Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings XIII Conference, Dec X 2016

Transcript of Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried...

Page 1: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

Thermal and Moisture Performance of Buried Ducts

Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens CorningBuildings XIII Conference, Dec X 2016

Page 2: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

2

Outline

• Background for the study

• Buried ducts in building codes

• Approach

• Results

• Discussion and conclusions

Page 3: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

3

High Performance Attic & Duct Solutions

Ducts in

Vented

Attic

Ducts in

Conditioned

Space

Unvented

Attic

Hybrid Attic Buried

Ducts

CURRENT PRACTICE

HIGH

PERFORMANCE

ATTICS & DUCTS

Page 4: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

4

Energy & Moisture Physics

Bill Miller, ORNL

Page 5: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

5

Building Science (System Approach)

Three critical competencies

Modeling FieldLab

Page 6: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

6

6722.56952.4

7432.7

3307.3 3420.83657.7

2535.7 2604.92771.3

1225 1264.1 1340.5

0

1000

2000

3000

4000

5000

6000

7000

8000

R30 R30 R30 R30 R30 R30

d06-R06-L04 d06-R06-L06 d06-R06-L10 d06-R12-L04 d06-R12-L06 d06-R12-L10

0.9

1: 300

Vented

Cooling, kWh

Heating, kWh

Effect of Duct Insulation !!!

AUSTIN

51 %

Improvement

Page 7: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

7

6722.56500.3

6952.46724.4

7432.77192.9

3307.3 3197.43420.8 3308.1

3657.7 3539.2

2535.72379

2604.92450.3

2771.32601.3

1225 1154.4 1264.1 1186.41340.5 1270.1

0

1000

2000

3000

4000

5000

6000

7000

8000

R30 R49 R30 R49 R30 R49 R30 R49 R30 R49 R30 R49

d06-R06-L04 d06-R06-L06 d06-R06-L10 d06-R12-L04 d06-R12-L06 d06-R12-L10

0.9

1: 300

Vented

Cooling, kWh

Heating, kWh

Effect of Attic Insulation Level!!!

AUSTIN

Page 8: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

8

2930.8 2940.8

3163.33272.6

3578.93721.4

1016.9 1024.7

1208.6 1245.41149.9 1182.6

0

500

1000

1500

2000

2500

3000

3500

4000

R30 boxed FG R30 boxed FG R30 R30 R30 R30

d06-R08-L00 d06-R08-L02 d06-R08-L00 d06-R08-L02 d06-R08-L00 d06-R08-L02

0.9 0.9 0.9

1:3000 1: 300 1:3000

Sealed Vented

Cooling, kWh

Heating, kWh

Effect of Attic Type (Vented vs Unvented)

AUSTIN

19 %

Improvement

Page 9: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

9

3288.2

2951.1

2710 2678.3 2667.8 2650.1

1140.21033

1176.6 1141.6

900.1 886.5

0

500

1000

1500

2000

2500

3000

3500

R22 sealed ocSPF R30 boxed FG R30+R10 R30+R10 R30+R10 R30+R10

d06-R08-L04 d06-R08-L04 d06-R12-L04 d06-R08-L04 d06-R12-L04

0.9 0.9 0.9

1:3000 1: 300 1:3000

Sealed Vented

Cooling, kWh

Heating, kWh

Effect of Attic Type (Unvented vs Hybrid)

AUSTIN

2.5 %

Difference

Page 10: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

10

Background

• Ducts in vented attics are penalized by the cold winters and hot summers

• The energy codes are pushing the idea to bring the ducts into conditioned space

• Burying the ducts inside the attic insulation in the ceiling would effectively increase the R-value of the duct towards the attic

• The blown-in insulation in the attic is vapor permeable which may cause a condensation risk

• The condensation risk has been largely not well-known despite of previous studies

Page 11: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

11

Literature on buried ducts previously states encapsulation in moist/humid climates

DOE Zero Energy exception to ducts in conditioned space (Apr ’14)

U.S. Dept. of Energy Building America Measure Guideline (Aug ’13)

Buried Ducts (dry climate) Buried and Encapsulated Ducts

(humid climate)

Determine if ducts can be strictly buried in humid climates without condensation concerns

DOE Zero Energy Ready Home National Program Requirements (Rev. 04) April 21, 2014.

Chapiro, C.; Zoeller, W.; and Mantha, P. (2013). Measure Guideline: Buried and/or Encapsulated Ducts. Golden, CO: National Renewable Energy Laboratory.

In moist and marine climates minimum of R-8 duct insulation with min. 1.5”

of closed-cell spray foam encapsulating the ducts

Page 12: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

12

Previous Work (Building America-Steven Winters)

Page 13: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

13

Previous (Building America-HIRL D. Mallay)

•The monitored data from the South Carolina

test house indicates that R-8 duct insulation

appears to be sufficient to prevent condensation.

• Regarding energy loss, the leakage rate of 1-2

CFM/100SFcfa for the attic ducts was selected

as a reasonable and achievable target.

•The buried ducts delivered colder air during

cooling than the attic ducts that were not buried

(on average nearly 7°F colder). The lower

delivery temperature results in increased energy

savings and improved occupant comfort.

•Simulations predicted 21% annual

heating/cooling site energy savings compared to

conventional insulated attic ducts. The compact

duct component contributed approximately 13%

of this energy savings, and the buried duct

component contributed approximately 8%

Develop design criteria for

buried ducts that use common

materials and do not rely on

encapsulation using spray foam

or disrupt traditional work

sequences.

Page 14: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

14

Is Encapsulation Needed?

• Previous studies by others resulted in a requirement to seal the ducts with 1.5” of closed cell spray foam insulation in addition to the existing duct insulation

• Consider that existing homes already have short “buried” duct section where the duct connects to the duct boot to supply air through ceiling

• No condensation issues

• The existing requirements for buried ducts have likely been overly cautious

Page 15: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

15

Approach (Three Prong Approach)

• Hygrothermal modeling of buried ducts exposed to constant and varying climatic conditions (DYNAMICS)

• Small-scale laboratory study

• Field testing

Modeling Lab-Scale Field Evaluation

Thermal and

moisture analysis

for condensation

• Relative humidity

• Vapor pressure

• Temperature

• Dew point

• Square vs round

ducts

• OH climate (5A)

• SC climate (3A)

Lab-scale buried duct

mimic evaluating %RH

and condensation

• Duct type

• Duct R-value

• Loosefill R-value

• “Attic” temperature

and % RH

• Duct temperature

Monitoring residential buried

duct installations for

condensation

• OC – monitoring buried ducts

in Cleveland, OH model home

• Plus: HIRL – monitoring

compact buried ducts in Lady’s

Island, SC.

Page 16: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

Simulation Results

Page 17: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

17

Buried Ducts in Hot and Humid Attic

2-D Hygrothermal Model

• Attic = 130F, 30%RH (90F dew point)

• Duct = 55F

• Held constant for 1 week.

4” R-8 round duct

4” R-8 square duct

4” R-8 square

duct, deeply

buried

8” R-8 square

duct, deeply

buried

• Round and square have different effective R-values vs

Nominal R-value

• Location where duct may condense is typically mid-

depth of blown insulation or above duct where vapor

drive is coming from.

Page 18: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

18

Simulations in Climatic Conditions

• Mid-summer is not necessarily the most

severe time of the year for

condensation.

• Early fall may be most severe time.

Full year simulation for Charleston, SC

• Constant duct temp. (45F, 50F, 55F)

• On-Off schedule (55F on-time)

Page 19: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

19

Simulations in Climatic Conditions

• End of August is when highest %RH occurs on

top of the duct.

Full year simulation for Cleveland, OH

• Simulated attic conditions

• Constant duct temp. (55F)

• R38 and R49 loosefill level

Page 20: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

20

Duct Buried in Insulation

•12” Loose Fill

•R8 all around vs. R8 bottom+R12 on sides and top

•Attic conditions

•Indoor conditions

Duct Condensation Analysis – Charleston SC

R8 vs R12 (6” square duct)

Page 21: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

21

Attic Conditions

•Temperature and Relative Humidity in the attic simulated

with WUFI-Plus for a vented attic in Charleston SC

Page 22: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

22

Summer T, RH and Water Content

•R8

•10am in the morning

Page 23: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

23

Summer T, RH and Water Content

•R12

•10am in the morning

Page 24: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

24

Summer T, RH and Water Content

•R12

•2pm in the afternoon

Page 25: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

25

RH on top and side of duct

•R8 experiences condensation

Page 26: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

26

RH on top and side of duct

•RH<100%

No condensation

with R12

Page 27: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

Laboratory Testing

Page 28: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

28

Laboratory testing for condensation

dry water contact irreversible

Page 29: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

29

Laboratory testing for condensation

Series of testing with many variables

Variables Output

Duct temp (controlled) Duct surface temp (2” height increments)

Attic temp (controlled) Duct surface %RH (2” height increments)

Attic %RH (controlled) Visual moisture indication

“Indoor” conditions (not actively

controlled)

Loosefill level

Duct type

Duct R-value

Page 30: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

31

Laboratory testing results

30%

40%

50%

60%

70%

80%

90%

100%

0 5000 10000 15000 20000 25000 30000

Elapsed Time (minutes)

%RH at different positions along R8 flex duct

0" above ceiling 2" above ceiling 4" above ceiling

6" above ceiling 8" above ceiling 10" above ceiling - represents enclosed %RH

30%

40%

50%

60%

70%

80%

90%

100%

0 5000 10000 15000 20000 25000 30000

Elapsed Time (minutes)

%RH at different positions along R8.7 duct board

0" above ceiling 2" above ceiling 4" above ceiling

6" above ceiling 8" above ceiling 10" above ceiling - represents enclosed %RH

a b

Set-Point Average

Duct conditioning 55F 54.9F

Attic conditioning 77F, 80% RH 78.4F, 80.7% RH

“Indoor”

conditioningNot controlled

68.5F, 50.7% RH(min. RH = 38%, max = 73.2%)

Example buried duct experiment – Extreme S. Carolina conditions

• Ducts: R-8 flex, R-8.7 duct board

• Attic insulation: R-38 (no mounding)

• Run time: 22 days (100% cooling air on)

• Measured %RH around flex and board

• Black line = %RH within “indoor” space

• 8” and 10” flex sensors maintained max humidity for duration of test

Page 31: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

32

Laboratory testing results

30%

40%

50%

60%

70%

80%

90%

100%

0 5000 10000 15000 20000 25000 30000

Elapsed Time (minutes)

%RH at different positions along R8 flex duct

0" above ceiling 2" above ceiling 4" above ceiling

6" above ceiling 8" above ceiling 10" above ceiling - represents enclosed %RH

30%

40%

50%

60%

70%

80%

90%

100%

0 5000 10000 15000 20000 25000 30000

Elapsed Time (minutes)

%RH at different positions along R8.7 duct board

0" above ceiling 2" above ceiling 4" above ceiling

6" above ceiling 8" above ceiling 10" above ceiling - represents enclosed %RH

a b

Set-Point Average

Duct conditioning 55F 54.9F

Attic conditioning 77F, 80% RH 78.4F, 80.7% RH

“Indoor”

conditioningNot controlled

68.5F, 50.7% RH(min. RH = 38%, max = 73.2%)

Example buried duct experiment – Extreme S. Carolina conditions

• Ducts: R-8 flex, R-8.7 duct board

• Attic insulation: R-38 (no mounding)

• Run time: 22 days (100% cooling air on)

• 10” board sensor maintained max humidity

for duration of test

• 8” board sensor reached max humidity

during periods of high “indoor” humidity

Page 32: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

33

Laboratory testing results

• Flex duct: visible moisture on surface,

loosefill moist in vicinity, but not in all areas.

Some indicator pieces unchanged while

others turned red.

• No dripping onto drywall prior to

moving ducts during observation.

• Duct board: no visible moisture in areas

of sensors, did not feel wet. No change in

indicator tape near sensors. Moisture

along top and edge at elbow. Tape

changed to red in top middle.

• No dripping onto drywall prior to

moving ducts during observation.

Page 33: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

Field Testing

Cleveland OH

Page 34: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

35

Buried duct field testing (Cleveland, OH)

• A model home in Cleveland, OH with buried ducts that was outfitted with

sensors for evaluation

Field Evaluation – Data Collection Temp / %RH Sensors

• Flex Duct

• 0”, 3 ½”, 7”, 9” (distance

up from bottom of duct)

• Loosefill

• 0”, 3 ½”, 7”, 9” (distance

up from drywall)

• Duct Air (flex duct core)

• Attic Ambient (attic air space)

• Indoor (upstairs bedroom)

• Outdoor (outside deck)

• T/RH sensors installed around R8 flex duct

• T/RH sensors installed through loosefill

• R49 loosefill installed in the attic

Page 35: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

36

Buried duct field testing (Cleveland, OH)

Data collection Feb 2016-Mar 2016

During cooling season, %RH increases

• Elevated humidity (≥ 90%)

observed during limited days May

– September.

• Measured periods of elevated

humidity followed by low humidity.

Maximum

Observed

%RH

Hours

≥ 80% RH

Hours

≥ 85% RH

Hours

≥ 90% RH

Hours

≥ 95%RH

Flex 0” (bottom) 88% 37 9.5 0 0

Flex 3.5” (middle) 96% 176 74.5 22 2

Flex 7” (middle) 96% 122.5 39.5 12 1

Flex 9.5” (top) 97% 126.5 49.5 13.5 1.5

During heating season, %RH around

flex duct remains low.

Page 36: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

37

Condensation Indicators

• No sign of condensation around the flex ducts

Page 37: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

38

Summary

• Attics experience very dynamic conditions

• Steady-state analyses can be misleading and result in overly conservative designs

• The laboratory and field tests as well as numerical simulations indicate that R-8 duct insulation could be sufficient to avoid condensation problems in deep buried ducts in moist climates

• Simulations and field tests did not show moisture accumulation that would have resulted in dripping water or wet insulation

Page 38: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

39

Conclusions

• Currently the majority of residential homes that have ducts in vented attics have buried ducts

• The hanging ducts that connect to the duct boots through the insulation layer have been working fine

• The results from the work suggest that R-8 buried duct system performs well in Climate Zone 5A

• Cost effective new options to drive energy saving

• Based on multiple studies, new building codes (ICC 2018) will include:

Page 39: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

40

Buried Duct Code Proposal

R403.3 Ducts

R403.3.6 Ducts buried within ceiling

insulation

1. Supply and return ducts insulated with ≥

R-8

2. Sum of ceiling insulation R-values above

and below duct ≥ R-19 (excluding duct R-

value)

3. CZ 1A, 2A, 3A where

supply ducts are

completely covered

with ceiling insulation

should be insulated

with ≥ R-13 and vapor

retarder

R403.3 Ducts

R403.3.6 Ducts buried within ceiling

insulation

R403.3.6.1 Deeply buried effective R-value

1. Installed according to R403.3.6

2. On or within 5.5” of ceiling board and

surrounded with ≥ R-30 attic insulation

and top of the duct is minimum 3.5” below

insulation

3. Claim effective R-value

of R-25 for deeply

buried section

R403.3 Ducts

R403.3.6 Ducts buried within ceiling

insulation

R403.3.7 Ducts located in conditioned

space

1. Duct system located completely within

continuous air barrier and building

thermal envelope

2. Installed according to R403.3.6

3. Air handler within continuous air barrier

and building thermal envelope

4. Duct leakage (rough-in

ducts or post-

construction total

system to outside) ≤

1.5CFM/100SF CFA

5. Ceiling insulation

immediately above

insulated duct ≥

proposed ceiling R-

value minus insulated

duct R-value

Page 40: Thermal and Moisture Performance of Buried Ducts · Thermal and Moisture Performance of Buried Ducts Mikael Salonvaara, Katrina Keeley and Achilles Karagiozis Owens Corning Buildings

THE PINK PANTHER™ & © 1964–2015 Metro-Goldwyn-Mayer Studios Inc. All Rights Reserved. The color PINK is a registered trademark of Owens Corning. © 2015 Owens Corning. All Rights Reserved.

Thank you.