Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

80
Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith

Transcript of Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

Page 1: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

Two Minute Drill #9

Copyright 2005 Ted "Smitty" Smith

Page 2: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide.

Each slide will transition to the correct answer automatically in 3:30 minutes. The correct answer will transition in 10 seconds. You may also left click on the slide to manually transition.

Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill

Good luck Remember to start the slide show to activate

the timer.

Copyright 2005 Ted "Smitty" Smith

Page 3: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

This drill is calculations only. Concentrate on the correct answer not on

the speed. Remember do not worry about

writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then.

Click on the slide to proceed.

Copyright 2005 Ted "Smitty" Smith

Page 4: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum/ maximum overload relay range that would be allowed for a 230 volt, single phase AC motor that is rated at 2 horsepower and a marked temperature rise of 30 degrees Celsius?

15a-16.8a 20a-22a 12a-14a 12a-15a

Copyright 2005 Ted "Smitty" Smith

Page 5: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 430.32 and 430.34

Copyright 2005 Ted "Smitty" Smith

Page 6: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum required length of a pull box that is placed between two 4” EMT conduits? The conduits will enter on either end and the wires will pull straight through the box. The conduits will contain six #1 THHN conductors, three #4 THW conductors and fifteen #12 THHN conductors. In addition a #4 ground conductor will be run in the conduits. The ground conductor will be THHN.

22” 18” 32” 24”

Copyright 2005 Ted "Smitty" Smith

Page 7: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C 314.28(a)(1)

Copyright 2005 Ted "Smitty" Smith

Page 8: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum required service for a single family dwelling that is 1100 square feet and is equipped with 12kw range, a 4.2kw water heater and 8.6kw of fixed electric heat? The house also has a 1.1kw dishwasher and a .75kw garbage disposal. The house is fed by a 230v, single phase service.

110a 125a 119.64a 120a

Copyright 2005 Ted "Smitty" Smith

Page 9: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

B Article 220 Part II

Copyright 2005 Ted "Smitty" Smith

Page 10: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized THHN conductor that can be used to feed a set of non-motor generator arc welders? The set is made up of four arc welders that have I1eff ratings of 40a, 50a, 65a and 75a. The termination lugs are rated at 75 degrees Celsius and the over current device is rated at 90 degrees Celsius.

4/0 2/0 3/0 1/0

Copyright 2005 Ted "Smitty" Smith

Page 11: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 210 630.11(b) and 630.11(a) and T310.16 75c column

Copyright 2005 Ted "Smitty" Smith

Page 12: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized THHN conductor that can be used on a branch circuit with a load of 42 amps? The load is a single motor for a control servo on a crane. The motor is designed to operate no more than 30 minutes at a time. The crane is permanently in place and is expected to operate at an ambient temperature of 46 degrees Celsius. The termination lugs are rated for 75 degrees Celsius.

  6 awg 4 awg 8 awg 10 awg

Copyright 2005 Ted "Smitty" Smith

Page 13: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A T610.14

Copyright 2005 Ted "Smitty" Smith

Page 14: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized neutral that can be used for the service entrance for a single family dwelling that is 56’ x 125’. The home is equipped with a 16.8kw range, 230v, 4.6kw dryer, 230v, a 1.2 kw dishwasher and a .89 kw garbage disposal.

6 awg 3 awg 1/0 awg 2 awg

Copyright 2005 Ted "Smitty" Smith

Page 15: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

. D 220 Part II

Copyright 2005 Ted "Smitty" Smith

Page 16: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

If six #14 TW conductors at .0319 square inches each, and eight number 8 THWN conductors were installed in an 18” conduit between two cabinets, the minimum sized PVC, schedule 80 conduit, permitted by the NEC would be __________.

A. ¾” B. 1” C. 1 ¼” D. 1 ½”

Copyright 2005 Ted "Smitty" Smith

Page 17: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C. Tables 1, 4 and 5 Chapter 9

Copyright 2005 Ted "Smitty" Smith

Page 18: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 40-unit condo, each condo has a 4.5kw water heater 230v. What is the total demand on the service of the water heaters?

A.135kw B. 150kw C. 180 D. 210

Copyright 2005 Ted "Smitty" Smith

Page 19: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A. 220.53

Copyright 2005 Ted "Smitty" Smith

Page 20: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum required service for a dwelling that is 1000sf and is equipped with two wall a mounted ovens each rated at 240v and 25 amps and one cooktop rated at 240v and 20 amps. It also has 1.2kw dishwasher?

110a 125a 75a 100a

Copyright 2005 Ted "Smitty" Smith

Page 21: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

D 220 Part II

Copyright 2005 Ted "Smitty" Smith

Page 22: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

Calculate the feeder demand for 55- 14kw ranges in an apartment building?

72.875kw 66.25kw 50kw 25kw

Copyright 2005 Ted "Smitty" Smith

Page 23: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A Tble 220.55

Copyright 2005 Ted "Smitty" Smith

Page 24: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized 480v, three phase service that would be required for a commercial restaurant that is 18,000 square feet and equipped with 110 receptacle outlets, 150 feet of non-simultaneous 3000 series wire mold, 2000 VA lighted sign circuit, 300 ft of decorative track lighting, two 19.6kw ovens, three 9.2 kw grills, a 9.8kw walk in freezer, a 7.2 kw walk in refrigerator, two 5.9 kw deep fryers, a 4.2 kw ventilated cooking hood and a 480v, three phase, 7.5 hp squirrel cage motor for the RTU for HVAC purposes.

225a 205a 200a 150a

Copyright 2005 Ted "Smitty" Smith

Page 25: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 225 Article 220 Part II

Copyright 2005 Ted "Smitty" Smith

Page 26: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized schedule 80, rigid nonmetallic conduit that could be used for a branch circuit requiring 11 phase conductors and 4 neutral conductors and one ground conductor? The phase conductors will all be #10 THHN, the neutral conductors will all be #8 THHN and the ground conductor will be #12 THW. The conduit will be run ¾ of its distance underground and approximately ¼ of its distance encased in 6 inches of hardened concrete with sand under-footing.

1” 2” 1 ¼” 1 ½”

Copyright 2005 Ted "Smitty" Smith

Page 27: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C Tables 1, 4 and 5 Chapter 9

Remember: Not the annexs.

Copyright 2005 Ted "Smitty" Smith

Page 28: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the ampacity for each conductor when a raceway contains nine No. 4 THW copper current carrying conductors that are installed in a room with an ambient temperature of 96 degrees F?

70 amperes 85 amperes 59.5 amperes 52.36 amperes

Copyright 2005 Ted "Smitty" Smith

Page 29: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

D. Article 310.15 and 310.16

Copyright 2005 Ted "Smitty" Smith

Page 30: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 480 volt three phase motor that has a nameplate FLC of 52 amps will require what sized minimum overload protection? The motor also has a marked service factor of 2.0.

65 ampere 59.8 ampere 67.6 ampere 72.8 ampere

Copyright 2005 Ted "Smitty" Smith

Page 31: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 430.32

Copyright 2005 Ted "Smitty" Smith

Page 32: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum size copper grounding electrode conductor required for a 120/208 volt, 3 phase 4 wire service using three No. 250 kcmil copper conductors per phase?

#2 AWG 1/0 AWG 2/0 AWG 3/0 AWG

Copyright 2005 Ted "Smitty" Smith

Page 33: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C 250-66

Copyright 2005 Ted "Smitty" Smith

Page 34: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized service that would be required for the following school using the optional method of calculation. The school is fed with a 480 volt, 3-phase service. It is 120,000 square feet and has a total connected load of 4,752,000-volt amps.

1500 ampere 5000 ampere 3000 ampere 6000 ampere

Copyright 2005 Ted "Smitty" Smith

Page 35: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C. 220.86

Copyright 2005 Ted "Smitty" Smith

Page 36: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the total demand of the kitchen equipment in a restaurant that is 3000 sf and is equipped with a 19.6 kw oven, a 22.6 kw oven, a 4.9 kw grill, a 9.7 kw grill, two 5.8 kw fryers, a 11.9 kw walk in freezer, a 11,6 kw walking refrigerator, a 9.6 kw ventilated cooking hood with environmental control. A 6.7 kw dishwasher and a 4.7 kw dough kneader.

42200 VA 73385 VA 67145 VA 55000 VA

Copyright 2005 Ted "Smitty" Smith

Page 37: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C.

Copyright 2005 Ted "Smitty" Smith

Page 38: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is total demand on the main service entrance for a single range in a single family dwelling that has a nameplate rating of 19.6 kw?

19600 VA 12000 VA 11200 VA 10800 VA

Copyright 2005 Ted "Smitty" Smith

Page 39: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C.

Copyright 2005 Ted "Smitty" Smith

Page 40: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the average locked rotor current of a three phase motor with a design letter K and a nameplate rating of 15 hp? The motor is operating at 480 volts three phase.

265.63 a 21 a 169 a 153.36

Copyright 2005 Ted "Smitty" Smith

Page 41: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

D. 430.7(B)

Copyright 2005 Ted "Smitty" Smith

Page 42: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

Each of the slides will now be repeated.

They are not timed in this segment. To change a slide, click on the side with your left mouse button.

Be sure to physically look up the answers in your code book to improve your look up speed and skill.

Copyright 2005 Ted "Smitty" Smith

Page 43: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum/ maximum overload relay range that would be allowed for a 230 volt, single phase AC motor that is rated at 2 horsepower and a marked temperature rise of 30 degrees Celsius?

15a-16.8a 20a-22a 12a-14a 12a-15a

Copyright 2005 Ted "Smitty" Smith

Page 44: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 430.32 and 430.34

Copyright 2005 Ted "Smitty" Smith

Page 45: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum required length of a pull box that is placed between two 4” EMT conduits? The conduits will enter on either end and the wires will pull straight through the box. The conduits will contain six #1 THHN conductors, three #4 THW conductors and fifteen #12 THHN conductors. In addition a #4 ground conductor will be run in the conduits. The ground conductor will be THHN.

22” 18” 32” 24”

Copyright 2005 Ted "Smitty" Smith

Page 46: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C 314.28(a)(1)

Copyright 2005 Ted "Smitty" Smith

Page 47: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum required service for a single family dwelling that is 1100 square feet and is equipped with 12kw range, a 4.2kw water heater and 8.6kw of fixed electric heat? The house also has a 1.1kw dishwasher and a .75kw garbage disposal. The house is fed by a 230v, single phase service.

110a 125a 119.64a 120a

Copyright 2005 Ted "Smitty" Smith

Page 48: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

B Article 220 Part II

Copyright 2005 Ted "Smitty" Smith

Page 49: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized THHN conductor that can be used to feed a set of non-motor generator arc welders? The set is made up of four arc welders that have I1eff ratings of 40a, 50a, 65a and 75a. The termination lugs are rated at 75 degrees Celsius and the over current device is rated at 90 degrees Celsius.

4/0 2/0 3/0 1/0

Copyright 2005 Ted "Smitty" Smith

Page 50: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 210 630.11(b) and 630.11(a) and T310.16 75c column

Copyright 2005 Ted "Smitty" Smith

Page 51: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

hat is the minimum sized THHN conductor that can be used on a branch circuit with a load of 42 amps? The load is a single motor for a control servo on a crane. The motor is designed to operate no more than 30 minutes at a time. The crane is permanently in place and is expected to operate at an ambient temperature of 46 degrees Celsius. The termination lugs are rated for 75 degrees Celsius.

  6 awg 4 awg 8 awg 10 awg

Copyright 2005 Ted "Smitty" Smith

Page 52: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A T610.14

Copyright 2005 Ted "Smitty" Smith

Page 53: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized neutral that can be used for the service entrance for a single family dwelling that is 56’ x 125’. The home is equipped with a 16.8kw range, 230v, 4.6kw dryer, 230v, a 1.2 kw dishwasher and a .89 kw garbage disposal.

6 awg 3 awg 1/0 awg 2 awg

Copyright 2005 Ted "Smitty" Smith

Page 54: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

. D 220 Part II

Copyright 2005 Ted "Smitty" Smith

Page 55: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

If six #14 TW conductors at .0319 square inches each, and eight number 8 THWN conductors were installed in an 18” conduit between two cabinets, the minimum sized PVC, schedule 80 conduit, permitted by the NEC would be __________.

A. ¾” B. 1” C. 1 ¼” D. 1 ½”

Copyright 2005 Ted "Smitty" Smith

Page 56: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C. Tables 1, 4 and 5 Chapter 9

Copyright 2005 Ted "Smitty" Smith

Page 57: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 40-unit condo, each condo has a 4.5kw water heater 230v. What is the total demand on the service of the water heaters?

A.135kw B. 150kw C. 180 D. 210

Copyright 2005 Ted "Smitty" Smith

Page 58: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A. 220.53

Copyright 2005 Ted "Smitty" Smith

Page 59: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum required service for a dwelling that is 1000sf and is equipped with two wall a mounted ovens each rated at 240v and 25 amps and one cooktop rated at 240v and 20 amps. It also has 1.2kw dishwasher?

110a 125a 75a 100a

Copyright 2005 Ted "Smitty" Smith

Page 60: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

D 220 Part II

Copyright 2005 Ted "Smitty" Smith

Page 61: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

Calculate the feeder demand for 55- 14kw ranges in an apartment building?

72.875kw 66.25kw 50kw 25kw

Copyright 2005 Ted "Smitty" Smith

Page 62: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A Tble 220.55

Copyright 2005 Ted "Smitty" Smith

Page 63: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized 480v, three phase service that would be required for a commercial restaurant that is 18,000 square feet and equipped with 110 receptacle outlets, 150 feet of non-simultaneous 3000 series wire mold, 2000 VA lighted sign circuit, 300 ft of decorative track lighting, two 19.6kw ovens, three 9.2 kw grills, a 9.8kw walk in freezer, a 7.2 kw walk in refrigerator, two 5.9 kw deep fryers, a 4.2 kw ventilated cooking hood and a 480v, three phase, 7.5 hp squirrel cage motor for the RTU for HVAC purposes.

225a 205a 200a 150a

Copyright 2005 Ted "Smitty" Smith

Page 64: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 225 Article 220 Part II

Copyright 2005 Ted "Smitty" Smith

Page 65: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized schedule 80, rigid nonmetallic conduit that could be used for a branch circuit requiring 11 phase conductors and 4 neutral conductors and one ground conductor? The phase conductors will all be #10 THHN, the neutral conductors will all be #8 THHN and the ground conductor will be #12 THW. The conduit will be run ¾ of its distance underground and approximately ¼ of its distance encased in 6 inches of hardened concrete with sand under-footing.

1” 2” 1 ¼” 1 ½”

Copyright 2005 Ted "Smitty" Smith

Page 66: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C Tables 1, 4 and 5 Chapter 9

Remember: Not the annexs.

Copyright 2005 Ted "Smitty" Smith

Page 67: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the ampacity for each conductor when a raceway contains nine No. 4 THW copper current carrying conductors that are installed in a room with an ambient temperature of 96 degrees F?

70 amperes 85 amperes 59.5 amperes 52.36 amperes

Copyright 2005 Ted "Smitty" Smith

Page 68: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

D. Article 310.15 and 310.16

Copyright 2005 Ted "Smitty" Smith

Page 69: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 480 volt three phase motor that has a nameplate FLC of 52 amps will require what sized minimum overload protection? The motor also has a marked service factor of 2.0.

65 ampere 59.8 ampere 67.6 ampere 72.8 ampere

Copyright 2005 Ted "Smitty" Smith

Page 70: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

A 430.32

Copyright 2005 Ted "Smitty" Smith

Page 71: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum size copper grounding electrode conductor required for a 120/208 volt, 3 phase 4 wire service using three No. 250 kcmil copper conductors per phase?

#2 AWG 1/0 AWG 2/0 AWG 3/0 AWG

Copyright 2005 Ted "Smitty" Smith

Page 72: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C 250-66

Copyright 2005 Ted "Smitty" Smith

Page 73: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the minimum sized service that would be required for the following school using the optional method of calculation. The school is fed with a 480 volt, 3-phase service. It is 120,000 square feet and has a total connected load of 4,752,000-volt amps.

1500 ampere 5000 ampere 3000 ampere 6000 ampere

Copyright 2005 Ted "Smitty" Smith

Page 74: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C. 220.86

Copyright 2005 Ted "Smitty" Smith

Page 75: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the total demand of the kitchen equipment in a restaurant that is 3000 sf and is equipped with a 19.6 kw oven, a 22.6 kw oven, a 4.9 kw grill, a 9.7 kw grill, two 5.8 kw fryers, a 11.9 kw walk in freezer, a 11,6 kw walking refrigerator, a 9.6 kw ventilated cooking hood with environmental control. A 6.7 kw dishwasher and a 4.7 kw dough kneader.

42200 VA 73385 VA 67145 VA 55000 VA

Copyright 2005 Ted "Smitty" Smith

Page 76: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C.

Copyright 2005 Ted "Smitty" Smith

Page 77: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is total demand on the main service entrance for a single range in a single family dwelling that has a nameplate rating of 19.6 kw?

19600 VA 12000 VA 11200 VA 10800 VA

Copyright 2005 Ted "Smitty" Smith

Page 78: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

C.

Copyright 2005 Ted "Smitty" Smith

Page 79: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

What is the average locked rotor current of a three phase motor with a design letter K and a nameplate rating of 15 hp? The motor is operating at 480 volts three phase.

265.63 a 21 a 169 a 153.36

Copyright 2005 Ted "Smitty" Smith

Page 80: Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.

D. 430.7(B)

Copyright 2005 Ted "Smitty" Smith