Thermostats www.usa.siemens.com/hvac Thermostats A-1 (Continued on next page) PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Pneumatic Room Thermostats—Powerstar Overview/Selection Guide A-3 Single Setpoint Room Thermostats TH 192S 155-065P25 A-5 Heating/Cooling Room Thermostats TH 192/4HC 155-066P25 A-7 Day/Night and Day/Night/Vent Room Thermostats TH 192/4DN/DNV 155-067P25 A-9 Free Energy Band Heating/Cooling Room Thermostats TH 193HC 155-068P25 A-11 (Hesitation) Free Energy Band Heating/Cooling Room Thermostats TH 193HC 155-069P25 A-13 Retroline ® Retrostat Room Thermostats TH 192/4 A-15 Pneumatic Room Thermostats—D Series Room Thermostats TH 832D 155-072P25 A-19 Pneumatic Thermostats for Specialized Applications Limitem Rigid Bulb Thermostats TH 356 155-070P25 A-21 Limitem Remote Bulb Thermostats TH 357 155-071P25 A-23 Unit Mounted Thermostats TH 188 155-064P25 A-25 High and Low Temperature Detection Thermostats TH 134 155-063P25 A-27 Electric Room Thermostats/Controllers Line Voltage Remote Bulb Thermostats ET 141 155-019P25 A-29 Line Voltage Room Thermostats—Heating/Cooling ET 134 155-017P25 A-31 Room Thermostats RAA... 155-519P25 A-33 Fan Coil Thermostats RAB... 155-524/526/528P25 A-37 Room Temperature Controllers for Two-pipe Fan Coil Units RCC... 155-712/713/323 A-41 Free Energy Band Room Temperature Controllers for Four-pipe Fan Coil Units RCC... 155-324 A-43 Room Temperature Controllers for CAV Systems RCU15/50... 155-327P25 A-47 Table of Contents Standard Shipping within 3 to 5 days Products ordered through the Rapid Response TM program can ship same day. Expect longer lead times for large quantities and unique parts. See inside back cover for details on Rapid Response TM shipping.

Transcript of Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit...

Page 1: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Thermostats

www.usa.siemens.com/hvac

Thermostats

A-1

(Continued on next page)

Product Product code technical instructions Page #

Pneumatic room thermostats—Powerstar

Overview/Selection Guide a-3

Single Setpoint Room Thermostats TH 192S 155-065P25 a-5

Heating/Cooling Room Thermostats TH 192/4HC 155-066P25 a-7

Day/Night and Day/Night/Vent Room Thermostats TH 192/4DN/DNV 155-067P25 a-9

Free Energy Band Heating/Cooling Room Thermostats TH 193HC 155-068P25 a-11

(Hesitation) Free Energy Band Heating/Cooling Room Thermostats TH 193HC 155-069P25 a-13

Retroline® Retrostat Room Thermostats TH 192/4 — a-15

Pneumatic room thermostats—d series

Room Thermostats TH 832D 155-072P25 a-19

Pneumatic thermostats for specialized applications

Limitem Rigid Bulb Thermostats TH 356 155-070P25 a-21

Limitem Remote Bulb Thermostats TH 357 155-071P25 a-23

Unit Mounted Thermostats TH 188 155-064P25 a-25

High and Low Temperature Detection Thermostats TH 134 155-063P25 a-27

electric room thermostats/controllers

Line Voltage Remote Bulb Thermostats ET 141 155-019P25 a-29

Line Voltage Room Thermostats—Heating/Cooling ET 134 155-017P25 a-31

Room Thermostats RAA... 155-519P25 a-33

Fan Coil Thermostats RAB... 155-524/526/528P25 a-37

Room Temperature Controllers for Two-pipe Fan Coil Units RCC... 155-712/713/323 a-41

Free Energy Band Room Temperature Controllers for Four-pipe Fan Coil Units RCC... 155-324 a-43

Room Temperature Controllers for CAV Systems RCU15/50... 155-327P25 a-47

Table of Contents

Standard Shipping within 3 to 5 days Products ordered through the Rapid ResponseTM program can ship same day. Expect longer lead times for large quantities and unique parts. See inside back cover for details on Rapid ResponseTM shipping.

Page 2: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-2

Table of Contents (Continued)

Product Product code technical instructions Page #

electric room thermostats/controllers (continued)

Room Temperature Controllers for CAV and VAV Systems RCU61 155-328P25 a-51

Room Temperature Controller with Two 0 to 10 Vdc Outputs RLA162.5U 155-515 a-55

Room Temperature Controllers with LCD for Heating and Cooling Systems RDU... 155-735 a-59

Room Temperature Controllers with LCD RDX... 155-747 a-63

Room Temperature Controllers with LCD for Two-Pipe Fan Coil Units RDF... 155-333/334/335/336 a-67

electric thermostats for specialized applications

Surface Mounted/High Temperature Limit Control Thermostats ET 141 155-021P25 a-71

Low Temperature Detection Thermostats ET 134 155-016P25 a-73

accessories and service Kits a-75

Page 3: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-3

Proven to provide fast response and highly accurate temperature control, Powerstar Pneumatic Room Thermostats are designed to control heating and/or cooling by operating a variety of pneumatic devices such as valves or damper actuators.

Powerstar thermostats are factory calibrated to control pneumatic devices over a 3 to 15 psi (103 to 207 kPa) range.

Powerstar pneumatic room thermostats are available for the following applications:• SingleTemperature • FreeEnergyBand• Day/Night • FreeEnergyBand• Day/Night/Vent withHesitation• Heating/Cooling

Coversareavailablewithconcealedorexposedsetpointadjustment, room temperature indication, and setpoint indicator.

OverviewPowerstar Room Thermostats

Selection Guide

Air Supply ApplicationsControlOutputs

Control Setpoints

Control Actions

Air Output Capacity

ModelLow

(1-pipe)High

(2-pipe)15 to 30 psi (103 to 207 kPa)

•HeatorCool Single Single Direct/Reverse • • 192 S

Cool18psi(124kPa)Heat25psi(172kPa)

•HeatandCool(autochangeover)•Factorycalibrated(194HC)forHoneywellorJohnsonretrofit

Single Dual Direct/Direct • 192 HC

Reverse/Reverse • 194 HC

Direct/Reverse •

Reverse/Direct •

Day18psi(124kPa)Night25psi(172kPa)

•DayandNight(autochangeover)•Factorycalibrated(194DN)for HoneywellorJohnsonretrofit •R2vent(“0”)day,fullsupplynight (DNVonly,3-pipe) •Nightoverrideselectorswitch

Single Dual(Day/Night)

Direct/Direct • 192 DN194 DNReverse/Reverse •

Day18psi(124kPa)Night25psi(172kPa)

•DayandNight(autochangeover)•Factorycalibrated(194DNfor HoneywellorJohnsonretrofit)•R2vent(“0”)day,fullsupplynight (DNVonly,3-pipes) •Nightoverrideselectorswitch

Dual Dual (Day/NightwithVent)

None • • 192 DNV194 DNV

15 to 30 psi(103 to 207 kPa)

•HeatandCool•Sequence-controlleddeviceswith two control lines (same or different range)

Dual Dual(Heat/Cool)

Direct/Direct • • 193 HC FreeEnergy BandReverse/Reverse • •

Direct/Reverse • •Reverse/Direct • •

15 to 30 psi(103 to 207 kPa)

•HeatandCool•Sequence-controlleddevices with one control line (different spring ranges)

Single Dual(Heat/Cool)

Direct/Direct • 193 HC FreeEnergy Band(Hesitation)

Page 4: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-4

Housings with No Logo OptionOuraward-winninghousingdesign,plusavarietyofenergy-savingfunctions and adaptability options, make Siemens thermostats a welcomeadditiontoanyroom.Lookforthe“NoLogo”coveroptiontoinconspicuously enhance a room’s aesthetics.

Page 5: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-5

Typical wall plate and screws.

192SThermostatchassis.

DescriptionProviding proportional single output, single setpoint, 1-pipeforlowaircapacityor2-pipeforhighaircapacitypneumaticroomtemperaturecontrol,the192SPowerstarSingle Setpoint Pneumatic Room Thermostat is the most economical model. Refer to the Retroline® Retrostats on pageA-15toreplacecompetitivemodels.

Features• SinglesetpointdialavailableinFahrenheitor

Celsiusscales• Availableindirectorreverseactingmodels• Sensitivebimetalrespondstotemperaturechanges• Integral,fieldadjustablelimitstops• Wallmountingplateforconnectiontoavarietyof

rough-interminalboxesincluded• Largevolumeaircapacityrelayin2-pipemodelsonly• Testportforfastcheckofoutputpressurewithout

removing the cover• Fieldreplaceablethermometer,setpointdial,restrictor

andfiltersfordecreasedmaintenancecost

Options• Quick-connectairconnectionsforeaseofinstallation

and service• Fixedlimitstopstomeetgovernmentspecifications• Large,1/2"setpointknobforconvalescenthomes

ApplicationsDesignedforheatingandcoolingapplicationsforcontrolofpneumaticvalvesanddamperactuators.The192SPowerstar Single Setpoint Pneumatic Room Thermostat is excellent for commercial and institutional facilities.

Recommendation1-pipe: Use when limited output air capacity is required to operate a single valve and/or actuator; requires external restrictor,20scim(5.4ml/s)airsupply.

2-pipe: Use for high output capacity for control of multiple valves and actuators, used with or without high/low limiting controls.

Application DrawingsDottedlinesarealternativecontrolschemes.

192 SPowerstar Single Setpoint Pneumatic Room Thermostat

Page 6: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-6

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Scale; Range Major(minor)Divisions............................................. 45to85°F,10(2)°F (7to30°C,5(1)°C)Factory Calibration .......................................................72°F,7.5psi±0.3 (22°C,[email protected])Sensitivity Adjustment Range .................1to4psi/°F(12to50kPa/°C)Factory Setting ......................................................2.5psi/°F(31kPa/°C)Limit Stop FieldAdjustmentRange .............................................. 45/85°F(7/30°C) FixedLimitStopRange ............................................. 55/75°F(13/24°C)Temperature Storage ......................................................-10to+140°F(-23to+60°C) Ambient Operating ........................................... 40to140°F(4to60°C)Accuracy at Factory Calibration ........................................................................ ±2°F(±1.1°C) Response ........................................................................ 0.1°F(0.06°C)Supply Air Pressure Recommended ............................................................. 25 psi (172 kPa) Maximum ...................................................................... 30 psi (207 kPa)

Nominal Air Consumption for Air Compressor Sizing 1-pipe .........................................................................25scim(6.8ml/s) 2-pipe ......................................................................... 20 scim (5.5 ml/s)Nominal Air Capacity for Air Main Sizing 1-pipe .........................................................................25scim(6.8ml/s) 2-pipe ......................................................................... 20 scim (5.5 ml/s)Nominal Chassis Air Capacity 1-pipeSupply .............................................................25scim(6.8ml/s) 2-pipeSupply ............................................................230scim(63ml/s) 1-pipeExhaust ..............................................................30scim(8ml/s) 2-pipeExhaust ..........................................................150scim(41ml/s)Air Connections ..................................................5/32"(4mm)ODtubingDimensions (with cover) ............................. 2.16"Wx3.34"Hx1.59"D (55mmWx85mmHx40mmD)Shipping Weights (with cover) ThermostatChassisandWallPlate .............................0.53lb.(0.24kg) PlasticCover/MetalCover ................0.07lb.(0.04kg)/0.27lb.(0.12kg)

For complete conversion kits, refer to the retroline® retrostats starting on page a-15.

192 S Thermostat Product Ordering

Model #

Thermostat Chassis Type Thermostat Chassis & Wall Plate

Output Setpoint Air Output CapacityThermometer & Setpoint Scales

Control ActionDirect Reverse

192S 1-pipe Single Single(HeatorCool) Low(NoRelay) °F

°C192-200 192-201192-220 192-221

192S 2-pipe Single Single(HeatorCool) High(IntegralRelay) °F

°C192-202 192-203192-222 192-223

Chassis Options:Chassiswith1/2"(13mm)diametersetpointadjustmentknobforconvalescentfacilities. AvailableinDesertBeigeonly.Adda“K”totheendofthePartNo.,forexample192-200K.

Thermostat Covers (Sold Separately)Plastic Part No. Metal Part No.

Desert Beige White• Adjustment setpoint concealed •Indicatorsetpointconcealed •Chassisthermometerconcealed •Nologo

192-257 192-257W 192-357

• Adjustment setpoint concealed •Indicatorsetpointconcealed •Chassisthermometerconcealed •Withlogo

192-256 192-256W 192-356

• Adjustment setpoint concealed •Indicatorsetpointconcealed •Chassisthermometerexposed

192-254 192-254W 192-354

• Adjustment setpoint key •Indicatorsetpointexposed •Chassisthermometerconcealed •Usewith1/2"setpointknoboption

192-265 192-265W 192-365

•Adjustment setpoint key •Indicatorsetpointexposed •Chassisthermometerexposed •Usewith1/2"setpointknoboption

192-266 192-266W 192-366

• Adjustment setpoint exposed •Indicatorsetpointexposed •Chassisthermometerconcealed

192-250 192-250W 192-350

• Adjustment setpoint exposed •Indicatorsetpointexposed •Chassisthermometerconcealed

192-252 192-252W 192-352

Note: •“Exposedfeatures”areindicatedingreen on corresponding illustration. •UniversalCoversoldonpage A-83. For194 refer to Powerstar Retroline section.

192 S Thermostat Specifications

Page 7: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-7

Typical wall plate and screws.192HCThermostatchassis.192HCThermostatwithplasticcover.Chassiswallplate witheasymaintenanceplug-inadaptersshown(optional).

ApplicationsDesignedfortemperaturecontrolofheatingandcoolingapplications,the192HCPowerstarHeating/CoolingPneumatic Room Thermostat controls valves and damper actuators in cooling equipment. Providing energy management and occupant comfort, the thermostat automatically adjusts to seasonal changes from heating setpoint to cooling setpoint in commercial and institutional facilities.

RecommendationForcontrolofmultiplevalvesandactuators,usewithorwithout high/low limiting controls.

DescriptionProviding proportional single output, dual setpoint with 2-pipeforhighaircapacitypneumaticroomtemperaturecontrol,the192HCPowerstarHeating/CoolingPneumaticRoom Thermostat provides two thermostats under one cover; one side for heating and the other for cooling. Switchover is accomplished by changing the air pressure to the thermostat.

Features• DualsetpointdialavailableinFahrenheitor

Celsiusscales• Availableindirectorreverseactingmodels• Sensitivebimetalrespondstotemperaturechanges• Integral,fieldadjustablelimitstops• Adjustablechangeoverpressure• Largevolumeaircapacityrelay• Wallmountingplatesprovidesconnectiontoavariety

ofrough-interminalboxes• Testportforfastcheckofoutputpressurewithout

removing the cover• Fieldreplaceablethermometer,setpointdials,restrictor

andfilters

Options• Fixedlimitstopstomeetgovernmentspecifications• Quick-connectairconnectionsforeaseofinstallation

and service• Large,1/2"setpointknobforconvalescenthomes

Application Drawing

Powerstar Heating/Cooling Pneumatic Room Thermostats

192 HC

Page 8: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-8

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Scale; Range Major(minor)Divisions...............................................45to85°F,10(2)°F (7to30°C,5(1)°C)Factory Calibration .......................................................72°F,7.5psi±0.3 (22°C,[email protected])Sensitivity Adjustment Range ..................1to4psi/°F(12to50kPa/°C)Factory Setting .......................................................2.5psi/°F(31kPa/°C)Limit Stop FieldAdjustmentRange ................................................45/85°F(7/30°C) FixedLimitStopRange .................................................55/75°F(3/24°C)Temperature Storage ....................................................... -10to+140°F(-23to+60°C) Ambient Operating .............................................40to140°F(4to60°C)Accuracy at Factory Calibration ..........................................................................±2°F(±1.1°C) Response ..........................................................................0.1°F(0.06°C)Supply Air Pressure TwoPressure(Recommended)Cooling/Heating .......... 18psi(124kPa)/ (124kPa)/25psi(172kPa)

Supply Air Pressure Two Pressure (Range) Cooling ................................................ 15to19psi(103to131kPa) Heating ................................................ 23to30psi(159to207kPa) TwoPressure,HoneywellCompetitiveModel Cooling/Heating ..............................13psi(90kPa)/18psi(124kPa) TwoPressure,JohnsonCompetitiveModel1 Cooling/Heating ............................15psi(103kPa)/20psi(138kPa)Nominal Air Consum. for Air Compressor Sizing .......25scim(6.8ml/s)Nominal Air Capacity for Air Main Sizing .....................40scim(11ml/s)Nominal Air Capacity Supply/ChassisExhaust............... 150scim(41ml/s)/150scim(41ml/s)Air Connections ......................................................5/32"(4mm)ODtubeDimensions (with cover) ...............................2.16"Wx3.34"Hx1.59"D (55mmWx85mmHx40mmD)Shipping Weights ThermostatChassisandWallPlate ..............................0.53lb.(0.24kg) PlasticCover ................................................................0.07lb.(0.04kg) MetalCover(single/dual) ......................0.27 lb. (0.12 kg)/0.7 lb. (0.3 kg)

For complete conversion kits, refer to the retroline® retrostats starting on page a-15.

1. SomeJohnsonControlsheat/coolthermostatshaveacoolingsupplypressureof20psi(138kPa)andaheatingsupplypressureof15psi(103kPa). Forthisapplication,theheatingandcoolingactionsmustbereversed.Ifexposedsetpointisrequired,orderspecialcover,192-773.

192 HC Thermostat Product Ordering

Model #

Thermostat Chassis Type Thermostat Chassis & Wall Plate

Output Setpoint Air Output CapacityThermometer & Setpoint Scales

Control ActionHeat Direct Heat Reverse

192HC 2-pipe Single Dual

(HeatandCool) High(IntegralRelay)

°F °F °C °C

192-207 Cool(DA) 192-209 Cool(DA)192-208 Cool(RA) 192-210 Cool(RA)192-227 Cool(DA) 192-229 Cool(DA)192-228 Cool(RA) 192-230 Cool(RA)

Chassis Options:Chassiswith1/2"(13mm)diametersetpointadjustmentknobforconvalescentfacilities. AvailableinDesertBeigeonly.Adda“K”totheendofthePartNo.,forexample192-207K.

Thermostat Covers (Sold Separately)Plastic Part No. Metal Part No.

Desert Beige White

• Adjustment setpoint concealed •Indicatorsetpointconcealed •Chassisthermometerconcealed •Nologo

192-257 192-257W 192-357

• Adjustment setpoint concealed •Indicatorsetpointconcealed•Chassisthermometerconcealed •Withlogo

192-256 192-256W 192-356

• Adjustment setpoint concealed •Indicatorsetpointconcealed•Chassisthermometerexposed

192-254 192-254W 192-354

• Adjustment setpoint key•Indicatorsetpointexposed•Chassisthermometerconcealed

192-267 192-267W 192-367

•Adjustment setpoint key •Indicatorsetpointexposed •Chassisthermometerexposed •Usewith1/2"setpointknoboption

192-268 192-268W 192-368

• Adjustment setpoint exposed •Indicatorsetpointexposed•Chassisthermometerconcealed •Usewith1/2"setpointknoboption

192-258 192-258W 192-358

• Adjustment setpoint exposed •Indicatorsetpointexposed•Chassisthermometerconcealed

192-260 192-260W 192-360

Note: •“Exposedfeatures”areindicatedingreen on corresponding illustration. •UniversalCoversoldonpage A-83.

192 HC Thermostat Specifications

Page 9: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-9

Typical wall plate and screws.

192DNThermostatchassis.192DNThermostatwithplasticcover.Chassiswallplate witheasymaintenanceplug-inadaptersshown(optional).

ApplicationsThe192DNandDNVPowerstarPneumaticRoomThermostat controls valves and damper actuators in cooling equipment, automatically performing setback changesfromdaytonight.The192DNValsoperformsapurgesequenceatnighttobringin“vent”outsideairtocool the building. A manual override selector switch allows individualroomorzone“day”controllocallyduringthenight cycle.

Duringthenightcontrolcycle,the192DNVmodelsprovide a separate output signal (full air supply) allowing ventilationcontrol.Periodicresettingtothe“night”controlmode during evening or weekend periods using time clocks ensures optimal energy management.

RecommendationUse192DNorDNVformultiplevalvesandactuators,withor without high/low limiting controls.

DescriptionProvidingproportionaldualsetpoint,2-pipeor3-pipehighair capacity pneumatic room temperature control, the 192DNorDNVPowerstarPneumaticRoomThermostatautomatically resets the room temperature setpoint during unoccupied hours by changing the air pressure to the thermostat. A manual override feature allows occupants to switch to day mode. The override returns to night mode the following night.

Features• DualsetpointdialavailableinFahrenheitor

Celsiusscales• Availableindirectorreverseactingmodels• Sensitivebimetalrespondstotemperaturechanges• Manualoverrideselectorforoff-houroccupantcomfort• Adjustablechangeoverpressure• Largevolumeaircapacityrelay• Integral,fieldadjustablelimitstops• Wallmountingplateforconnectiontoavarietyof

rough-interminalboxesincluded• Testportforfastcheckofoutputpressurewithout

removing the cover• Fieldreplaceablethermometer,setpointdial,restrictor

andfilters

Options• Fixedlimitstopstomeetgovernmentspecifications• Quick-connectairconnectionsforeaseofinstallation

and service• Large,1/2"setpointknobforconvalescenthomes

Application Drawings

Chassis Port Operation Mode Switching Relay R2 Pressure (Air Supply) Connection FullAirSupply Night(S=25psi) A-D 0psi NightOccupied B-D 0psi Day(S=18psi) B-D

Day/Night. Day/Night/Vent.

Powerstar Day/Night/Vent Pneumatic Room Thermostats

192 DN/DNV

Page 10: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-10

Scale; Range Major(minor)Divisions............................................. 45to85°F,10(2)°F (7to30°C,5(1)°C)Factory Calibration ...............................................................72°F,7.5psi (22°C,31kPa)Sensitivity Adjustment Range .................1to4psi/°F(12to50kPa/°C)Factory Setting ...................................................... 2.5psi/°F(31kPa/°C)Limit Stop FieldAdjustmentRange .............................................. 45/85°F(7/30°C) FixedLimitStopRange ............................................... 55/75°F(3/24°C)Temperature Storage ......................................................-10to+140°F(-23to+60°C) Ambient Operating ........................................... 40to140°F(4to60°C)Accuracy at Factory Calibration ........................................................................ ±2°F(±1.1°C) Response ........................................................................ 0.1°F(0.06°C)Supply Air Pressure Two Pressure Day(recommended) ................................................ 18psi(124kPa) Night(recommended) .............................................. 25 psi (172 kPa) Vent-Day/Night ................................... 0 psi (0 kPa)/25 psi (172 kPa)

Two Pressure Day(range).......................................... 15to19psi(103to131kPa) Night(range)........................................ 23to30psi(159to207kPa) TwoPressure(HoneywellCompetitiveModel) Day/Night ........................................13psi(90kPa)/18psi(124kPa) TwoPressure(JohnsonControlsCompetitiveModel) Day/Night ......................................15psi(103kPa)/20psi(138kPa)Nominal Air Consumption for Air Compressor Sizing ................................................25scim(6.8ml/s)Nominal Air Capacity for Air Main Sizing ................... 40scim(11ml/s)Nominal Chassis Air Capacity Supply .......................................................................230scim(63ml/s) Exhaust .....................................................................150scim(41ml/s)Air Connections .................................................... 5/32"(4mm)ODtubeDimensions (with cover) 192DN ....................................................... 2.16"Wx3.34"Hx1.59"D (55mmWx85mmHx40mmD) 192DNV ....................................................... 2.5"Wx3.34"Hx1.59"D (64mmWx85mmHx40mmD)Shipping Weights ThermostatChassisandWallPlate .............................0.53lb.(0.24kg) PlasticCover ...............................................................0.07lb.(0.04kg) MetalCover(dual) ........................................................0.27 lb. (0.12 kg)

For complete conversion kits, refer to the retroline® retrostats starting on page a-15.

192 DN/DNV Thermostat Product Ordering

Model #

Thermostat Chassis Type Thermostat Chassis & Wall Plate

Output SetpointAir Output Capacity

Thermometer & Setpoint Scales

Control ActionD (DA) / N (DA) D (RA) / N (RA) D (DA) / N (DA)

(with Night Vent)192DN

Single Dual (DayandNight)

High (IntegralRelay)

°F 192-204 192-205 192-206192DNV 3-pipe °C 192-224 192-225 192-226

Chassis Options:Chassiswith1/2"(13mm)diametersetpointadjustmentknobforconvalescentfacilities. AvailableinDesertBeigeonly.Adda“K”totheendofthePartNo.,forexample192-204K.

Thermostat Covers (Sold Separately)Plastic Part No. Metal Part No.

Desert Beige White

• Adjustment setpoint concealed •Indicatorsetpointconcealed •Chassisthermometerconcealed

192-262 192-262W 192-362

• Adjustment setpoint concealed •Indicatorsetpointconcealed •Chassisthermometerexposed

192-264 192-264W 192-364

• Adjustment setpoint key •Indicatorsetpointexposed •Chassisthermometerconcealed •Usewith1/2"setpointknoboption

192-269 192-269W 192-369

• Adjustment setpoint key •Indicatorsetpointexposed •Chassisthermometerexposed •Usewith1/2"setpointknoboption

192-270 192-270W 192-370

• Adjustment setpoint key (night) exposed (day) •Indicatorsetpointexposed •Chassisthermometerexposed

192-271 192-271W 192-371

Note: •DNV3-pipemodelprovidesfullairsupplyonR2ventportduringnightcontrolcycle. •“Exposedfeatures”areindicatedingreen on corresponding illustration. •For194 refer to Powerstar Retroline section. •UniversalCoversoldonpage A-83.

192 DN/DNV Thermostat Specifications

Page 11: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-11ApplicationsDesignedforbuildingswithearlymorningheatrequirementsandmid-morningtoafternooncoolingrequirements,thePowerstarFreeEnergyBandPneumaticRoom Thermostat two temperature thermostat controls valves, damper actuators and mechanical heating and cooling equipment. Providing energy management and occupant comfort, the thermostat automatically reduces heating load and increases cooling load.

Recommendation2-pipe (dual 1-pipe): Use when a limited air capacity is required to operate a single valve and/or actuator.

3-pipe (dual 2-pipe): Use for multiple valves and actuators with or without high/low limiting controls which require higher air capacities.

DescriptionProvidingproportional,dualoutput,dualsetpoint,2-pipe(dual1-pipelowaircapacity)or3-pipe(dual2-pipehighair capacity) pneumatic room temperature control, the 193HCPowerstarFreeEnergyBandPneumaticRoomThermostat creates a deadband so that no heating or coolingoccursduringtheFreeEnergyBand.

Features• DualsetpointdialsavailableinFahrenheitor

Celsiusscales• Integral,fieldadjustablelimitstops• Sensitivebimetalrespondstotemperaturechanges• AdjustableFreeEnergyBand• Testportforfastcheckofoutputpressurewithout

removing the cover• Wallmountingplatesforconnectiontoavarietyof

rough-interminalboxesincluded• Fieldreplaceablethermometer,setpointdials,

restrictorsandfilters• Competitiveadaptermountingkitsavailable

Options• Fixedlimitstopstomeetgovernmentspecifications• Quick-connectairconnectionsforeaseofinstallation

and service• Large,1/2"setpointknobforconvalescenthomes

Typical wall plate and screws.

193HCThermostatchassis.193HCThermostatwithplasticcover.Chassiswallplatewitheasymaintenanceplug-inadaptersshown(optional).

Input/Output Characteristics

Application Drawings

2-pipe (dual 1-pipe)

3-pipe (dual 2-pipe)

Powerstar Free Energy Band Heating/Cooling Pneumatic Room Thermostats

193 HC

Page 12: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-12

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Scale; Range Major(minor)Divisions.............. 45to85°F,10(2)°F(7to30°C,5(1)°C)Factory Calibration .......................................................72°F,7.5psi±0.3 (22°C,[email protected])Sensitivity Adjustment Range .................1to4psi/°F(12to50kPa/°C)Factory Setting ...................................................... 2.5psi/°F(31kPa/°C)Limit Stop FieldAdjustmentRange .............................................. 45/85°F(7/30°C) FixedLimitStopRange ............................................. 55/75°F(13/24°C)Temperature Storage ......................................................-10to+140°F(-23to+60°C) Ambient Operating ........................................... 40to140°F(4to60°C)Accuracy at Factory Calibration ........................................................................ ±2°F(±1.1°C) Response ........................................................................ 0.1°F(0.06°C)Supply Air Pressure Two Pressure (recommended) ..................................... 25 psi (172 kPa) Maximum ...................................................................... 30 psi (207 kPa)

For complete conversion kits, refer to the retroline® retrostats starting on page a-15.

Nominal Air Consumption for Air Compressor Sizing 1-pipe ..........................................................................50scim(14ml/s) 2-pipe .......................................................................... 40scim(11ml/s)Nominal Air Capacity for Air Main Sizing 1-pipe ..........................................................................50scim(14ml/s) 2-pipe .......................................................................... 40scim(11ml/s)Nominal Chassis Air Capacity 1-pipeSupply ............................................... 25scim(6.8ml/s)perside 2-pipeSupply .............................................. 230scim(63ml/s)perside 1-pipeExhaust ................................................ 30scim(8ml/s)perside 2-pipeExhaust ............................................ 150scim(41ml/s)persideAir Connections ..................................................5/32"(4mm)ODtubingDimensions (with cover) .............................. 2.16"Wx3.34"Hx1.59"D (55mmWx85mmHx40mmD)Shipping Weights ThermostatChassisandWallPlate .............................0.53lb.(0.24kg) PlasticCover ...............................................................0.07lb.(0.04kg) MetalCover(dual) ........................................................0.27 lb. (0.12 kg)

193 HC Thermostat Product Ordering

Model #

Thermostat Chassis Type Thermostat Chassis & Wall Plate

Output Setpoint Air Output CapacityThermometer & Setpoint Scales

Control ActionHeat Direct Heat Reverse

193HC 1-pipe Single Dual

(HeatandCool)Low

(NoRelay)

°F °F °C °C

193-211 Cool(DA)193-212 Cool(RA)193-231 Cool(DA)193-232 Cool(RA)

193-213 Cool(DA)193-214 Cool(RA)193-233 Cool(DA)193-234 Cool(RA)

193HC 2-pipe

Dual (HeatandCool)

High (IntegralRelay)

°F °F °C °C

193-215 Cool(DA)193-216 Cool(RA)193-235 Cool(DA)193-236 Cool(RA)

193-217 Cool(DA)193-218 Cool(RA)193-237 Cool(DA)193-238 Cool(RA)

Chassis Options:Chassiswith1/2"(13mm)diametersetpointadjustmentknobforconvalescentfacilities. AvailableinDesertBeigeonly.Adda“K”totheendofthePartNo.,forexample193-211K.

Thermostat Covers (Sold Separately)Plastic Part No. Metal Part No.

Desert Beige White

• Adjustment setpoint concealed •Indicatorsetpointconcealed •Chassisthermometerconcealed •Nologo

192-257 192-257W 192-357

• Adjustment setpoint concealed •Indicatorsetpointconcealed•Chassisthermometerconcealed •Withlogo

192-256 192-256W 192-356

• Adjustment setpoint concealed •Indicatorsetpointconcealed•Chassisthermometerexposed

192-254 192-254W 192-354

• Adjustment setpoint key•Indicatorsetpointexposed•Chassisthermometerconcealed

192-267 192-267W 192-367

•Adjustment setpoint key •Indicatorsetpointexposed •Chassisthermometerexposed •Usewith1/2"setpointknoboption

192-268 192-268W 192-368

• Adjustment setpoint exposed •Indicatorsetpointexposed•Chassisthermometerconcealed •Usewith1/2"setpointknoboption

192-258 192-258W 192-358

• Adjustment setpoint exposed •Indicatorsetpointexposed•Chassisthermometerconcealed

192-260 192-260W 192-360

Note: •“Exposedfeatures”areindicatedingreen on corresponding illustration. •UniversalCoversoldonpage A-83.

193 HC Thermostat Specifications

Page 13: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-13

193 HCPowerstar (Hesitation) Free Energy Band Heating/Cooling Pneumatic Room Thermostats

Typical wall plate and screws.

193HCThermostatchassis.193HCThermostatwithplasticcover.Chassiswallplate witheasymaintenanceplug-inadaptersshown(optional).

ApplicationsThe193HCPowerstar(Hesitation)FreeEnergyBandHeating/CoolingPneumaticRoomThermostatisanexcellent choice for saving energy by sequencing heatingandcoolingvalves.Inmostheat/coolpneumaticapplications,a3to8psi(21to55kPa)heatingvalveanda10to14psi(69to103kPa)coolingvalveisused.Bydesign,thisprovidesa2psi(14kPa)deadbandwhereno heating or cooling is occurring. The hesitation feature allowsyoutochangethedeadbandrangetoa3,4or5psi(21,28,or34kPa)rangetosaveenergy.RefertotheInput/Outputchartbelowformoreinformation.

DescriptionProviding proportional, single output, dual setpoint, 2-pipepneumaticroomtemperaturecontrol,the193HCPowerstar(Hesitation)FreeEnergyBandHeating/CoolingPneumatic Room Thermostat is designed to sequence a heating device or a cooling device.

The hesitation feature keeps the output pressure constantthrougha6°F(10.8°C)range(typical),causing a deadband.

Features• DualsetpointdialsavailableinFahrenheitor

Celsiusscales• Sensitivebimetalrespondstotemperaturechanges• Integral,fieldadjustablelimitstops• AdjustableFreeEnergyBand• Wallmountingplateforconnectiontoavarietyof

rough-interminalboxesincluded• Testportforfastcheckofoutputpressurewithout

removing the cover• Fieldreplaceablethermometer,setpointdials,

restrictors,andfilters

Options• Fixedlimitstopsto

meet government specifications

• Quick-connectair connections for ease of installation and service

• Large,1/2"setpoint knob for convalescent homes

Application Drawing

Input/Output Characteristics

Page 14: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-14

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Scale; Range Major(minor)Divisions............................................ 45to85°F,10(2)°F/ (7to30°C,5(1)°C)Factory Calibration “FEB”OutputPressure .................................................. 7.5 psi (52 kPa) Temperature ........................................................................ 72°F(22°C) Sensitivity .............................................................2.5psi/°F(31kPa/°C)Sensitivity Adjustment Range ............................................. 1to4psi/°F (12to50kPa/°C)Limit Stop, Field Adjustment Range ......................... 55/75°F(13/24°C)Temperature Storage ......................................................-10to+140°F(-23to+60°C) Ambient Operating ........................................... 40to140°F(4to60°C)Accuracy at Factory Calibration ........................................................................ ±2°F(±1.1°C) Response ........................................................................ 0.1°F(0.06°C)Supply Air Pressure Recommended ............................................................. 25 psi (172 kPa) Maximum ...................................................................... 30 psi (207 kPa)

Free Energy Band Output Pressure Adjustment .......................... 1 to 15 psi (7 to 103 kPa) Range .................................................................... 0to40°F(0to20°C)Nominal Air Capacity for Compressor Sizing ............ 40scim(11ml/s)Nominal Air Capacity for Air Main Sizing ................... 40scim(11ml/s)Nominal Chassis Air Capacity Supply .......................................................................150scim(41ml/s) Exhaust .....................................................................150scim(41ml/s) Supply/2-pipeExhaust ................................ 150scim(41ml/s)persideAir Connections ..................................................5/32"(4mm)ODtubingDimensions (with cover) ............................. 2.16"Wx3.34"Hx1.59"D (55mmWx85mmHx40mmD)Shipping Weights ThermostatChassisandWallPlate .............................0.53lb.(0.24kg) PlasticCover ...............................................................0.07lb.(0.04kg) MetalCover(dual) ........................................................0.27 lb. (0.12 kg)

193 HC Thermostat Product Ordering

Model #

Thermostat Chassis Type Thermostat Chassis & Wall Plate

Output Setpoint Air Output CapacityThermometer & Setpoint Scales

Control ActionHeat (DA) / Cool (DA) Heat (RA) / Cool (RA)

193HC Hesitation Single Dual

(HeatandCool)High

(IntegralRelay)°F 193-219 193-220

°C 193-239 193-240

Chassis Options:Chassiswith1/2"(13mm)diametersetpointadjustmentknobforconvalescentfacilities. AvailableinDesertBeigeonly.Adda“K”totheendofthePartNo.,forexample193-219K.

Thermostat Covers (Sold Separately)Plastic Part No. Metal Part No.

Desert Beige White

• Adjustment setpoint concealed •Indicatorsetpointconcealed •Chassisthermometerconcealed •Nologo

192-257 192-257W 192-357

• Adjustment setpoint concealed •Indicatorsetpointconcealed•Chassisthermometerconcealed •Withlogo

192-256 192-256W 192-356

• Adjustment setpoint concealed •Indicatorsetpointconcealed•Chassisthermometerexposed

192-254 192-254W 192-354

• Adjustment setpoint key•Indicatorsetpointexposed•Chassisthermometerconcealed

192-267 192-267W 192-367

•Adjustment setpoint key •Indicatorsetpointexposed •Chassisthermometerexposed •Usewith1/2"setpointknoboption

192-268 192-268W 192-368

• Adjustment setpoint exposed •Indicatorsetpointexposed•Chassisthermometerconcealed •Usewith1/2"setpointknoboption

192-258 192-258W 192-358

• Adjustment setpoint exposed •Indicatorsetpointexposed•Chassisthermometerconcealed

192-260 192-260W 192-360

Note: •“Exposedfeatures”areindicatedingreen on corresponding illustration. •UniversalCoversoldonpage A-83.

193 HC Thermostat Specifications

Page 15: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-15

192/194DualSetpointPneumaticRoomThermostatKit.

easily replaces:• Barber-Colman(Siebe)• JohnsonControls• Honeywell

• Robertshaw (Siebe)

ApplicationsRetrolineRetrostatkitsareavailableformost2-pipeapplications in direct and reverse acting models, including:

• SingleTemperature• Day/Night• Heat/CoolRefer to the Powerstar products to select the appropriate application.

DescriptionThe Powerstar Retroline Retrostat Pneumatic Room Thermostat converts most existing pneumatic room thermostatstoaPowerstar192/194directorreverseacting,2-pipe,singleordualsetpointunit.

Day/NightorHeat/CoolRetrostatisfactorycalibrated to match the appropriate changeover pressure of the competitive thermostat.

Features• CompletekitincludingRetrostatcoverkitwithexposed

or concealed setpoint adjustment• SetpointdialsavailableinFahrenheitorCelsiusscales• Factorycalibratedforaccuracy• Allinstallationhardwareandcalibrationwrench

provided.• Fitsintolargeformatwallopenings,usingincluded

“goofplate.”• Integral,fieldadjustablelimitstops• Testportforfastcheckofoutputpressurewithout

removing the cover• Fieldreplaceablethermometer,setpointdial(s),

restrictor(s),andfilter(s)

Options• Quick-connectairconnectionsforeaseofinstallation

and service• Large,1/2"setpointknobforconvalescenthomes

192/194 Powerstar Retrostat Pneumatic Room Thermostats

Page 16: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-16

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Accessories & Service Kits A-75

Single Setpoint

Description Thermometer & Setpoint Scales

Control ActionDirect Reverse

Single Temperature°F 192-840 192-841°C 192-850 192-851

Kits include covers. If a different cover is required, refer to the Accessories and Service Kit section.

Dual Setpoint

Action/Changeover Pressure ManufacturerThermometer & Setpoint Scales

Kit Part No. (Desert Beige)

Kit Part No. (White)

Day/NightDay(DA)13psi(90kPa)/Night(DA)18psi(124kPa) Honeywell °F 194-3042 194-3042WDay (DA)13psi(90kPa)/Night (DA)18psi(124kPa) Honeywell °C 194-3142 194-3142WDay (DA)15psi(103kPa)/Night (DA)20psi(138kPa) Johnson/B-C °F 194-3043 194-3043WDay (DA)15psi(103kPa)/Night (DA)20psi(138kPa) Johnson/B-C °C 194-3143 194-3143WDay (DA)18psi(124kPa)/Night (DA)25psi(172kPa) Siemens °F 192-3044 192-3044WDay (DA)18psi(124kPa)/Night (DA)25psi(172kPa) Siemens °C 192-3144 192-3144WDay (RA)13psi(90kPa)/Night (RA)18psi(124kPa) Honeywell °F 194-3052 194-3052WDay (RA) 15 psi (103 kPa) / Night (RA)20psi(138kPa) Johnson/B-C °F 194-3053 194-3053WDay (RA)18psi(124kPa)/Night (RA) 25 psi (172 kPa) Siemens °F 192-3054 192-3054WDay (RA)18psi(124kPa)/Night (RA) 25 psi (172 kPa) Siemens °C 192-3154 192-3154WHeat/CoolHeat (DA)18psi(124kPa)/Cool (RA)13psi(90kPa) Honeywell °F 194-3082 194-3082WHeat (DA)20psi(138kPa)/Cool (RA) 15 psi (103 kPa) Johnson/B-C °F 194-3083 194-3083WHeat (DA)25psi(172kPa)/Cool (RA)18psi(124kPa) Siemens °F 192-3084 192-3084WHeat (DA)25psi(172kPa)/Cool (RA)18psi(124kPa) Siemens °C 192-3184 192-3184W

Note: •FordetailedspecificationsonDay/Night,referto192DNorDNV. •FordetailedspecificationsonHeat/Cool,referto193HC. •ThechangeoverpressuresforRobertShawthermostatsare16psiDay/25psiNight. • All kits include covers.

Chassis Options:Chassiswith1/2"(13mm)diametersetpointadjustmentknobforconvalescentfacilities. AvailableinDesertBeigeonly.Adda“K”totheendofthePartNo.,forexample192-207K.

192/194 Pneumatic Room Thermostats Specifications

Page 17: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Thermostats

A-17

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Retroline Powerstar Retrostat Pneumatic Room Thermostat Product Ordering

Manufacturer Part No. Manufacturer Control Action/Temperature Scale

Retroline Part No.

KitReplace.Chassis

T-4002-2011 JohnsonControls SingleTemperature,DirectActing 192-840 192-202

T-4002-2021 JohnsonControls Single Temperature, Reverse Acting 192-841 192-203

T-4002-203 JohnsonControls SingleTemperature,DirectActing 192-840 192-202

T-4002-204 JohnsonControls Single Temperature, Reverse Acting 192-841 192-203

T-4506-2011 JohnsonControls Day(DA)15psi(103kPa)changeover/Night(DA)20psi(138kPa) 194-3043 194-2043

T-4506-202 JohnsonControls Day(DA)15psi(103kPa)changeover/Night(DA)20psi(138kPa) 194-3043 194-2043

T-4506-2031, 2 JohnsonControls Day(DA)15psi(103kPa)changeover/Night(DA)20psi(138kPa) 194-3043 194-2043

T-4506-2042 JohnsonControls Day(DA)15psi(103kPa)changeover/Night(DA)20psi(138kPa) 194-3043 194-2043

T-4506-2011 JohnsonControls Day(DA)15psi(103kPa)changeover/Night(DA)20psi(138kPa) 194-3043 194-2043

T-4506-202 JohnsonControls Day(DA)15psi(103kPa)changeover/Night(DA)20psi(138kPa) 194-3043 194-2043

T-4506-2031, 2 JohnsonControls Day(DA)15psi(103kPa)changeover/Night(DA)20psi(138kPa) 194-3043 194-2043

T-4506-2042 JohnsonControls Day(DA)15psi(103kPa)changeover/Night(DA)20psi(138kPa) 194-3043 194-2043

T-4506-2091 JohnsonControls Day(RA)15psi(103kPa)changeover/Night(RA)20psi(138kPa) 194-3053 194-2053

T-4506-2171, 2 JohnsonControls Day(RA)15psi(103kPa)changeover/Night(RA)20psi(138kPa) 194-3053 194-2053

T-4756-2051 JohnsonControls Heat(DA)20psi(138kPa)changeover/Cool(RA)15psi(103kPa) 194-3083 194-2083

T-4756-206 JohnsonControls Heat(DA)20psi(138kPa)changeover/Cool(RA)15psi(103kPa) 194-3083 194-2083

TP970A1002 Honeywell SingleTemperature,DirectActing 192-840 192-202

TP970A1012 Honeywell SingleTemperature,DirectActing 192-840 192-202

TP970A1035 Honeywell SingleTemperature,DirectActing 192-840 192-202

TP970A1038 Honeywell SingleTemperature,DirectActing 192-840 192-202

TP970A1053 Honeywell SingleTemperature,DirectActing 192-840 192-202

TP970A1061 Honeywell SingleTemperature,DirectActing 192-840 192-202

TP970A2004 Honeywell SingleTemperature,DirectActing 192-840 192-202

TP970A1002 Honeywell Single Temperature, Reverse Acting 192-841 192-203

TP970B1028 Honeywell Single Temperature, Reverse Acting 192-841 192-203

TP970B1036 Honeywell Single Temperature, Reverse Acting 192-841 192-203

TP970B1044 Honeywell Single Temperature, Reverse Acting 192-841 192-203

TP971A1003 Honeywell Day(DA)13psi(90kPa)changeover/Night(DA)18psi(124kPa) 194-3042 194-2042

TP971A1029 Honeywell Day(DA)13psi(90kPa)changeover/Night(DA)18psi(124kPa) 194-3042 194-2042

TP971A1037 Honeywell Day(DA)13psi(90kPa)changeover/Night(DA)18psi(124kPa) 194-3042 194-2042

TP971A1045 Honeywell Day(DA)13psi(90kPa)changeover/Night(DA)18psi(124kPa) 194-3042 194-2042

TP971A1086 Honeywell Day(DA)13psi(90kPa)changeover/Night(DA)18psi(124kPa) 194-3042 194-2042

TP971B1001 Honeywell Day(RA)13psi(90kPa)changeover/Night(RA)18psi(124kPa) 194-3052 194-2052

TP971B1004 Honeywell Day(RA)13psi(90kPa)changeover/Night(RA)18psi(124kPa) 194-3052 194-2052

TP972A1002 Honeywell Heat(DA)18psi(124kPa)changeover/Cool(RA)13psi(90kPa) 194-3082 194-2082

TP972A1028 Honeywell Heat(DA)18psi(124kPa)changeover/Cool(RA)13psi(90kPa) 194-3082 194-2082

TP972A1036 Honeywell Heat(DA)18psi(124kPa)changeover/Cool(RA)13psi(90kPa) 194-3082 194-2082

TP972A1101 Honeywell Heat(DA)18psi(124kPa)changeover/Cool(RA)13psi(90kPa) 194-3082 194-2082

Ordering Notes1. SuggestedRetrofitKitconvertshorizontalthermostattoverticalposition.2. SuggestedRetrofitKithasanadditionalmanualchangeoverswitch,notprovidedontheoriginal.

Page 18: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-18

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Retroline Powerstar Retrostat Pneumatic Room Thermostat Product Ordering

Manufacturer Part No. Manufacturer Control Action/Temperature Scale

Retroline Part No.

KitReplace.Chassis

TK-18 Barber-Colman SingleTemperature,DirectActing 192-840 192-202

TK-19 Barber-Colman Single Temperature, Reverse Acting 192-841 192-203

TK-19-1 Barber-Colman Single Temperature, Reverse Acting 192-841 192-203

TK-19-19 Barber-Colman Single Temperature, Reverse Acting 192-841 192-203

TK-1001 Barber-Colman SingleTemperature,DirectActing 192-840 192-202

TK-1101 Barber-Colman Single Temperature, Reverse Acting 192-841 192-203

TK-1001-116 Barber-Colman SingleTemperature,DirectActing 192-850 192-222

TK-1002 Barber-Colman SingleTemperature,DirectActing 192-840 192-202

TK-1002 Barber-Colman Single Temperature, Reverse Acting 192-841 192-203

TK-5001-116 Barber-Colman SingleTemperature,DirectActing 192-850 192-222

TKR-18 Barber-Colman SingleTemperature,DirectActing 192-840 192-202

TKR-18-91 Barber-Colman SingleTemperature,DirectActing 192-840 192-202

TKR-19 Barber-Colman Single Temperature, Reverse Acting 192-841 192-203

TKR-1001 Barber-Colman SingleTemperature,DirectActing 192-840 192-202

TKR-1101 Barber-Colman Single Temperature, Reverse Acting 192-841 192-203

2212-118 Robertshaw SingleTemperature,DirectActing 192-840 192-202

2212-119 Robertshaw Single Temperature, Reverse Acting 192-841 192-203

2212-128 Robertshaw SingleTemperature,DirectActing 192-840 192-202

2212-129 Robertshaw Single Temperature, Reverse Acting 192-841 192-203

2212-418 Robertshaw SingleTemperature,DirectActing 192-840 192-202

2212-419 Robertshaw Single Temperature, Reverse Acting 192-841 192-203

2212-518 Robertshaw SingleTemperature,DirectActing 192-840 192-202

2212-519 Robertshaw Single Temperature, Reverse Acting 192-841 192-203

T15-101 Robertshaw SingleTemperature,DirectActing 192-840 192-202

T18-101 Robertshaw SingleTemperature,DirectActing 192-840 192-202

T18-201 Robertshaw SingleTemperature,DirectActing 192-840 192-202

T18-301 Robertshaw SingleTemperature,DirectActing 192-840 192-202

T18-3011 Robertshaw SingleTemperature,DirectActing 192-840 192-202

192-202 Powers SingleTemperature,DirectActing 192-840 192-202

192-203 Powers Single Temperature, Reverse Acting 192-841 192-203

192-204 Powers Day(DA)18psi(124kPa)/Night(DA)25psi(172kPa)changeover 192-3044 192-204

192-205 Powers Day(RA)18psi(124kPa)/Night(RA)25psi(172kPa)changeover 192-3054 192-205

192-208 Powers Heat(DA)25psi(172kPa)/Cool(RA)18psi(124kPa)changeover 192-3084 192-208

192-222 Powers SingleTemperature,DirectActing 192-850 192-222

192-223 Powers Single Temperature, Reverse Acting 192-851 192-223

192-224 Powers Day(DA)18psi(124kPa)changeover/Night(DA)25psi(172kPa) 192-3144 192-224

192-225 Powers Day(RA)18psi(124kPa)changeover/Night(RA)25psi(172kPa) 192-3154 192-225

192-228 Powers Heat(DA)25psi(172kPa)changeover/Cool(RA)18psi(124kPa) 192-3184 192-228

Page 19: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-19

832DPneumaticRoomThermostat and screws.

DescriptionThe single setpoint, direct acting thermostat provides gradual acting pneumatic room temperature control for heatingandcoolingapplications.The832DThermostatisruggedlyconstructedfordependable,long-termservice.

Features• Allmetalconstruction• Rapidresponsetotemperaturechange• Uniquedesignofsupplyandexhaustairvalves

prevents waste• Quietoperation• Easy-to-calibrateandservice• Tamper-proofcoverscrews• Exposedremotechangeovercontrol• Calibratedthermometer

ApplicationsDesignedforcontrollingroomsheatedorcooledbyradiation, ventilation, or an air conditioning system, the 832DPneumaticRoomThermostatisversatileandresponsive for individual room control.

Other applications include room control of radiant panels, finnedradiation,andunitventilators.

Application DrawingDottedlinesarealternativecontrolschemes.

832 DPneumatic Room Thermostats

Page 20: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-20

Control Action .................................................................................DirectOperating Range ................................................. 60to85°F(15to30°C)Sensitivity Fixed ....................................................2.5psi/°F(31kPa/°C)Temperature Response ...................................................... 0.5°F(0.3°C)Maximum Ambient Temperature ........................................110°F(43°C)Dial Graduations .................................................................... 2°F(1.1°C)Normal Air Supply Pressure ......................................... 18psi(124kPa)

Maximum Operating Pressure ...................................... 30 psi (207 kPa)Dimensions .................................................. 2.88"Wx5.63"Hx2.19"D (73mmWx143mmHx56mmD)Air Consumption for Compressor Sizing .................. 10 scim (2.7 ml/s)Cover Style ....................................KeyorconcealedsetpointadjustmentCover Finish ......................................Silver;Specialorderotherfinishes.Shipping Weight ..............................................................3.0lb.(1.36kg)

order the calibration Kit in the accessories and service Kits section.

832 D Pneumatic Room Thermostat Specifications

Accessories & Service Kits A-75

832 D Pneumatic Room Thermostat Product Ordering

DescriptionThermostat

Part No.2Cover

AssemblyConcealedAdjustmentwithThermometer 832-0120 856-036ConcealedAdjustmentwithoutThermometer 832-0490 856-0461

ExposedKeyAdjustmentwithThermometer 832-0500 856-044ExposedKnobAdjustmentwithThermometer 832-1260 856-044

Ordering Notes1. Blindcover,856-046, does not include mounting screws, 856-014, that are required for installation.2. Doesnotincludeadjustmentkey,856-055, that is required for installation.

Thermostat comes complete

with cover.

TECH TIPto calibrate any pneumatic thermostat, perform the following:

1. Remove the cover.2. Measure the ambient temperature.3. Set the setpoint dial to the ambient temperature.4. Measure the controller output pressure (branch pressure).5. Turn the calibration screw(s) until the branch pressure equals the midpoint of the control span

[usually 8 psi (55 kPa)].6. Replace the cover.

Page 21: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-21

356LimitemRigidBulbThermostat.

DescriptionThe356LimitemRigidBulbThermostatisapneumaticallyoperated,duct-mountedthermostat,whichisavailableineither direct or reverse acting in a variety of ranges.

Features• Durablecoppermotortubeandsteelrodtemperature

sensing element• Two-valvedesignreducesairwaste• Ductmountinghardwareincluded• Allmetalconstruction• 18"(46cm)sensingtube

ApplicationsThe356LimitemRigidBulbThermostatprovidesprimarycontrol for unit ventilators, fan coils and other air handling units.Canalsobeusedaslowlimitcontrolforairflowtoacontrolled space.

Application DrawingsDottedlinesarealternativecontrolschemes.

2-pipe.

1-pipe.

356Limitem Rigid Bulb Thermostats

Page 22: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-22

Control Action ...............................................................DirectorReverseMaximum Supply Air Pressure ..................................... 30 psi (207 kPa)Sensitivity Range (adjustable) .............0.25to2psi/°F(3to25kPa/°C)Factory Sensitivity Setting .................................1.25psi/°F(15kPa/°C)Temperature Response .................................................... 0.50°F(0.9°C)Dial Graduations ................................................. 5°F(2.7°C)/2°C(3.6°F)Maximum Ambient Temperature Case ................................................................................. 200°F(93°C) Bulb(DirectActing).......................................................... 225°F(107°C) Bulb(ReverseActing)...................................................... 250°F(121°C)

Nominal Air Supply Pressure ................... 18to25psi(124to172kPa)Maximum External Pressure (on bulb) .................... 250 psi (1722 kPa)Mounting ....................................................................Flangeor3/8"NPTAir Connections .........................................................................1/8"NPTDimensions BulbLength .......................................................................18"(457mm) FlangeOD ........................................................................2.56"(65mm) Case .......................................................................1.5"Diameterx3"L (33mmDiameterx76mmL)Shipping Weight ..............................................................2.0lb.(0.91kg)

356 Limitem Remote Bulb Thermostat Specifications

356 Limitem Remote Bulb Thermostat Product OrderingControl Action Temperature Operating Range Part No.DirectActing 0to100°F(-18to+38°C) 356-0012DirectActing 30to180°F(-1.11to+82.2°C) 356-0750Reverse Acting 0to100°F(-18to+38°C) 356-0013Reverse Acting 30to180°F(-1.11to+82.2°C) 356-1005Reverse Acting 100to250°F(37.8to121°C) 356-1006

Accessories & Service Kits A-75

TECH TIPWhen using the Limitem as a one-pipe device, a 40 scim (11 ml/s) restrictor will limit your output to 80% of supply. A 20 scim (5 ml/s) restrictor will limit your output to 60% of supply.

Example: With a 20 scim (5 ml/s) restrictor and 25 psi (11.3 kPa) supply, your maximum output is 15 psi (6.8 kPa).

Page 23: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-23

357DLimitemRemote Thermostat with an average bulb.

DescriptionThe357DLimitemRemoteBulbThermostatisapneumatically-operatedthermostatthatisgradual,directacting with a remote or averaging bulb.

Features• Directactingonly• Remoteoraveragingbulbsforflexibilityininstallation• Liquid-filledsensingelementforrapidresponseto

temperature changes• Two-valvedesignreducesairwaste• Adjustablesensitivity

ApplicationsThe357DLimitemRemoteBulbThermostatprovidesprimary monitoring and control for air handling units or a low limit control.

Application DrawingsDottedlinesarealternativecontrolschemes.

2-pipe.

1-pipe.

357 DLimitem Remote Bulb Thermostats

Page 24: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-24

Control Action ..................................................................................DirectMaximum Supply Air Pressure ...................................... 30 psi (207 kPa)Sensitivity Range (adjustable) .......... 0.33to3.5psi/°F(4to43kPa/°C)Factory Sensitivity Setting ................................. 1.25psi/°F(15kPa/°C)Bulb ..........................................................................................Liquid-filledTemperature Response ....................................................... 0.5°F(0.3°C)Dial Graduations .................................................5°F(2.7°C),2°C(3.6°F)

Maximum Ambient Temperature (case) ............................. 180°F(82°C)Nominal Air Supply Pressure ....................18to25psi(124to172kPa)Mounting .........................................................................BracketsuppliedAir Connection ............................................................................1/8"NPTDimensions (Case) ..............................................1.75"Diameterx3.5"H (44.5mmDiameterx88.9mmH)Shipping Weight ................................................................ 2.0lb.(0.9kg)

357 D Limitem Remote Bulb Thermostat Specifications

357 D Limitem Remote Bulb Thermostat Product OrderingTemperature

Operating Range Sensing Element Capillary BulbMaximum

Ambient Temp. Part No.20to100°F(-6.7to+37.8°C) RemoteBulb 8'(2.4m) 3/8"x4'(0.95mmx10.2cm) 201°F(94°C) 357-00035to145°F(1.7to62.8°C) AveragingBulb 40'(12.2m) 3/32"x15'(0.24mmx457cm) 210°F(99°C) 357-0004

120to230°F(48.9to110°C) RemoteBulb 40'(12.2m) 3/8"x4"(0.95mmx10.2cm) 261°F(127°C) 357-000535to145°F(1.7to62.8°C) AveragingBulb 6"(15cm) 3/32"x8'(0.24mmx244cm) 211°F(99.4°C) 357-0001

Accessories & Service Kits A-75

Page 25: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-25

188UnitMountedThermostat.

ApplicationsThe188UnitMountedThermostatsaredesignedprimarilyfor use in fan coil induction units and unit ventilators to control the temperature within an occupied space. The thermostat’s temperature range is limited to applications at ambient temperatures.

DescriptionThe188UnitMountedThermostatisagradualactingthermostatwitharemotebulboperatingontheforce-balance principle, using pneumatic feedback to obtain linearity and maintain selected room temperature by positioning pneumatic devices to control heating or cooling.

Features• Liquid-filledthermalsystemtemperature

sensing element• Durabledie-castmetalcasewithruggedsetpointknob• Adjustablesensitivity• Universalmountingbracketforeasyinstallation• Integraladjustablelimitstops• Availableas: –DirectActingonly(Heating) –ReverseActingonly(Cooling) –HeatorCooldependingonsupplyairpressure

Typical Connections

188Unit Mounted Thermostats

Page 26: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-26

Control Action ...............................Heating/Cooling,DirectandReverse; Directonly;ReverseonlyOperating Range ........................................... 60to85°F(15.5to29.4°C)Operating Pressure ...............................................30 psi (207 kPa) max.Adjustment Sensitivity ........................1to5.25psi/°F(12to65kPa/°C)Factory Sensitivity Setting .................................2.25psi/°F(28kPa/°C)Temperature Response ...................................................... 0.2°F(0.1°C)Maximum Ambient Temperature Case .............................................................................. 135°F(57.2°C) Bulb ................................................................................231°F(111°C)Scale Graduations ............................................................... 1°F(0.55°C)Nominal Air Supply Pressure DirectorReverseActing............................................... 25 psi (172 kPa) Heating/Cooling .................................25psi(172kPa)/18psi(124kPa)

Average Air Usage 20 scim Restrictor.......................................................25scim(6.8ml/s) 40scimRestrictor.....................................................45scim(12.2ml/s)Air Connections ......... 1/4"(6mm)BrassbarbedforpolyethylenetubingBulb Size ............................................................ 3/8"Diameterx3-1/2"L (9.5mmDiameterx89mmL)Capillary Length ..................................................48"(121.9cm)approx.Finish ................................................Corrosion-resistantZincChromateDimensions (case) Heating/Cooling,ReverseActing.................... 3.1"Wx2.4"Hx2.13"D (100mmWx61mmHx54mmD) DirectActing ................................................... 3.1"Wx2.4"Hx1.38"D (100mmWx61mmHx35mmD)Shipping Weight ..............................................................3.0lb.(1.36kg)

188 Unit Mounted Thermostat Specifications

188 Unit Mounted Thermostat Product OrderingControl Action Changeover Pressure Average Air Usage Part No.

Single Setpoint DirectActing/25psi(172kPa) — 40scim(11ml/s) 188-0031

Single Setpoint ReverseActing(Cooling)18psi — 20 scim (5 ml/s) 188-0024

Heat/Cool DirectActing/ReverseActing(Cooling) 18psi(124kPa) — 40scim(11ml/s) 188-0030

Heat/CoolRetrolineDirectActing/ReverseActing 18psi(124kPa)/13psi(90kPa).Retroline replacement for Honeywell LP916BXXXX.

15 psi (103 kPa) 40scim(11ml/s) 188-0033

Heat/CoolRetrolineDirectActing/ReverseActing 20psi(138kPa)/15psi(103kPa).Retroline replacement for Johnson Controls T-3300-2.

17 psi (117 kPa) 40scim(11ml/s) 188-0034

Accessories & Service Kits A-75

Page 27: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-27

134PneumaticLowTemperatureDetectionThermostat.

DescriptionThe134HighandLowTemperatureDetectionPneumaticThermostatsautomatically“lockout”atsetpointandrequiremanual reset.

Features• Snap-actingpneumaticswitch• Sight-setcalibratedsetpointscale• Noleakageofairpriortoresetofswitch• Easily adjustable settings• Normallyclosedairvalve;bleedstolessthan2psi

(14kPa)whensuppliedthrougharestrictor• Barbfittingforpush-onconnectionof1/4"(6mm)

ODpolyethylenetubing• Holdsdead-endedlinetoapproximately22psi

(152 kPa) air pressure

ApplicationsThe134PneumaticHighandLowTemperatureDetectionThermostats are used on pneumatic heating and cooling systems in areas protected from the weather.

On a typical high limit application, the thermostat shuts down air conditioning or ventilating fans when the duct temperature becomes excessively high. A normally closed switch opens at setpoint.

On a typical low temperature application, the thermostat stops the fan or closes a damper when the temperature drops to the setpoint at any one foot (30.5 cm) or more of the sensing element.

Application Drawings

134Pneumatic High and Low Temperature Detection Thermostats

Page 28: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-28

Part No. 134-1700Ambient Temperature Range .............................Greater than setpoint to 140°F(60°C)Pneumatic Switch ...........................NC,0.020"(0.6mm)diameterbleedControl Point Low Temperature Thermostat ..............................Lowest temperature at any one foot section of the sensing bulbCase Finish ..............................................................GrayBakedEnamelShipping Weight ............................................................2.45lb.(1.11kg)

Part No. 134-1710Ambient Temperature Range .............................................-40to+140°F (-40to+60°C)Pneumatic Switch .............................NC,0.02"(0.6mm)diameterbleedControl Point Low Temperature Thermostat ..............................Lowest temperature at any one foot section of the sensing bulbCase Finish ..............................................................GrayBakedEnamelShipping Weight ............................................................2.38lb.(1.08kg)

Dimensionsshownininches(mm).

Dimensions

134 Pneumatic Thermostat Specifications

134 Pneumatic Thermostat Product Ordering

Temp.Temperature

Range DifferentialMax. Bulb

Temp.Bulb & Capillary

Length Switch Reclose Part No.

Low

15to55°F(-9to+12.8°C)with stop at 35°F(1.67°C)

5°F(2.8°C)Non-Adjustable

400°F(204°C) 20'(6m)

Temperature must increase by 5°F(2.8°C)beforepneumaticswitch can be reclosed.

134-1700

High 100to170°F (38to77°C)

10°F(5.6°C) Non-Adjustable

250°F(121°C)

2.7"(69mm)Dia.x10"(25.4cm)Lbulbwith6'(183mm)capillary

Temperaturemustdrop10°F(5.6°C)beforepneumaticswitch can be reclosed.

134-1710

Accessories & Service Kits A-75

Page 29: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-29

141ElectricLineVoltageRemoteBulbThermostat.

DescriptionThe141ElectricLineVoltageRemoteBulbThermostat isatwo-positionelectriclinevoltagethermostatwithremote bulb.

Features• Temperaturesensitive,liquid-filledsensingelement• Single-pole,double-throwsnap-actingswitches• Enclosedswitchessuitableforloworlinevoltage

power switching• Graybakedenamelcase

ApplicationsThe141ElectricLineVoltageRemoteBulbThermostatis used for temperature control in heating and cooling application,typicallytodirectlyoperatetwo-positiondamper motor actuators, motor actuated valves, relays and similar equipment. Typical applications includes summer-winterchangeoverandthedirectcontrolof liquidorairtemperatureswheretwoposition(ON-OFF)control is acceptable.

Typical Connections

YELLOW

BLUE

RED (COM)

CLOSE ON RISEOF TEMPERATURE

OPEN ON RISEOF TEMPERATURE

141Electric Line Voltage Remote Bulb Thermostats

Page 30: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-30

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Inductive Amps FullLoadAmps 120Vac ..........................................................................................7.4 240Vac ..........................................................................................3.7 Locked Rotor Amps 120Vac ........................................................................................44.5 240Vac ........................................................................................22.2

141 Electric Line Voltage Remote Bulb Thermostat Specifications

141 Electric Line Voltage Remote Bulb Thermostat Product OrderingTemperature Scale Range Max. Bulb Temp. Bulb Size Switch Differential Part No.

0to120°F(-7to+49°C) 130°F(54°C).038"Diameterx4.03"L

(9.9mmDiameterx102mmL)Capillary6'(183cm)

Adjustable6to30°F (3to16°C) 141-0520

100to240°F(38to110°C) 250°F(121°C).029"Diameterx2.33"L

(7.4mmDiameterx59.2mmL)Capillary6'(183cm)

Adjustable7to45°F (14to25°C) 141-0521

Accessories & Service Kits A-75

Resistive Amps 120Vac ...............................................................................................25 240Vac ...............................................................................................20Dimensions .................................................... 2.5"Wx5.38"Hx2.31"D (64mmx(136mmx59mm)Shipping Weight ..............................................................1.8lb.(0.82kg)

Page 31: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-31

134ElectricLineVoltageRoomThermostat—Heating/Cooling.

ApplicationsThe134ElectricLineVoltageRoomThermostat controlsheatingandcoolingapplicationsoryear-round air conditioning units in commercial, industrial, or residential installations.

DescriptionThe134ElectricLineVoltageRoomThermostatisa line voltage On/Off room thermostat for heating and cooling applications.

ModelsareavailablewithSPSTorSPDTcontactactionandforstandard,nominal1/4hp/10ampsnoninductive,or heavy duty, nominal 1 hp / 22 amps noninductive applications.

Features• Singlesetpointdial• Exposedbimetalthermometer• Temperaturerangefrom50to90°F(10to30°C)• Highandlowlimitstops• Standardorheavydutymodels• DualFahrenheit/Celsiusscaleplate

Typical Connections

134Electric Line Voltage Room ThermostatsHeating/Cooling

Page 32: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-32

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Part No. 134-1083Motor Rating 120Vac ...........................................................................................6.0A 240Vac ...........................................................................................3.7 ASwitch Action ........................................SPSTwith“Auto-Off-Fan”switchDimensions .................................................. 2.78"Wx5.19"Hx1.88"D (71mmWx132mmHx48mmD)Shipping Weight ..............................................................1.3lbs.(0.6kg)

Part No. 134-1086Motor Rating 120Vac ...........................................................................................6.0A 240Vac ...........................................................................................3.0 ASwitch Action .................................................................................. SPSTDimensions ....................................................... 3"Wx4.75"Hx1.44"D (75mmWx120mmHx36mmD)Shipping Weight 1.3lb.(0.6kg)

Part No. 134-1084Motor Rating 120Vac ...........................................................................................6.0A 240Vac ...........................................................................................3.0 AResistive Rating 120Vac ..................................................................................10.0 amps 240Vac ..................................................................................10.0 ampsSwitch Action ..................................................................................SPDTDimensions ....................................................... 3"Wx4.75"Hx1.44"D (75mmWx120mmHx36mmD)Shipping Weight ................................................................1.0lb.(0.6kg)

Part No. 134-1085Motor Rating 120Vac ...........................................................16.0Heating/8.0Cooling 240Vac .............................................................8.0Heating/8.0CoolingResistive Rating 120Vac ..............................................................................22.0Heating 240Vac ..............................................................................22.0HeatingSwitch Action ..................................................................................SPDTDimensions ....................................................... 3"Wx4.75"Hx1.44"D (75mmWx120mmHx36mmD)Shipping Weight ................................................................1.0lb.(0.6kg)

134 Electric Line Voltage Room Thermostat Specifications

134 Electric Line Voltage Room Thermostat Product OrderingSwitch Action Temp. Set Point Range Temp. Set Point Adjustment Temperature Difference Part No.

SPST 40to90°F(5to30°C) Concealed 1.8°F(1°C) 134-1083

SPST 40to90°F(5to30°C) Concealed 1.8°F(1°C) 134-1086

SPDT 40to90°F(5to30°C) ExposedKnoborConcealed1 1.8°F(1°C)Heating 2.31°F(1.3°C)Cooling 134-1084

SPDT 40to90°F(5to30°C) ExposedKnoborConcealed1 3°F(1.7°C)Heating 3.5°F(2°C)Cooling 134-1085

Ordering Note1. Each thermostat is shipped with a blank faceplate for use when concealed adjustment is desired.

Accessories & Service Kits A-75

Page 33: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

www.usa.siemens.com/hvac

Thermostats

A-33

RAA10CFanCoilThermostatwith concealed setpoint knob.

RAA20U Room Thermostat with exposed setpoint knob.

ApplicationsThe RAA… Electric Room Thermostats are typically used in public buildings, storage rooms, entrance hallways and maintenanceroomswheretwo-position(On/Off)control is required.

Descriptions of models are as follows:RAA10Cmodelisaheatingorcoolingonlythermostatthat has a concealed setpoint knob for use in areas where setpoint adjustment is limited to authorized personnel. Typical applications are frost and overheat protection and temporary heat for buildings under construction.

RAA20U model is a heating or cooling only thermostat that has an external setpoint knob for occupant adjustment.

Note:ARG 70 wall plate is required in order to be UL compliant for switching line voltage.

The RAA… Room Thermostats are designed for either simpleheatingorcoolingorfor2-pipeheatingandcoolingsystems where fan control is not required.

DescriptionDesignedforsimpleheatingorcoolingorheating/coolingapplications, RAA… Electric Room Thermostats are an attractiveandeconomicalsolutionthatutilizetwo-wire, gas membrane technology.

RAA… Electric Room Thermostats are available in singlescaleFahrenheitorCelsiusmodels,excepttheRAA10C,withmodelsfordrywallorelectricalwallboxmounting. Models designed for wall box mounting include wall box plate adapter and screws.

Features• Two-pointcontrolalgorithmforon/offcontrol• 24to120,277Vacline• Twomountingstyles:electricalwallboxordrywall• DualFahrenheit/Celsiusscale(RAA20U)

Options• Tamperproofcover(concealedsetpointknob)noted

withaC• Availablewithwallplate

RAA…Electric Room Thermostats

Page 34: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

A-34

Part no. in black box ships same day when requested through rapid responsetM shipping. see inside back cover for details.

Operating Voltage ......................................................24to120,277VacFrequency ..............................................................................50or60HzSetpoint Adjustment Range .............................. 50to85°F(10to29°C)Switching Differential ......................................................... <1.8°F(1°C)Switch Rating ............................................. 6ARES,3.5AFLA,12ALRATime Constant ...............................................................................14min.Switch Action Output ..................................SPDTTwo-position(On/Off)Operation–Conditions Operating Temperature .................................... 32to122°F(0to50°C) RelativeHumidity ...................................................................<95%RH

Transportation/Storage Conditions Temperature ...............................................-4to+122°F(-20to+50°C) RelativeHumidity ...................................................................<95%RHHousing Material ........................................................................................Plastic Color ............................................................................................White Bellows ..................................................... Environmentally-friendlygasWiring ........................................................... Screw terminals for wires of 2x16AWGor1x14AWG,20AWGmax.Agency Listings ........................................ConformstoCErequirements ULlistedto873 cULlistedtoCanadianstandardC22.2No.24-93Shipping Weight ............................................................0.31lb.(0.14kg)

RAA Electric Room Thermostat Specifications

RAA Electric Room Thermostat Product Ordering

DescriptionElectric Wall Box1

Part No.Dry Wall Part No.

Thermostat for heating or cooling only RAA10CW RAA10CThermostat for heating or cooling only with exposed setpoint knob RAA20UW RAA20U

Ordering Note1. Includeswallplate,ARG70, to be UL compliant for switching line voltage.

Accessories & Service Kits A-75

Page 35: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

RAA10C... Thermostat

Wall Plate (ARG70) for Mounting (RAA10CW and RAA20UW)

Dimensionsshownininches(mm).

3.80(96.4)

3.92

(99.

6)

1.42(36)T

H05

03R

2RAA20U... Thermostat

3.80(96.4)

3.92

(99.

6)

1.68(42.8)T

H04

97R

2

RAA Electric Room Thermostat DimensionsTherm

ostats

A-35

www.usa.siemens.com/hvac

Page 36: Thermostats - HVAC USA Pages_1-36.pdfLimitem Remote Bulb Thermostats TH 357 155-071P25 a-23 Unit Mounted Thermostats TH 188 155-064P25 a-25 High and Low Temperature Detection Thermostats

Ther

mos

tats

www.usa.siemens.com/hvac

A-36

RAA Electric Room Thermostat Engineering Drawings

Wiring Diagrams

HeatingMode CoolingMode

RAA10C…/RAA20U…

KeyD1 HeatingdeviceD2 CoolingdeviceL Operating voltageN NeutralN1 Room thermostat

S On/Off switchT ThermostatW HeatingcontroloutputY Coolingcontroloutput

Operating Diagrams

HeatingMode CoolingMode

KeyT Room temperatureSD Switching differentialSP Room temperature setpoint

W HeatingoutputsignalY Coolingoutputsignal

RAA10C…/RAA20U…