Touch Display Unit TDU

4
1 Document no. 4189390003E Product sheet Touch Display Unit TDU General description TDU 107 is a preprogrammed touch screen solution for connection to DEIF’s AGC-4 controllers via an Ethernet port. * The displays provide user-friendly touch screen control, visualisation and graphical overviews with a quality display that is easily readable even at sharp angles. Combines both a HMI display and 6 AOP (Additional Operator Panel) on one device. Easy to use icon driven HMI providing fast access and configurable instrument pages. Provides Tier 4 final support. The TDU 107 is available in two versions: • TDU 107 Core • TDU 107 Extended * AGC-4 requires the Ethernet option N for connection. Common features Easy setup Simply connect an Ethernet cable to the AGC-4 controller. Supervision Instant overview of all connected controllers in your application, including live status and alarms. Tier 4 final support Full support for Tier 4 icons including an Exhaust After-treatment dashboard. Exhaust After-Treatment Dashboard DEIF 0 10 20 30 40 50 60 70 80 90 100 24 % 66 % 255 h Feature comparison Core Extended Tier 4 final support Resistive touch screen Capacitive touch screen VNC support (Remote access) Temperature range 0 °C to + 50 °C Temperature range -20 °C to + 60 °C 2 ports Ethernet switch DEIF Standard plant MB17 TB17 GB1 GB2 kW kW kW kW kW kW 0 350 0 0 1 6 2 1 24 % 66 % 255 h AOP 1 / 6 ACTIVE FIXED POWER DEIF 24 % Generator voltage L1-L2 Generator f L1 Fuel level Total Running hours 1* h % Hz V 400 50.00 66 93 CAN ID: 2 Priority: 2 66 % 255 h

Transcript of Touch Display Unit TDU

Page 1: Touch Display Unit TDU

1Document no. 4189390003E

Product sheet

Touch Display Unit TDU

General descriptionTDU 107 is a preprogrammed touch screen solution for connection to DEIF’s AGC-4 controllers via an Ethernet port. *

The displays provide user-friendly touch screen control, visualisation and graphical overviews with a quality display that is easily readable even at sharp angles.

Combines both a HMI display and 6 AOP (Additional Operator Panel) on one device. Easy to use icon driven HMI providing fast access and configurable instrument pages.

Provides Tier 4 final support.

The TDU 107 is available in two versions:

• TDU 107 Core• TDU 107 Extended

* AGC-4 requires the Ethernet option N for connection.

Common featuresEasy setupSimply connect an Ethernet cable to the AGC-4 controller.

SupervisionInstant overview of all connected controllers in your application, including live status and alarms.

Tier 4 final supportFull support for Tier 4 icons including an Exhaust After-treatment dashboard.

Exhaust After-Treatment Dashboard

DEIF

010

2030

40 50 6070

8090100

24 %66 % 255 hFeature comparison Core Extended

Tier 4 final support ● ●

Resistive touch screen ●

Capacitive touch screen ●

VNC support (Remote access) ●

Temperature range 0 °C to + 50 °C ●

Temperature range -20 °C to + 60 °C ●

2 ports Ethernet switch ●

DEIFStandard plant

MB17

TB17

GB1 GB2

kWkW

kWkW

kWkW

0

350

0

0 1

6

21

24 %66 % 255 h

AOP

1 / 6

ACTIVEFIXED POWER

DEIF 24 %

Generator voltage L1-L2

Generator f L1

Fuel level

Total Running hours

1* h

%

Hz

V400

50.00

66

93 CAN ID: 2Priority: 2

66 % 255 h

Page 2: Touch Display Unit TDU

2 Document no. 4189390003E

TDU 107 Technical specifications

TDU 107 Core

• Type: TFT• Resolution: 800 x 480 pixel (WVGA)• Active display area: 7” diagonal• Aspect ratio H/V: 16:9• Viewing angle (H/V): 140/120• Colours: 16 bit (64K)• Brightness: 200 Cd/m2 typ.• Backlight: LED• Screen saver: Yes

• Interfaces

• Touch screen: Resistive• Ethernet: 1 x 10/100 Mbit• USB: 1 x USB 2.0 (hosts) - max. 500 mA

• Power supply

• Power supply voltage: 24 V DC (10 to 32 V DC)• Current consumption: 0.3 A at 24 V DC (max.)• Fuse: No• Weight: Approx. 0.6 kg (un-boxed)• Battery: Supercapacitor

• Environment

• Operating temperature: 0 °C to +50 °C (vertical install)• Storage temperature: -20 °C to +70 °C• Operating/storage humidity: 5-85% RH, non condensing• Vibration: 2 to 13.2 Hz ±1 mm, 13.2 to 100 Hz 0.7 g• Shock: 50 g 11 ms• Protection class: IP 66 Type 2 and 4X (front), IP20 (rear)

• Approvals

• CE• UL• cULus Listed to UL508 Industrial control equipment• cULus Class I, Division 2

TDU 107 Extended

• Type: TFT• Resolution: 800 x 480 pixel • Active display area: 7” diagonal• Aspect ratio H/V: 16:9• Viewing angle (H/V): 170/170• Colours: 24 bit (16 million)• Brightness: 500 Cd/m2 typ.• Backlight: LED• Screen saver: Yes

• Interfaces

• Touch screen: Projected capacitive, multi-touch• Ethernet: 2 x 10/100 Mbit, 1 x 10/100/1000 Mbit• USB: 2 x USB 2.0 (hosts) - max. 500 mA• VNC server - Remote access

• Power supply

• Power supply voltage: 24 V DC (10 to 32 V DC)• Current consumption: 0.7 A at 24 V DC (max.)• Fuse: Automatic, self-resettable• Weight: Approx. 1.3 kg (un-boxed)• Battery: Rechargeable Lithium battery

• Environment

• Operating temperature: -20 °C to +60 °C (vertical install)• Storage temperature: -30 °C to +70 °C• Operating/storage humidity: 95% RH Condensation• Vibration: 2 to 13.2 Hz ±1 mm, 13.2 to 100 Hz 0.7 g• Shock: 50 g 11 ms• Protection class: IP 66 (front), IP20 (rear)

• Approvals

• CE• UL UL508 Listed (Pending), Haz. Loc. Class I, Division 2,

Groups A, B, C and D (Pending)• cULus Listed to UL508 Industrial control equipment• Lloyds Register - LR Type Approval Certificate• DNV GL

Page 3: Touch Display Unit TDU

3Document no. 4189390003E

TDU 107Common features

Alternator curveVisual display for the safe operation limits for the alternator. * GENSET actual working point is represented by the green dot.

DEIF

4

3 21

5 6 6 5

4

3

2

1

100

P(%)

0100 Q< (%) Q> (%)0 100

24 %66 % 255 h

* AGC-4 requires option C2 to see operation limits.

Fast instrument selectionEasily configure your live data information by selecting the required instrument readout, directly on the screen.

Additional operator panels (AOP)Configure up to 6 additional operator panels, providing customisable buttons and LEDs for controller functions.

Light or dark themesSwitch the display between light or dark themes.

Alarm or event logsEasily filter only alarm or log events, or merge them back into one single list. Filter events for a given date start and end.

Quick Input / output overviewQuick overview for the status of all inputs and outputs.

INSTRUMENT SELECTION

DEIFBattery Voltage

Generator power

Engine Speed

1* RPM

kW

V26.6

360

1500

None UL1-L2 UL2-L3 UL3-L1

UL1-N UL2-N UL3-N f L1

f L2 f L3 U angle L1-L2 U angle L2-L3

U angle L3-L1 I L1 I L2 I L3

+

24 %96 % 255 h

Available power PMS

kW120

DEIF

AUTO

LED 2

LED 3

LED 4

Low fuel

LED 6

LED 7

LED 8

Warning

LED 10

LED 11

LED 12

LED 13

LED 14

LED 15

LED 16

AUTO MODE

BTN 2

TEST MODE

BTN 4

BTN 5

BTN 6

BTN 7

BTN 8

24 %66 % 255 h

1 / 9

Description

DEIF

GB OFF

14/05/2019 - 09:27:26

Timestamp

Clear parameter edit

3490 Emergency STOP

2320 Busbar blocked

Primary controller

Power management

2180 GB Pos fail

14/05/2019 - 09:27:26

14/05/2019 - 08:54:28

14/05/2019 - 08:54:22

14/05/2019 - 08:53:12

10/05/2019 - 12:08:59

10/05/2019 - 12:08:53

10/05/2019 - 12:08:35

10/04/2019 - 07:36:48

24 %66 % 255 h

Digital Inputs

DEIF

Digital input 43 43

24 %66 % 255 h

Outputs

44

45

46

47

48

49

50

51

Digital input 44

Digital input 46

Digital input 47

Digital input 49

Digital input 50

Digital input 51

Auto start/stop

External P

Reactive (Q) line ON LS Q SW

05

08

11

14

17

20

21

119

Relay 5

MB ON relay

GB OFF relay

Relay 20

Relay 21

Run coil relay

MB OFF relay

GB ON relay

AOP

1 / 6

ACTIVEFIXED POWER

DEIF 24 %

Generator voltage L1-L2

Generator f L1

Fuel level

Total Running hours

1* h

%

Hz

V400

50.00

66

184 CAN ID: 2Priority: 2

66 % 184 h

Page 4: Touch Display Unit TDU

4 Document no. 4189390003E

Touch Display Unit TDUDrawings

Connections

Dimensions

For more information, please contact:DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · DenmarkTel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com

© Copyright DEIF A/S 2020. All rights reserved.

TDU 107 CoreTDU 107 Core

187 mm 29 mm

147

mm

5 mm

136

mm

176 mm

Cutout

TDU 107 Extended

187 mm 47 mm8 mm

147

mm

136

mm

176 mm

Cutout

24 V DC Ethernet USB 2.0

Serial 24 V DC

1

2

7

8SD slot

2x USB 2.0

2x Ethernet RJ45 Ethernet RJ45 / 1Gbit

TDU 107 Core TDU 107 Extended

TDU 107 Core TDU 107 Extended