TRANSDUCERS
Current and voltage transducers are applied for the measurement of sinusoidal alternating
currents (Nominal-input current from 0,05 to 20A) and alternating voltages (Nominal input
voltages from 200 to 690 V). For higher currents or voltages transformers have to be con-
nected before. All transducers are able to snap on DIN rails.
6/1
MULTIFUNCTIONAL TRANSDUCER
CPQT is a configurable multi transducer for all electrical networks. Any of the
parameters can be linked to the 2 analog outputs.
The configuration is simple with the software “ConfigLQT” through the USB
port..
Configurable multifunctional transducer
Connections:
CPQT
Order informationDescription Output Article number
CPQT 2 Analog outputs 70051 - 1001
Technical DataInputs - Voltage
Input (Un) 100 – 400 V
Overload 1.5 x Un – continuously, 2 x Un – 10 s
Measuring range 0 – 500 V TRMS
Consumption Un x 1 mA / Phase
Frecuency 10…40….70…120 Hz
Inputs - Current
Input (Un) 1 – 5 A
overload 2 x In continuously, 10 x In 15 s, 40 x In 1 s
Measuring range 0 – 10 A TRMS
Load <0.05 VA / Phase
Aux. suppy
Universal current 24 – 250 VDC / 80 – 250 VAC
Consumption max 8 W
Outputs - Analog
Analog outputs 2
Range +/- 20 mA, Option: +/- 10 V
Load max 750 ohm (15V)
Response time < 100 ms
General Data
Accuracy class 0,2
Galvanic isolation Supply, in- and output are galvanically isolated
USB 1 pc for configuration
Temperature rangeOperation: -10 to +55 C° Storage -40 to +70 C°
Temperature coefficient < 0.1% / 10 C°
Test voltage 4 kV AC / min
Inputs Overvoltage cat. III
Outputs Overvoltage cat. II
Dimensions (w x h x d) 70 x 132 x 137 mm – DIN-rail
Weight approx. 0.5 kg
StandardSS-EN 60688SS-EN 601010 EN 61000-6-2 / -6-4 / -6-5
6/2
MULTIFUNCTIONAL TRANSDUCER
CPQT13 is a configurable multi transducer for all electrical networks. All of
the parameters can be linked to the 5 analog outputs.
There are 2 pulse outputs for kWh+ and kWh-.
The configuration is simple with the software “ConfigCPQT” through the USB
port.
Configurable multifunctional transducer
Connections:
CPQT13
Order informationDescription Output Article number
CPQT13 5 Analog outputs 70051 - 1000
Technical DataInputs - Voltage
Input (Un) 100 – 400 V
overload 1.5 x Un – continuously, 2 x Un – 10 s
Measuring range 0 – 500 V TRMS
Consumption Un x 1 mA / Phase
Frecuency 10…40….70…120 Hz
Inputs - Current
Input (Un) 1 – 5 A
Overload 2 x In continuously, 10 x In 15 s, 40 x In 1 s
Measuring range 0 – 10 A TRMS
Load <0.05 VA / Phase
Aux. suppy
Universal current 24 – 250 VDC / 80 – 250 VAC
Consumption max 8 W
Outputs - Analog
Number 5
Range +/- 20 mA, Option: +/- 10 V
Load max 750 ohm (15V)
Response time < 100 ms
Outputs - Digital
Number 2 ,110 V AC/DC, 100 mA
Communication
Serial RS485
General Data
Accuracy class 0,2
Galvanic isolation Supply, in- and output are galvanically isolated
USB 1 pc for configuration
Temperature rangeOperation -10 to +55 C° Storage: -40 to +70 C°
Temperature coefficient < 0.1% / 10 C°
Test voltage 4 kV AC / min
Inputs Overvoltage cat. III
Outputs Overvoltage cat. II
Dimensions (w x h x d) 150 x 70 x 73 mm – DIN-rail
Weight approx. 0.5 kg
StandardSS-EN 60688SS-EN 601010 EN 61000-6-2 / -6-4 / -6-5
6/3
TRANSDUCERS FOR POWER
Available Versions
Single phasealternatingcurrent
3-phase 3-lines current 3-phase 4-lines current
balanced load unbalanced load balanced load unbalanced load
Active power CPR/1 w NV CPR/1 d NV CPR/2 NV CPR/1 NV CPR/3 NV
Reactive power CPR/1 wb NV CPR/1 db NV CPR/2 b NV CPR/1 b NV CPR/3 b NV
Description
This transducer is applied for measuring active and reactive power of sinu-
soidal current at a frequency of 50-60Hz. They can be directly connected to
rated input currents of 0,1 to 20A and to rated input voltages of 50 to 720
V. At higher currents and/or voltages they must be preceeded by AC measu-
rement transformers.
An auxiliary voltage supply always is required. If the measurement circuit vol-
tage does not vary more than ±10% this can be used as an auxiliary energy
supply. In this case with client specification an internal connection between
measurement voltage and auxiliary voltage contacts will be carried out.
FMode of operation
Current and voltage are galvanically insulated (5.2kV/1min), multiplied, in-
tegrated and converted into an output signal (current or voltage) linearly
proportional to the active or reactive power. The addition of letter "L" in
their denomination indicates a live-zero output signal (e.g. 4-20mA).
Symetric inputBipolar output
Transducers for active and reactive power
• Class 0,5
• For mounting on DIN rail (DIN EN 50 022) or for screw fixing with 2 cylinder-head screw M4
CPRNV
Output characteristic
Life-zero Standardoutput output
6/4
TRANSDUCERS FOR POWER
Dimensions of housing D10 (CPR/1w, ..1d, ..1, 1wb, ..1db, ..1bNV)
Dimensions of housing D20 (CPR/2, ..3, ..2b, ..3bNV)
Technical Data (according to DIN EN 60688)Typ 1) CPR ... NV
Output short-circuit and open-circuit protected
Current output 0-20 mA, 4-20mA
Limiting current none or approx. 22,5 mA
Open-circuit voltage ca. 30 V
Output load 0...750 Ω , 0...1000 Ω
Variation < 1 ppm/Ω
Voltage output 0-10 V or 2-10 V
Limiting current approx. 22,5 mA
Limiting voltage ca. 18 V
Output resistance < 30 Ω
Input
Current input Available nominal ranges
100mA ...20A5...120 %
Voltage inputAvailable nominal ranges
50...720 V 40...120 %
Frecuency 45...65 Hz
Excessive inputs continuos / short duration voltage input current input
120 %5-fold20-fold
Transmission
Accuracy class 0,5 0,2
Ripple (peak-to-peak) < 1 % < 0,4 %
Response time < 0,3 s < 0,6 s
Drift vs. temperature (0...45ºC) < 200 ppm/ºK
Drift vs. auxiliary supply < 20 ppm/V
Auxiliary supply voltageAC DC
90...110 %85...125 %
Nominal consumption
Measuring input < 1 W
Auxiliary supply input < 3 W
1) other values on request.
Order exampleProduct Input Output @ KW @ V
CPR/1wNV @/1A (Please indicate on the order) 0 ...20 mA Please indicate on the order Please indicate on the order
CPR/1dNV @/1A (Please indicate on the order) 4 ...20 mA Please indicate on the order Please indicate on the order
CPR/2NV @/1A (Please indicate on the order) 0 ...10 V Please indicate on the order Please indicate on the order
CPR/1NV @/1A (Please indicate on the order) 2 ...10 V Please indicate on the order Please indicate on the order
Order information for CPR...NV
6/5
TRANSDUCERS FOR POWER
Single phaseAC current
Active power
CPR/1 w NV
3-Phase Current 3-wires
Active power
balanced load
CPR/1 d NV
3-Phase Current 3-wires
Active power
unbalanced load
CPR/2 NV
3-Phase Current 4-wires
Active power
balanced load
CPR/1 NV
3-Phase Current 4-wires
Active power
unbalanced load
CPR/3 NV
6/6
TRANSDUCERS FOR POWER
Single phaseAC current
Reactive power
CPR/1 wb NV
3-Phase Current 3-wires
Reactive power
balanced load
CPR/1 db NV
3-Phase Current 3-wires
Reactive power
unbalanced load
CPR/2 b NV
3-Phase Current 4-wires
Reactive power
balanced load
CPR/1 b NV
3-Phase Current 4-wires
Reactive power
unbalanced load
CPR/3 b NV
6/7
TRANSDUCERS FOR PHASE ANGLE
Life-zero StandardOutput Output
Transducers for phase angle (COS φ)
• Class 0,5
• For mounting on DIN rail (DIN EN 50 022)
Description
The transducers Phwd-MU is used to convert and isolate the phase angle bet-
ween current and voltage of an AC and three-phase mains of balanced load
into a load-independent direct-current and direct voltage signal.
Conformity
This equipment conforms to the requirements of the Directive from the Council
of the European Community on the harmonisation of the member states re-
garding electromagnetic compatibility, EMC Directive 2004/108/EC, as
well as Low Voltage Directive 2006/95/EC.
Application
The measuring transducer Phwd-MU serve to convert and isolate the phase
angle between current and voltage of an AC and three-phase mains of ba-
lanced load into a load-independent direct-current and direct-voltage signal.
Function
The quantities to be measured will get via internal current transformers and
voltage divider to the null comparator. At the null comparator there is a rec-
tangular signal which is directly connected with the phase angle. A subse-
quent integrating step forms the direct-voltage mean value. This direct voltage
will be converted into a load-independent direct current and into an impres-
sed direct voltage. The galvanic separation between input and output signals
is effected by means of an optocoupler. The secondary amplifiers will supply
the load- independent direct current and direct-voltage signals. Both outputs
are no-load resistant and short-circuit proof. Any connection between both
outputs will be unacceptable. An auxiliary voltage will be required.
Phwd - MU
Characteristic lines: Output characteristics
4 - Quadrantal operation (Option)
cap.Received
ind.Supplied
cap.Supplied
ind.Received
Supplied Supplied
Received Received
cap.
cap.
ind.
ind.
Aux. supply
Current- impression
Voltage- impression
null-comparator
6/8
TRANSDUCERS FOR PHASE ANGLE
Connections
Dimensions
Technical Data (according to DIN EN 60688)Input
Input quantity Phase angle between sinusoidal current andvoltage in AC (or) three-phase systems
Rated value-60° - 0 - +60° electrical, cos phi 0,5 cap - 1 - 0,5 ind or-45,6 ° - 0 - +72,5 °electrical, cos phi 0,7 cap - 1 - 0,3ind
Rated voltage 100 V, 110 V, 230 V, 400 V, 500 V or 600 V(690 V in ground installation)
Rated current 1 A or 5 A , 0,3 VA
Rated frequency 50 Hz, 60 Hz or 400 Hz
Permanent overload voltage 1,2-fold, current 2-fold
Surge overload voltage 2-fold 1 sec., current 20-fold 1 sec.
Output
Output quantitiesproportional direct current and proportional direct voltage When using both outputs at the same time the voltage out-put must be charged with max. 1 mA.
Doble output0-20 mA/ 0-500 Ohm burden and 0-10 V max. 10 mA load, as well as 4-20 mA/0-500 Ohm burden and 2-10V max. 10 mA load, switchable at the front.
Options
4 Quadrant Operation for AC or three phase current with two-sided energy directionFrequency control a value of 0-5 Hz bis 0-10 kHz“ Open-collector” NPN, max. 30 V 100 mA resilient, Pulse/ pause 50/50 % Square wave signal 5 V, max. 10 mA load, pulse /
break 50/50 %
Dynamic system behaviour
Accuracy +/- 0,5 % (linear to the angular degrees)
Current range 4-200 % of the rated current
Current influence < 0,5 % for 0,15 up to a twice rated current
Voltage influence < 0,1 % for +/- 10 % of rated voltage
Frequency influence < 0,1 % with difference frequency 10 Hz
Temperature range -15 up to + 20 up to +30 bis +55 °C
Temperature influence < 0,2 % at 10 K
Influence of Aux. none
Load influence none
External magneticfield influence none (up to 400 A/m)
Residual ripple < 30 mVss
Response time < 400 ms
Open-circuit voltage max. 24 V
Current limitation max. 2-fold in case of saturation
Aux. suppy 230 V AC +/- 20 %, 45-65 Hz, 2,5 VA
Option110 V AC +/i 20 %, 45-65 Hz, 2,5 VA24 V DC, -15 % up to + 25 %, 2 W, (EMV DIN EN 61326 Class A)
Wide range aux. supply (Option)
6-30 VAC + DC or 36-265 VAC + DC, 2 VA,(EMV DIN EN 61326 Class A)
Weight Standard type 200 g
Regulations
EMV DIN EN 61326
Mechanical strength DIN EN 61010 Part 1
Electric security
DIN EN 61010 part 1Housing all insulated, protection class II,at a working voltage up to 300V (network to neutral con-ductor) degree of pollution 2, overvoltage category CAT IIIat a working voltage up to 600V (network to neutral con-ductor) degree of pollution 2, overvoltage category CAT II
Accuracy, overload DIN EN 60688
Separation DIN EN 61010 Part 1, 3,52 kV 50 Hz 10 sec.
Air gaps and creep distance DIN EN 61010 Part 1
System protection DIN EN 60529 Housing IP30, terminal IP20
Connections DIN 43807
Order information for Phwd-MU
Order exampleProduct Input
Output
Phwd-MU 380 V / 5 A 4 ...20 mA / 37º - 0 - 53º
Phwd-MU 110 V / 5 A 4 ...20 mA / 60º - 0 - 60º
6/9
TRANSDUCERS FOR ALTERNATING CURRENT
CIR
Technical Data (according to DIN EN 60688)Typ 1) CIR CIR/IOutput short-circuit and open-circuit protected short-circuit and open-circuit protectedCurrent output 0 ...20 mA 4 ...20 mALimit current none or approx. 22,5 mA approx. 22,5 mAOpen-circuit voltage approx. 30V approx. 30VOutput load 0 - 750 Ω 0 - 750 ΩVariation < 50% < 1ppm/ΩVoltage output 0 ...10V 0 ...10VLimiting current none or approx. 22,5 mA < 30 ohmLimiting voltage approx. 18V approx. 18VOutput resistance 500 Ω < 30 ΩInput 1A or 5A (Please indicate on the order) 1A or 5A (Please indicate on the order)Working range 50 ...120% 5 ...120%Frequency of input quantity 45 ...55 Hz. (Opt. 55-65Hz) 45 ...65 Hz.
Excessiv inputs (overload)continuos short duration (1s)Voltage inputCurrent Input
120 %
2 fold20 fold
120 %
5 fold20 fold
Accuracy class 0,5 0,5
Ripple (peak-to-peak)100 Ω: <6%750 Ω: <1%
< 1%
Response time100 Ω: <0,4s750 Ω: <0,8s
< 0,15s
Drift vs. temperature (0 ...45ºC)
Drift vs. Aux. suppy
< 1%
---< 200ppm/ºK< 20ppm/V
Aux. suppy 2)
AC
DC
passive------
external aux. suppy50 ...110%50 ...125%
Nominal consumption measuring input
Nominal consumption aux. suppy input3W---
1W3W
1) other values on request. 2.) According to DIN EN 60688 a nominal range of use from 80...120% (for AC) and 85...125% (for DC) is required. 50...120% or 50...125% is valid in consideration of the decre-sead load capability according to the auxiliary supply diagrams.
Application
The transducers are to be applied for the measurement of alternating currents
(Nominal input currents 1 or 5 A).
Mode of operation
The input value is being galvanically insulated (5 kV / 1 min), rectified (ave-
raging) and transformed into a proportional, graven direct current.
The CIR doesn’t require any auxiliary supply. The type CIR/I is active (Output
4...20 mA) and requires some auxiliary supply of 230V AC or 24V DC.
Design
The small design of measuring converts with a width of only 22,5 mm is reali-
zed , as well, by a precise selection of components, as by a precise coordi-
nation of components and circuits, geared to power requirements and
warming. The low power loss allows mounting of any quantity of transducers
side by side, within the operating temperature range, without need to consi-
der of minimum distances.
Transducers for alternating current
• Class 0,5
• For mounting on DIN rail (DIN EN 50022-35)
• only 22,5mm width
• Load resistance up to 1000 Ohm @ 20mA
6/10
TRANSDUCERS FOR ALTERNATING CURRENT
Connection diagrams
Current output
Voltage output
DimensionsOrder exampleProduct Input Output Aux. suppy
CIR 1A 0 ...20 mA ---
CIR 5A 0 ...10 V ---
CIR/I 1A 0 ...10 V 24 V DC
CIR/I 5A 4 ...20 mA 230 V AC
Order information for CIR
Output
Input
Output
Input
Output
Input
Output
Input
Output
Input
Output
Input
Aux. supply 230V AC Aux. supply 24V DC
Aux. supply 230V AC Aux. supply 24V DC
6/11
TRANSDUCERS FOR ALTERNATING VOLTAGE
CUR
Description
The transducers are to be applied for the measurement of alternating voltages
(Nominal input voltages 100 to 690 V). Please indicate the exact voltage
on the order. For higher voltage transformers to be inserted before.
Mode of operation
The input value is being galvanically insulated (5 kV / 1 min), rectified (ave-
raging) and transformed into a proportional, graven direct current. The CUR
doesn’t require any auxiliary supply. The type CUR/I is active (Output 4...20
mA) and requires some auxiliary supply of 230V AC or 24V DC
Design
The small design of measuring converts with a width of only 22,5 mm is reali-
zed , as well, by a precise selection of components, as by a precise coordi-
nation of components and circuits, geared to power requirements and
warming. The low power loss allows mounting of any quantity of transducers
side by side, within the operating temperature range, without need to consi-
der of minimum distances.
Transducers for alternating voltage
• Class 0,5
• For mounting on DIN rail (DIN EN 50022-35)
• only 22,5mm width
• Load resistance up to 1000 Ohm @ 20mA
Technical Data (according to DIN EN 60688)Typ 1) CUR CUR/IOutput short-circuit and open-circuit protected short-circuit and open-circuit protectedCurrent output 0 ...20 mA 4 ...20 mALimit current none or approx. 22,5 mA approx. 22,5 mAOpen-circuit voltage approx. 30V approx. 30VOutput load 0 - 750 Ω 0 - 750 ΩVariation < 50% < 1ppm/ΩVoltage output 0 ...10V 0 ...10VLimiting current none or approx. 22,5 mA < 30 ohmLimiting voltage approx. 18V approx. 18VOutput resistance 500 Ω < 30 ΩInput 100 ... 720V (Please indicate on the order) 100 ... 720V (Please indicate on the order)Working range 50 ...120% 5 ...120%Frequency of input quantity 45 ...55 Hz. (Opt. 55-65Hz) 45 ...65 Hz.
Excessiv inputs (overload)continuos short duration (1s)Voltage inputCurrent Input
120 %
2 fold20 fold
120 %
5 fold20 fold
Accuracy class 0,5 0,5
Ripple (peak-to-peak)100 Ω: <6%750 Ω: <1%
< 1%
Response time100 Ω: <0,4s750 Ω: <0,8s
< 0,15s
Drift vs. temperature (0 ...45ºC)
Drift vs. Aux. suppy
< 1%
---< 200ppm/ºK< 20ppm/V
Aux. suppy 2)
AC
DC
passive------
external aux. suppy50 ...110%50 ...125%
Nominal consumption measuring input
Nominal consumption aux. suppy input3W---
1W3W
1) other values on request. 2.) According to DIN EN 60688 a nominal range of use from 80...120% (for AC) and 85...125% (for DC) is required. 50...120% or 50...125% is valid in consideration of the decre-sead load capability according to the auxiliary supply diagrams.
6/12
TRANSDUCERS FOR ALTERNATING VOLTAGE
Dimensions
Connections diagrams
Current output
Voltage output
Order exampleProduct Input Output Aux. suppy
CUR 500V 0 ...20 mA ---
CUR 500V 0 ...10 V ---
CUR/I 500V 0 ...20 mA 230V AC
CUR/I 500V 0 ...10 V 24V DC
Order information for CUR
Output
Input
Output
Input
Output
Input
Output
Input
Output
Input
Output
Input
Aux. supply 230V AC Aux. supply 24V DC
Aux. supply 230V AC Aux. supply 24V DC
6/13
TRANSDUCERS FOR FREQUENCY
Description
The transducer series CFRNV are to be applied for measuring frequencies in
a range 40 to 70Hz (to be specified). Rated input voltages are from 50 to
720V. The dynamic range goes from 20 to 120%
Mode of operation
The input value is being galvanically insulated (5kV/1min), a frequency
proportional value is calculated and this is converted into a proportional
and load-independent DC current (or DC voltage). Auxiliary supply is re-
quired, standard 24VDC or 230VAC.
Characteristic line
f1 = lower measuring frequency(can’t be used for the determination oferror limit).
f2 = upper measuring frequency (final value of measuring range for deter-mination of the error limit).
CFRNV
Transducers for frecuency
• only 22,5mm width
• Load resistance up to 1000 Ohm @ 20mA
Connections diagrams
Aux. supply 230V ACOutput: 0(4) - 20mA
Aux. supply 230V ACOutput: 0(2) - 10 V
Aux. supply 230V ACOutput: 0(4) - 20mA
Aux. supply 230V ACOutput: 0(2) - 10 V
6/14
TRANSDUCERS FOR FREQUENCY
Dimensions
Technical Data (according to DIN EN 60688)Typ 1) CFRNV
Output short-circuit and open-circuit protected
Current output 0-20 mA
Limiting current none or approx. 22,5 mA
Open-circuit voltage ca. 30 V
Output load 0...750 Ω , 0...1000 Ω
Variation < 1 ppm/Ω
Voltage output 0-10 V or 2-10 V
Limiting current none or approx. 22,5 mA
Limiting voltage approx. 18 V
Output resistance < 30 Ω
Input
Measuring range45...55Hz; 47...53Hz;55...65Hz; 57...63Hz;45...65Hz;
Voltage input 50...720 V
Available nominal ranges 20...120 %
frecuency 40...70 Hz
Excessive inputs continuos / short duration voltage input
120 %2-fold
Transmission
Accuracy class 0,5 0,2
Ripple (peak-to-peak) < 1 % < 0,4 %
Response time < 0,4 s < 0,8 s
Drift vs. temperature (0...45ºC) < 1% < 0,5 %
Auxiliary supply voltage
AC DC
90...110 %85...125 %
Nominal consumption
Measuring input < 1 W
Auxiliary supply input < 3 W
1) other values on request.
Order exampleProduct Measuring range Input Output Aux. suppy
CFRNV 45-55 Hz 100V 4 ...20 mA 230V AC
CFRNV 55-65 Hz 230V 4 ...20 mA 230V AC
CFRNV 45-65 Hz 220V 0 ...20 mA 220V AC
CFRNV 47-53 Hz 100V 0 ...20 mA 24V DC
Order information for CFRNV
6/15
TRANSDUCERS FOR DIRECT CURRENT / VOLTAGE
Technical DataInput Strom DC(0,01 - 15 A)* Protection class housing IP 30
Output All standard signals** Max. consumption 2 W
Max. burden 750 Ω Width 22,5 mm
Auxiliary voltage supply 20 - 250 V AC/DC Lenght 80 mm
Fuse max. 16 A Height 79 mm
Ambient temperature -10 – +65 °C Material of housing PA
Storage temperature -40 – +70 °C Colour Green
Connection wire square size 1,5 qmm Weight 90 - 120 gr.
Protection class terminals IP 10 Class 0,5
* Input current has to be indicated for ordering Transducer is completly galvanic insulated.
** Output signal has to be indicated for ordering
Dimensions DMI / DMU Connections DMI / DMU
Order information for DMI
DMI (Transducers for direct current)
DMU (Transducers for direct voltage)
Technical DataInput Voltage DC (0,01 - 500 V)* Protection class housing IP 30
Output All standard signals** Max. consumption 2 W
Max. burden 1000 Ω Width 22,5 mm
Auxiliary voltage supply 20 - 250 V AC/DC Lenght 80 mm
Fuse max. 16 A Height 79 mm
Ambient temperature -10 – +65 °C Material of housing PA
Storage temperature -40 – +70 °C Colour Green
Connection wire square size 1,5 qmm Weight 90 - 120 gr.
Protection class terminals IP 10 Class 0,5
* Input current has to be indicated for ordering Transducer is completly galvanic insulated.
** Output signal has to be indicated for ordering
Order exampleProduct
InputMeasuring range from .. to ...A DC
Output
DMI 0 - 5 A DC 4 ...20 mA
DMI 0 - 10 A DC 0 ...20 mA
DMI 0 - 6 A DC 0 ...10 V
Order information for DMU
Order exampleProduct
InputMeasuring range from .. to ...V DC
Output
DMU 0 - 150 V DC 4 ...20 mA
DMU 0 - 100 mV DC 0 ...20 mA
DMU 0 - 20 V DC 0 ...10 V
6/16
TRANSDUCERS FÜR TEMPERATUR / GRENZWERTRELAIS
Dimensions DTV / GWS Connections DTV / GWS
DTV (Transducers for temperature)
Technical DataInput PT100/1000/Thermocouple*)* Protection class housing IP 30
Output All standard signals** Max. consumption 2 W
Max. burden 1000 Ω Width 22,5 mm
Auxiliary voltage supply 20 - 250 V AC/DC Lenght 109 mm
Fuse max. 16 A Height 108 mm
Ambient temperature -10 – +65 °C Material of housing PA
Storage temperature -40 – +70 °C Colour Green
Connection wire square size 1,5 qmm Weight 110 gr.
Protection class terminals IP 10 Class 0,1
* Input current has to be indicated for ordering Transducer is completly galvanic insulated.
** Output signal has to be indicated for ordering
GWS (Limit relay)
Technical DataInput Current/Voltage AC/DC* Protection class housing IP 30
Output 1 change over switch** Max. consumption 2 W
Max. burden 250 V 5 A AC Width 22,5 mm
Auxiliary voltage supply 20 - 250 V AC/DC Lenght 110 mm
Fuse max. 16 A Height 100 mm
Ambient temperature -10 – +65 °C Material of housing PA
Storage temperature -40 – +70 °C Colour Green
Connection wire square size 1,5 qmm Weight k.A-
Protection class terminals IP 10 Class 0,1
* Input current/voltage has to be indicated for ordering Transducer is completly galvanic insulated.
** 2 insulated change over switches on request
Order information for DTV
Order example
Product InputInputMeasuring rangefrom .. to...A DC
Wire Output
DTV PT100 0 - 100 ºC 3+4 - wire 4 ...20 mA
DTV PT1000 -30 ... +30 ºC 3 - wire 0 ...10 V
DTV Thermocouple 0 - 200 ºC - 0 ...20 mA
Order information for GWS
Order example
ProductInputCurrent/voltageAC/DC
InputMeasuring rangefrom .. to ...V DC
Output* Onrequest: with 2 insul-taed change over switches
GWS alternating current 0 - 1 A AC 1 change
GWS direct voltage 0 - 100 mV DC 1 change
GWS direct current 4 - 20 mA2 insulated changeover switches
6/17
LIMIT RELAY
Description
The electronical limit value relay type GWR is applied to control direct current
or alternating current as well as direct voltage or alternating voltage. The AC
variables of any curve shape are measured as r.m.s values.
Conformity
This equipment conforms to the requirements of the Directive from the Council
of the European Community on the harmonisation of the member states re-
garding electromagnetic compatibility, EMC Directive 2004/108/EC, as
well as Low Voltage Directive 2006/95/EC.
Application
The limiting values are adjustable in steps of 1 % by means of coding swit-
ches. The delay in response as well as closed-circuit and open-circuit current
principles can be selected. The instantaneous switching condition of the out-
put relay is indicated by means of light-emitting diodes. The limit value relays
are installed in a housing of 22,5 mm of breadth and can be mounted on
DIN-rail. They are extremely solid and do not dispose of any mechanically
movable parts except the output relay. Thus they are very suitable for hard
operating conditions.
Limit relay
• Switching accuracy +/- 1%
• Type GMA with digital display and programing on request)
• For mounting on DIN rail (DIN EN 50 022 - 35)
Dimensions
Connections
GWR
6/18
LIMIT RELAY
Technical Data (according to DIN EN 60688)Input
Input quantity
direct current or direct voltage, alternating current or alter-nating volta-ge; the AC variables of any curve shape (up tocrest factor 4) are measured as root mean square in therange of DC + AC 40 to 1000 Hz
Setting of the limitvalue
0-99% in steps of 1%
Relay point 1 change-over contact
Functional displayred LED lights up in case of relay drop-outgreen LED lights up in case of relay pick up
Testing voltage4 kV between measurement input and relay as well asaux.voltage
Switching operation
Switching accuracy +/- 1 % of the final value of the measurement range
Hysteresis approx. 4 % of the limit value
Delay in response adjustable between 0,1 and 10 sec.
Switching conditions closed-circuit or open-circuit current principle, optional
Temperature range -15 to +20 up to +30 up to +55 °C
Temperature effect < 0,1 % at 10 K
Overload capacibilityvoltage input: fivefold (750 V max.)current input: twofold, permanent, 20-fold 1 sec. (50 Amax.)
Switching capacibility max. 8 A, 250 V, 2000 VA
Auxiliary voltage 230 V AC ± 15 %, 45-65 Hz, 2,5 VA
Optional110 V AC ± 15 %, 45-65 Hz, 3 VA24 V DC, -15 % up to +25 %, 2,5 W, (EMC DIN EN 61326 class A)
Wide range aux. sup-ply
6-30 V AC + DC or 36-265 V AC + DC, 2 VA, (EMC DIN EN 61326 class A)
Measuring range
Alternating/direct cur-rent AC+DC effective
Adjustable Internal resistantfrom to
10 A 0,1 A 9,9 A 0,006 Ohm
5 A 0,05 A 4,95 A (5A =100 %) 0,012 Ohm
1 A 0,01 A 0,99 A 0,06 Ohm
100 mA 1 mA 99 mA 0,6 Ohm
10 mA 0,1 mA 9,9 mA 6 Ohm
20 mA (just direct-current DC) 0,2 mA 19,8 mA (20 mA=100 %) 3 Ohm
4 - 20 mA (just direct-current DC) 4 mA 19,84 mA (20 mA=100 %) 3 Ohm
Alternating/direct vol-tage AC+DC effective
Adjustable Internal resistantfrom to
500 V 5 V 495 V 1 MOhm
100 V 1 V 99 V 1 MOhm
10 V 0,1 V 9,9 V 100 kOhm
1 V 0,01 V 0,99 V 10 kOhm100 mV (just direct-voltageDC)
1 mV 99 mV 1 kOhm
4 - 20 mA (just direct-voltageDC)
0,6 mV 59,4 mV (60 mV=100 %) 1 kOhm
Vorschriften
EMC DIN EN 61326
Mechanical strength DIN EN 61010 Part 1
Electrical security
DIN EN 61010 part 1housing all insulated, protection class II, at a working vol-tage up to 300V (network to neutral conductor) degree ofpollution 2, overvoltage category CAT III, at a working vol-tage up to 600V (network to neutral conductor) degree of pollution 2, overvoltage category CAT II
Order information for GWR
Order example
ProductInputMeasuring range from .. to ...A DC
Aux. suppy
GWR 0 - 100mV 230 V AC
GWR 4 - 20 mA DC 230 V AC
6/19
UNIVERSAL ISOLATING AMPLIFIER
Application
The universal isolating amplifier DTVU20 is applied for transforming standard
signals. It can be used in complex measuring and control circuits, process
data acquisition systems, data-loggers and multiplex. In remote control sy-
stems detectors and sensors, which are connected on central points by long
leads, can be isolated.
Selection of input-ranges is made by the frontside-switch at the DTVU20. The
different outputs are selected by connecting to the relevant clamps. Input, au-
xiliary and output are galvanic separated (3-way-separation). Isolation-vol-
tage is 2kV. The DTVU20 can work with input of 0-10 V, 0-20 mA or 4-20
mA. The output can be selected of 0-10 VDC, 2-10 VDC, 0-20 mA or 4-20
mA.
Technical DataAuxiliary supply 24-230 V AC/DC
Consumption 2,8 VA
Ambient temperature -10 to +65 °C
Storage temperature - 40 to +70º C
Protection class housing IP30
Housing Polyamid, for mounting on DIN rail(DIN EN 5022-35
Weight approx.105 g
RegulationsEN 60204-1/ VDE 0113VDE 0110/ IEC 664EMC according EN 50081-1 and 50082-2
Input resistence V=20 kΩ / V, I:50 Ω
Output 4-20 mA, 0-20 mA, 0-10 V, (burden max. 1000 Ohm)
Accuracy 0,1º%
Position of switch Input Output
0-0 0-20mA/0-10V 0-20mA/0-10V0-0 4-20mA/2-10V 4-20mA/2-10V 4-0 4-20mA/2-10V 0-20mA/2-10V 0-4 0-20mA/0-10V 4-20mA/0-10V
Output signal ± 6%Offset adjustment
Dimensions
Connections
Universal isolating amplifier
• For standard signals – with wide range power supply
• For mounting on DIN rail (DIN EN 50 022 - 35
DTUV20
Order information for DTVU20
Order exampleProduct
Position ofswitch
Input Output
DTVU20 0 - 0 0 - 20 mA / 0 - 10V 0 - 20mA / 0 - 10V
DTVU20 0 - 0 4 - 20 mA / 2 - 10V 4 - 20 mA / 2 - 10V
DTVU20 4 - 0 4 - 20 mA / 2 - 10V 0 - 20 mA / 2 - 10V
DTVU20 0 - 4 0 - 20 mA / 0 - 10V 4 - 20 mA / 0 - 10V
6/20