Three-Phase a.C. Circuits

download Three-Phase a.C. Circuits

of 32

Transcript of Three-Phase a.C. Circuits

  • 8/13/2019 Three-Phase a.C. Circuits

    1/32

    Three-Phase A.C. Circuits

    Chapter 3

    Learning Outcomes

    This chapter introduces the concepts and principles of the three-phase electrical supply, and the

    corresponding circuits. On completion you should be able to:

    1 Describe the reasons for, and the generation of the three-phase supply.

    2 Distinguish between star (3 and 4-wire) and delta connections.

    3 State the relative advantages of three-phase systems compared with single-phase-systems.

    4 Solve three-phase circuits in terms of phase and line quantities, and the power developed in

    three-phase balanced loads.

    5 Measure power dissipation in both balanced and unbalanced three-phase loads, using the

    1, 2 and 3-wattmeter methods, and hence determine load power factor.

    6Calculate the neutral current in a simple unbalanced 4-wire system.

    85

    3.1 Generation of a Three-Phase Supply

    In order to understand the reasons for, and the method of generating

    a three-phase supply, let us firstly consider the generation of a single-phase supply. Alternating voltage is provided by an a.c. generator,

    more commonly called an alternator.The basic principle was outlined

    in Fundamental Electrical and Electronic Principles,Chapter 5.

    It was shown that when a coil of wire, wound on to a rectangular

    former, is rotated in a magnetic field, an alternating (sinusoidal)

    voltage is induced into the coil. You should also be aware that for

    electromagnetic induction to take place, it is the relativemovement

    between conductor and magnetic flux that matters. Thus, it matters not

    whether the field is static and the conductor moves, or vice versa.

    For a practical alternator it is found to be more convenient to rotate the

    magnetic field, and to keep the conductors (coil or winding) stationary.

  • 8/13/2019 Three-Phase a.C. Circuits

    2/32

    86 Further Electrical and Electronic Principles

    In any rotating a.c. machine, the rotating part is called the rotor, and

    the stationary part is called the stator. Thus, in an alternator, the field

    system is contained in the rotor. The winding in which the emf is

    generated is contained in the stator. The reasons for this are as follows:

    In this context, the term field refers to the magnetic field. This field is normally produced

    by passing d.c. current through the rotor winding. Since the winding is rotated, the

    current is passed to it via copper slip-rings on the shaft. The external d.c. supply is

    connected to the slip-rings by a pair of carbon brushes.

    (a) When large voltages are generated, heavy insulation is necessary.

    If this extra mass has to be rotated, the driving device has to

    develop extra power. This will then reduce the overall efficiency

    of the machine. Incorporating the winding in the stator allows the

    insulation to be as heavy as necessary, without adversely affecting

    the efficiency.

    (b) The contact resistance between the brushes and slip-rings is very

    small. However, if the alternator provided high current output (in

    hundreds of ampere), theI2Rpower loss would be significant. The

    d.c. current (excitation current) for the field system is normally

    only a few amps or tens of amps. Thus, supplying the field current

    via the slip-rings produces minimal power loss. The stator winding

    is simply connected to terminals on the outside of the stator casing.

    (c) For very small alternators, the rotor would contain permanent

    magnets to provide the rotating field system. This then altogether

    eliminates the need for any slip-rings. This arrangement is referred

    to as a brushless machine.

    The basic construction for a single-phase alternator is illustrated in

    Fig. 3.1. The conductors of the stator winding are placed in slots

    G

    J

    L

    B

    D

    F

    H

    S

    N

    rotor

    stator

    K

    M

    A

    C

    E

    Fig. 3.1

  • 8/13/2019 Three-Phase a.C. Circuits

    3/32

    Three-Phase A.C. Circuits 87

    around the inner periphery of the stator. The two ends of this winding

    are then led out to a terminal block on the casing. The rotor winding

    is also mounted in slots, around the circumference of the rotor. This

    figure is used to illustrate the principle. A practical machine would

    have many more conductors and slots.

    Since the conductors of the stator winding are spread around the whole

    of the slots, it is known as a distributed winding. As the rotor field

    sweeps past these conductors an emf is induced in each of them in turn.

    These individual emfs reach their maximum values only at the instant

    that the rotating field cuts them at 90. Also, since the slots have an

    angular displacement between them, then the conductor emfs will be

    out of phase with each other by this same angle. In Fig. 3.1 there are a

    total of twelve conductors, so this phase difference must be 30. The

    total stator winding emf will therefore not be the arithmeticsum of the

    conductor emfs, but will be thephasorsum, as shown in Fig. 3.2. Theratio of the phasor sum to the arithmetic sum is called the distribution

    factor. For the case shown (a fully distributed winding) the distribution

    factor is 0.644.

    30

    E

    F

    GH

    L

    K

    M

    JD

    CB

    A

    AB, CD etc. are conductor (coil) emfs.AM is the phasor sum

    Fig. 3.2

    Now, if all of the stator conductors could be placed into a single pair

    of slots, opposite to each other, then the induced emfs would all bein phase. Hence the phasor and arithmetic sums would be the same,

    yielding a distribution factor of unity. This is not a practical solution.

    However, if the conductors are concentrated so as to occupy only one

    third of the available stator slots, then the distribution factor becomes

    0.966. In a practical single-phase alternator, the stator winding is

    distributed over two thirds of the slots.

    Let us return to the option of using only one third of the slots. We will

    now have the space to put two more identical windings into the stator.

    Each of the three windings could be kept electrically separate, with

    their own pairs of terminals. We would then have three separate single-

    phase alternators in the same space as the original. Each of these would

  • 8/13/2019 Three-Phase a.C. Circuits

    4/32

    88 Further Electrical and Electronic Principles

    also have a good distribution factor of 0.966. The three winding emfs

    will of course be mutually out of phase with each other by 120, since

    each whole winding will occupy 120 of stator space. What we now

    have is the basis of a three-phase alternator.

    The term three-phase alternator is in some ways slightly misleading.What we have, in effect, are three identical single-phase alternators

    contained in the one machine. The three stator windings are brought

    out to their own separate pairs of terminals on the stator casing. These

    stator windings are referred to as phase windings, or phases. They

    are identified by the colours red, yellow and blue. Thus we have the

    red, yellow and blue phases. The circuit representation for the stator

    winding of such a machine is shown in Fig. 3.3. In this figure, the three

    phase windings are shown connected, each one to its own separate

    load. This arrangement is known as a three-phase, six-wire system.

    However, three-phase alternators are rarely connected in this way.

    LOAD 2

    LOAD 1

    LOAD 3

    Fig. 3.3

    voltageVR

    0180 360 (deg)

    VY VB

    Fig. 3.4

    Since the three generated voltages are sinewaves of the same

    frequency, mutually out-of-phase by 120, then they may be

    represented both on a waveform diagram using the same angular or

    time axis, and as phasors. The corresponding waveform and phasor

    diagrams are shown in Figs. 3.4 and 3.5 respectively. In either case,

  • 8/13/2019 Three-Phase a.C. Circuits

    5/32

    Three-Phase A.C. Circuits 89

    we need to select a reference phasor. By convention, the reference is

    always taken to be the red phase voltage. The yellow phase lags the

    red by 120, and the blue lags the red by 240 (or, if you prefer, leads

    the red by 120). The windings are arranged so that when the rotor is

    driven in the chosen direction, the phase sequence is red, yellow, blue.

    If, for any reason, the rotor was driven in the opposite direction, then

    the phase sequence would be reversed, i.e. red, blue, yellow. We shall

    assume that the normal sequence of R, Y, B applies at all times.

    It may be seen from the waveform diagram that at any point along the

    horizontal axis, the sum of the three voltages is zero. This fact becomes

    even more apparent if the phasor diagram is redrawn as in Fig. 3.6. In

    this diagram, the three phasors have been treated as any other vector

    quantity. The sum of the vectors may be determined by drawing themto scale, as in Fig. 3.6, and the resultant found by measuring the

    distance and angle from the beginning point of the first vector to the

    arrowhead of the last one. If, as in Fig. 3.6, the first and last vectors

    meet in a closed figure, the resultant must be zero.

    VR

    VY

    VB

    Fig. 3.5

    VR

    VB VY

    Fig. 3.6

    3.2 Three-Phase, Four-Wire System

    It is not necessary to have six wires from the three phase windings to

    the three loads, provided there is a common return line. Each winding

    will have a start (S) and a finish (F) end. The common connection

    mentioned above is achieved by connecting the corresponding ends

  • 8/13/2019 Three-Phase a.C. Circuits

    6/32

    90 Further Electrical and Electronic Principles

    of the three phases together. For example, either the three F ends or

    the three S ends are commoned. This form of connection is shown

    in Fig. 3.7, and is known as a staror Y connection. With the resulting

    4-wire system, the three loads also are connected in star configuration.

    The three outer wires are called the lines,and the common wire in the

    centre is called the neutral.

    S

    F

    S

    S

    F

    F

    Fig. 3.7

    If the three loads were identical in every way (same impedance and

    phase angle), then the currents flowing in the three lines would be

    identical. If the waveform and/or phasor diagrams for these currents

    were drawn, they would be identical in form to Figs. 3.4 and 3.5. These

    three currents meet at the star point of the load. The resultant currentreturning down the neutral wire would therefore be zero. The load in

    this case is known as a balanced load, and the neutral is not strictly

    necessary. However it is difficult, in practice, to ensure that each of

    the three loads are exactly balanced. For this reason the neutral is left

    in place. Also, since it has to carry only the relatively small out-of-

    balance current, it is made half the cross-sectional area of the lines.

    Let us now consider one of the advantages of this system compared

    with both a single-phase system, and the three-phase 6-wire system.

    Suppose that three identical loads are to be supplied with 200 A each.

    The two lines from a single-phase alternator would have to carry the

    total 600 A required. If a 3-phase, 6-wire system was used, then each

    line would have to carry only 200 A. Thus, the conductor csa would

    only need to be 1/3 that for the single-phase system, but of course,

    being six lines would entail using the same total amount of conductor

    material. If a 4-wire, 3-phase system is used there will be a saving on

    conductor costs in the ratio of 3.5:6 (the 0.5 being due to the neutral).

    If the power has to be sent over long transmission lines, such as the

    National Grid System, then the 3-phase, 4-wire system yields an

    enormous saving in cable costs. This is one of the reasons why the

    power generating companies use three-phase, star-connected generators

    to supply the grid system.

  • 8/13/2019 Three-Phase a.C. Circuits

    7/32

    Three-Phase A.C. Circuits 91

    3.3 Relationship between Line and Phase Quantities in aStar-connected System

    Consider Fig. 3.8, which represents the stator of a 3-phase alternator

    connected to a 3-phase balanced load. The voltage generated by eachof the three phases is developed between the appropriate line and the

    neutral. These are called the phase voltages, and may be referred to in

    general terms as Vph, or specifically as VRN, VYNand VBNrespectively.

    However, there will also be a difference of potential between any pair

    of lines. This is called a line voltage, which may be generally referred

    to as VL, or specifically as VRY, VYBarid VBRrespectively.

    IL

    VLIN

    IL

    Vph

    Vph

    Vph

    VL

    VL

    Iph

    Iph

    Iph

    R

    N

    B

    Y

    Fig. 3.8

    VYN

    VBN

    VYN C

    B

    0 A

    VRN

    30

    30

    Fig. 3.9

    A line voltage is thephasor differencebetween the appropriate pair

    of phase voltages. Thus, VRYis the phasor difference between VRN

    and VYN. In terms of a phasor diagram, the simplest way to subtract

    one phasor from another is to reverse one of them, and then find the

    resulting phasor sum. This is, mathematically, the same process as

    saying that a b a (b).The corresponding phasor diagram is

    shown in Fig. 3.9.

  • 8/13/2019 Three-Phase a.C. Circuits

    8/32

    92 Further Electrical and Electronic Principles

    Note:If VYNis reversed, it is denoted either as VYNor as VNY.We

    shall use the first of these.

    The phasor difference between VRNand VYNis simply the phasor sum

    of VRN (VYN). Geometrically this is obtained by completing the

    parallelogram as shown in Fig. 3.9. This parallelogram consists of twoisosceles triangles, such as OCA. Another property of a parallelogram is

    that its diagonals bisect each other at right angles. Thus, triangle OCA

    consists of two equal right-angled triangles, OAB and ABC. This is

    illustrated in Fig. 3.10. Since triangle OAB is a 30, 60, 90 triangle,

    then the ratios of its sides AB:OA:OB will be 1:2:3respectively.

    B

    30 60

    O A

    C

    Fig. 3.10

    Hence,OB

    OA

    so OBOA

    but OC OB OAand since OC ,

    3

    2

    3

    2

    2 3

    .

    .VRY and OA

    then

    V

    V V

    RN

    RY RN3

    Using the same technique, it can be shown that:

    V V V V YB YN BR BN 3 3and

    Thus, in star configuration, V VL ph 3 (3.1)

    The complete phasor diagram for the line and phase voltages for a star

    connection is shown in Fig. 3.11. Also, considering the circuit diagram

    of Fig. 3.8, the line and phase currents must be the same.

    Hence, in star configuration,I IL ph (3.2)

    We now have another advantage of a 3-phase system compared with

    single-phase. The star-connected system provides two alternative

    voltage outputs from a single machine. For this reason, the stators

    of all alternators used in electricity power stations are connected in

    star configuration. These machines normally generate a line voltage

  • 8/13/2019 Three-Phase a.C. Circuits

    9/32

    Three-Phase A.C. Circuits 93

    of about 25 kV. By means of transformers, this voltage is stepped up

    to 400 kV for long distance transmission over the National Grid. For

    more localised distribution, transformers are used to step down the

    line voltage to 132 kV, 33 kV, 11 kV, and 415 V. The last three of these

    voltages are supplied to various industrial users. The phase voltage

    derived from the 415 V lines is 240 V, and is used to supply both

    commercial premises and households.

    Worked Example 3.1

    Q A 415 V, 50 Hz, 3-phase supply is connected to a star-connected balanced load. Each phase of the loadconsists of a resistance of 25 and inductance 0.1H, connected in series. Calculate (a) phase voltage,

    (b) the line current drawn from the supply, and (c) the power dissipated.

    A

    Whenever a three-phase supply is specied, the voltage quoted is always the

    line voltage. Also, since we are dealing with a balanced load, then it is necessary

    only to calculate values for one phase of the load. The gures for the other two

    phases and lines will be identical to these.

    VL 415 V; f 50 Hz; Rph 25 ; Lph 0.1H

    IL Iph

    VL 0.1H

    Vph

    25

    Fig. 3.12

    VBN

    VRN

    VRYVBR

    VYN

    VYB

    30

    30

    30

    Fig. 3.11

  • 8/13/2019 Three-Phase a.C. Circuits

    10/32

    94 Further Electrical and Electronic Principles

    (a)

    VV

    V

    phL

    ph

    3

    4 5

    3

    240

    1

    so V Ans

    (b) Since it is possible to determine the impedance of a phase of the load, and

    we now know the phase voltage, then the phase current may be calculated:

    X fL

    X

    Z R X

    L

    L

    ph ph L

    2 2 50 0

    3 42

    25 32 2 2

    ohm

    hence

    ohm

    .

    .

    1

    1

    11

    1

    1

    .

    .

    .

    .

    42

    40 5

    240

    40 5

    5 98

    2

    Z

    V

    Z

    ph

    phph

    ph

    ph

    I

    I

    amp

    so A

    In a star-connected circuit,ILIPhthereforeIL 5.98 A Ans

    The power in one phase, wattP R

    P

    ph ph ph

    ph

    I2

    25 98 25

    893 2

    .

    . 99 W

    and since there are three phases, then the total power is:

    P P

    P

    ph

    3 3 893 29

    2 68

    watt

    hence kW

    .

    . Ans

    3.4 Delta or Mesh Connection

    If the start end of one winding is connected to the finish end of the

    next, and so on until all three windings are interconnected, the result

    is the delta or mesh connection. This connection is shown in Fig. 3.13.

    The delta connection is not reserved for machine windings only, since

    a 3-phase load may also be connected in this way.

    IL

    IL

    VL

    Iph

    Iph Iph

    IL

    SF

    F

    F

    S

    S

    Fig. 3.13

  • 8/13/2019 Three-Phase a.C. Circuits

    11/32

    Three-Phase A.C. Circuits 95

    3.5 Relationship between Line and Phase Quantities in aDelta-connected System

    It is apparent from Fig. 3.13 that each pair of lines is connected across

    a phase winding. Thus, for the delta connection:

    V VL ph (3.3)

    It is also apparent that the current along each line is the phasor

    difference of a pair of phase currents. The three phase currents are

    mutually displaced by 120, and the phasor diagram for these is shown

    in Fig. 3.14. Using exactly the same geometrical technique as that for

    the phase and line voltages in the star connection, it can be shown that:

    I IL ph 3 (3.4)

    IB(ph)

    IY(ph)

    IR(ph)120

    120

    120

    Fig. 3.14

    The phasor diagram for the phase and line currents in delta connection

    is as in Fig. 3.15. Note that the provision of a neutral wire is not

    applicable with a delta connection. However, provided that the load

    IL

    IL

    IL

    Iph

    Iph

    Iph

    30

    30

    30

    Fig. 3.15

  • 8/13/2019 Three-Phase a.C. Circuits

    12/32

    96 Further Electrical and Electronic Principles

    is balanced, there is no requirement for one. Under balanced load

    conditions the three phase currents will be equal, as will be the three

    line currents. If the load is unbalanced, then these equalities do not

    exist, and each phase or line current would have to be calculated

    separately. This technique is beyond the scope of the syllabus you are

    now studying.

    Worked Example 3.2

    Q A balanced load of phase impedance 120 is connected in delta. When this load is connected to a600 V, 50 Hz, 3-phase supply, determine (a) the phase current, and (b) the line current drawn.

    A

    Zph 120 ; VL 600 V; f 50 HzThe circuit diagram is shown in Fig. 3.16.

    IL

    Iph

    VL Vph600V

    Z120

    Fig. 3.16

    (a)

    In delta, V

    amp

    so, A

    V V

    V

    Z

    ph L

    phph

    ph

    ph

    600

    600

    20

    5

    I

    I

    1

    Ans

    (b)

    in delta, amp

    therefore A

    I I

    I

    L ph

    L

    3 3 5

    8 66. Ans

    3.6 Power Dissipation in Star and Delta-connected Loads

    We have seen in Example 3.1 that the power in a 3-phase balanced

    load is obtained by multiplying the power in one phase by 3. In many

    practical situations, it is more convenient to work with line quantities.

    PphVphIphcos watt

    where cos is the phase power factor.

    total power,

    cos watt.............

    P P

    V I

    ph

    ph ph

    3

    3 1 [ ]

  • 8/13/2019 Three-Phase a.C. Circuits

    13/32

    Three-Phase A.C. Circuits 97

    Considering a STAR-connected load,

    VV

    I IphL

    ph L 3

    , and

    Substituting for VphandIphin eqn [1]:

    PV

    IL L 33

    cos

    therefore cos wattP V IL L 3 (3.5)

    For a delta-connected load,

    V V I Iph L phph

    and3

    and substituting these values into eqn [1] will yield the same result

    as shown in (3.5) above. Thus, the equationfor determining power

    dissipation, in both star and delta-connected loads is exactly the

    same. However, the valueof power dissipated by a given load when

    connected in star is not the same as when it is connected in delta. This

    is demonstrated in the following example.

    Worked Example 3.3

    Q A balanced load of phase impedance 100 and power factor 0.8 is connected (a) in star, and (b) indelta, to a 400 V, 3-phase supply. Calculate the power dissipation in each case.

    A

    Zph 100 ; cos 0.8; VL 400 V

    (a) the circuit diagram is shown in Fig. 3.17

    VL400V

    Z100Vph

    IL Iph

    Fig. 3.17

  • 8/13/2019 Three-Phase a.C. Circuits

    14/32

    98 Further Electrical and Electronic Principles

    VV

    V

    V

    Z

    phL

    ph

    L phph

    ph

    L

    3

    400

    3

    23

    23

    00

    volt

    so V

    amp

    and

    1

    1

    1I I

    I

    2 3

    3 3 400 2 3 0 8

    28

    .

    . .

    .

    1

    1

    1

    A

    cos watt

    therefore kW

    P V

    P

    L LI

    Ans

    (b) The circuit diagram is shown in Fig. 3.18.

    IL

    Iph

    VL

    Vph400V

    Z100

    Fig. 3.18

    V V

    V

    Z

    ph L

    phph

    ph

    ph

    L ph

    400

    400

    00

    4

    3 3 4

    V

    amp

    so A

    but

    so

    I

    I

    I I

    1

    A

    cos watt

    therefore

    I

    I

    L

    L LP V

    P

    6 93

    3 3 400 6 93 0 8

    3 8

    .

    . .

    .

    44 kW Ans

    Comparing the two answers for the power dissipation in the above

    example, it may be seen that:

    Power in a delta-connected load is

    that when i

    three times

    tt is connected in star configuration. (3.6)

    Worked Example 3.4

    Q A balanced star-connected load is fed from a 400 V, 50 Hz, three-phase supply. The resistance in eachphase of the load is 10 and the load draws a total power of 15 kW. Calculate (a) the line current

    drawn, (b) the load power factor, and (c) the load inductance.

    A

    VL 400 V; f 50 Hz; R 10 ; P 15 000 W

  • 8/13/2019 Three-Phase a.C. Circuits

    15/32

  • 8/13/2019 Three-Phase a.C. Circuits

    16/32

    100 Further Electrical and Electronic Principles

    Worked Example 3.5

    Q A balanced delta-connected load takes a phase current of 15 A at a power factor of 0.7 lagging whenconnected to a 115 V, 50 Hz, three-phase supply. Calculate (a) the power drawn from the supply, and

    (b) the resistance in each phase of the load.

    A

    VL Vph 115 V; f 50 Hz;Iph 15 A; cos 0.7

    (a) I I

    I

    I

    L ph

    L

    L LP V

    3 3 5

    25 98

    3 3 5 25 98 0

    amp

    A

    cos watt

    1

    11

    .

    . . 77

    3622 5so WP . Ans

    (b) PP

    P R

    RP

    ph

    ph ph

    ph

    ph

    3

    3622 5

    3207 5

    2

    2

    ..1

    1

    W

    and watt

    so ohm

    I

    I

    2207 5

    5

    5 37

    2

    .

    .

    1

    R Ans

    3.7 Star/Delta Supplies and LoadsAs explained in Section 3.3, the distribution of 3-phase supplies is

    normally at a much higher line voltage than that required for many

    users. Hence, 3-phase transformers are used to step the voltage down

    to the appropriate value. A three-phase transformer is basically three

    single-phase transformers interconnected. The three primary windings

    may be connected either in star or delta, as can the three secondary

    windings. Similarly, the load connected to the transformer secondary

    windings may be connected in either configuration. One important

    point to bear in mind is that the transformation ratio (voltage or turnsratio) refers to the ratio between the primaryphaseto the secondary

    phasewinding. The method of solution of this type of problem is

    illustrated in the following worked example.

    115 V

    VL Vph

    R

    L

    IL

    Iph15 A

    Fig. 3.21

  • 8/13/2019 Three-Phase a.C. Circuits

    17/32

    Three-Phase A.C. Circuits 101

    Worked Example 3.6

    Q Figure 3.22 shows a balanced, star-connected load of phase impedance 25 and power factor0.75, supplied from the delta-connected secondary of a 3-phase transformer. The turns ratio of the

    transformer is 20:1, and the star-connected primary is supplied at 11kV. Determine (a) the voltages

    V2, V3and V4, (b) the currents I1, I2, and I3, and (c) the power drawn from the supply.

    I1

    I2

    I3

    V3

    V4 Z25

    cos0.75V2

    20:1

    V111kV

    Fig. 3.22

    A

    V1 11000 V; Np/Ns 20/1;Zph 25 ; cos 0.75

    (a)

    VV

    V

    V

    V

    N

    N

    VN V

    N

    s

    p

    s

    p

    21

    2

    3

    2

    32

    3

    11000

    3

    6 351

    635

    kV

    so volt

    . Ans

    11

    20

    317 45

    3

    317 45

    3

    183 3

    3

    43

    4

    hence V

    and V

    V

    VV

    V

    .

    .

    .

    Ans

    Ans

    (b) In order to calculate the currents, we shall have to start with the load, andwork back through the circuit to the primary of the transformer:

    I

    I

    II

    I

    I

    34

    3

    23

    2

    83 3

    25

    7 33

    3

    7 33

    3

    4 23

    V

    Zphamp

    A

    A

    1

    1

    .

    .

    .

    .

    Ans

    Ans

    II

    II

    I

    2

    2 4 23

    20

    0 2 2

    N

    N

    N

    N

    s

    p

    s

    p

    so amp

    hence A

    1

    1 1

    .

    . Ans

  • 8/13/2019 Three-Phase a.C. Circuits

    18/32

    102 Further Electrical and Electronic Principles

    (c) P V

    P

    3

    3 0 0 2 2 0 75

    3 02

    3

    cos watt

    therefore kW

    1 1

    11 1 1

    I

    . .

    . AAns

    Worked Example 3.7

    Q The star-connected stator of a three-phase, 50 Hz alternator supplies a balanced delta-connectedload. Each phase of the load consists of a coil of resistance 15 and inductance 36 mH, and the phase

    voltage generated by the alternator is 231V. Calculate (a) the phase and line currents, (b) the load

    power factor, and (c) the power delivered to the load.

    A

    f 50 Hz; R 15 ; L 36 mH; Vph 231V

    R

    L

    I2I1

    V2

    36 mH

    15

    V1

    231 V

    Fig. 3.23

    (a)

    For the alternator:

    V V

    V V V

    V

    ph

    L ph

    ph L

    1

    1

    1

    23 V

    V

    2

    2

    3

    400

    I I I

    For the load:

    V V V

    X fL

    X

    Z R X

    L ph

    L

    L

    ph L

    2

    3

    2

    2 00 36 0

    3

    400 V

    ohm

    1 1

    11 1.

    22 2 2

    2

    2

    5 38 79

    400

    8 79

    2

    ohm

    amp

    1 11 11

    1

    1

    ..

    .

    Z

    V

    Z

    ph

    phph

    ph

    I I

    I ..

    .

    .

    29

    3 3 2 29

    36 88

    2

    A

    A

    Ans

    Ans

    I I I

    I

    L

    1

    1

    1

    (b) p.f. cos

    p.f. lagging

    R

    Z

    11

    58 79

    0 8

    .

    . Ans

  • 8/13/2019 Three-Phase a.C. Circuits

    19/32

    Three-Phase A.C. Circuits 103

    (c) P V

    PL L

    3 3 400 36 88 0 8

    20 4

    I cos watt

    kW

    Alternativel

    . .

    . Ans

    yy, watt

    kW

    P P R

    P

    ph

    3 3

    3 2 29 5

    20 4

    22

    2

    I

    1 1.

    . Ans

    3.8 Measurement of Three-phase Power

    In an a.c. circuit the true power may only be measured directly by

    means of a wattmeter. The principle of operation of this instrument

    is described in Fundamental Electrical and Electronic Principles,

    Chapter 5. As a brief reminder, the instrument has a fixed coil through

    which the load current flows, and a moving voltage coil (or pressure

    coil) connected in parallel with the load. The deflection of the pointer,carried by the moving coil, automatically takes into account the

    phase angle (or power factor) of the load. Thus the wattmeter reading

    indicates the true power, PVIcos watt.

    If a three-phase load is balanced, then it is necessary only to measure

    the power taken by one phase. The total power of the load is then

    obtained by multiplying this figure by three. This technique can be

    very simply applied to a balanced, star-connected system, where the

    star point and/or the neutral line are easily accessible. This is illustrated

    in Fig. 3.24.

    R

    N

    B

    Y

    W1

    Fig. 3.24

    In the situation where the star point is not accessible, then an artificial

    star point needs to be created. This is illustrated in Fig. 3.25, where

    the value of the two additional resistors is equal to the resistance of the

    wattmeter voltage coil.

    In the case of an unbalanced star-connected load, one or other of the

    above procedures would have to be repeated for each phase in turn.

    The total power P P1 P2 P3, where P1, P2and P3represent the

    three separate readings.

  • 8/13/2019 Three-Phase a.C. Circuits

    20/32

    104 Further Electrical and Electronic Principles

    For a delta-connected load, the procedure is not quite so simple.

    The reason is that the phase current is not the same as the line current.Thus, if possible, one of the phases must be disconnected to allow

    the connection of the wattmeter current coil. This is shown in

    Fig. 3.26. Again, if the load was unbalanced, this process would have

    to be repeated for each phase.

    W1R

    B

    Y

    R R

    Fig. 3.25

    W1R

    B

    Y

    Fig. 3.26

    3.9 The Two-Wattmeter Method

    The measurement of three-phase power using the above methods can

    be very awkward and time-consuming. In practical circuits, the power

    is usually measured by using two wattmeters simultaneously, as shown

    in Fig. 3.27.

    The advantages of this method are:

    (a) Access to the star point is not required.

    (b) The power dissipated in both balanced and unbalanced loads is

    obtained, without any modification to the connections.

    (c) For balanced loads, the power factor may be determined.

  • 8/13/2019 Three-Phase a.C. Circuits

    21/32

    Three-Phase A.C. Circuits 105

    Considering Fig. 3.27, the following statements apply:

    Instantaneous power for watt

    and for ,1

    2 2

    W p v i

    W p vRB R

    YB

    , 1

    ii

    p p

    v i v i

    Y

    RB R YB Y

    watt

    total instantaneous power

    ]

    1 2

    1[

    Now, any line voltage is the phasor difference between the appropriate

    pair of phase voltages, hence:

    v v v v v vRB RN BN YB YN BN and

    and substituting these into eqn [1] yields:

    p p i v v i v v

    v i v i v i i

    i

    R RN BN Y YN BN

    RN R YN Y BN R Y

    1 2

    ( ) ( )

    ( )

    but, RR Y Bi i

    i.e. the phasor sum of three equal currents is zero.

    therefore p p v i v i v iRN R YN Y BN B1 2

    The instantaneous sum of the powers measured by the two wattmeters

    is equal to the sum of instantaneous power in the three phases.

    Hence, total power,

    P P P P P PR Y B 1 2 watt (3.7)

    Consider now the phasor diagram for a resistive-inductive balanced

    load, with the two wattmeters connected as in Fig. 3.27. This phasor

    diagram appears as Fig. 3.28, below.

    W1

    W2

    IB

    IY

    VRB

    VYB

    IRR

    B

    Y

    Fig. 3.27

  • 8/13/2019 Three-Phase a.C. Circuits

    22/32

    106 Further Electrical and Electronic Principles

    The power indicated by W1,

    P V IL L1 cos (30 ) (3.8)

    and that for W2,

    P V IL L2 cos (30 ) (3.9)

    From these results, and using Fig. 3.29,the following points should be

    noted:

    IB

    VBRVBN VR

    VRN

    VRBVYN

    VYB

    IY

    IR(30)

    (30)

    Fig. 3.28

    wattmeterreadings

    90

    30 30 90 150 (30

    )

    Fig. 3.29

    1 If the load p.f. 0.5 (i.e. 60); both meters will give a positive

    reading.

    2 If the load p.f. 0.5 (i.e. 60); W1indicates the total power,

    and W2

    indicates zero.

    3 If the load p.f. 0.5 (i.e. 60); W2attempts to indicate a

    negative reading. In this case, the connections to the voltage coil

  • 8/13/2019 Three-Phase a.C. Circuits

    23/32

    Three-Phase A.C. Circuits 107

    of W2need to be reversed, and the resulting reading recorded as a

    negative value. Under these circumstances, the total load power will

    be P P1P2.

    4 The load power factor may be determined from the two wattmeter

    readings from the equation:

    tan 1 2 1

    2 1

    3P P

    P P

    (3.10)

    hence, power factor, cos can be determined.

    Worked Example 3.8

    Q The power in a 3-phase balanced load was measured, using the two-wattmeter method. The recordedreadings were 3.2 kW and 5 kW respectively. Determine the load power and power factor .

    A

    P P

    P P P

    P

    1

    1

    3 2 5

    3 2

    8 2

    2

    2

    .

    .

    .

    kW; kW

    watt ( 5) kW

    therefore, kW AAns

    tan

    tan

    1 1

    1

    1

    3

    35 3 2

    5 3 2

    2

    2

    P P

    P P

    .

    .

    hence,

    and p.f. cos

    20 82

    0 935

    .

    . Ans

    Worked Example 3.9

    Q A 3-phase balanced load takes a line current of 24 A at a lagging power factor of 0.42, when connectedto a 415 V, 50 Hz supply. If the power dissipation is measured using the two-wattmeter method,

    determine the two wattmeter readings, and the value of power dissipated. Comment on the results.

    A

    IL 24 A; cos 0.42; VL 415 V

    cos

    cos (30 ) watt

    cos (

    1

    1

    1

    1

    0 42 65 7

    4 5 24

    . .

    P VL LI

    335 7

    8 42

    302

    .

    .

    1

    11

    )

    therefore, kW

    cos ( ) watt

    P

    P VL L

    Ans

    I

    44 5 24 95 7

    896 72

    2

    1 1

    1

    cos ( )

    therefore, W

    watt

    .

    .P

    P P P

    Ans

    88 42 896 7

    7 244

    1

    ( )

    hence, kW

    .

    .P Ans

    To obtain the negative reading on W2, the connections to its voltage coil must

    have been reversed.

  • 8/13/2019 Three-Phase a.C. Circuits

    24/32

    108 Further Electrical and Electronic Principles

    Worked Example 3.10

    Q A delta-connected load has a phase impedance of 100 at a phase angle of 55, and is connected to a415 V three-phase supply. The total power consumed is measured using the two-wattmeter method.

    Determine the readings on the two meters and hence calculate the power consumed.

    A

    Zph 100 ; 55; VL 415 V Vph

    VL 415V

    VL 415V

    IL

    ILW1

    W2

    Zph100

    Fig. 3.30

    I

    I I

    I

    phph

    ph

    L ph

    L L

    V

    Z

    P V

    amp A

    A

    c

    4 5

    004 5

    3 3 4 5 7 9

    1

    11

    1 1

    1

    .

    . .

    oos ( ) watt cos

    kW

    cos

    30 4 5 7 9 25

    2 704

    2

    1 1

    1

    .

    .P

    P VL L

    Ans

    I ( ) watt cos 85

    W

    watt

    30 4 5 7 9

    260

    270

    2

    2

    1 1

    1

    .

    P

    P P P

    Ans

    44 260

    2 964

    P . kW Ans

    3.10 Neutral Current in an Unbalanced Three-phase Load

    We have seen that the neutral current for a balanced load is zero. This is

    because the phasor sum of three equal currents, mutually displaced by

    120, is zero. If the load is unbalanced, then the three line (and phase)

    currents will be unequal. In this case, the neutral has to carry the resulting

    out-of-balance current. This current is simply obtained by calculating the

    phasor sum of the line currents. The technique is basically the same as

    that used previously, by resolving the phasors into horizontal and vertical

    components, and applying Pythagoras theorem. The only additional fact

    to bear in mind is that both horizontal and vertical components can have

    negative values. This is illustrated by the following example.

  • 8/13/2019 Three-Phase a.C. Circuits

    25/32

    Three-Phase A.C. Circuits 109

    Worked Example 3.11

    Q An unbalanced, star-connected load is supplied from a 3-phase, 415 V source. The three phase loadsare purely resistive. These loads are 25 , 30 and 40 , and are connected in the red, yellow and

    blue phases respectively. Determine the value of the neutral current, and its phase angle relative to

    the red phase current.

    A

    VL 415 V; RR 25 ; RY 30 ; RB 40 The circuit diagram is shown in Fig. 3.31.

    Vph

    VL

    IR

    IY

    IB

    IN

    R

    Y

    B

    30

    40

    25

    Fig. 3.31

    V

    V

    V

    R

    V

    R

    V

    R

    ph

    L

    Rph

    RY

    ph

    YB

    ph

    B

    3

    4 5

    3 240volt V

    amp; amp;

    1

    I I I amp

    A A A

    240

    25

    240

    30

    240

    40

    9 6 8 6I I IR Y B.

    The corresponding phasor diagrams are shown in Fig. 3.32.

    IB

    IY

    IR

    INV.C.

    H.C.

    60

    60

    Fig. 3.32

  • 8/13/2019 Three-Phase a.C. Circuits

    26/32

    110 Further Electrical and Electronic Principles

    Horizontal components, H.C. cos cos

    (

    I I IR Y B60 60

    9 6. 88 0 5 6 0 5

    2 6

    . .

    .

    ) ( )

    so, H.C. A

    Vertical components, V.C. IB ssin sin

    ( ) ( )

    so V.C. A

    The

    60 60

    6 0 866 8 0 866

    732

    IY

    . .

    .1

    neutral current, V.C. H.C. amp

    hence,

    I

    I

    N

    2 2

    2 2732 2 61. .

    NN

    3 24

    732

    2 6

    33

    .

    .

    .

    .

    1

    11 1

    A

    tanV.C.

    H.C.tan

    hence,

    Ans

    667relative toIR Ans

    3.11 Advantages of Three-phase Systems

    In previous sections, some of the advantages of three-phase

    systems, compared with single-phase systems, have been outlined.

    These advantages, together with others not yet described, are listed

    below. The advantages may be split into two distinct groups: those

    concerned with the generation and distribution of power, and those

    concerning a.c. motors. The last four of the advantages listed refer

    to the second group, and their significance will be appreciatedwhen you have completed Chapter 5, which deals with a.c.

    machines.

    1 The whole of the stator of a three-phase machine is utilised.

    A single phase alternator utilises only two thirds of the stator

    slots.

    2 A three-phase alternator has a better distribution factor.

    3 A three-phase, four-wire system provides considerable savings

    in cable costs, for the distribution of an equivalent amount of

    power.

    4 A three-phase, four-wire system provides alternative voltages for

    industrial and domestic users.

    5 For a given machine frame size, the power output from a

    three-phase machine is greater than that from a single-phase

    machine.

    6 A three-phase supply produces a rotating magnetic field; whereas

    a single-phase supply produces only a pulsating field.

    7 Three-phase motors are inherently self-starting; whereas single-phase

    motors are not.

    8 The torque produced by a three-phase motor is smooth; whereas

    that produced by a single-phase motor is pulsating.

  • 8/13/2019 Three-Phase a.C. Circuits

    27/32

    111

    Summary of Equations

    Phase and line quantities: In star,ILIph;VL 3Vph

    In delta,VL Vph; IL 3Iph

    Power dissipation: P V IL L 3 cos watt

    P P V I I Rph ph ph ph ph 3 3 32cos watt

    and for the same load, P(delta) 3 P(star)

    Power measurement: For two wattmeter method: P P1 P2watt

    Load phase angle, tan

    1 2 1

    2 1

    3 P P

    P P

    Three-Phase A.C. Circuits

  • 8/13/2019 Three-Phase a.C. Circuits

    28/32

    112 Fundamental Electrical and Electronic PrinciplesFurther Electrical and Electronic Prinicples

    1 A three-phase load is connected in star to a

    400 V, 50 Hz supply. Each phase of the load

    consists of a coil, having inductance 0.2 H and

    resistance 40 . Calculate the line current.

    2 If the load specied in Question 1above is now

    connected in delta, determine the values for

    phase and line currents.

    3 A star-connected alternator stator generates

    300 V in each of its stator windings. (a) Sketch

    the waveform and phasor diagrams for the

    phase voltages, and (b) calculate the p.d.

    between any pair of lines.

    4 A balanced three-phase, delta-connected

    load consists of the stator windings of an a.c.motor. Each winding has a resistance of 3.5

    and inductance 0.015 H. If this machine is

    connected to a 415 V, 50 Hz supply, calculate

    (a) the stator phase current, (b) the line current

    drawn from the supply, and (c) the total power

    dissipated.

    5 Repeat the calculations for Question 4, when

    the stator windings are connected in star

    conguration.

    6 Three identical coils, connected in star, take

    a total power of 1.8 kW at a power factor of

    0.35, from a 415 V, 50 Hz supply. Determine the

    resistance and inductance of each coil.

    7 Three inductors, each of resistance 12 and

    inductance 0.02 H, are connected in delta to a

    400 V, 50 Hz, three-phase supply. Calculate (a)

    the line current, (b) the power factor, and (c)

    the power consumed.

    8 The star-connected secondary of a three-phase

    transformer supplies a delta-connected motor,

    which takes a power of 80 kW, at a lagging

    power factor of 0.85. If the line voltage is 600 V,

    calculate (a) the current in the transformer

    secondary windings, and (b) the current in the

    motor windings.

    9 A star-connected load, each phase of which

    has an inductive reactance of 40 and

    resistance of 25 , is fed from the secondary of

    a three-phase, delta-connected transformer.

    If the transformer phase voltage is 600 V,

    calculate (a) the p.d. across each phase of the

    load, (b) the load phase current, (c) the current

    in the transformer secondary windings, and (d)the power and power factor.

    10 Three coils are connected in delta to a 415 V,

    50 Hz, three-phase supply, and take a line

    current of 4.8 A at a lagging power factor

    of 0.9. Determine (a) the resistance and

    inductance of each coil, and (b) the power

    consumed.

    11 The power taken by a three-phase motor

    was measured using the two-wattmeter

    method. The readings were 850 W and

    260 W respectively. Determine (a) the powerconsumption and, (b) the power factor of the

    motor.

    12 Two wattmeters, connected to measure the

    power in a three-phase system, supplying a

    balanced load, indicate 10.6 kW and2.4 kW

    respectively. Calculate (a) the total power

    consumed, and (b) the load phase angle and

    power factor. State the signicance of the

    negative reading recorded.

    13 Using the two-wattmeter method, the power

    in a three-phase system was measured.The meter readings were 120 W and 60 W

    respectively. Calculate (a) the power, and (b)

    the power factor.

    14 Each branch of a three-phase, star-connected

    load, consists of a coil of resistance 4 and

    reactance 5 . This load is connected to a

    400 V, 50 Hz supply. The power consumed

    is measured using the two-wattmeter

    method. Sketch a circuit diagram showing

    the wattmeter connections, and calculate the

    reading indicated by each meter.

    15 A three-phase, 415 V, 50 Hz supply is connected

    to an unbalanced, star-connected load, having

    a power factor of 0.8 lagging in each phase.

    The currents are 40 A in the red phase, 55 A in

    the yellow phase, and 62 A in the blue phase.

    Determine (a) the value of the neutral current,

    and (b) the total power dissipated.

    Assignment Questions

    112

  • 8/13/2019 Three-Phase a.C. Circuits

    29/32

    Fundamental Electrical and Electronic Principles 113Fundamental Electrical and Electronic Principles 113Three-Phase A.C. Circuits

    Suggested Practical Assignments

    Assignment 1To determine the relationship between line and phase quantities in three-phase

    systems.

    Apparatus:

    Low voltage, 50 Hz, three-phase supply

    3 1krheostats

    3 ammeters

    3voltmeters (preferably DMM)

    Method:

    1 Using a digital meter, adjust each rheostat to exactly the same value (1k).

    2 Connect the rheostats, in star conguration, to the three-phase supply.

    3 Measure the three line voltages and the corresponding phase voltages, and

    record your results in Table 1.

    4 Measure the three line currents, and record these in Table 1.

    5 Check that the neutral current is zero.

    6 Carefully unbalance the load by altering the resistance value of one or two

    of the rheostats. ENSURE that you do not exceed the current ratings of the

    rheostats.

    7 Measure and record the values of the three line currents and the neutral

    current, in Table 2.

    8 Switch off the three-phase supply, and disconnect the circuit.

    9 Carefully reset the three rheostats to their original settings, as in paragraph

    1of the Method.

    10 Connect the rheostats, in delta conguration, to the three-phase supply,

    with an ammeter in each line.

    11 Switch on the supply, and measure the line voltages and line currents.

    Record your values in Table 3.

    12 Switch off the supply, and connect the three ammeters in the three phases

    of the load, i.e. an ammeter in series with each rheostat. This will involve

    opening each phase and inserting each ammeter.

    13 Switch on and record the values of the three phase currents. Record values

    in Table 3.

    14 From your tabulated readings, determine the relationship between line and

    phase quantities for both star and delta connections.

    15 From your readings in Table 2, calculate the neutral current, and compare

    this result with the measured value.

    16 Write an assignment report. Include all circuit and phasor diagrams, and

    calculations. State whether the line and phase relationships measuredconform to those expected (allowing for experimental error).

    Assignment 2To measure the power in three-phase systems, using both single and two-

    wattmeter methods.

    Apparatus:

    Low voltage, 50 Hz, three-phase supply

    3 1krheostats

    2 wattmeters

    1DMM

    113

  • 8/13/2019 Three-Phase a.C. Circuits

    30/32

    114

    Method:

    1 As for Assignment 1, carefully adjust the three rheostats to the same value

    (1k).

    2 Connect the circuit shown in Fig. 3.33, and measure the power in the red

    and yellow phases.

    W1

    W2

    R

    N

    Y

    B

    Fig. 3.33

    W1

    W2

    R

    B

    Y

    Fig. 3.34

    3 Transfer one of the wattmeters to the blue phase, and measure that power.

    4 Add the three wattmeter readings to give the total power dissipation. Check

    to see whether this is three times the individual phase power.

    5 Switch off the power supply, and reconnect as in Fig. 3.34.

    6 Record the two wattmeter readings, and check whether their sum is equal

    to the total power recorded from paragraph 4 above.

    7 Switch off the power supply and reconnect the circuit as in Fig. 3.35.

    8 Record the two wattmeter readings.

    9 Switch off the supply, and transfer one of the wattmeters to the third phase.

    10 Record this reading. Add the three readings to give the total power, and

    check that this is three times the phase power.

    11 Switch offthe supply and connect the circuit of Fig. 3.36.12 Record the two wattmeter readings, and check that their sum equals the

    total power obtained from paragraph 10 above.

    114 Further Electrical and Electronic Principles

  • 8/13/2019 Three-Phase a.C. Circuits

    31/32

    W1

    W2

    R

    B

    Y

    Fig. 3.35

    W1

    W2

    R

    B

    Y

    Fig. 3.36

    Assignment 3Show how the two-wattmeter method of power measurement can be

    accomplished by means of a single wattmeter, together with a suitable

    switching arrangement. You may either devise your own system, or discoveran existing system through library research.

    Three-Phase A.C. Circuits 115

  • 8/13/2019 Three-Phase a.C. Circuits

    32/32