    DIRECTIONAL SPRAY NOZZLES, OPENTYPE D3 LARGE CAPACITY PROTECTOSPRAY@ - 1 NPT

    g/16 ll4.3mm)MAKE-IN

    L SPRAY ANGLE IINCLUDED ANGLE OF DISCHARGE)AND ORIFICE SInDDn91TE 9tnc ZE STAMPED ONI I I I c .YLFIGURE ATYPE D3 LARGE CAPACITY PROTECTOSPRAY NOZZLES

    The Type D3 Large Capacity Pro-tectospray Nozzles are open (non-au-tomatic) directional spray nozzles andthey are designed for use in waterspray fixed systems for fire protectionapplications. The 1 inch NPT Type D3Large Capacity Nozzles are externaldeflector type nozzles that discharge auniformly filled cone of medium veloc-ity water droplets.

    inch NPT Type D3S Nozzles with indi-vidual strainers and K-factors of 1.1 to2.8 (15.8 to 40.3). Information on auto-matic Type EA-1 ProtectosprayNozzles is given in Technical DataSheet TD61 OA.

    dependi ng on the char acteri stics andnatu re of the hazard, the basic pur-pose of th e spr ayi ng system, th e con-f igur ation of the hazard, andwin d/ dr aft condi t ions. Because ofth ese var iat ions as well as th e wi der ange of avail able nozzle spr ay char-acteri stics, th e design of wat er spra yfixed systems for fir e pr otection mu stonl y be perfor med by experi enced de-signers w ho thoroughly understandthe l im i tat ions as wel l as capabi l i t iesof such systems.

    They are especially effective in cover-ing exposed vertical, horizontal,curved, and irregular shaped surfacesin a high density cooling spray to pre-vent excessive absorbtion of heat froman external fire and to prevent possiblestructural damage or spread of fire tothe protected equipment. In some ap-plications, depending on water designdensity requirements, they may alsobe used for fire control and extinguish-ment.

    The natural finish, chrome plated,nickle plated, and lead coated bronzeType D3 Large Capacity Pro-tectospray Nozzles are listed by Un-derwriters Laboratories Inc. andUnderwriters Laboratories of Canada.The Type D3 Large Capacity Pro-tectospray Nozzles are also approvedby the New York City Board of Stan-dards and Appeals under CalendarNumber 334-79-SA.

    Th e owner is responsibl e for mai n-taini ng their fi r e protection systemand devices in pr oper oper ati ng con-di t ion. The instal l ing contr actor orman ufactu rer should be cont acted r el-ati ve t o any questi ons.

    WARNINGS

    The Type D3 Large Capacity Nozzlesare available in four orifice sizes and awide variety of spray angles (includedangles of discharge) to provide versa-tility in system design.Refer to TD620Afor information on l/2inch NPT Type D3 ProtectosprayNozzles with K-factors of 1.2 to 7.2(17.3 to 103.7) and Technical DataSheeet TD620C for information on l/2

    Th e Typ e 03 Lar ge Capaciit y Pro-tectospra y N ozzles descr ibed h er einmust be instal l ed and maintain ed incompl i ance wi th thi s document, aswel l as wit h th e appl icable standard sof th e Na ti onal Fi re Pr otection Asso-ciation, in addi t ion to the standard sof any other authori t ies havingjur is-dict ion. Fai l ur e to do so may im pairth e in tegrit y of these devices.

    The Type D3 Large Capacity Pro-tectospray Nozzles are rated for use ata maximum service pressure of 175psi (12.1 bar). They are available innatural finish bronze, electrolessnickel plated bronze, chrome platedbronze, lead coated bronze, or FEPTeflon? coated bronze.

    T?Le esign of indi vidual water sprayfixed systems can vary considerably,

    The frame is bronze per ASTM 8584(C83600 or C84400), the Deflector issilicon bronze per ASTM B98(C66100). the Splitter is brass perPrinted in U.S.A. 11-92 TD620B

  • 7/29/2019 Type D3 MV Sprayer 1

    2/4

    RADIAL DISTANCEFROM NOZZLE CENTERLINE, FEET2 3 4 5 6 7 6

    !- 4i 5ElM 6p 7 6e

    180

    801516

    0 1 2 3 4 5 6 7 8RADIAL DISTANCEFROM NOZZLE CENTERLINE, FEET

    Design Spray Profiles-Feet and Inches-RADIAL DISTANCEFROM NOZZLE CENTERLINE, METRES

    0 0.5 1.0 1.5 2.0 2.50

    0.53E 1.0Y9 1.5Ms> 2.0&g 2.5Z2g 3.0azQ 3.5

    4.0

    4.50 0.5 1.0 1.5 2.0 2.5

    RADIAL DISTANCEFROM NOZZLE CENTERLINE, METRES

    180160

    140

    125

    110

    95

    MAXIMUM AXIAL DISTANCEBETWEEN NOZZLE TIP AND PLANE-OF PROTECTIONFOR EXPOSURE PROTECTIONFEET AND INCHES(METRES)

    FIXEDANGLE

    0

    SPRAY ANGLE65' 80' 95 110 125 140 160 180'17-O 16-O 13-6 12-6 11-O 9-o 8-O 7-o(5.2) (4.9) (4.1) (3.8) (3.4) (2.7) (2.4) (2.1)

    i ,-. PLANE-OF-PROTECTIONI /I

    /

    w

    / RADIAL DISTANCEL

    FIXED ANGLE (ORIENTATION)GRAVITY

    NOTES:1. Design data obtained from tests in still air.2. Design data applies to a residual (flowing) pressure range at thenozzle inlet of 20 to 60 psi (1.4 to 4.1 bar). For pressures up to 175psi (12.1 bar) consult the Technical Data Department.

    Refer to the authority having jurisdiction for their minimum requiredresidual pressure.

    3. The shapes of the Design Spray Profiles remain essentially un-changed over the maximum Axial Distances shown in the table.4. For axial distances of 2 feet (0.6 meters) and less and for nozzlespray angles of 65 to 140, the Design Spray Profile is the sameas the nominal spray angle.5. The maximum Axial Distances shown in the table are based onexposure protection.

    Design Spray Profiles FIGURE B-Metres- WATER DISTRIBUTION DESIGN DATA-2-

  • 7/29/2019 Type D3 MV Sprayer 1

    3/4

    60

    25

    40 50 60 70 80 90 100 110 120 130 140DISCHARGE IN U. S. GALLONS PER MINUTE (GPM)

    NOTE: Q= KG where Q = flow in U.S. gallons per minute, p = pressure in pounds per square inch, and K is the nominaldischarge coefficient.

    4.0

    3.55L 3.0ii28 2.5if 2.0

    1.5

    1.0160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520

    DISCHARGE IN LITRES PER MINUTENOTE: Q= Kfi where Q = flow in liters per minute, p = pressure in bar, and K is the nominal discharge coefficient.

    FIGURE CNOMINAL DISCHARGE CURVES(Refer to the authority having jurisdiction for their minimum required residual pressure.)

    OrificeSize

    No. 39No. 44No. 48No. 50

    Mlnimum K-factorDiameter NFPA ISO/SI(GPM + +/) (LPM i G)0.604 (15.34mm) 10.7 154.10.670 (17.02mm) 13.5 194.40.750 (19.05mm) 16.4 236.20.787 (19.99mm) 18.1 260.6

    TABLE A TABLE BSELECTION OF ORIFICE SIZES SELECTION OF SPRAY ANGLES

    I 65 12580 14095 160110 180

    -3-

  • 7/29/2019 Type D3 MV Sprayer 1

    4/4

    ASTM B16 (CSSOOO), and the Pin isphosphor bronze.Orifice Sizes. Each orifice size has anumerical designation and the avail-able sizes are as shown in Table A.The nominal discharge curves and K-factors for the various orifice sizes aregiven in Figure C.Spray Angles. The nominal spray an-gles (included angles of discharge) areavailable as shown in Table B.Nozzle Placement. Where direct im-pingement of the water spray onto allof the protected surface is required bythe authority having jurisdiction, thenozzles are to be spaced and directedso that their spray patterns will com-pletely cover the plane-of-protectionwith the minimum required averagedensity; however, it is recommendedthat indoor nozzle spacings be 12 feet(3.7 metres) or less and that outdoornozzle spacings be 10 feet (3.0 me-tres) or less. Where rundown or slip-page is planned, e.g. exposure protec-tion of vessels per NFPA 15, thepreceding recommended indoor andoutdoor spacings also apply.When used for protecting the surfacesof a vessel, for example, the nozzlesare positioned normal to and approxi-mately 2 feet (0.6 metres) from thesurface. This approach, in conjunctionwith a properly selected spray angle,will tend to make more effective use ofthe spray as well as help minimize thedisturbance effects of wind/draft condi-tions on the water spray pattern.Spray Patterns. The Design SprayProfiles for the nozzle spray angles of65 to 180 are as shown in Figure Band apply to discharge pressures of 20to 60 psi (1.4 to 4.1 bar). Dischargepressures in excess of 60 psi (4.1 bar)will result in a decrease in coveragearea since the spray patterns tend todraw inwards at higher pressures.Refer inquiries on higher dischargepressures to the Technical Data De-partment.The maximum axial distances be-tween the nozzle tip and plane-of-pro-tection, for exposure protection, aregiven in the table that appears in Fig-ure B. When the axial distance fromthe nozzle tip to the plane-of-protec-tion is 2 feet (0.6 metres) or less, theDesign Spray Profile is the same asthe nominal spray angle for spray an-gles of 65 through 140.

    NOTESRefer to the War ni ng Section for anim portan t noti ce concer ni ng th e de-sign of ind ividu al water spray fixedsystems.I nqui ri es concern in g nozzle in stall a-

    PSN49 -3xx-x-xxx

    FINISH & MATERIAL1 Natural Finish Bronze4 Teflon Coated Bronze5 Electroless Nickel Plated Bronze7 Lead Coated Bronze9 Chrome Plated Bronze

    TABLE CPRODUCT SYMBOL NUMBER SELECTION

    ti on and usage crit eri a, not covered byth ese in stru ctions, should be mai ledto th e att ent ion of the Techn ical Dat aDepart ment. In clude sketches andtechni cal detail s, as appr opri ate.

    The Type D3 Large Capacity Pro-tectospray Nozzles may be installedby using a Crescent type adjustablewrench.

    Care must be exercised to avoid dam-age to the nozzles - both before andafter installation. Nozzles damaged bydropping, striking, wrench twist/slip-page, or the like, must be replaced.Water spray fixed systems for fire pro-tection service require regularlyscheduled care and maintenance bytrained personnel. It is recommendedthat the Protectospray Nozzles be pe-riodically inspected for loading/ob-structions, or other evidence of im-paired protection. The inspectionsshould be scheduled weekly or as fre-quently as may be necessary and, cor-rective action taken to ensure that thenozzles will perform as intended in theevent of a fire.

    NOTEBefore closin g a ir e pr otecti on systemmain contr ol valve for maint enance

    wor k on th e fi re pr otection systemwhi ch i t contr ols, perm ission to shutdown th e affected f ir e pr otection sys-tem must be obtained fr om th e pr operauthori t ies and all personnel whomay be affected by thi s action mu st benoti f ied.It is recommended that water sprayfixed systems for fire protection be in-spected by a qualified Inspection Ser-vice.

    Seller warrants for a period of one yearfrom the date of shipment (warrantyperiod) that the products furnishedhereunder will be free from defects inmaterial and workmanship.For fur ther detai l s on Warr anty, seePrice List.

    Large Capacity ProtectosprayNozzles:Specify: No. (specify number) orifice,Type D3 Large Capacity Pro-tectospray Nozzle in (specify fin-ish/coating and material) with (specifynumber) degree spray angle, PSN(specify from Table C).Contact your local distributor foravailabilty.

    ?-DuPont Registered Trademark@ Reg. trademark of GRINNELL CORPORATION, 3 TYCO PARK, EXETER, NH 03833 A tqCOINTERNATIONAL L TO. COMPANY