Copyright © SEL 2016 Traveling Waves For Fault Location and Protection Venkat Mynam Copyright © SEL 2016

Transcript of Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault...

Page 1: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Copyright © SEL 2016

Traveling Waves ForFault Location and Protection

Venkat Mynam

Copyright © SEL 2016

Page 2: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Source-Free Wave Equation…Free Space

0

0

2

0 0 2

22

2 2

B HxEt t

D ExHt t

Ex xEt

1 EE 0c t

0 0

1c

Page 3: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

On a Lossless Line

Solutions are any function of the form:

2 2

2 2 2V 1 V 0

x c t

Page 4: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Propagation Along a Line

• Forward (Left) and backward (right) traveling waves maintain their shape if there are no losses, until they “hit” something

• Losses cause traveling waves to attenuate and usually distort…

…unless R GL C

Page 5: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Propagation Along a Line

• Skin effect vs frequencyincreases R, decreases L

• Corona can far exceed I2R losses

• Ground mode is more resistive

Page 6: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Discontinuities: Faults, Buses, …

At the discontinuity,

ρV, Reflection Coefficient

I RD

I R

D CR I

D C

C DR I

C D

v vv Zi i i

1 shortZ Zv vZ Z 1 open

1 shortZ Zi iZ Z 1 open

Page 7: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator
Page 8: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Out on the Power Line(The birth of a traveling wave)

GROUND

t

408 kVVoltage Collapse

InsulatorSportsman

Zot!!

Page 9: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

At the Instant of Voltage Collapse

• A traveling 408 kV wave front emanates in both directions on the faulted conductor

• Current waves are con”currently*” producedvF

iF

vFiF

Page 10: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

As the voltage/current Wave Front Travels

X

• Rise time increases• Amplitude decreases

e

High frequencies attenuated due to conductor skin effect losses

Page 11: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Faults Launch Traveling Waves

Page 12: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

No Detectable High-Frequency Transient at Line Terminal When Fault

Inception Angle Is Zero

Page 13: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Am

pere

s

TW Fault Location PrincipleSingle End and Double End

Page 14: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

BPA and BC Hydro Successfully Used This Technology to Locate

Faults

Page 15: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Accurately Locate Faults With Traveling Waves

For a fault at 38.16 miles

Method Distance (miles) Difference (miles)

Impedance 34.03 4.13

Traveling wave (TW) 37.98 0.18

Page 16: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

CT Bandwidth Is Adequate to Capture TWs

R. C. Dugan, M. F. McGranaghan, and H. W. Beaty, Electrical Power Systems Quality. McGraw Hill, New York, NY, 1995.

Page 17: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

CVTs Have Limited Bandwidth

M. Kezunovic, L. Kojovic, V. Skendzic, C. W. Fromen, D. R. Sevcik, and S. L. Nilsson, “Digital Models of Coupling Capacitor Voltage Transformers for Protective Relay Transient Studies,” IEEE Transactions on Power Delivery, Vol. 7, Issue 4, October 1992, pp. 1927–1935.

Page 18: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

• Forming vI, vR uses all the information (v and i) helps sort out reflected, transmitted waves

• CTs are pretty “hi-fi” for transients: over 100 kHz

• CCVTs are not, except at the capacitive voltage divider tap, but that means new cabling

• Use currents and two-end method

• Perfect in current differential relays

• Reuse same communications channel

Practical Considerations

Page 19: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

• Availability of TWFL for all lines

• No need for new wires or sensors

• Built-in relay-to-relay communication

• Built-in time synchronization

• Protection elements to aid fault location

• Z-based fault locator that complements TWFL

Advantages of TWFL in Relays

Page 20: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

• Filter and sample phase currents

• Isolate desired aerial mode

• Accurately measure time of arrival

• Exchange arrival time with other end, over same 87L channel

• Calculate location using two-ended TWFL equation

TW Fault Locator Design

Page 21: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Differentiator-Smoother Works GreatBorrowed Idea From “Leading-Edge

Tracking”

Interpolate to50 ns Accuracy

s

a

s

s

Current Arrival Timei(t) is(t)

tadis/dt

Page 22: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Relative Accuracy ~ 50 ns

Mean Error = 17 ns or 8′

Standard Deviation = 32 ns or 16′

Page 23: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

First Application Helps Locate Faults on Challenging 161 kV Line

SEL-411LSEL-411L

Page 24: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

SEL-411L Reported Ground Fault at 59.04 Miles

Page 25: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

“We Know Where Your Faults Are”

Nature of Fault Line Patrol (miles) TW (miles)

Flashover 67.91 68.19

Lead projectile 38.16 37.98

Lightning 66.86 67.25

Flashover 61.50 61.42

Flashover 50.18 50.56

Flashover 59.04 59.04

Accuracy within one to two tower spans

Page 26: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

SEL-411L TW Works on Tapped Lines115 kV, 112.85-Mile Line

Page 27: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Line Energization From Brasada Identifies Tap Locations

Am

pere

s

Page 28: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Line Patrol – It Was Like “Chasing Ghosts on This Line”

Nature of Fault Line Patrol (miles) TW (miles)

Flashover 36.65 36.33

Flashover 36.65 36.76

Flashover 6.92 6.92*

Flashover 91.62 91.76

Flashover 4.94 4.94*

Bird waste 47.1 47.35

*Single-ended fault location

Accuracy within one to two tower spans

Page 29: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Single-Ended TWFLChallenging to Identify Correct Reflections

First Wave

Reflection 1Reflection 2

Page 30: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Impedance-Based Fault Location Sorts Reflections

Calculates FL at 6.95 MilesBrasada Terminal Open

Ideal Condition for Impedance FL

Page 31: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Impedance Points Way, TW Finds Fault Calculated at 6.92 Miles

First Wave

Reflection From Fault

Page 32: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW Fault Location Is Perfect for Series-Compensated Lines

Page 33: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Estimate Propagation Velocity and Fault Location

First Wave

Reflection From FaultReflection From Remote Terminal

fault remote

2 •LLVelocity = = 0.98069(∆t +∆t ) • c

Page 34: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

CFE Reported 55.67 Miles for This Fault

SEL-411L TW (miles) Standalone TW (miles)

55.66 55.43

Page 35: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

SEL-411L Relays With TW Function In Service on 345 kV Underground Cables

Page 36: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Waves Propagate Slower in Underground Cables

Wave Velocity = 0.48 Times Speed of Light

Event captured during cable energization

Page 37: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Locate Temporary and Permanent Faults Using Traveling Waves

Page 38: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW Technology for Protection of Transmission Lines

Page 39: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

15 MW more per millisecond savedR. B. Eastvedt, BPA, 1976 WPRC

The Need for SpeedMoving Energy at the Speed of Light

Safer • Less Damage • Improved Dynamics

Page 40: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Why Today? The Need for Speed

Faster communicationsPowerful processors

Better simulationsMay be simpler

Page 41: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Practical Traveling Wave RelayingBuild on TWFL Experience

Single-ended: sort out reflections; easier with voltages

Two-ended:

Directional comparison

Current differential

Page 42: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Speed of Light Limits Relay Time

The fastest communications path is the line

S R100-mile line ≈ 600 µs X

300 μs 300 μs

600 μs by line or 1,000 μs by fiber

900 μs or 1,300 μs

Page 43: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW Directional Element Principle

vTW iTW

+–

–+ Forward

+–

+– Reverse

vTW

iTW

iFvTW iTW vF

vF

Page 44: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW32F Asserts – Forward Fault

TW32F Operate

Page 45: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

0 100 200 300 400 500-100

0

100

Time (µs)600

-5

0

5

0 100 200-50

0

50

Time (µs)300 400 500 600

-2

0

2

0 100 200 300 400 500 600-1000

-500

0

Time (µs)

TW32R Asserts – Reverse Fault

TW32R Operate

Page 46: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW32F Asserts if vTW and iTW Are Opposite in Polarity

Page 47: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

New TW Differential PrincipleCurrent Only

• Internal fault surges: same polarity• External fault surges: Generally of opposite polarity

Spaced one travel time T apart

Σ of aligned surges = OPERATE

∆ of surges T apart = RESTRAIN

Page 48: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Internal Mid-Line Fault

S R

IF(0)

Σ = Is(300) + Ir(300) = BIG∆ = Is(300) − Ir(300 +/− 600) = small

Page 49: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

IF(0)

Internal Fault Closer to SΣ = Is(200) + Ir(400) = BIG

∆ = Is(200) − Ir(200 +/− 600) = small

S R

Page 50: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW87 Principle – Internal Fault

Line propagation time

m87 < 1 pu

Page 51: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

S

IF(0)

External Fault Travels the Entire LineΣ = Is(50) + Ir(650) = small

∆ = Is(50) − Ir(50 +/− 600) = BIGR

Page 52: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW87 Principle – External Fault

Line propagation time

m87 = 1 pu

Loca

l Cur

rent

(A)

Rem

ote

Cur

rent

(A)

Page 53: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW87 Element Operates When IOP Exceeds IRST

OP

RST

87

Page 54: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

TW87 Performance: 161 kV,117 km LineBG Fault, 117 km, Fault is at 18%

Pha

se A

TW (A

)P

hase

BTW

(A)

Pha

se C

TW (A

)

IL = 0.68 AIR = 0.35 AIOP = 1.03 AIRST = 0.13 Am87 = 0.81 pu

TT=396 s

Page 55: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

F F

Trip in 1.2 ms

Time (µs)

321

972

TW87 Operating Time on a 117 km Line

75

Page 56: Traveling Waves For Fault Location and Protection · PDF fileTraveling Waves For Fault Location and Protection ... For a fault at 38.16 miles Method Distance (miles) ... TW Fault Locator

Traveling Waves Provide Accurate Fault Location and High Speed Line Protection