Tuned-Mass Damper Design-A Case Study

download Tuned-Mass Damper Design-A Case Study

of 16

Transcript of Tuned-Mass Damper Design-A Case Study

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    1/16

    Tuned-Mass Damper DesignA Case Study

    Dr. James (Jay) Lamb

    Structural Engenuity, Inc.

    (972) 247-9250 x212

    [email protected]

    http://www.structuralengenuity.com/http://www.structuralengenuity.com/
  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    2/16

    Tuned-Mass Damper DesignCase Study, 2

    Agenda

    What is a Tuned-Mass Damper?

    Case Study: TETRA Technologies Project

    Initial Site SurveyWill a Tuned-Mass Damper Work?

    Tuned-Mass Damper Design and Analysis

    Prototype Testing

    Installation and Performance Verification

    Summary and Conclusions

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    3/16

    Tuned-Mass Damper DesignCase Study, 3

    Tuned-Mass Dampers

    m

    kf

    Spring

    TMD

    2

    1

    Mass and Coil Spring PendulumMass and Flexure

    L

    g

    fTMD2

    1

    mL

    EIfTMD 3

    48

    2

    1

    A tuned-mass damper is a mass-spring-damper system that is attached to a structure

    to reduce the amplitude of undesirable motion

    The mass, spring stiffness, and damping factor must be tuned relative to the existing

    structures dominant mode (frequencyfModefTMD) responsible for the motion

    The location on the structure where the TMD(s) is/are attached is critical

    TMDs can have many different forms depending upon the application:

    A very compact form of TMD; ideal

    for space-limited applications or

    when concealment is criticalProbably the least expensive form of

    TMD; can be tailored for almost any

    application

    Ideal for low-frequency

    applications like tall

    buildings or flexiblewalkways

    L

    L

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    4/16

    Tuned-Mass Damper DesignCase Study, 4

    TETRA Technologies CaCl2 Plant

    SEI Asked to Perform a Site Vibration Survey, Identify the Cause of

    the Problem, and Provide Recommendations for Possible Solutions

    Control room swayed side-

    to-side immediately when

    plant opened

    Motion persists throughout

    the day and night

    Staff irritated by level ofmotion and complained to

    management

    Original engineers tried and

    failed to solve the problem

    Control Room

    Site Overview

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    5/16

    Tuned-Mass Damper DesignCase Study, 5

    Site SurveyProblem Diagnosis (1/2)

    SEI Measured and Identified all Significant Sources of Vibration;

    The 3.5-Hz Motion is the Primary Source of the Staffs Discomfort

    Motion

    Measured vibration data at foundation,

    along a column, and in the control room

    Power Spectrum

    Control Room and Structural Frame

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    6/16

    Tuned-Mass Damper DesignCase Study, 6

    Site SurveyProblem Diagnosis (2/2)

    Vibration Near 3.5 Hz is 3 Times Higher than the Human-Comfort Limit;

    Ground-Borne Vibration Excites the Sway Mode of Structural Frame

    Need to Reduce Vibration by 70%Tuned-Mass Damper is Practical Solution

    Human Perception Criteria

    Front-to-Back

    Criteria

    0.005-g

    Limit

    Measured Control Room Vibration (3.5 Hz)

    Limit = 0.005 g

    Data filtered around 3.5 Hz

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    7/16Tuned-Mass Damper DesignCase Study, 7

    Structural Dynamics Model of Existing Building

    Finite Element ModelControl Room Mass

    (both sides)

    12 ft

    28 ft

    24 ft

    18 ft

    Structural member properties taken fromexisting-structure drawings

    Mass of cables and pipes (not shown) at each

    level estimated from photographs

    Mass of prefabricated control room (not shown)

    obtained from manufacturer; additional mass of

    fit-out estimated

    Structural Model has Same Stiffness and Mass Properties as Existing Structure;

    Only 3 Bays Modeled Because They Act Independently in East/West Direction

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    8/16Tuned-Mass Damper DesignCase Study, 8

    Model Validation via Frequency Response

    Frame Sway Mode (3.5 Hz) Frequency Response

    3.5 Hz

    Model Parameters Adjusted so Models Sway Mode Matches the Measured

    Motion of 3.5 HzModel can now be Used to Design/Assess TMDs

    Motion at top (control

    room) is magnified by

    factor of 85 relative to

    motion of foundation

    Ratio of control room motion

    to foundation motion

    |H(f)|

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    9/16Tuned-Mass Damper DesignCase Study, 9

    TMD Conceptual Design

    Simple Design of Flexure-Based TMD Minimizes Cost and Performance

    can be Verified During Prototype Testing Before Final Installation

    Damping

    in joint

    FlexureBars

    Mass

    Attach to

    Existing Bldg

    Flexure-type (cantilever) TMD is

    appropriate for this structure

    Constrained-layer damping is

    incorporated into joint

    Flexure bars must be stiffer to

    compensate for joint flexibility

    East/West flexural mode (fTMD)required to be 3.4 Hz ( 3.5 Hz)

    Place 3 TMDs on the columns

    supporting the control room

    Idealized

    Model

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    10/16Tuned-Mass Damper DesignCase Study, 10

    Optimum TMD Performance

    ReinforcementTMD and Bldg

    Move in Phase

    CancellationTMD Opposes Bldg

    Motion

    DampingTMD and Bldg

    90 Out of Phase

    Reduction in Vibration(Increases With TMD Mass)

    TMD

    Mass

    TMD

    Mass

    BldgBldg

    Original Bldg

    Bldg with TMD

    TMD Has No Effect at Frequencies Belowor Above the Tuning Frequency

    Analysis Indicates TMDs Reduce Vibration by 90% of Initial

    Level Near 3.5 HzReal Performance will not be this Good

    In-Phase Mode Out-of-Phase Mode

    |H(f)|

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    11/16Tuned-Mass Damper DesignCase Study, 11

    TMD Internal Damping Optimization

    Maximum

    Reduction

    Original Bldg

    Out-of-phase modeIn-phase mode

    There is an Optimal Level of Internal Damping, but 8% to 16% Critical

    Damping Usually Yields a Robust Range for Very Good Performance

    Frequency Response: Effect of TMD Damping

    If TMD damping is too low, bothpeaks for the in-phase and out-

    of-phase modes will be present

    Optimal damping produces a

    nearly flat curve

    If damping is too high, the twomodes merge into a single peak

    TMDs made of steel or alum-

    inum usually require additional

    damping be incorporated

    |H(f)|

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    12/16

    Tuned-Mass Damper DesignCase Study, 12

    Vibration Mitigation Effectiveness = TMD Mass

    Select TMD Mass to Achieve Desired Mitigation Over Narrow Band (1 Hz)

    Need to Reduce Vibration by at Least 70% HereUse 1500 lbm/TMD

    Results for optimized dampingfor each TMD mass

    Results (1-Hz Bandwidth):190 lbm 47% reduction

    375 lbm 55% reduction

    750 lbm 63% reduction

    1500 lbm 71% reduction3000 lbm 78% reduction

    Selection of bandwidth is

    somewhat arbitrary

    Increment of improvement in

    vibration mitigation diminishes

    with increasing mass

    Frequency Response: Effect of TMD Mass

    Determine vibration

    reduction over band for

    broadband excitation

    High

    Low

    High

    Low

    f

    f

    f

    fm

    dffH

    dffHR

    2

    0

    2

    )(

    )(1

    |H(f)|

    fLow fHigh

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    13/16

    Tuned-Mass Damper DesignCase Study, 13

    Prototype TMD Testing45-in Long Flexure

    41-in Long Flexure

    31-in Long Flexure

    Constrained-Layer

    Damping

    SBR Rubber Layers and a Flexure Bar of 37.5 inches Identified

    as Best Combination and Provides About 12% Damping

    SEI Tested Various Combinations of TMD Flexure Bar Lengths and

    Constrained-Layer Damping Materials to Find Best Combination

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    14/16

    Tuned-Mass Damper DesignCase Study, 14

    Installation and Performance Assessment

    Tuned-Mass Dampers Successfully Reduce the Vibration in the Control Room

    Below 0.005-g Limit; Staff Report Environment is Significantly Better Now

    TMDs Installed on Structure Before/After Vibration

    SEI tested the TMDs after installation to verify the tuning. Data were also

    acquired in the control room for comparison with the original motion

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    15/16

    Tuned-Mass Damper DesignCase Study, 15

    Summary and Conclusions

    Tuned-mass dampers can be fabricated in many different forms

    based on the physical and aesthetic constraints of the application

    Tuned-mass dampers are viable vibration mitigation solutions whenthe motion is caused by a low-damped mode of the structure

    Design process for tuned-mass dampers

    Site Survey: Measure the frequency and magnitude of the undesirable motion

    Analyze/Design: Develop model of existing structure and determine the TMDmass and placement of TMD(s) to achieve vibration mitigation requirement

    Test: Perform prototype testing of the TMD to fine-tune the design

    Install/Verify: Measure the motion of the TMD(s) on the structure to confirmperformance and that the mitigation objective was achieved

    Expect 70% to 80% reduction in the vibration after installation

    Weight of TMD is typically about 5% to 10% of effective weight ofmode responsible for the motion

  • 7/22/2019 Tuned-Mass Damper Design-A Case Study

    16/16

    Tuned-Mass Damper DesignCase Study, 16

    Questions? Contact SEI

    Please contact us with any vibration mitigation issues you

    have and let us help you to resolve them

    Structural Engenuity, Inc.

    Dr. James (Jay) L. Lamb

    Office: (972) 247-9250

    Cell: (214) 412-8388

    [email protected]

    www.structuralengenuity.com

    mailto:[email protected]:[email protected]