    INTRODUCTION 3

    CONNECTING RSVIEW32 4

    Start a New Project 4

    Create a Device Node 5

    Browse For Available Servers 7

    Create a Tag 9

    Check the OPC Connection 13

    CONNECTING WITH RSVIEWSE 15

    Open a New Project 15

    Define an OPC Server 16

    Browse For Available Servers 18

    Create a Tag 19

    Test the OPC Connection 22

    SUMMARY 23

    Contact Us 23

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    3/23

    Page 3 of 23

    Introduction

    Rockwell Softwares RSView is one of many HMIs that can be used as an OPC Client to connect to an

    OPC Server. There are two versions that we will cover here, RSView32 and RSView SE standalone. The

    purpose of this document is to show the user how to make an OPC connection to TOPServer with the

    RSView products.

    The document is geared to the new user, although the experienced user may find value in this document as

    well. We make the assumptions that the user 1) has a valid installation of RSView32 or SE, 2) has a valid

    installation of TOPServer, 3) has TOPServer properly configured for communications to the PLC.

    TOPServer is a product of Software Toolbox and may be referred to as the server or OPC Server.RSView is a product of Rockwell Software and may be referred to as HMI, client, or OPC Client. You

    will also see OPC items referred to as tags or items. Also note that while it is not covered here nor is it

    recommended by Software Toolbox, the server can also act as a DDE Server to RSView.

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    4/23

    Page 4 of 23

    Connecting RSView32

    The following steps will show you how to make an OPC connection from RSView32 to TOPServer. This

    was done using version 6.50.07 of RSView32.

    Start a New Project

    First, open a copy of RSView32 and start a new project.

    Figure 1

    Save the file with a descriptive name.

    Figure 2

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    5/23

    Page 5 of 23

    This will open your new project in Edit Mode.

    Figure 3

    Create a Device Node

    In RSView32 double-click on the System folder and then double-click on Node in the Project Control Panel.

    If you have multiple devices in the server project, you may want to create multiple nodes in RSView and link

    them to the devices in the server.

    Figure 4

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    6/23

    Page 6 of 23

    This will show your node assignment screen.

    Figure 5

    Select a data source, in this case OPC Server, check the Enabled check box and give the source a

    meaningful name. Then we will browse for the server.

    Figure 6

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    7/23

    Page 7 of 23

    Browse For Available Servers

    To browse for the server that you want to connect, click the button to the right of the Name text box.

    Figure 7

    This will show your list of available servers in the OPC Server Browser window. Select

    SWToolbox.TOPServer from the list of Servers and click OK.

    Figure 8

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    8/23

    Page 8 of 23

    Select the Type of connection you are going to make to the server. Select Local for connection to a server

    on the same PC. Select Remote to connect to a server running on another PC. This will enable the Server

    Computer Name or Address field. You can enter either a computer name or IP address for the PC running

    the server. You will also want to set your update rate to 0. This tells RSView that the server will use the

    fastest possible rate to send data. If you design a large RSView project with multiple nodes, you may want

    to slow down the update rates of your nodes.

    Figure 9

    RSView allows you to create the node with or without an Access Path. By leaving the Access Path blank

    RSView can link to any tag within the server from this node. This means you can access tags from multiple

    devices in the server application. Had we entered an Access Path, only tags from a single device could beaccessed through this node. Check "Enabled" so that the node will connect to the server when you run

    your RSView project. Click Accept and Close. This will show your server in your node list. Click Close.

    Figure 10

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    9/23

    Page 9 of 23

    Create a Tag

    Next, we need to create a tag(s) to access the data in the device(s). Double-click on the System folder and

    then double-click on Tag Database in the Project Control and open the Tag Database dialog box.

    Figure 11

    This will show your tag database dialogue.

    Figure 12

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    10/23

    Page 10 of 23

    In the Tag Database, enter the tag name and description information and select the tag type. Set your

    minimum and maximum values as needed. In the Data Source section Click on the Device radio button.Then click the Node Browser button.

    Figure 13

    This will display your Node Browser window.

    Figure 14

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    11/23

    Page 11 of 23

    Select the node name, in this case TOPServer, and click OK to assign the node to the tag you are defining.

    In our example, we have only TOPServer node that we have added. This will bring you back to the Tag

    Database tag definition. Click on the Address Browser button located to the right of the Address field.

    Figure 15

    This will show you the OPC Address Browser.

    Figure 16

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    12/23

    Page 12 of 23

    Expand your server Node and channel that contains the device and highlight the device to show the tags in

    the right pane. Then select the tag you want to read in the right pane. Click OK. Remember, we are using

    predefined tags from TOPServer in this instance.

    Figure 17

    This will bring you back to the tag database, showing you the access path to the tag.

    Figure 18

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    13/23

    Page 13 of 23

    Click accept to add the tag to the tag database. This will show you the tag in the tag list in the bottom right

    pane. Click Close to close the tag database.

    Figure 19

    Check the OPC Connection

    We need to verify the OPC Connection to the server. To do this, double-click Tag Monitor in the System

    Folder.

    Figure 20

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    14/23

    Page 14 of 23

    This will show you the Tag Monitor dialogue.

    Figure 21

    Enter the Tag Name or names that you want to check. In this case we entered "Tag1" which is the name of

    our tag that we added. Hit the Enter key after typing in the tag name. You should see a State of "valid" in

    the Tag Monitor window for the tag and a Value that is ramping or incrementing very quickly. If you see

    this, you have established a good OPC connection to the server from RSView32.

    Figure 22

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    15/23

    Page 15 of 23

    Connecting with RSViewSE

    The following steps will show you how to make an OPC connection from RSViewSE standalone to

    TOPServer. This was done using version xxx of RSView Studio.

    Open a New Project

    Open RSView Studio and choose the appropriate type of application and click Continue.

    Figure 23

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    16/23

    Page 16 of 23

    Create a new application, giving it a descriptive name and any description necessary. Click Create.

    Figure 24

    This will load your blank Studio screen.

    Define an OPC Server

    To define an OPC Server, do the following. First, click File|New|OPC

    Figure 25

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    17/23

    Page 17 of 23

    This will open the OPC Data Server Properties dialogue.

    Enter a meaningful name and description (optional) for the Server. Select if the server will be on the local

    computer or a remote computer. If remote, click the browse button in the Computer hosting the serversection. If not the box will be inactive with localhost populated in the field, then skip to browse for the

    server.

    Figure 26

    This will bring up the network browser. Browse to and select the computer where your OPC Server resides.

    The computer name will then show in the text box in the Computer hosting the server section. Now we

    can browse for the OPC Server.

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    18/23

    Page 18 of 23

    Browse For Available Servers

    To browse for the server, click the browse button beside the OPC Server Name (ProgID) text box. This will

    open the OPC Server browser window.

    Figure 27

    Select Software Toolbox OPC Power Server and click OK. This will populate the server ProgID in the text

    box. Alternatively, you could just type the ProgID, SWToolbox.TOPServer, into the text box without

    browsing. Click OK to continue.

    Figure 28

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    19/23

    Page 19 of 23

    You will see an informational message at the bottom of RSView alerting you that the server is now active.

    Figure 29

    Create a Tag

    We now need to create the tags in RSView to read data from TOPServer. At this time, if it is not already

    open, then open your Application Explorer by clicking the second icon from the right in the toolbar. Right

    click on HMI Tags|Tags and click open.

    Figure 30

    This will open your tag database window. Here you will need to define your tag.

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    20/23

    Page 20 of 23

    In the Tag Database, enter the tag name and description information and select the tag type. Set your

    minimum and maximum values as needed. In the Data Source section Click on the Device radio button.Then click the Tag Browser button to the right of the address text box.

    Figure 31

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    21/23

    Page 21 of 23

    This will show your Tag Browser window. Here you will browse to your server tags and select the tag you

    want to read. You will see when you select the tag the tag access path in the Selected Tag section at the

    bottom. Click OK.

    Figure 32

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    22/23

    Page 22 of 23

    This will populate the tag address field. Click Accept to add the tag to the database and it will add the tag to

    the list in the bottom pane. Click close.

    Figure 33

    Test the OPC Connection

    To test your OPC connection, you will want to set up a new simple display with a single tag with a known

    changing value. After creating your display, you will want to launch the runtime to verify the changing data

    from your tag.

  • 8/2/2019 TOPServer to Rockwell Software Connectivity

    23/23

    Page 23 of 23

    Summary

    This document has been provided to assist the end-user in the basic configuration of Rockwell Softwares

    RSView family to read data from an OPC Server, specifically, TOP Server. From this guide, we hope that

    you have gained a better understanding of how TOPServer and RSView interact and in the process, some

    insight into OPC itself. While the document is not an exhaustive reference or Users Guide to RSView, it

    has been designed to cover the items that are needed by the vast majority of users to connect the client

    and server. If you have further questions or need assistance our experienced staff is more than happy to

    help. We can be contacted in the methods outlined below.

    Contact Us

    If you have any questions, or seek further information and help:

    Online Support http://support.softwaretoolbox.com/

    Email Support [email protected]

    Phone Support +1 (704) 849-2773

    Fax +1 (704) 849-6388

    Mailing Address

    Software Toolbox, Inc. 148 A East Charles Street, Matthews, NC, 28105. USA.

    http://support.softwaretoolbox.com/mailto:[email protected]:[email protected]://support.softwaretoolbox.com/