 7524A03G10

150 1.5 150 100 7524A01G11 7524A02G11 7524A03G11

200 1.5 150 100 7524A01G12 7524A02G12 7524A03G12

300 1.5 150 100 7524A01G13 7524A02G13 7524A03G13

400 1.5 150 100 7524A01G14 7524A02G14 7524A03G14

500 1.0 150 100 - - 7524A03G15

500 1.5 150 100 7524A01G19 7524A02G17 -

600 1.5 150 100 7524A01G15 7524A02G15 7524A03G16

800 1.33 110 75 7524A01G16 7524A02G16 7524A03G17

1000 1.2 110 75 7524A01G21 - -

1000 1.0 110 75 - - 7524A03G21

1200 1.0 110 75 7524A01G20 7524A02G19 7524A03G18

Page 6: Types KIR-60, KIR-75, & KIR-11 Current Transformers€¦ ·  · 2010-12-01Types KIR-60, KIR-75, and KIR-11 Current Transformers 5 - 15 kV; 60, 75, & 110 kV ... IEEE test reports

ABB Inc.3022 NC 43 NorthPinetops, NC 27864Tel: +1-252-827-3212www.abb.com/mediumvoltage

1V

AP

429141-D

B R

ev.

B A

ugust

2007 (

repla

ces 4

2-9

14)

© C

opyright

2005 A

BB

. A

ll rights

reserv

ed.