New Product 1 Three-phase Undervoltage and Phase-sequence Phase-loss Relay K8DS-PU Ideal for Monitoring 3-phase Power Supplies for Industrial Facilities and Equipment. • Greater resistance to inverter noise. • Monitor undervoltages, phase sequence, and phase loss in three- phase three-wire circuits with one unit. • One SPDT output relay, 5 A at 250 VAC (resistive load). • World-wide power specifications supported by one unit. (Set with a rotary switch.) Relay status can be monitored using LED indicator. Ordering Information List of Models Note: The input range is set with a rotary switch. * The power supply voltage is the same as the rated input voltage. Refer to Safety Precautions on page 9. Refer to page 7 for commonly asked questions. For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Rated input voltage* Model 3-phase 3-wire mode 200, 220, 230, or 240 VAC K8DS-PU1 380, 400, 415, or 480 VAC K8DS-PU2

Transcript of Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or...

Page 1: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

New Product

1

Three-phase Undervoltage and Phase-sequence Phase-loss RelayK8DS-PU

Ideal for Monitoring 3-phase Power Supplies for Industrial Facilities and Equipment.• Greater resistance to inverter noise.• Monitor undervoltages, phase sequence, and phase loss in three-

phase three-wire circuits with one unit.• One SPDT output relay, 5 A at 250 VAC (resistive load).• World-wide power specifications supported by one unit. (Set with a

rotary switch.)•Relay status can be monitored using LED indicator.

Ordering InformationList of Models

Note: The input range is set with a rotary switch.* The power supply voltage is the same as the rated input voltage.

Refer to Safety Precautions on page 9.Refer to page 7 for commonly asked questions.

For the most recent information on models that have been certified for safety standards, refer to your OMRON website.

Rated input voltage* Model

3-phase 3-wire mode200, 220, 230, or 240 VAC K8DS-PU1

380, 400, 415, or 480 VAC K8DS-PU2

Page 2: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

2

Ratings and SpecificationsRatings

Rated input voltage

K8DS-PU1 3-wire 3-phase mode: 200, 220, 230, or 240 VAC

K8DS-PU2 3-wire 3-phase mode: 380, 400, 415, or 480 VAC

Input load K8DS-PU1: Approx. 1.7 VAK8DS-PU2: Approx. 2.8 VA

Operating value setting range (UNDER) Undervoltage−30% to 25% of rated input voltage

Operating value Operates at 100% of set value.

Reset value 5% of operating value (fixed)

Reset method Automatic reset

Operating time setting range (T)

Asymmetry 0.1 to 30 s

Phase sequence 0.1 s±0.05 s

Phase loss 0.1 s max.

Power ON lock time (LOCK) 1 s±0.5 s

Indicators Power (PWR): Green, Relay output (RY): Yellow, UNDER: Red

Output relays One SPDT relay output

Output relay ratings

Rated loadResistive load5 A at 250 VAC5 A at 30 VDC

Maximum switching capacity: 1,250 VA, 150 WMinimum load: 5 VDC, 10 mA (reference values)Mechanical life: 10 million operations min.Electrical life: 5 A at 250 VAC: 50,000 operations

3 A at 250 VAC: 100,000 operations

Ambient operating temperature −20 to 60°C (with no condensation or icing)

Storage temperature −25 to 65°C (with no condensation or icing)

Ambient operating humidity 25% to 85% (with no condensation)

Storage humidity 25% to 85% (with no condensation)

Altitude 2,000 m max.

Terminal screw tightening torque 0.49 to 0.59 N·m

Terminal wiring method

Recommended wireSolid wire: 2.5 mm2

Twisted wires: AWG16, AWG18Note: 1. Ferrules with insulating sleeves must be used with twisted wires.

2. Two wires can be twisted together.Recommended ferrules

Al 1,5-8BK (for AWG16) manufactured by Phoenix ContactAl 1-8RD (for AWG18) manufactured by Phoenix ContactAl 0,75-8GY (for AWG18) manufactured by Phoenix Contact

Case color N1.5

Case material PC and ABS, UL 94 V-0

Weight Approx. 65 g

Mounting Mounts to DIN Track.

Dimensions 17.5 × 80 × 74 mm (W×D×H)

Page 3: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

3

SpecificationsInput frequency 50/60 Hz

Overload capacity Continuous 500 V

Repeat accura-cy

Operating value ±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage, 50/60 Hz sine wave input)

Operating time ±50 ms (at 25°C and 65% humidity, rated power supply voltage)

Applicable standards

Conforming standards EN 60947-5-1Installation environment (pollution level 2, installation category III)

EMC EN 60947-5-1

Safety standards UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA: C22.2 No.14, CCC: GB14048.5

Insulation resistance20 MΩ min.

Between external terminals and caseBetween input terminals and output terminals

Dielectric strength2,000 VAC for one minute

Between external terminals and caseBetween input terminals and output terminals

Noise immunity 1,500 V power supply terminal common/normal modeSquare-wave noise of ±1 µs/100 ns pulse width with 1-ns rise time

Vibration resistance Frequency: 10 to 55 Hz, acceleration 50 m/s2

10 sweeps of 5 min each in X,Y, and Z directions

Shock resistance 100 m/s2, 3 times each in 6 directions along 3 axes

Degree of protection Terminals: IP20

Distance between products d [mm]

Am

bien

t tem

pera

ture

[°C

]

0

10

20

30

40

50

60

70

5 10 15 20 25 30 35 5040 45

K8DS

No.3

K8DS

No.2

K8DS

No.1

K8DS

No.4

K8DS

No.5

DIN Track Distance between products: d

Sample: K8DS-PUDistance between products: 0, 5, 10, and 50 mm

Test method

Relationship of Mounting Distance between K8DS-PU Relays and Ambient Temperature (Reference Values)The following diagram shows the relationship between the mounting distances and the ambient temperature.If the relay is used with an ambient temperature that exceeds these values, the temperature of the K8DS may rise and shorten the life of the internal components.

Page 4: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

4

ConnectionsTerminal Diagram

Note: Use the recommended ferrules if you use twisted wires.

Wiring Example

Timing ChartsUndervoltage Operation Diagram

Note: 1. The K8DS-PU output contacts are normally operative.2. The power ON lock prevents unnecessary alarms from

being generated during the unstable period when the power is first turned ON. There is no contact output during timer operation.

3. Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes below 60% of the rated input.

4. L2 and L3 are also used for the power supply. If the voltage becomes very low, the Relay will not operate.

5. Phase loss (on power supply side and load side) is not detected in the motor load during operation.

Operation Table

*1 L2 and L3 are also used for the power supply. If the voltage becomes very low, the indicator will turn OFF.

*2 The indicator will flash once per second after an incorrect phase is detected and once per 0.5 second during the detection time.

Relay output250 VAC, 5 A (resistive load)

3-phase, 3-wire power supply

30 VDC, 5 A (resistive load)

Phase-to-phase voltage: 200 to 480 VAC

L1 L2 L3

111214

Control Output

Relay Output

Input Voltages

L1 L2 L3

14 12 11

14 12 11

L1 L2 L3

L1

L2

L3

3-phase voltage

Motor

Power supply AC/DC

Flashing Flashing

Phase Loss Operation Phase sequence Operation

Alarm indicator

Undervoltage set value

Input

Flashing

L2Input

L1

L3

L2

L3

L2

L1

L1

L2

L3

t

t1

Undervoltage contacts

L1L2L3

L1

L3

Undervoltage alarm indicator

Undervoltage relay 11-14

Hysteresis: Fixed at 5%

t: Operating time (0.1 to 30 s)

t1: Power ON lock (1 s)

Lit

Lit Flashing

L2

L1

L3

ItemIndicators Contact

operationRY_LED ALM_LED

Undervoltage OFF ON OFF

Phase loss OFF ON*1 OFF

Phase sequence

Incorrect phase OFF Flashing*2 OFF

Correct phase ON OFF ON

Page 5: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

5

NomenclatureFront

Indicators

* This indicator uses the input across L2 and L3 as the internal power supply. It will not light unless there is an input across L2 and L3.

Setting Knobs

Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with insulating sleeve for the terminal connection.The length of the exposed current-carrying part inserted into the terminal must be 8 mm or less to maintain dielectric strength after connection.

Recommended ferrulesPhoenix Contact• Al 1,5-8BK (for AWG16)• Al 1-8RD (for AWG18)• Al 0,75-8GY (for AWG18)

2. Tightening torque: 0.49 to 0.59 N·m

Operation MethodsConnectionsInput

Wire the input to the L1, L2, and L3 terminals (3-phase, 3-wire).Make sure the phase sequence is wired correctly. The Unit will not operate normally if the phase sequence is incorrect.

OutputsTerminals 11, 12, and 14 are the output terminals.

* Use the recommended ferrules if you use twisted wires.

L1 L2 L3

14 12 11

Power indicator

Relay status indicator

Terminal block(See notes 1 and 2.)

Terminal block(See notes 1 and 2.)

Input voltage range rotary switch

Undervoltage knob (UNDER)

Operating time knob (T)

Alarm indicator

Item Meaning

Power indicator (PWR: Green) Lit when power is being supplied.*

Relay status indi-cator(RY: Yellow)

Lit when relay is operating (normally lit).

Alarm indicator (ALM: Red)

• Lit for undervoltage or phase loss error.When the input exceeds the undervoltage value, the indicator flashes for the operating time to indicate the error status.

• Lit for phase sequence error.

Item Description

Input voltage range rotary switch

Used to change the input voltage range.K8DS-PU1: 200, 220, 230, or 240 VK8DS-PU2: 380, 400, 415, or 480 V

Undervoltage knob (UNDER)

Used to set from −30% to 25% of the rated in-put.

Operating time knob (T) Used to set the operating time to 0.1 to 30 s.

For 2.5 mm2 or smaller solid wires

For ferrules with an insulation sleeve.

8 mm max. 8 mm max.

Load

Voltage input

Signal output14

12

L1

L2

L3

11

Relay signaloutput

L1 L2 L3

Page 6: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

6

Setting MethodsUndervoltage

Undervoltage is set using the undervoltage knob (UNDER).The undervoltage can be set to between −30% and 25% of the rated input.Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same level.)Use this as a guide to set the voltage.The rated input depends on the model and the rotary switch setting.Example: K8DS-PU1 with Rotary Switch Set to 200 V

The rated input voltage is 200 VAC and the setting range is 140 to 250 V.

Operating TimeThe operating time is set using the operating time knob (T).The operating time can be set to between 0.1 and 30 s.Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same level.)Use this as a guide to set the operating time.If the input exceeds (or drops lower than) the voltage set value, the alarm indicator will start flashing for the set period and then stay lit.

Dimensions (Unit: mm)

Three-phase Undervoltage and Phase-sequence Phase-loss Relay

Optional Parts for DIN Track Mounting

17.5

80

74

69

44

K8DS-PU1K8DS-PU2

*Dimensions in parentheses are for the PFP-50N.

4.5

15 25 2510 10

1,000 (500)*

25 25 15 (5)*

35±0.3

7.3±0.15

27±0.15

1

DIN TracksPFP-100NPFP-50N

Page 7: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

7

Checking Operation

UndervoltageGradually reduce the input from 120% of the set value. The input will equal the operating value when the input goes below the set value and the alarm indicator starts flashing. Operation can be checked because the Relay will operate after the operating time has passed.

How to Measure the Operating Time

UndervoltageChange the input value quickly from 120% to 70% of the set value and measure the time required for the Relay to operate.Operating TimeAdjust the slide resistor so that the voltage applied to the K8DS terminals is 80% of the set value when the auxiliary relay in connection diagram 2 operates.Close the switch and use a cycle counter to measure the operating time.

Checking the Phase Sequence and Phase Loss Operation

Phase SequenceSwitch the wiring, as shown by the dotted lines in connection diagram 1, to reverse the phase sequence and check that the K8DS operates.Phase lossCreate a phase loss for any input phase and check that the K8DS operates.

Questions and Answers

Q

Input voltage

Operating set value

Alarm indicatorFlashing

5 s

Lit

Relay output

3-phase, 200 VAC

0 to 150 V

3-phase variable autotransformer

V3

V1

V2L1

L2

L3

L1

L2

L3

Example: Monitoring Mode for Rated Voltage of 200 V and an Operating Time Setting of 5 s

Connection Diagram 1

Q

3-phase, 200 VAC

R1: Sliding resistor, 200 Ω, 200 WR2: 100 Ω, 400 W

Cycle counter

V3

V1

V2

X/aX/b

R1

R2

L1

L2

L3

L3

L2

L1

± C 200 V

X

Connection Diagram 2

Q

Page 8: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

8

Load-side Phase Loss

In principle, phase loss cannot be detected on the load side because the K8DS-PU measures three-phase voltage to determine phase loss.

Motor Load Phase Loss during Operation

Motor load phase loss cannot be detected during operation. It can be used to detect phase loss at startup. Normally, three-phase motors will continue to rotate even if one phase is open. The three-phase voltage will be induced at the motor terminals. The diagram shows voltage induction at the motor terminals when phase R has been lost with a load applied to a three-phase motor. The horizontal axis shows the motor load as a percentage of the rated load, and the vertical axis shows voltage as a percentage of the rated voltage. The lines in the graph show the voltage induced at the motor terminals for each load phase loss occurs during operation. As the graph shows, phase loss cannot be detected because the motor terminal voltage does not drop very much even if a phase is lost when the load on the motor is light. To detect motor load phase loss during operation, use the undervoltage detection function to detect the motor terminal voltages at phase loss.Set the operating time carefully because it will affect the time from when the phase loss occurs until tripping when this function is used.

Characteristic Curve Diagram

Note: For phase loss of phase R. VST, VTR, and VRS indicate the motor terminal voltage at phase loss.

Is an undervoltage detected if only one of the three-phase phase-to-phase voltages is less than the undervoltage set value?

The K8DS monitors all three phase voltages. Therefore, an undervoltage is detected if only one of the phase-to-phase voltage is less than the set value.

Questions and Answers

Q

Q

100

95

90

85

80

75

70

65

60

55

50

45

100 20 30 40 50 60 70 80 90 100 110

VST

VTR

VRS

Note: This characteristic curve shows the approximate values only.

Vol

tage

(as

a p

erce

ntag

e of

rat

ed v

olta

ge)

Motor load (as a percentage of rated load)

Q

Page 9: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

9

Safety Precautions

Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/.

Warning Indications

Meaning of Product Safety Symbols

Electrical shock may occasionally cause serious injury. Confirm that the input voltage is OFF before starting any wiring work and wire all connections correctly.

Electrical shock may cause minor injury.Do not touch terminals while electricity is being supplied.

There is a risk of minor electrical shock, fire, or device failure. Do not allow any pieces of metal, conductors, or cutting chips that occur during the installation process to enter the product.

Explosions may cause minor injuries. Do not use the product in locations with inflammable or explosive gases.

There is a risk of minor electrical shock, fire, or device failure. Do not disassemble, modify, repair, or touch the inside of the product.

Loose screws may cause fires. Tighten terminal screws to the specified torque of 0.49 to 0.59 N·m.

Use of excessive torque may damage the terminal screws. Tighten terminal screws to the specified torque of 0.49 to 0.59 N·m.

Use of the product beyond its life may result in contact welding or burning. Make sure to consider the actual operating conditions and use the product within its rated load and electrical life count. The life of the output relay varies significantly with the switching capacity and switching conditions.

WARNING

Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property damage.

CAUTIONIndicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage.

Precautions for Safe Use

Supplementary comments on what to do or avoid doing, to use the product safely.

Precautions for Correct Use

Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction, or undesirable effects on product performance.

Used to warn of the risk of electric shock under specific conditions.

Used for general prohibitions for which there is no specific symbol.

Used to indicate prohibition when there is a risk of minor injury from electrical shock or other source if the product is disassembled.

Used for general mandatory action precautions for which there is no specified symbol.

WARNING

CAUTION

Page 10: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

K8DS-PU

10

1. Do not use or store the product in the following locations.• Locations subject to water or oil

• Outdoor locations or under direct sunlight

• Locations subject to dust or corrosive gases (particularly sulfurizing gases, ammonia, etc.)

• Locations subject to rapid temperature changes

• Locations prone to icing and dew condensation

• Locations subject to excessive vibration or shock

• Locations subject to wind and rain

• Locations subject to static electricity and noise

• Habitats of insects or small animals

2. Use and store the product in a location where the ambient temperature and humidity are within the specified ranges. If applicable, provide forced cooling.

3. Mount the product in the correct direction.4. Do not wire the input and output terminals incorrectly.5. Make sure the input voltage and loads are within the

specifications and ratings for the product.6. Make sure the crimp terminals for wiring are of the specified size.7. Do not connect anything to terminals that are not being used.8. Use a power supply that will reach the rated voltage within 1

second after the power is turned ON.9. Keep wiring separate from high voltages and power lines that

draw large currents. Do not place product wiring in parallel with or in the same path as high-voltage or high-current lines.

10.Do not install the product near equipment that generates high frequencies or surges.

11.The product may cause incoming radio wave interference. Do not use the product near radio wave receivers.

12.Install an external switch or circuit breaker and label it clearly so that the operator can quickly turn OFF the power supply.

13.Make sure the indicators operate correctly. Depending on the application environment, the indicators may deteriorate prematurely and become difficult to see.

14.Do not use the product if it is accidentally dropped. The internal components may be damaged.

15.Be sure you understand the contents of this catalog and handle the product according to the instructions provided.

16.Do not install the product in any way that would place a load on it.17.When discarding the product, properly dispose of it as industrial

waste.18.The product must be handled only by trained electrician.19.Prior to operation, check the wiring before you supply power to

the product.20.Do not install the product immediately next to heat sources.21.Perform periodic maintenance.

Observe the following operating methods to prevent failure and malfunction.1. Use the input power and other power supplies and converters

with suitable capacities and rated outputs.2. Use a precision screwdriver or similar tool to adjust the setting

knobs and rotary switches.3. The distortion in the input waveform must be 30% max. If the

input waveform is distorted beyond this level, it may cause unnecessary operation.

4. The product cannot be used for thyristor control or on the secondary side of an inverter. To use the product on the secondary side of an inverter, install a noise filter on the primary side of the inverter.

5. To reduce the error in the setting knob, always turn the setting knob from the minimum setting toward the maximum setting.

6. Phase loss is detected only when the power supply to the motor is turned ON. Phase loss during motor operation is not detected.

7. Phase loss can be detected only from the input contacts to the power supply side. Phase loss cannot be detected from the input contacts to the load side.

8. When cleaning the product, do not use thinners or solvents. Use commercial alcohol.

Mounting and Removing• The product may be mounted in any direction, but it must be

mounted securely and as level as possible.• To mount the product to the DIN Track, hook it on the DIN Track at

(A) and then press in on the Unit in direction (B).

• To remove the product, insert a flat-blade screwdriver at (C) and pull down the hook to release the Unit.

• Leave at least 30 mm of space between the product and other devices to allow easy installation and removal.

Operating the Setting Knobs and Rotary Switch• Use a screwdriver to adjust the setting knobs and rotary switch.

The knobs have a stopper that prevents them from turning beyond the full right or left position. Do not force a knob beyond these points.

Precautions for Safe Use

Precautions for Correct Use

(A)

(B)

30 mm min.(C)

Hook

Setting knob

Page 11: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

Terms and Conditions of Sale1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed

part of all quotes, agreements, purchase orders, acknowledgments, price lists,catalogs, manuals, brochures and other documents, whether electronic or inwriting, relating to the sale of products or services (collectively, the "Products")by Omron Electronics LLC and its subsidiary companies (“Omron”). Omronobjects to any terms or conditions proposed in Buyer’s purchase order or otherdocuments which are inconsistent with, or in addition to, these Terms.

2. Prices; Payment Terms. All prices stated are current, subject to change with-out notice by Omron. Omron reserves the right to increase or decrease priceson any unshipped portions of outstanding orders. Payments for Products aredue net 30 days unless otherwise stated in the invoice.

3. Discounts. Cash discounts, if any, will apply only on the net amount of invoicessent to Buyer after deducting transportation charges, taxes and duties, and willbe allowed only if (i) the invoice is paid according to Omron’s payment termsand (ii) Buyer has no past due amounts.

4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month orthe maximum legal rate, whichever is less, on any balance not paid within thestated terms.

5. Orders. Omron will accept no order less than $200 net billing. 6. Governmental Approvals. Buyer shall be responsible for, and shall bear all

costs involved in, obtaining any government approvals required for the impor-tation or sale of the Products.

7. Taxes. All taxes, duties and other governmental charges (other than generalreal property and income taxes), including any interest or penalties thereon,imposed directly or indirectly on Omron or required to be collected directly orindirectly by Omron for the manufacture, production, sale, delivery, importa-tion, consumption or use of the Products sold hereunder (including customsduties and sales, excise, use, turnover and license taxes) shall be charged toand remitted by Buyer to Omron.

8. Financial. If the financial position of Buyer at any time becomes unsatisfactoryto Omron, Omron reserves the right to stop shipments or require satisfactorysecurity or payment in advance. If Buyer fails to make payment or otherwisecomply with these Terms or any related agreement, Omron may (without liabil-ity and in addition to other remedies) cancel any unshipped portion of Prod-ucts sold hereunder and stop any Products in transit until Buyer pays allamounts, including amounts payable hereunder, whether or not then due,which are owing to it by Buyer. Buyer shall in any event remain liable for allunpaid accounts.

9. Cancellation; Etc. Orders are not subject to rescheduling or cancellationunless Buyer indemnifies Omron against all related costs or expenses.

10. Force Majeure. Omron shall not be liable for any delay or failure in deliveryresulting from causes beyond its control, including earthquakes, fires, floods,strikes or other labor disputes, shortage of labor or materials, accidents tomachinery, acts of sabotage, riots, delay in or lack of transportation or therequirements of any government authority.

11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship

except in “break down” situations.b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall

constitute delivery to Buyer;c. All sales and shipments of Products shall be FOB shipping point (unless oth-

erwise stated in writing by Omron), at which point title and risk of loss shallpass from Omron to Buyer; provided that Omron shall retain a security inter-est in the Products until the full purchase price is paid;

d. Delivery and shipping dates are estimates only; ande. Omron will package Products as it deems proper for protection against nor-

mal handling and extra charges apply to special conditions.12. Claims. Any claim by Buyer against Omron for shortage or damage to the

Products occurring before delivery to the carrier must be presented in writingto Omron within 30 days of receipt of shipment and include the original trans-portation bill signed by the carrier noting that the carrier received the Productsfrom Omron in the condition claimed.

13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that theProducts will be free from defects in materials and workmanship for a period oftwelve months from the date of sale by Omron (or such other period expressedin writing by Omron). Omron disclaims all other warranties, express or implied.(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-

ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THEPRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIRINTENDED USE. Omron further disclaims all warranties and responsibility ofany type for claims or expenses based on infringement by the Products or oth-erwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obli-gation hereunder shall be, at Omron’s election, to (i) replace (in the formoriginally shipped with Buyer responsible for labor charges for removal orreplacement thereof) the non-complying Product, (ii) repair the non-complyingProduct, or (iii) repay or credit Buyer an amount equal to the purchase price ofthe non-complying Product; provided that in no event shall Omron be responsi-ble for warranty, repair, indemnity or any other claims or expenses regardingthe Products unless Omron’s analysis confirms that the Products were prop-erly handled, stored, installed and maintained and not subject to contamina-tion, abuse, misuse or inappropriate modification. Return of any Products byBuyer must be approved in writing by Omron before shipment. Omron Compa-nies shall not be liable for the suitability or unsuitability or the results from theuse of Products in combination with any electrical or electronic components,circuits, system assemblies or any other materials or substances or environ-ments. Any advice, recommendations or information given orally or in writing,are not to be construed as an amendment or addition to the above warranty.See http://www.omron247.com or contact your Omron representative for pub-lished information.

14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLEFOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANYWAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM ISBASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.Further, in no event shall liability of Omron Companies exceed the individualprice of the Product on which liability is asserted.

15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies andtheir employees from and against all liabilities, losses, claims, costs andexpenses (including attorney's fees and expenses) related to any claim, inves-tigation, litigation or proceeding (whether or not Omron is a party) which arisesor is alleged to arise from Buyer's acts or omissions under these Terms or inany way with respect to the Products. Without limiting the foregoing, Buyer (atits own expense) shall indemnify and hold harmless Omron and defend or set-tle any action brought against such Companies to the extent based on a claimthat any Product made to Buyer specifications infringed intellectual propertyrights of another party.

16. Property; Confidentiality. Any intellectual property in the Products is the exclu-sive property of Omron Companies and Buyer shall not attempt to duplicate itin any way without the written permission of Omron. Notwithstanding anycharges to Buyer for engineering or tooling, all engineering and tooling shallremain the exclusive property of Omron. All information and materials suppliedby Omron to Buyer relating to the Products are confidential and proprietary,and Buyer shall limit distribution thereof to its trusted employees and strictlyprevent disclosure to any third party.

17. Export Controls. Buyer shall comply with all applicable laws, regulations andlicenses regarding (i) export of products or information; (iii) sale of products to“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens ofregulated technology or information.

18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any rightand no course of dealing between Buyer and Omron shall operate as a waiverof rights by Omron. (b) Assignment. Buyer may not assign its rights hereunderwithout Omron's written consent. (c) Law. These Terms are governed by thelaw of the jurisdiction of the home office of the Omron company from whichBuyer is purchasing the Products (without regard to conflict of law princi-ples). (d) Amendment. These Terms constitute the entire agreement betweenBuyer and Omron relating to the Products, and no provision may be changedor waived unless in writing signed by the parties. (e) Severability. If any provi-sion hereof is rendered ineffective or invalid, such provision shall not invalidateany other provision. (f) Setoff. Buyer shall have no right to set off any amountsagainst the amount owing in respect of this invoice. (g) Definitions. As usedherein, “including” means “including without limitation”; and “Omron Compa-nies” (or similar words) mean Omron Corporation and any direct or indirectsubsidiary or affiliate thereof.

Certain Precautions on Specifications and Use1. Suitability of Use. Omron Companies shall not be responsible for conformity

with any standards, codes or regulations which apply to the combination of theProduct in the Buyer’s application or use of the Product. At Buyer’s request,Omron will provide applicable third party certification documents identifyingratings and limitations of use which apply to the Product. This information byitself is not sufficient for a complete determination of the suitability of the Prod-uct in combination with the end product, machine, system, or other applicationor use. Buyer shall be solely responsible for determining appropriateness ofthe particular Product with respect to Buyer’s application, product or system.Buyer shall take application responsibility in all cases but the following is anon-exhaustive list of applications for which particular attention must be given:(i) Outdoor use, uses involving potential chemical contamination or electricalinterference, or conditions or uses not described in this document.(ii) Use in consumer products or any use in significant quantities. (iii) Energy control systems, combustion systems, railroad systems, aviationsystems, medical equipment, amusement machines, vehicles, safety equip-ment, and installations subject to separate industry or government regulations. (iv) Systems, machines and equipment that could present a risk to life or prop-erty. Please know and observe all prohibitions of use applicable to this Prod-uct. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUSRISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUTENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO

ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THEOVERALL EQUIPMENT OR SYSTEM.

2. Programmable Products. Omron Companies shall not be responsible for theuser’s programming of a programmable Product, or any consequence thereof.

3. Performance Data. Data presented in Omron Company websites, catalogsand other materials is provided as a guide for the user in determining suitabil-ity and does not constitute a warranty. It may represent the result of Omron’stest conditions, and the user must correlate it to actual application require-ments. Actual performance is subject to the Omron’s Warranty and Limitationsof Liability.

4. Change in Specifications. Product specifications and accessories may bechanged at any time based on improvements and other reasons. It is our prac-tice to change part numbers when published ratings or features are changed,or when significant construction changes are made. However, some specifica-tions of the Product may be changed without any notice. When in doubt, spe-cial part numbers may be assigned to fix or establish key specifications foryour application. Please consult with your Omron’s representative at any timeto confirm actual specifications of purchased Product.

5. Errors and Omissions. Information presented by Omron Companies has beenchecked and is believed to be accurate; however, no responsibility is assumedfor clerical, typographical or proofreading errors or omissions.

Page 12: Three-phase Undervoltage and Phase-sequence …...Phase loss is detected by a drop in the L1, L2, or L3 voltage. A phase loss is detected when any of the phase-to-phase voltages goes

OMRON CANADA, INC. • HEAD OFFICEToronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com

OMRON ELECTRONICS DE MEXICO • HEAD OFFICEMéxico DF • 52.55.59.01.43.00 • 01-800-226-6766 • [email protected]

OMRON ELECTRONICS DE MEXICO • SALES OFFICEApodaca, N.L. • 52.81.11.56.99.20 • 01-800-226-6766 • [email protected]

OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICESão Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br

OMRON ARGENTINA • SALES OFFICECono Sur • 54.11.4783.5300

OMRON CHILE • SALES OFFICESantiago • 56.9.9917.3920

OTHER OMRON LATIN AMERICA SALES54.11.4783.5300

Authorized Distributor:

Note: Specifications are subject to change. © 2014 Omron Electronics LLC Printed in U.S.A.

Printed on recycled paper.

Automation Control Systems• Machine Automation Controllers (MAC) • Programmable Controllers (PLC) • Operator interfaces (HMI) • Distributed I/O • Software

Drives & Motion Controls • Servo & AC Drives • Motion Controllers & Encoders

Temperature & Process Controllers • Single and Multi-loop Controllers

Sensors & Vision• Proximity Sensors • Photoelectric Sensors • Fiber-Optic Sensors• Amplified Photomicrosensors • Measurement Sensors• Ultrasonic Sensors • Vision Sensors

Industrial Components • RFID/Code Readers • Relays • Pushbuttons & Indicators • Limit and Basic Switches • Timers • Counters • Metering Devices • Power Supplies

Safety • Laser Scanners • Safety Mats • Edges and Bumpers • Programmable Safety Controllers • Light Curtains • Safety Relays • Safety Interlock Switches

OMRON AUTOMATION AND SAFETY • THE AMERICAS HEADQUARTERS • Chicago, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com

OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu