TraceTek Water Sensing System External Audible Alarm 95 dB alarm triggered by relay closure;...

4
Scope of this Guide This guide will help you select TraceTek products for water detection in commercial buildings. Detailed product information in this guide complements the TraceTek Application Guide for Commercial Building Protection (H53147). Additional TraceTek products are available for other liquids—fuels and oils, organic sol- vents—and for other types of applications. See the TraceTek Selection Guide for Industrial and Environmental Applications (H55869) for further detail. Modular Design Approach TraceTek leak detection is a versatile modular system, with interchangeable components that can be configured in many different ways. Standard lengths of TraceTek cable plug together with no special tools, making it easy to modify or add to the system in the future. The range of TraceTek alarm modules and modular components allows you to tailor the monitoring approach and layout to the application. Contents of this Guide The first two pages of this guide show typical configurations for TraceTek leak detection systems. Many other configura- tions are possible as well. The last two pages present product listings—detailed technical and ordering information for the products available. Other Raychem literature can be obtained from our Fax-on-Demand service at (800) 329-4494. A voice prompt leads you through the process. Elements of a TraceTek System A Basic System Every TraceTek leak detection system has these basic parts: An alarm module Leader and/or jumper cables (nonsensing cables between the module and the areas monitored) Sensing cable End termination Accessories such as hold-down clips and tags. A Locating System A TraceTek locating system often includes these additional circuit components: Branching connectors Weighted lengths These components make it possible for a locating system to monitor one or more large areas or lengths. A locating system has one more essential element: A graphic map (see an example on the next page) Tags TT-TAG Hold-Down Clips TT-HDC-1/4 Water Sensing Cable TT1000-x-PC Modular Leader Cable TT-MLC-PC TraceTek Alarm Module Modular End Termination TT-MET-PC Modular Jumper Cable TT-MJC-x-PC between module and area monitored Modular Leader Cable TT-MLC-PC Water Sensing Cable TT1000-x-PC Alarm and Locating Module TTDM Water Sensing Cable TT1000-x-PC daisy-chained together to provide as much coverage as needed Modular Branching Connector TT-MBC-PC Tags TT-TAG Hold-Down Clips TT-HDC-1/4 Modular End Termination TT-MET-PC (required at end of every branch) LEAK DETECTION powered by ® Water Sensing System Product Selection Guide TTSIM-1A

Transcript of TraceTek Water Sensing System External Audible Alarm 95 dB alarm triggered by relay closure;...

Page 1: TraceTek Water Sensing System External Audible Alarm 95 dB alarm triggered by relay closure; requires 24 V supply. Jumper Cables Modular Leader Cable TT-MLC-PC Modular Leader Cable

Scope of this GuideThis guide will help you select TraceTekproducts for water detection in commercialbuildings. Detailed product information inthis guide complements the TraceTekApplication Guide for Commercial BuildingProtection (H53147).Additional TraceTek products are availablefor other liquids—fuels and oils, organic sol-vents—and for other types of applications.See the TraceTek Selection Guide forIndustrial and Environmental Applications(H55869) for further detail.

Modular Design ApproachTraceTek leak detection is a versatilemodular system, with interchangeablecomponents that can be configured inmany different ways. Standard lengths ofTraceTek cable plug together with nospecial tools, making it easy to modify oradd to the system in the future. Therange of TraceTek alarm modules andmodular components allows you to tailorthe monitoring approach and layout tothe application.

Contents of this GuideThe first two pages of this guide showtypical configurations for TraceTek leakdetection systems. Many other configura-tions are possible as well. The last twopages present product listings—detailedtechnical and ordering information for theproducts available.Other Raychem literature can beobtained from our Fax-on-Demand serviceat (800) 329-4494. A voice prompt leadsyou through the process.

TraceTek Leak DetectionProduct Selection Guide for Water Sensing Systems

Elements of a TraceTek System

A Basic SystemEvery TraceTek leak detection systemhas these basic parts:• An alarm module• Leader and/or jumper cables

(nonsensing cables between the module and the areas monitored)

• Sensing cable• End termination• Accessories such as hold-down clips

and tags.

A Locating SystemA TraceTek locating system oftenincludes these additional circuit components:• Branching connectors • Weighted lengthsThese components make it possible for alocating system to monitor one or morelarge areas or lengths.A locating system has one more essentialelement:• A graphic map (see an example on the

next page)

TagsTT-TAG

Hold-Down ClipsTT-HDC-1/4

Water Sensing CableTT1000-x-PC

Modular Leader CableTT-MLC-PC

TraceTekAlarm Module

TTC-1 (or TTA-1)

Modular End TerminationTT-MET-PC

Modular Jumper CableTT-MJC-x-PCbetween module and area monitored

Modular Leader CableTT-MLC-PC

Water Sensing CableTT1000-x-PC

Alarm and Locating ModuleTTDM

Water Sensing CableTT1000-x-PCdaisy-chained togetherto provide as much coverage as needed

Modular BranchingConnectorTT-MBC-PC

TagsTT-TAG

Hold-Down ClipsTT-HDC-1/4

Modular End TerminationTT-MET-PC

(required at end of every branch)

LEAK DETECTION

powered by

® Water Sensing SystemProduct Selection Guide

TTSIM-1A

Page 2: TraceTek Water Sensing System External Audible Alarm 95 dB alarm triggered by relay closure; requires 24 V supply. Jumper Cables Modular Leader Cable TT-MLC-PC Modular Leader Cable

A TraceTek locating system can monitorone or more large areas. If water contactsthe sensing cable, the alarm and locatingmodule indicates the location with a digitaldisplay. A system map created after instal-lation provides reference points (e.g., in the illustration) to facilitate a quick,effective response.

shows where the sensing circuitjumps to a new room and a weightedlength is used. The weighted length simulates 15 ft of sensing cable so thesystem map will show a clear divisionbetween the separate areas.

shows a branch in the sensing circuit. ATraceTek branching connector is wired sothe connected branches appear in series,middle leg first. The branching connectoralso adds a simulated cable length of 15 fton each branch to make a clear divisionbetween areas. Although not shown, a system may have branches within branches.The number of branches is limited only bythe length of the sensing circuit.

BA

25

Modular jumper cables

Modularbranchingconnector

Modularendtermination

Modular end termination

Weighted LengthTT-WL-4.5M/15FT-PC

Bulk Jumper CableTT-JC

Jumper Splice KitTT-JSK-HS18

Modularleadercable

Watersensingcable

75

90

130

245

395

345

270

295

320

205

230

50

25

180

155115

1

B

Drawingnot to scale

Alarm and locating moduleTTDM

A

370

Wide Area Coverage: TraceTek Locating System

Note: A TraceTek alarm system can include several lengths of sensing cable. However, for large and/or separate areas, consider a TraceTek locating system.

Modularleadercable

Modular jumper cable(s)

Modular endtermination

TTC-1alarmmodule

Hold-down clip

Sensing cables

Tag

TTA-1alarmmodule

Modularleadercable

Alarm relays from the TTC-1 module may be used to control equipment (e.g., close a valve), to annunciate an alarm, and/or to signal an alarm to a host system.

Sensing cable can be positioned to provide complete leakdetection coverage of pumps, boilers, and other equipment.

The TTA-1 module can be installed in an occupied area to make use of the module’s audible alarm. The use of jumper cable allows the alarm module to be positioned in a location remote from the sensing cable it monitors.

Modular endtermination

Hold-down clip

Sensing cable

Tag

Small Area Coverage: Basic TraceTek Alarm System

TTSIM-1Aalarm module

Alarm relays from the TTSIM-1A module may be used to control equipment (e.g., close a valve), to annunciate an alarm, and/or to signal an alarm to a host system.

TTSIM-1Aalarm module

TTSIM-1A module can be installed in an occupied area to make use of the module‘s audible alarm. The use of jumper cable allows the alarm module to be positioned in a location remote from the sensing cable it monitors,

Page 3: TraceTek Water Sensing System External Audible Alarm 95 dB alarm triggered by relay closure; requires 24 V supply. Jumper Cables Modular Leader Cable TT-MLC-PC Modular Leader Cable

Product Catalog No. Selection DescriptionAlarm Modules

TTDM Alarm and TTDM-1 115 Vac Supply Alarm and locating module; indicates liquid location withLocating Module TTDM-2 230 Vac Supply digital display. Monitors up to 5000 ft (1500 m) of sensing

TTDM-24 24 V Supply cable. Metal enclosure, NEMA 12. Data logging.Outputs: Audible alarm, 4 LEDs, backlit LCD

3 DPDT Form C relays (leak, service, and fault)4-20 mA analog output

For details on approvals Serial port configurable for RS-232 or RS-485see data sheets.

TTA Alarm ModuleTTA-1 115 or 240 Vac Supply Nonlocating single-channel alarm module.

Monitors up to 100 ft (30 m) of sensing cable.Metal enclosure, NEMA 1.Outputs: Audible alarm, 3 LEDs

4PDT Form C relay (leak or fault)

TTC Alarm ModuleTTC-1 24 V Supply Nonlocating single-channel alarm module. Monitors up to

100 ft (30 m) of sensing cable. Plastic enclosure, NEMA 1.Outputs: 3 LEDs

DPDT Form C relay (leak)SPDT Form C relay (fault)

TT-DRC Din Rail Clip Mounting clip for attachment to DIN rail in electrical panel.

External or Remote Alarm

TTE-XAL External Audible Alarm 95 dB alarm triggered by relay closure; requires 24 V supply.

Jumper CablesModular Leader Cable

TT-MLC-PC Modular Leader Cable Cable with one end prepared for connection to terminals(with plastic connector) in module (or for splicing to bulk jumper cable), and with Length: 12 ft (3.5 m) socket-type plastic connector at other end.

Modular Jumper CableTT-MJC-x*-PC Modular Jumper Cable Jumper cable with pin-type plastic connector at one end;

TT-MJC-1M/3FT-PC 1 m 3 ft socket-type plastic connector at other end.TT-MJC-3M/10FT-PC 3 m 10 ftTT-MJC-7.5M/25FT-PC 7.5 m 25 ftTT-MJC-15M/50FT-PC 15 m 50 ft *Cable lengthTT-MJC-30M/100FT-PC 30 m 100 ft

Bulk Jumper CableTT-JC-76M/250FT Bulk Jumper Cable Bulk jumper cable with four color-coded 18 AWG

(250-ft reel) conductors. Connectors not included.

Jumper Splice KitTT-JSK-HS18 Jumper Splice Kit Splice kit for jumper cable; contains parts for 5 splices.

Includes 20 crimps and 5 heat-shrinkable tubes.For use with 18 AWG jumper wire.

Sensing CablesWater Sensing Cable

TT1000-x*-PC Modular Sensing Cable TT1000 water sensing cable with pin-type plastic connector TT1000-1M/3FT-PC 1 m 3 ft at one end, socket-type plastic connector at other end.TT1000-3M/10FT-PC 3 m 10 ftTT1000-7.5M/25FT-PC 7.5 m 25 ftTT1000-15M/50FT-PC 15 m 50 ft *Cable length

®

R

®

R

R RC

F M

APPROVED

PRODUCT SERVICE geprüfteSicherheit

TraceTek Products for Water Detection in Commercial Buildings

Product Catalog No. Selection DescriptionAlarm Modules

TTDM Alarm and TTDM-1 115 Vac Supply Alarm and locating module; indicates liquid location withLocating Module TTDM-2 230 Vac Supply digital display. Monitors up to 5000 ft (1500 m) of sensing

TTDM-24 24 V Supply cable. Metal enclosure, NEMA 12. Data logging.Outputs: Audible alarm, 4 LEDs, backlit LCD

3 DPDT Form C relays (leak, service, and fault)4-20 mA analog output

For details on approvals Serial port configurable for RS-232 or RS-485see data sheets.

TTA Alarm ModuleTTA-1 115 or 240 Vac Supply Nonlocating single-channel alarm module.

Monitors up to 100 ft (30 m) of sensing cable.Metal enclosure, NEMA 1.Outputs: Audible alarm, 3 LEDs

4PDT Form C relay (leak or fault)

TTC Alarm ModuleTTC-1 24 V Supply Nonlocating single-channel alarm module. Monitors up to

100 ft (30 m) of sensing cable. Plastic enclosure, NEMA 1.Outputs: 3 LEDs

DPDT Form C relay (leak)SPDT Form C relay (fault)

TT-DRC Din Rail Clip Mounting clip for attachment to DIN rail in electrical panel.

External or Remote Alarm

TTE-XAL External Audible Alarm 95 dB alarm triggered by relay closure; requires 24 V supply.

Jumper CablesModular Leader Cable

TT-MLC-PC Modular Leader Cable Cable with one end prepared for connection to terminals(with plastic connector) in module (or for splicing to bulk jumper cable), and with Length: 12 ft (3.5 m) socket-type plastic connector at other end.

Modular Jumper CableTT-MJC-x*-PC Modular Jumper Cable Jumper cable with pin-type plastic connector at one end;

TT-MJC-1M/3FT-PC 1 m 3 ft socket-type plastic connector at other end.TT-MJC-3M/10FT-PC 3 m 10 ftTT-MJC-7.5M/25FT-PC 7.5 m 25 ftTT-MJC-15M/50FT-PC 15 m 50 ft *Cable lengthTT-MJC-30M/100FT-PC 30 m 100 ft

Bulk Jumper CableTT-JC-76M/250FT Bulk Jumper Cable Bulk jumper cable with four color-coded 18 AWG

(250-ft reel) conductors. Connectors not included.

Jumper Splice KitTT-JSK-HS18 Jumper Splice Kit Splice kit for jumper cable; contains parts for 5 splices.

Includes 20 crimps and 5 heat-shrinkable tubes.For use with 18 AWG jumper wire.

Sensing CablesWater Sensing Cable

TT1000-x*-PC Modular Sensing Cable TT1000 water sensing cable with pin-type plastic connector TT1000-1M/3FT-PC 1 m 3 ft at one end, socket-type plastic connector at other end.TT1000-3M/10FT-PC 3 m 10 ftTT1000-7.5M/25FT-PC 7.5 m 25 ftTT1000-15M/50FT-PC 15 m 50 ft *Cable length

®

R

®

R

R RC

F M

APPROVED

PRODUCT SERVICE geprüfteSicherheit

TraceTek Products for Water Detection in Commercial Buildings

Sensor-Interface-Module

Sensor-Interface-Module

TTSIM-1

TTSIM-1A

Sensor-Interface-Module for circuit-entering to the TTDM-128 Locating Module or direct to the central computer with supervisor software.For monitoring of max. 1500m sensing cable

Sensor-Interface-Module for circuit-entering to the TTDM-128 Locating Module or direct to the central computer with supervisor software.For monitoring of max. 150m sensing cable

Page 4: TraceTek Water Sensing System External Audible Alarm 95 dB alarm triggered by relay closure; requires 24 V supply. Jumper Cables Modular Leader Cable TT-MLC-PC Modular Leader Cable

Product Catalog No. Selection DescriptionCircuit Components

End TerminationTT-MET-PC Modular End Termination Terminates sensing circuit; has pin-type plastic connector.

(with plastic connector) Required at end of sensing circuit and all branches.

Branching ConnectorTT-MBC-PC Modular Branching Allows a “T” or branch in the sensing circuit. Has one pin-

Connector (with type connector to connect to cable from alarm module, two plastic connectors) socket-type connectors to connect two branches. Wires the

branches in series and adds a simulated length of 15 fton each branch to make clear division between areas.

Weighted LengthTT-WL-4.5M/15FT-PC Weighted Length Simulates 15 ft (4.5 m) of sensing cable. Makes a

(with plastic connectors) clear division between separate areas in a locating system.

AccessoriesHold-down Clips

TT-HDC-1/4/200-N/A No adhesive (200/bag) Hold-down clips attach cable to flat surfaces.TT-HDC-1/4 Adhesive-backed (50/bag) Pressure-sensitive adhesive bonds to clean, flat surfaces.

Use a clip for each 4 ft (1.3 m) of sensing cable.

TagsTT-TAG TraceTek Tags Tags to identify TraceTek sensing cable and record

mapped distance. Tag attaches to sensing cable by closing on itself (like a cable tie). Package contains 50 high-visibility yellow tags and a permanent marker.Use a tag on each length of cable and at mapping points.

ToolsPortable Test Box

TT-PTB-1000 Portable Test Box Battery-operated device to test TraceTek sensing cables.Allows testing of anything from an individual length up to2000 ft (or 1000 m) of sensing cable. Useful for installationand maintenance.

Crimp ToolAD-1522-1 Crimp Tool Tool sized to properly crimp connectors in TT-JSK-HS18

jumper splice kit

Pre-Packaged KitsComplete Kits

TTC-KIT-1 25 ft of TT1000 Cable Each kit contains a TTC-1 alarm module, a modular TTC-KIT-2 50 ft of TT1000 Cable leader cable, a modular sensing cable of length indicated,

a modular end termination, 15 hold-down clips, and 5 tags.

©19

97 R

aych

em C

orpo

ratio

n P

rinte

d in

US

A

H53

874

P

/N 1

7126

9

3/97

Tr

aceT

ek is

a tr

adem

ark

of R

aych

em C

orpo

ratio

n.

All information, including illustrations, is believed to be reliable. Users, however, should inde-pendently evaluate the suitability of each product for their application. Raychem makes no war-ranties as to the accuracy or completeness of the information, and disclaims any liabilityregarding its use. Raychem’s only obligations are those in the Raychem Standard Terms andConditions of Sale for this product, and in no case will Raychem be liable for any incidental,indirect, or consequential damages arising from the sale, resale, use, or misuse of the product.Specifications are subject to change without notice. In addition, Raychem reserves the right tomake changes—without notification to Buyer—to materials or processing that do not affectcompliance with any applicable specification.

Raychem CorporationCommercial & IndustrialInfrastructure Division300 Constitution DriveMenlo Park, CA 94025-1164Tel (800) 545-6258Fax (800) 611-2323 Fax-on-Demand (800) [email protected]

The TraceTek Products Group is part of the Raychem Chemelex Division.Chemelex Division is ISO 9001 certified.

9 0 01ISO

TraceTek Products for Water Detection in Commercial Buildings (continued)

Vertriebsbüro West

Veilchenweg 13A-4210 GallneukirchenT. +43 7235 66910F: +43 7235 [email protected]

VertriebsgmbH

Industriestrasse B-4A-2345 Brunn/GebirgeT. +43 2236 90300F: +43 2236 90300/[email protected]

2 of 2 (800) 545-6258www.tycothermal.com H58260 5/08

©20

08 T

yco

Ther

mal

Con

trols

LLC

H

5826

0 5

/08

TT1100-OHP

Tyco Thermal Controls307 Constitution DriveMenlo Park, CA 94025-1164USATel (800) 545-6258Fax (650) [email protected]

Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes—without notification to Buyer—to processing or materials that do not affect compliance with any applicable specification.

Tyco and TraceTek are trademarks of Tyco Thermal Controls LLC or its affiliates.

Braided fiber jacket(8.2 mm diameter)

Yellow tracer

Sensor wires (2)

Signal wires (2)

0.92 in(23 mm)

Product Characteristics

Finished cable diameter 8.2 mm nominal

Cable diameter with connectors 23 mm nominal

Signal wires 2 x 26 AWG with fluoropolymer insulation

Sensor wires 2 x 30 AWG with conductive fluoropolymer jacket

Carrier rod 20 AWG core wire flame retarded polymer

Cable weight 5.86 kg / 100 m nominal

Breaking strength > 100 kg

Cut-through force > 50 kg (using 0.05” radius blade)

Maximum continuous operatingtemperature

80˚C

Resistance to Humidity <2 µA leakage per 100 feet @ 90% RH / 20C

Approvals

9 0 01ISO The TraceTek products group is a part of Tyco Thermal Controls, Tyco International. Tyco Thermal Controls is ISO 9001 certified.

TraceTek sensing cables are approved only when used with an agency approved TraceTek alarm module.