The maintenance manager's guide to circuit protection

download The maintenance manager's guide to circuit protection

of 16

Transcript of The maintenance manager's guide to circuit protection

  • 8/14/2019 The maintenance manager's guide to circuit protection

    1/16

    Powe

    rQuality

    Maintenance Managers Guide

    Power Quality

    The Maintenance Managers Guide

    to circuit protection

    Hydraulic-magnetic CB operation; a, b, c - overcurrent; d - fault current

  • 8/14/2019 The maintenance manager's guide to circuit protection

    2/16

    Power Quality

    2

    www.leonardo-energy.org

    1. Why is circuit protection installed?

    The primary objective of Electrical Installation Practice is to provide an

    installation that is safe and functional. Since it is inevitable that faults will

    sometimes occur in electrical systems and the appliances that they

    supply, steps need to be taken to ensure that the safety of people and

    property is maintained. For the protection of people, exposure to

    dangerous voltages must be prevented by, for example, good insulation of

    live parts, proper earthing and earth fault detection. For property

    protection it is necessary to prevent over-currents that could causeoverheating and fire and fault current, i.e. the uncontrolled flow of energy

    that might lead to ignition or explosion. This document is concerned

    primarily with protection against the effects of over-currents and fault

    currents, but, of course, the rapid disconnection of faults enhances safety

    by reducing the risk of exposure of people to dangerous voltages.

    Typically, electrical installations follow a tree architecture, the root of

    which is the point of common coupling (PCC) where there is a protective

    device provided by the energy supplier. At this point, the supply is definedin terms of capacity the maximum power that can be normally drawn

    and the prospective short circuit current the maximum short circuit

    current that could flow through a solid short circuit applied at the PCC.

    Next in line are the installations main switch and distribution board where

    the supply splits into a number of sub-circuits, which may be final circuits

    or feeders to other sub-distribution boards, each with a protective device,

    as shown in Figure 1.

    Figure 1 Generic installation topology

  • 8/14/2019 The maintenance manager's guide to circuit protection

    3/16

    The Maintenance Managers Guide to circuit protection

    3

    www.leonardo-energy.org

    2. How are protective devices selected?

    At every point where the current carrying capacity of the conductor

    changes (e.g. points a to d), there is a circuit breaker, for which there are

    three specific requirements:

    it must be capable of breaking the maximum prospective fault current

    at that point

    it must respond to over-current in such a way as to disconnect the

    circuit before the excess heat generated in the load circuit cable is

    sufficient to damage the cable or materials in contact with it

    it must limit potential damage to the load circuit by limiting the

    magnitude, duration or energy of a fault current to a safe level while

    disconnecting the circuit from the supply.

    In an ideal situation, only the breaker for the faulted circuit will open,

    disconnecting the fault and leaving the rest of the installation unaffected.

    This is essential for critical loads, but it is often difficult to achieve

    completely at an affordable cost, so alternative strategies are also used.

    3. Prospective fault current

    The prospective fault current is the maximum current that could flow at a

    particular point of the installation if a solid short circuit were to be applied

    there. The prospective fault current depends on the supply impedance at

    that point, including the source impedance and all cables and accessories

    in the circuit, so, assuming that there are no transformers, it decreases as

    electrical distance from the source increases.

    The prospective fault current is very important in the selection of the

    protection strategy and of the individual protection devices. Every

    protective device must be either capable of breaking this current (at its

    position in the installation) without excessive arcing and without being

    damaged in the process or must be assisted to do so by an upstreamcircuit breaker. This is discussed further under Selectivity or

    discrimination.

  • 8/14/2019 The maintenance manager's guide to circuit protection

    4/16

    Power Quality

    4

    www.leonardo-energy.org

    4. Circuit breakers

    There are three main types of circuit breaker used within installations:

    Miniature circuit breakers, MCBs, are used in residential, commercial

    and industrial applications for final sub-circuit protection. They are

    relatively cheap, compact and available in a wide range of ratings (5

    to 100 A), but have limited breaking capacity, typically 6, 10 or 15 kA.

    Moulded case circuit breakers, MCCBs, are designed to high

    breaking current capacity with low let-through energy. They are

    available in frame sizes from 100 A up to about 3000 A forinstallations where the prospective short circuit fault currents could be

    as high as 100 kA. The characteristics are not standardised and the

    trip levels and trip times are often adjustable to provide the desired

    type and level of discrimination.

    Air circuit breakers, ACBs, are more correctly defined as Power

    Circuit Breakers, with the fundamental difference being that the short

    time withstand current of the ACBs is equal to the interrupting rating.

    5. Characteristics

    A typical CB characteristic curve is shown in Figure 2.

    Figure 2 Characteristic curve of a circuit breaker

  • 8/14/2019 The maintenance manager's guide to circuit protection

    5/16

    The Maintenance Managers Guide to circuit protection

    5

    www.leonardo-energy.org

    The so-called inverse time part of the characteristic is designed to protect

    against over-current. It allows for substantial short overloads without

    tripping, because the rate at which the cable conductor temperature rises

    due to the extra heat generated is relatively slow due to the high specific

    heat of the copper conductors. As the over-current level increases, the

    time to respond reduces rapidly to restrict the rise in temperature and

    reduce the risk of damage. The characteristic takes advantage of the

    inherent short time over-current tolerance of the cable and allows short

    duration inrush currents to flow without tripping the breaker.

    The instantaneous characteristic is intended to respond very rapidly to

    fault current. Fast action is needed because fault currents are high

    enough to pose a high risk of damage to load circuits.

    The most common to achieving these characteristics is the thermal-

    magnetic breaker. The thermal characteristic is provided passing the

    load current through an element including a bi-metal strip which deflects

    according to its temperature. Once a set deflection has been reached, the

    mechanism is tripped, disconnecting the load circuit. Since the trip issensitive to temperature, a relatively small over-current will build up heat

    and eventually cause tripping over an extended time, while a larger over-

    current will heat up and cause tripping in a shorter time. In this area of

    operation, the device will not respond to very short duration over-currents.

    The magnetic characteristic is intended to protect against fault currents. It

    is provided by a small solenoid which exerts a force on the release

    mechanism. At a predetermined multiple of the rated current, the force is

    sufficient to operate the trip mechanism, and the load circuit is

    disconnected.

    Breaking fault current rapidly is not easy. Without special measures, an

    arc will form as the contacts separate which will be sustained until the next

    current zero crossing point. It is possible that a half cycle of fault current

    will flow, feeding a relatively large amount of energy into the fault.

    Reducing the energy supplied to the fault requires rapid opening of the

    contacts and fast quenching of the arc.

  • 8/14/2019 The maintenance manager's guide to circuit protection

    6/16

    Power Quality

    6

    www.leonardo-energy.org

    To ensure rapid opening, the contacts are designed (Figure 3) so that the

    magnetic force generated by the current flowing up one contact and down

    the other tends to push the contacts apart.

    Figure 3 MCB construction

    As the contacts part, an arc is formed and current continues to flow. The

    arc suppressor, a stack of U-shaped steel plates forming a channel

    around the contacts, extinguishes the arc. The magnetic field produced

    by the arc forces the ionised gasses into the plates, rapidly cooling and

    dividing the gasses and so breaking the arc.

    Figure 4 Arc quenching during MCB operation

  • 8/14/2019 The maintenance manager's guide to circuit protection

    7/16

    The Maintenance Managers Guide to circuit protection

    7

    www.leonardo-energy.org

    An alternative method to achieving the inverse-time operating

    characteristic in circuit breakers, is to use a hydraulic-magnetic principle.

    The device consists of a solenoid with a moving core which is normally

    displaced by a spring so that it is outside the magnetic circuit. The core is

    sealed within a cylinder filled with viscous silicone oil so that its movement

    is rate limited or damped. The moving armature is coupled to the tripping

    mechanism such that when the armature is attracted to the solenoid pole

    piece, the breaker will trip.

    Under normal load current the magnetic force generated by the air cored

    coil is insufficient to overcome that exerted by the spring, so no movement

    takes place (a).

    Upon the occurrence of an over-current, the magnetic force induced in the

    coil exceeds that of the opposing spring. The magnetic core moves

    towards the pole piece at a rate determined by magnetic force, the

    viscosity of the silicone oil and the mechanical clearance between the

    magnetic core and the enclosing tube (b). In due course, the magneticcircuit is completed and the armature is attracted, tripping the circuit

    breaker (c). The actual time-current characteristic in such devices is

    easily controllable through a combination of the opposing spring force and

    the viscosity of the silicone oil that is sealed inside the tube assembly.

    At very high currents, such as a fault current, the magnetic field generated

    by the air-cored coil is sufficiently strong to attract the moving armature

    without the core being in the energised position, so the breaker trips

    instantaneously (d).

    Figure 5 Hydraulic-magnetic CB operation; a, b, c - overcurrent; d - fault

    current

  • 8/14/2019 The maintenance manager's guide to circuit protection

    8/16

    Power Quality

    8

    www.leonardo-energy.org

    Electronic sensing for over-current and fault circuit protection in circuitbreakers is generally restricted to higher current devices for the present,

    mainly due to cost considerations. On the other hand, electronic sensing

    has resulted in a step-function improvement in both the reliability and

    performance of sensitive earth leakage protection, whilst costs have been

    held within affordable limits.

    The use of electronic sensing allows much more accurate protection and

    enables developments such as annunciators, true RMS protection and

    communication between circuit breakers. Once cost restrictions have

    been overcome, technologies such as load and fault signature recognition

    could become a reality. Intelligent circuit protection is likely to have

    applications in future Smart homes.

    6. Practical Characteristics

    In practice, as with any other manufactured device, the performance

    characteristics of circuit breakers are subject to variation. For MCBs, the

    thermal characteristic which provides protection against over-current

    the following test points are given in Standards EN 60898:

    This relates to practice as follows. The circuit is designed to provide

    power to a load or group of loads and so has an expected maximum

    current, Ib. The nominal MCB rating, In, must be greater than Ib. The

    conductor size for the circuit is selected to have a current carrying

    capacity, Iz, that is greater than In. In addition, the current that causeseffective operation of the device within the required time, I2, must not be

    greater than 1.45 times the current carrying capacity of any part of the

    Current I (A) Nominal trip

    current

    In (A)

    Result

    I = 1.13 x In All Must not trip within 1 hour

    I = 1.45 x In < 63A Must trip within 1 hour

    I = 1.45 x In > 63 A Must trip within 2 hours

    I = 2.55 x In < 32A Must trip between 1 and 60 seconds

    I = 2.55 x In > 32A Must trip between 1 and 120 seconds

  • 8/14/2019 The maintenance manager's guide to circuit protection

    9/16

    The Maintenance Managers Guide to circuit protection

    9

    www.leonardo-energy.org

    circuit. As can be seen from the table, for an MCB meeting EN 60898, a

    current of 1.45 x In will trip in less than one or two hours, so this condition

    is deemed to be satisfied.

    The magnetic trip provides protection against the effects of fault current.

    Since it operates within one cycle, MCBs are sensitive to inrush, starting

    and surge currents. To avoid a high level of nuisance tripping, MCBs are

    available with nominal magnetic trip ratings of 5, 10 and 20 times the trip

    rating as shown in Figure 2. Fault current protection must operate within a

    prescribed time, which, for 230 V circuits, is 0.4 seconds. This places

    another requirement on conductor sizing a short circuit at the far end of

    the circuit must cause a fault current large enough to operate the

    magnetic trip. Consequently, there is a maximum limit on the circuit loop

    impedance according to the class of the breaker. So, if Class D MCBs are

    used (to avoid nuisance tripping on inrush currents, for example), the loop

    impedance must be lower than if a Class B device is used. Where the

    load is concentrated, the loop impedance required by a Class D device

    should be met if the circuit voltage drop has been correctly taken into

    account when sizing the cable. However, this may not be the case fordistributed loads so it should always be checked.

    Figure 6 shows the overall responses of Class B, C and D MCBs.

    Figure 6 MCB Characteristics, showing minimum and maximum instantaneous

    tripping currents

  • 8/14/2019 The maintenance manager's guide to circuit protection

    10/16

    Power Quality

    10

    www.leonardo-energy.org

    Since circuit breakers are thermally operated devices, they are sensitiveto temperature with the nominal trip current decreasing as the ambient

    temperature rises. Devices are designed and tested to operate singly in a

    vertical orientation at 30 C. At higher temperatures or where the circuit

    breakers are mounted in groups (as is typical in a distribution board),

    derating factors must be applied. It must be remembered that circuit

    breakers also generate heat due to their internal resistance.

    Manufacturers publish power dissipation values and derating tables for

    ambient temperatures above 30 C and for grouping factors.

    As can be seen from Figure 6, the tolerances on circuit breaker

    characteristics are rather wide. In overload conditions, for example, the

    time to trip at 1.5 x In is a minimum of 40 seconds and a maximum of 400

    seconds at 30 C. In fault conditions, a Class C device may trip at a

    minimum current of 5 x In or may not trip until the current exceeds 10 x In.

    These tolerances must be taken into account in design by using the worst

    case. For example, when considering the required value of loop

    impedance, the highest value of tripping current must be used, but whenconsidering resilience to inrush current, the lowest value is the relevant

    one.

    7. Selectivity or Discrimination

    Ideally, when a fault occurs, only the circuit breaker immediately upstream

    of the fault should open, thereby isolating the fault without disconnecting

    any other circuit. In Figure 7, the fault should result in only the breaker C3opening. In order to achieve that, the discrimination between the breakers

    at levels A, B and C must be total and breaker C3 must be capable of

    breaking the prospective fault current at C3.

    Where resilience is important, total discrimination is essential. In other

    circumstances it is often necessary to compromise and adopt a less

    stringent strategy such as backup protection.

  • 8/14/2019 The maintenance manager's guide to circuit protection

    11/16

    The Maintenance Managers Guide to circuit protection

    11

    www.leonardo-energy.org

    Figure 7 Typical system topology

    Discrimination between breakers in a system can be achieved either on

    the basis of current difference or time difference. A co-ordination study

    must be undertaken to ensure predictable behaviour.

    Current discrimination is achieved if the downstream device has a lower

    current trip level, under all circumstances, than the upstream device.

    Figure 8 shows an example of this. Since there is no overlap, the

    downstream breaker will always disconnect the fault and perfect

    discrimination is achieved. The difficulty is that the downstream breaker

    must be capable of breaking the full prospective short circuit current,

    which will often mean that a more expensive device must be used.

  • 8/14/2019 The maintenance manager's guide to circuit protection

    12/16

    Power Quality

    12

    www.leonardo-energy.org

    Figure 8 Breaker combination giving complete current discrimination

    Figure 9 Breaker combination giving limited current discrimination

    8. Cascade or Backup protection

    Cascade protection is intended to allow the use of lower cost circuit

    breakers in positions where their current breaking capacity might be lessthan the prospective fault current. Figure 9 illustrates a case where the

    breaker characteristics are allowed to overlap at a high fault current level.

  • 8/14/2019 The maintenance manager's guide to circuit protection

    13/16

    The Maintenance Managers Guide to circuit protection

    13

    www.leonardo-energy.org

    Here, the upstream breaker will operate first if the fault current exceedsthe current at which the curves cross about 2700 A in this example

    otherwise the downstream breaker will operate. In practice this means

    that fault currents less than 2700 A will be disconnected by the

    downstream device while larger fault currents, which might exceed the

    breaking capacity of the downstream device, are disconnected by the

    upstream device. Many faults will result in a current considerably less

    than the full prospective fault current, perhaps because the fault has some

    resistance, or because it occurs (and operates the breaker) at less than

    full voltage, and will be cleared solely by the downstream breaker. Note

    that the characteristics in the overload area do not overlap so, for overload

    conditions, the downstream breaker will always be responsible for clearing

    overload currents.

    The disadvantage of this approach is that a high fault current will cause

    the upstream breaker to operate, removing power from healthy circuits

    and increasing business disruption.

    Breaker manufacturers publish comprehensive performance data for

    cascade protection systems. However, it must be remembered that

    cascade protection always introduces the probability that power will be

    removes from a much greater part of the installation than is strictly

    necessary.

    Time discrimination is achieved by delaying the action of the upstream

    breaker until the downstream breaker has had time to open, as shown inFigure 10. This scheme requires the use of suitable breakers; the

    upstream breaker must be designed for this purpose and the downstream

    breaker must be capable of breaking the full prospective fault current.

  • 8/14/2019 The maintenance manager's guide to circuit protection

    14/16

  • 8/14/2019 The maintenance manager's guide to circuit protection

    15/16

    The Maintenance Managers Guide to circuit protection

    15

    www.leonardo-energy.org

    prescribed adjustments have not been correctly carried out often

    installed breakers are found in the as shipped state. It is important that

    these problems are rectified by reference to the design documentation

    rather than trial and error the erroneous operation may be delayed, but it

    may also be catastrophic.

    9.2. Post commissioning issues and modifications

    The most common problems are, as for new installations, nuisance

    tripping and a perceived lack of discrimination, but the cause is different

    the use of the installation has changed.

    Nuisance tripping usually becomes apparent following a change in the

    nature, number or use of the loads connected to the network. In one

    case, a tutorial room in an academic institution had been converted into a

    small computer suite housing 42 personal computers. For software

    management purposes, these computers were audited and updated

    overnight, using Wake on Lan or magic packet instructions to bring them

    out of standby and into full power mode. These instructions were sent inrapid succession, resulting in a virtually simultaneous power-up of all the

    computers. The result was a large inrush current, retrospectively

    measured at >500 A in the worst case, resulting in the MCBs operating.

    The corrective action taken was to replace the Class B MCBs which trip

    at 5 times their nominal rating with Class D devices that would trip at 20

    times their nominal rating. This would have been a reasonable response,

    if the loop impedance had been checked to ensure that a true fault current

    would have been high enough to trip a Class D breaker. No such check

    had been made, so the nuisance tripping issue was resolved, but the

    circuit may not be protected in the event of a real fault! The moral is that

    any maintenance action that could alter the behaviour of the protection

    system should be carefully checked.

    Where there is a perceived lack of discrimination it is usually brought

    about by a change of function in that area of the installation, such as the

    installation of more mission critical equipment, for example, or simply a

    change in the perception of the criticality of the existing equipment.Complete discrimination schemes can be more costly and may have been

    implemented only in areas where they were considered essential for

  • 8/14/2019 The maintenance manager's guide to circuit protection

    16/16

    Power Quality

    16

    www.leonardo-energy.org

    critical operations. When changes of use occur, it is possible that theprotection scheme will need to be readjusted or upgraded.

    10. Conclusions

    The design of the protection scheme requires a systems approach. It

    should not be assumed that additional circuits can be added to a

    distribution board without some consideration of the possible effects on

    upstream protection devices and their settings.

    Any change of wiring that could affect the loop impedance such as

    conductor upsizing or re-routing via a longer or shorter path must be

    considered in conjunction with the effect it could have on prospective fault

    currents and on clearing times for up and downstream protection devices.

    Even the apparently innocuous change of substituting, say, a Class D

    MCB in place of a Class B MCB requires reconsideration of loopimpedance.