The Designer Series - Denlar Hoods- Include power disconnect (electric, gas or dual element),...

6
Typ. cfm +/- 200 Model: DS-30 & DS-30TD Spec & Submittal Version 2.0 DS-30TD 7” Ductwork Cabinet Range Hood Air Flow 120VAC Input Line Volts Hz Amps Fan Control Light Bulb 120VAC 60 2 2 Speed (hi/l ow) 45W halogen 120VAC Output Line, Power Disconnect Cabinet Range Hood Air Flow DS-30 120VAC Input Line 120VAC Output Line, Power Disconnect TYPICAL SPECIFICATIONS Hood shall: - Be of Denlar Fire Protection Designer Series; - Be of under cabinet or wall mount; - Be of spot welded steel construction, with hemmed edges and a powder coated or stainless steel finish; - Be recirculating, front vented with activated carbon filter unless ducted calibration (TD) is required; - Have a 2 speed fan with air delivery of approximately 200 C F M ; - Include preinstalled automatic fire suppression system; - Have suppression activation by fast response mechanical links, 250F; - Have extinguishing agent to be wet chemical potassium citrate or Potassium acetate solution in a pressurized cylinder; - Be ETL listed to UL300A and UL507 test standards; - Be mounted so that the underside of the unit sits 18”-26” above the stove top; - Include internal audible buzzer (90 dba), activated upon system discharge; - Include fire alarm interface to communicate to fire alarm, activated upon suppression system discharge; - Include power disconnect (electric, gas or dual element), activated upon suppression system discharge. SPECIFICATIONS Gas disconnect (optional) 120VAC Solenoid The Designer Series 1 Electric disconnect (optional) 50A-208VAC Relay Standard Options*: MPK - Manual Pull Station Kit ADA - Handicap Accessible Control Box CLBX - THE CLOCKBOX (Password Protected, Range Element Timer) Standard Color is Appliance White Additional Color Options: BLK - Black Finish, BSQ - Bisque Finish, SS - Stainless Steel

Transcript of The Designer Series - Denlar Hoods- Include power disconnect (electric, gas or dual element),...

Page 1: The Designer Series - Denlar Hoods- Include power disconnect (electric, gas or dual element), activated upon suppression system discharge. 1 SPECIFICATIONS Gas disconnect (optional)

Typ. cfm +/- 200

Model: DS-30 & DS-30TD

Spec & Submittal

Version 2.0

DS-30TD

7” Ductwork

Cabinet

Range Hood

Air Flow

120VAC Input Line

Volts

Hz

Amps

Fan Control

Light Bulb

120VAC

60

2

2 Speed (hi/low)

45W halogen

120VAC Output Line,

Power Disconnect

Cabinet

Range Hood Air Flow

DS-30

120VAC Input Line

120VAC Output Line, Power Disconnect

TYPICAL SPECIFICATIONS

Hood shall:

- Be of Denlar Fire Protection Designer Series;

- Be of under cabinet or wall mount;

- Be of spot welded steel construction, with hemmed edges and a powder coated or stainless steel finish;

- Be recirculating, front vented with activated carbon filter unless ducted calibration (TD) is required;

- Have a 2 speed fan with air delivery of approximately 200 CFM; - Include preinstalled automatic fire suppression system; - Have suppression activation by fast response mechanical links,

250◦F; - Have extinguishing agent to be wet chemical potassium citrate

or Potassium acetate solution in a pressurized cylinder;

- Be ETL listed to UL300A and UL507 test standards;

- Be mounted so that the underside of the unit sits 18”-26” above

the stove top; - Include internal audible buzzer (90 dba), activated upon system

discharge; - Include fire alarm interface to communicate to fire alarm,

activated upon suppression system discharge; - Include power disconnect (electric, gas or dual element),

activated upon suppression system discharge.

1

SPECIFICATIONS

Gas disconnect (optional) 120VAC Solenoid

The Designer Series

1

Electric disconnect (optional)

50A-208VAC Relay

Standard Options*:

MPK - Manual Pull Station Kit

ADA - Handicap Accessible Control Box

CLBX - THE CLOCKBOX (Password Protected, Range Element

Timer)

Standard Color is Appliance White

Additional Color Options: BLK - Black Finish, BSQ - Bisque Finish,

SS - Stainless Steel

Page 2: The Designer Series - Denlar Hoods- Include power disconnect (electric, gas or dual element), activated upon suppression system discharge. 1 SPECIFICATIONS Gas disconnect (optional)

7”

19”

30”

2 Model: DS-30 & DS-30TD

Spec & Submittal

Version 2.0

FAN SWITCH LIGHT SWITCH

External Measurements

The Designer Series

System Anatomy :: DS-30 & DS-30TD

ELECTRICAL AND ALARM ACCESS PANEL

Page 3: The Designer Series - Denlar Hoods- Include power disconnect (electric, gas or dual element), activated upon suppression system discharge. 1 SPECIFICATIONS Gas disconnect (optional)

Connections & Installation Specs

The Designer Series 3

Model: DS-30 & DS-30TD

Spec & Submittal

Version 2.0

7” Diameter for TD option Note: Opening is only present on the

TD option, not on the recirculating option

Page 4: The Designer Series - Denlar Hoods- Include power disconnect (electric, gas or dual element), activated upon suppression system discharge. 1 SPECIFICATIONS Gas disconnect (optional)

DS-G: Controlled

Gas Solenoid Valve

Included:

2-3 feet cable with junction

DS-E: Electric Range

Element Disconnect

Needed:

6 feet shielded control wire

DS-MPK:

Manual Pull

Station Kit Included:

18 feet wire rope cable

3 corner pulleys

* indicates opTionaL component 4 Model: DS-30 & DS-30TD

The Designer Series Spec & Submittal

Version 2.0

*

* Indicates OPTIONAL component 4

Model: DS-30 & DS-30TD

Spec & Submittal

Version 2.0

Junction Box

120 VAC supply line from hood

Page 5: The Designer Series - Denlar Hoods- Include power disconnect (electric, gas or dual element), activated upon suppression system discharge. 1 SPECIFICATIONS Gas disconnect (optional)

*

*

DS-ADA:

Handicap

Accessible

Control Box

Included:

8 feet MC wire

-Plug & Play connection

DS-CLBX:

CLOCKBOX

Range element

Timer / Password

Protected System

Included:

20ft shielded communic

communication cable

5 Model: DS-30 & DS-30TD

The Designer Series Spec & Submittal

Version 2.0

20 feet shielded communication cable

* Indicates OPTIONAL component

5

Model: DS-30 & DS-30TD

Spec & Submittal

Version 2.0

Wall Surface Mount

HMI Touchscreen

Wall Flush Mount

Page 6: The Designer Series - Denlar Hoods- Include power disconnect (electric, gas or dual element), activated upon suppression system discharge. 1 SPECIFICATIONS Gas disconnect (optional)

Wiring Diagram

The Designer Series 6

Model: DS-30 & DS-30TD

Spec & Submittal

Version 2.0

Schematic ID

Component Name

Component Location

F1 Fuse 1

Behind the Left side access panel

MP1 Main Plug 1

Behind the Left side access panel

MP2 Main Plug 2 In the Tank Assembly

AP1 Alarm Plug 1

Behind the Left side access panel

FSW Fan Speed Switch

Front of the Hood

LSW Light Switch Front of the Hood

LT1 Light 1

In the Light Housing Assembly the left light socket

LT2 Light 2

In the Light Housing Assembly the right light socket

MSW1 Micro Switch 1

In the Tank Assembly next to the Actuator Arm

MSW2 Micro Switch 2

In the Tank Assembly next to the Actuator Arm

FMTR Fan Motor

Under the air filter in the Light Housing

Assembly

BUZZER Audible Buzzer

In the Light Housing assembly