Three Phase Circuits. Introduction: The generator , motor , transformer or rectifier have only one winding is called a single phase system If the current or voltage follows a phase difference 90 0 in a two windings , called two phase systems - PowerPoint PPT Presentation

Transcript of Three Phase Circuits

Page 1: Three Phase Circuits

ThreeThree Phase Phase CircuitsCircuits

1www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

Page 2: Three Phase Circuits

Introduction:• The generator , motor , transformer or rectifier have only

one winding is called a single phase system• If the current or voltage follows a phase difference 900 in a

two windings , called two phase systems• If the phase difference is 1200 between voltages or currents

in a three winding , called as Three phase systems• In poly-phase systems , there are more than three windingsAdvantages of three phase system:• More efficient than single phase system• Cost is less• Size is small . Compared to single phase system

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

2

Page 3: Three Phase Circuits

Adavantages of Three Phase Circuits• The amount of conductor material is required less for

transmitting same power, over the same distance , under same power loss

• Three phase motors produce uniform torque , where as torque produced by single motor is pulsating

• Three phase generators not produce the harmonics when they are connected in parallel

• Three phase motors are self starting whereas single phase motors are not self starting

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

3

Page 4: Three Phase Circuits

Generation of Three Phase Voltages

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

4

Page 5: Three Phase Circuits

• Vectorially r.m.s values of voltages induced in three windings are representedin the diagram

• ER = E ∟0o v,

• EY = E ∟-120o v

• EB= E ∟+120o v www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

5

Page 6: Three Phase Circuits

Balanced three phase supply:• A three phase supply is said to be balanced, when all the three

voltages have the same magnitude but differ in phase by 120° with respect to one another.

• The three phase supply is said to be unbalanced, even if one of the above conditions is not satisfied.

Balanced Load: • A three phase load is said to be balanced, when the impedances of

all the three phases are exactly the same. Even if one of them is different from the other, then the three phase load is said to be unbalanced

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

6

Page 7: Three Phase Circuits

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

7

Page 8: Three Phase Circuits

• In a three phase balanced load, whether star connected or delta connected, the magnitudes of the phase currents are the same but differ in phase by 120o with respected to one another

• But in an unbalanced load, when a three phase balanced supply is given, the magnitudes and phases of all the three phase currents will be different.

Three phase connections:• There are two types of three phase connections • Star connection (Y) • Delta connection (Δ)Star connection (Y):• In this method of inter-connection, the similar ends, say, “start”

ends of three coils (it could be “finishing” ends also) are joined together at point ‘N’

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

8

Page 9: Three Phase Circuits

• The point ‘N’ is known as star point or neutral point

• If this three-phase voltage is applied across a balanced symmetrical load, the neutral wire will be carrying three currents which are exactly equal in magnitude but are 120o out of phase with each other. Hence, their vector sum is zero

IR + IY + IB = 0

Voltages and Currents in Y-Connection:• The voltage induced in each winding is called the

‘phase’ voltage and current in each winding isknown as ‘phase’ current.

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

9

Page 10: Three Phase Circuits

• The vector diagram for phase voltages and currents in a star connection shows that

ER = EY = EB = Eph (phase e.m.f)

• Line voltage VRY between line 1 and line 2 is the vector difference of ER and EY.

• Line voltage VYB between line 2 and line 3 is the vector difference of EY and EB.

• Line voltage VBR between line 3 and line 1 is the vector difference of EB and ER.

•  

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

10

Page 11: Three Phase Circuits

• The p.d. between lines 1 and 2 is VRY = ER - EY (Vector difference)

• VRY is found by compounding ER and EY

reversed and its value is given by the diagonal of the paral1elogram in figure.

• The angle between ER and EY reversed is 60°.

If ER = EY = EB = Eph the Phase e.m.f then,

•  

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

11

C

O

ph

RYo

E

V230cos

ophRY EV 30cos2

phph EE 32

32

Page 12: Three Phase Circuits

• Hence, in star connection

It will be noted from figure that• (a) Line voltages are 120° apart.• (b) Line voltages are 30° ahead of their respective phase

voltages.• (c) The angle between the line currents and the corresponding

line voltages is (30 + ɸ) with current lagging.

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

12

ph

BYYB

E

DifferenceVectorEEV

similarly

3

)(

ph

RBBR

E

DifferenceVectorEEVand

3

)(

L

BRYBRY

Vvoltageline

VVV

,

phL EV 3

Page 13: Three Phase Circuits

Line Currents and Phase Currents:

• Current in line 1 = IR

• Current in line 2 = IY

• Current in line 3 = IB

Since IR = IY = IB = say,

Iph - the phase current

Line current IL = Iph

Power:• The total power in the circuit is the sum of the three phase powers.

Hence • Total Power =3 x phase power=

• www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

13

Page 14: Three Phase Circuits

Delta (Δ) or Mesh Connection:• Phase sequence is R, Y, B• R leads Y by 120° and Y leads B by 120°.

• The voltage between lines 1 and 2 as VRY

• The voltage between lines 2 and 3 as VYB

VRY leads VYB by 120

VYB leads VBR by 120°.

• VRY =VYB = VBR = line voltage VL

• Then, it VL = Eph

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

14

Page 15: Three Phase Circuits

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

15

Page 16: Three Phase Circuits

Line Currents and Phase Currents:

• Current in line 1 is I1 = IR – IB

• Current in line 2 is I2 = IY – IR

• Current in line 3 is I3 = IB - IY

• Current in line 1 is found by compounding IR with IB reversed

and its value is given by the diagonal of the parallelogram

• The angle between IR and IB reversed (-IB) is 60°.

• If IB = IR = IY = Iph phase current, then current in line 1 is

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

16

Page 17: Three Phase Circuits

Contd..

Since all line currents are equal in magnitude i.e., I1= I2 = I3 = IL

From Vector diagram, it should be noted that• (a) Line currents are 120o apart.• (b) Line currents are 30o behind the respective phase

currents.• (c) The angle between the line current and the corresponding

line voltage is (30 + ɸ) with the current lagging.

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

17

Page 18: Three Phase Circuits

Power:

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

18

cos3 phph IEP

Lph VEbut

3L

phII

cos3

3 LL

IVP

cos3 LL IVP

Page 19: Three Phase Circuits

 Measure of power in Three Phase Circuits: • Wattmeter is the instrument which

is used to measure power in an electrical circuit. • It consists of (i) a current coil ML’

through which the line current flows • (ii) a potential coil PV, which is connected

across the circuit.• The full voltage is applied across the potential coil and it carries

a very small current proportional to the applied voltage.• Three single phase watt-meters may be connected in each phase• The algebraic sum of their readings gives the total power

consumed by the three phase circuit. • It can be proved that only two watt-meters are sufficient to

measure power in a three phase circuit.www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

19

Page 20: Three Phase Circuits

Two Wattmeter Method:1. Balanced or Unbalanced Load:• The current coils of the two watt meters are inserted in any two

lines • The potential coils joined to the third line. • Sum of the instantaneous powers indicated by

W1 and W2 gives the instantaneous power

absorbed by the three loads L1, L2 and L3.

• Instantaneous current through W1 = IR

• Instantaneous P.D. Across W1 = VRB = ER - EB

• Power read by W1 = IR (ER – EB)

 www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

20

Page 21: Three Phase Circuits

Contd..

• Instantaneous current through W2 = IY

• Instantaneous P.D. across W2 = VYB = EY - EB

• Power read by W2 = IY (EY – EB)

 Therefore, W1 + W2= IR (ER – EB) + IY (EY – EB)

= IR ER + IY EY – EB (IR + IY)

IR + IY + IB = 0

IR + IY = -IB

= IR ER + IY EY – EB (-IB)

= IR ER + IY EY + EB IB

= P1 + P2 + P3

• Where P1 is the power absorbed by load L1, P2 that absorbed by L2 and P3 that absorbed by L3.

W1 + W2 = total power absorbedwww.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

21

Page 22: Three Phase Circuits

Balanced Load:• The load is said to be balanced, when the impedances of the

three phases are equal• The supply is said to be balanced,

if the three voltages are equal andare displaced by 120o with respect to one another.

• When a balance supply is given to a balanced load, the currents flowing through the three phases will be equal in magnitude and are displaced by 120o with respect to each other.

• Two wattmeter connections to measure power in a three phase balanced circuitas shown above figure

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

22

Page 23: Three Phase Circuits

• Let ER, EY and EB be the r.m.s. values of the three-phase voltages and IR, IY and IB be the r.m.s. values of the currents

• The currents lagging behind their phase voltages by ‘ɸ’.

• Current through wattmeter W1 = IR

• P.D. across voltage coil of W1 = VRB = ER – EB

• Now reading W1 = VRB IR cos (30° - ɸ)

• Current through wattmeter W2 = IY

• P.D. across voltage coil of W2 = VYB = EY – EB

• W2 = VYB IY cos (30° + ɸ)

• Since the load is balanced, VRB = VYB = line voltage, VL

IR = IY = line current, IL

W1 = VL IL cos (30° - ɸ) --------(1)

W2 = VL IL cos (30° + ɸ)-------(2)

•  www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

23

-EB

Page 24: Three Phase Circuits

Contd..W1 + W2 = VL IL cos (30° - ɸ) + VL IL cos (30° + ɸ)

= VL IL [cos 30° cos ɸ + sin 30° sin ɸ + cos 30° cos ɸ - sin 30° sin ɸ] = VL IL (2 cos 30° cos ɸ)

• Expression for Power Factor (p.f):W1 - W2 = VL IL cos (30° - ɸ) - VL IL cos (30° + ɸ)

= VL IL [cos 30° cos ɸ + sin 30° sin ɸ - cos 30° cos ɸ + sin 30° sin ɸ]

= VL IL (2 sin 30° sin ɸ)

= VL IL sin ɸwww.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

24

cos321 LL IVPWW

Page 25: Three Phase Circuits

www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

25

Contd..

Page 26: Three Phase Circuits

• Effect of p.f. on W1 and W2: W1 = VL IL cos (30° - ɸ) = VL IL cos 30° (ɸ = 0) = (√3/2) VL IL

W2 = VL IL cos (30° + ɸ) = VL IL cos 30° (ɸ = 0) = (√3/2) VL IL

The two wattmeter readings are positive and equal.

W1 = VL IL cos (30° - 60o) = VL IL cos (-30°)(ɸ = 60o) = (√3/2) VL IL

W2 = VL IL cos (30° + 60o) = VL IL cos 90° (ɸ = 60o) = 0One of the watt meters reads zero.

W1 = VL IL cos (30° - 90o) = VL IL cos (-60°) (ɸ = 90o) = (1/2) VL IL

W2 = VL IL cos (30° + 90o) = VL IL cos (120°) (ɸ = 90o) = - (1/2) VL IL

One of the watt-meters, reads negative (-ve). www.bookspar.com | Website for Students | VTU NOTES | QUESTION PAPERS

26

Page 27: Three Phase Circuits

Observations: • One of the watt-meters reads -ve. The pointer of this watt-

meter kicks back and hence the reading can not be taken. • Then, either the current coil connections or potential coil

connections are interchanged, pointer moves in the forward direction and the reading can be taken.

• But this reading has to be considered as -ve.Conclusion: • For p.f. lying between 0 to 0.5, one of the watt-meters, reads

negative (-ve). • When p.f. = 0.5, one wattmeter reads zero (0). • When p.f. lies between 0.5 to 1.0, both watt-meter readings

are positive (+). • When p.f. = 1, the readings of both watt-meters are equal. 