    DISTANCE PROTECTION PZ-1000

    Page 1 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    2/22

    Page 2

    PZ1000 distance protection has 4 zoMHO characteristic firing and / or sadditional square phase-phase faultsTeleprotection and schemes, monito(Per pole) and other functions, comimportance of high level.

    DESCRIPTION

    PZ1000 teams are numerical distance protections,particularly suitable for primary protection of linessingle or double overhead transmission and subtransmission(AT and MT).

    Its advanced design algorithms multiprocessor with rapidtwo signal processing and ensure prompt actionmaintaining safe and high reliability featuresservices necessary for the management of networks of trans-mission and distribution.

    The team has a serial port PZ1000 front communicationand may have up to two rear ports that allow:

    Connect to an integrated system of protection and control.

    Access to status information, historical data and adjustedtees, locally, centrally or remotelyvia telephone.

    It also includes a third port dedicated rear communicationed to teleprotection, which allows direct connection between twoprotections.

    INTRODUCTION

    Page 2 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    3/22

    It adds protection unit and breaker fa recloser mono / pole with up to 4 rTheswitch monitoring functions, numbeare performed per pole.

    2

    FUNCTIONAL DIAGRAM

    Page 3

    Extension of Zone 1.

    Phase

    DISTANCE UNIT

    Page 3 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    4/22

    Teleprotection.The effect of using direct-sequence voltage and polarity

    tion, an expansion to the back of the MHO.

    Directional overcurrent unitsThe PZ1000 has 2 additional units oDirectional phase overcurrent and 2support for the main units of distancThus the reliability of operation of t

    Over / UndervoltageThe PZ1000 has two units of three-overvoltage and undervoltage other.

    The analysis was performed toeach phase separately.Surge homopolarThis feature provides protection aga

    Breaker failure protection

    Check the correct operation of a swifailure, causing otherwise, the shot spositions are needed to isolate the fa

    Protection heeled (STUB)Protects the faults that occur betweeline switch settings and media.

    Is a unitovercurrent switch activated with thThermal imageLine protects against thermal overlotemperature based on current load cRecent protected computer.

    Intensity imbalanceLine protects against imbalances thaintensity as a result of abnormalitiesin the power system or against the oQuilibra.

    All these features are supported by other functions

    tion functions and supervision, to ensure operationsecure protection.

    Negative sequence directionalAll units are monitored by an impedancenegative sequence directional unit, which provides the sen-Tido of failure.

    Teleprotection schemesIt allows, through communication with other terminals,following protection schemes:

    I Rolling Triggering

    I Permissive overreach: POTTI Permissive underreach: PUTT

    I Directional lock: DCB

    I Directional release: DCUB

    Additional schemes:

    I ECO (permits)

    I Reverse Address Blocking

    I Food weak (Weak infeed)

    I Download trip.

    The teleprotection is by digital inputs and / or communitycation series.

    two-phaseovercurrent

    ,monophasic and biphasic threshold

    Fuse failure detectionUnit blocks away, if it detects the dsome of the tensions.You can also lock the unitdirectional and / or voltage units deadjust.

    Power swing (Out of step)Blocks away units phase-phase, if osituation and gives power swing osunstable power.

    Masking areaBlocks away units phase-phase, if tview is within the charging zone se

    Closing on lack DetectorProvides non-directional instantanecloses the switch to a void in the lin

    ADDITIONAL FEATURESFOR PROTECTION

    Page 4 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    5/22

    This function as a directional settindirectional.

    3

    Page 4

    Monitoring switch (per pole)An event is generated when the counter Ski 2somephase exceeds the programmed threshold.

    Supervisory circuits 74TC/CC opening and closing (forpole)Make the detection of any abnormalities in the circuits, boththe switch is open or closed.

    Excessive number of shots (per pole)An event occurs and a control signal, when anumber of shots per stage than scheduled in a tim-po default. The recloser locks when you exceed the set valueTreaty.

    Open stage alarmGenerates an alarm when it detects an open phase situation.

    CTs monitoringGenerates an alarm to detect failure in any channelcurrent input. (Only on models with the calculated Inown line).

    Recloser mono / phaseNo. of programmable up to 4 reenlistment

    The first reclosing is mono / pole and the other pole

    Different times for each reinstatement

    Counter move for each reinstatement

    Commissioning or out of service by setting, go-da and communications

    Timing CheckerThe function compares the voltage signals of a phase (in modulesand the story), the two sides of the switch, giving permissionclosing the switch when it meets the conditions setpresets. Serves both manual and automatic closing.

    The angle difference is calculated by compensation

    MONITORING FUNCTIONS

    AUTOMATION AND CONTROL

    Pole discrepancyThis unit checks the discrepancy inpoles, leading to the opening of theafter a set time in a state with a poledifferent from the rest.

    Programmable LogicThe user can configure up to 6 logiccan be assigned to output relays andConsole SIPCON protections.

    Page 5 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    6/22

    .

    Dead line detection (DLD)Detected phases disconnected from a line, generating asignal.

    Self DiagnosisPZ1000 digital protection makes the following autodiag-permanent diagnoses:

    Software ImplementationSupply voltage

    Hardware

    Uptake measures

    The shortcomings identified in the self-test is signaledby any of the dual output (configurable).

    4

    Page 5

    MeasurePZ1000 protection relay provides real-timefollowing quantities:

    Intensities per phase and neutral (1%)

    Frequency (0.01 Hz)

    Active and reactive power and power factor (1%)

    Bidirectional power (Class 5)

    Note 1: Further details on request.Note 2: Depending on the model, the units include the measurement of battery voltageexternal.

    Disturbance recordingThe PZ1000 can be stored in nonvolatile memory, asModel:

    I 20 records of 30 cyclesI 10 records of 60 cycles

    Each record contains the samples of 8 analog andstores the status of 16 digital signals can be selected.

    Preboot shot configurable.

    The disturbances are collected and exported formatsCOMTRADE.

    DATA ACQUISITION FUNCTIONS

    Event LogStored in nonvolatile memory aqueue of 200 eventsrecoverable from PC-textEach event is accompanied by:

    I Date and time of occurrence of thI Description of the event codeI Values of electrical parameters (

    occurrence of the same.

    Page 6 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    7/22

    5

    Fault reportsNon-volatile memory stores the last 9 faults with

    following:

    I Date and time of pickup, beginning and end of absenceI Values of electrical parameters of pre-fault and faultI Duration and type of the lack

    I Actuated unitsI Distance to the lackI Shooting area and / or intertrip

    Fault locatorThe fault locator processes the information in eachabsence, returning as a result of this calculation the distance topoint of failure. The measure the distance is given in km and isaccessible from the display of the team and from the PC.

    Setting tables

    The team has 4 separate tables. The selection ofactive table can be done through the keyboard / display,from console screens or input activationdigital.

    Historical measuresStored in nonvolatile memory, a que

    cos, the maximum and minimum vosimple average, within a programma

    Time synchronizationIn communications

    Demodulated IRIG-B input

    The unit has clock with battery back

    Demand Maximum demand

    The unit stores the maximum intensimaximum values previously calculatime instant that has occurred.

    Page 6

    ARTECHE TEAM program haProtections developed for Windallows a simple and clear dialoto access information stored inmake the necessary adjustment

    SOFTWARE

    The PZ1000 has the following communicationwith the user:

    Display / keyboard

    HMI MM QUINA

    Page 7 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    8/22

    All configuration accesses arekey prevents tampering by non-Curly.

    Among the program features SIinclude:

    Automatic detection team thatdialogue.Presentation of equipmentstatus through pan-state sizes.

    Presentation and modificationof settings

    File and presentation of allinformation storedgiven by the relay: events, fa

    SIPCON, Protection software islizado in the integrated protectiTEAM ARTECHE, so that is ias a more functional module.

    Features:Liquid crystal display 2 lines of 16 characters

    16-key keypad

    Optical signaling 12 programmable LEDs and 1 alarm

    ma bicolor.

    4 buttons, which can be disabled by setting:

    Allows:Viewing entries, measurements, date and time, statistical data

    cos and ultimate failure.View and change settings and active table, as well as the allocation of

    inputs, outputs and LEDs.

    Optionally the computer may include a front cover con-guiendo a degree of protection IP54.

    CommunicationsThe team has:Front serial for local communication.

    Two exits later series (1 optional), for local access and / or

    Remote control and protection information.

    For all these outputs can collect all the informationprotection available, and modify all sorts of settingsthrough the Software-Protectors SIPCON ARTECHE TEAM.

    PZ1000 protection also has an option of aserial output back to Teleprotection.

    Communication protocols backdoorThe communication protocol is always the first port protocolsProcome it. The protocol of the second rear port, if any, ischosen by the user from DNP or Procome.

    The third rear port communication protocol uses a privatewith whom do you send and receive signals from remote protection.

    Switch closure

    Breaker open

    Local / Remote

    Permit maneuver

    Page 8 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    9/22

    6

    Page 7

    The accompanying drawing shows an application of computer PZ1000,for overhead lines fed by bothends.

    In this protection scheme applies fuTeleprotection.

    The image shows an application ofprotection of one and a half breakerprotection to the heel, is protected aline switch, where the latter is open

    The existence of three switches andbreaker failure, reclosing and syncrone of them is solved by using unifPL-70 functional-ARTECHE TEA

    PL-70 SY: For syncrocheckfunction.PL-70 FI: For breaker failurefunction.PL-70 IT: recloser function.

    APPLICATIONS

    PROTECTION OF POWER BY AIRLINE WITH BOTH ENDS

    HEEL PROTECTION (STUB)

    Page 9 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    10/22

    7

    Page 8

    DISTANCE PROTECTION (21)

    ADJUSTMENT RANGES

    Settings Range StepZones 1 to 4 Phase - Neutral ()0,01-300,00 0,01Zones 1 to 4 Phase - Phase ()0,01-300,00 0,01Note: All settings for the 4 zones are independent.

    MHO Scope

    Settings Range StepReactor zones 1 to 5 Phase - Neutral ()0,01-300,000,01Resistance zones 1 to 5 Phase - Neutral ()0,01-300,000,01Reactor zones 1 to 5 Phase - Phase ()0,01-300,000,01Resistance zones 1 to 5 Phase - Phase ()0,01-300,000,01Note: All settings for the 4 zones are independent.

    Settings Range StepZone 1 Module 0,01-50,000,01Plot Area 1 0-3590 10Zone 2 Module 0,01-50,000,01Plot Area 2 0-3590 10Module rest areas 0,01-50,000,01Argument rest areas 0-3590 10Module comp. KMO mutual Zone 1 0,01-300,000,01Argument comp. KMO mutual Zone 1 0-3590 10Module comp. KMO mutual Zone 2 0,01-300,000,01Argument comp. KMO mutual Zone 2 0-3590 10Module com . KMO mutual 0 01 0 01

    Quadrangular

    Homopolar Compensation

    SettingsProtection scheme -Esc-Perover-Perund-DireLoc-Unldire

    Time relapse entrda RTP 0,-1,

    Additional time block (s) 0,-1,

    Time signal loss 0,-0,

    Enabling ECOECO timing (s) 0

    -1

    Enabling direcc lock. reverseTiming direcc lock. reverse 0

    -1

    Enabling low powerEnabling direct hit

    Teleprotection scheme

    Address OverreachSettings RaZone 2 N

    FroBacktoShootiShotbackwithou

    Zone 3 NFro

    BackShot

    Page 10 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    11/22

    8

    rest areas -

    300,00Argum. Comp. KMO mutual rest areas0-3590 10

    Settings Range StepPhase - Earth Zone 1 (s) 0,0-100 0,01Phase - Earth Zone 2 (s) 0,0-100 0,01Phase - Earth Zone 3 (s) 0,0-100 0,01Phase - Earth Zone 4 (s) 0,0-100 0,01

    Phase - Earth zone 5 (s) 0,0-100 0,01Phase - Phase Zone 1 (s) 0,0-100 0,01Phase - Phase Zone 2 (s) 0,0-100 0,01Phase - Phase Zone 3 (s) 0,0-100 0,01Phase - Phase Zone 4 (s) 0,0-100 0,01Phase - Phase zone 5 (s) 0,0-100 0,01

    Timing

    SettingsPhase faults Units - Land MHO, Foursquare

    MHO and square, noFaults units Phase - Phase MHO, Foursquare

    MHO and square, noSingle-phase tripping YES / NO

    General

    SettingsEnabling (independent) YES / NOOvercurrent phase (A) (0.2 to 30) In 0,1Overcurrent phase (A) (0.2 to 30) In 0,1T. additional (s) (independent)0,00-10 0,01

    Single-phase overcurrent / Biphasic

    Shooti

    backwithou

    one4 NBack

    toShootiShotbackwithou

    Zone 5 NFroBe

    Nondi

    Settings R

    Qualification

    Interior X () 0,0-300

    R interior () 0,0-300

    Exterior X () 0,0-300

    Foreign R () 0,0-300

    Threshold direct sequence (A) (0.to30In

    T. activation (s) 0,0-50,

    Threshold Imax(A) (0.to30

    In

    Value I2/ Imax 1-

    5

    Lock zone Z1, Z2, Z3, Z4, Z5

    Power swing

    Settings Range StepQualification YES / NOReverse sequence threshold (V)10,00-165,00 0,1Threshold reverse sequence (A)(0.2 to 30) In 0,1

    Fuse failure (68FF)

    Settings RaQualificationThreshold direct sequence (A)(0.2

    to30)In

    Impedance ()(Independent front and rear)

    0,0-300Angle + (gnd)

    (Independent front and rear)0-35

    Angle - (gnd)(Independent front and rear)

    0-35

    Masking Area (68ZC)

    Settings RaQualification

    Direct Sequence Threshold (V)10,0-165,

    Threshold direct sequence (A)(0.2to30)In

    Close on Lack detector (SOF)

    Settings Range Step

    Qualification YES / NOReverse sequence threshold (V)10,00-165,00 0,1Threshold reverse sequence (A)(0.2 to 30) In 0,1

    Open Stage

    Page 9

    ADJUSTMENT RANGES

    Settings Range StepQualification YES / NOUndervoltage threshold (V)10-165 1Minimum current threshold (A)(10-200)% In 0,01

    DEAD LINE DETECTION

    THERMAL IMAGE (49)Settings Range Step

    TRIP PERMIT AFTER RECLOSERSettings Step

    RangeZone 1 YESNOZone 2 YESNOZone 3 YESNOZone 4 YESNOPhase Inst YESNOTemp. phase YES

    Page 11 of 22DISTANCE PROTECTION PZ-1000

    12/12/2010http://translate.googleusercontent.com/translate_c?hl=en&sl=es&u=http://www.integrate ...

  • 8/13/2019 Translate c Hl=en&Sl=Es&

    12/22

    Directional phase and neutral (67)

    HEEL PROTECTION (PHASE / NEUTRAL)

    Settings Range StepReclosing mode Monopolar, tripolar, mono/tri-

    polar, as shotNumber of reenlistment 1-4 1T. 1erreinstatement phase (s)0,1-20 0,1T. 1erreinstatement phase (s)0,1-20 0,1

    T. 2orreinstatement (s) 1-300 0,1T. 3erreinstatement (s) 1-300 0,1T. 4orreinstatement (s) 1-300 0,1T. single phase lock security. (S)1-300 0,1T. Safety closure phase (s)1-300 0,1T. closing safety manual (s)1-100 0,1T. expected voltage (s) 1-300 0,1

    Settings Range StepEnabling timed NO, YES, YES

    + RelapseSoft start (0.2 to 4) In 0,1Timed response type Fixed time

    IEC-curve inversenormal BSCCurve IEC veryinverse-BSCIEC Curve-BSCextr. INVERAIEC Curve-BSCuser (mod.)ANSI inversenormal curveANSI very inversecurveANSI curve extr.

    reverseANSI curve user(mod.)Ind. Time

    ANSIIEC-BSC

    0,5-300,05-1,09

    0,10,01

    Fixed time 0-100 0,1Torque Control YES / NOEnabling instant YES / NOInstant Start (0.2 to 30) In0,1Additional time instant 0-10 0,01Torque Control YES / NOAng. sec. Reverse / homopolar0-3590 10Directional lock If Vpol