The Code Corner No. 15 - Building Classification Part 2 - Construction Types(1)

3
  ©2009 RLGA Technical Services LLC   www.specsandcode s.com  No. 15 Building Classification - Part 2: Construction Types Page 1 No. 15 — February 2006 RLG A Technical Services Build ing Class ificatio n - Part 2: Const ruction Types  By Ronald L. Geren, AIA, CSI, CCS, CCCA, SCIP In my last article, I discussed the first of two types of building classifications used in the building code: Occupanc ies. The second, wh ich is frequently m isunderstood by new use rs of the building code, is the Const ruc tio n Typ e cl ass ifi ca tion. The Cons tru cti on Typ e has litt le to not hin g to do wi th the Occupancy cla ssification. But, like the two towers of the Golden Gate suspension bridge, without both, the whole thing wouldn’t hold together. A Construction Type, as the term clearly states, is based on how the building is constructed, and the requirements are found in Chapter 6 of the  International Building Code  (IB C). Most peo ple wil l relate the Constr ucti on Type to the materi als used for con struc ting a build ing. But, it’s a litt le more than that . The “little more” is called combustibility and fire-resistance. There are a total of nine types of construction that span from noncombustible types to combustible type s of constru ctio n, with varyin g deg rees of eac h in betwee n that are based on fire resi stance. Tabl e 601,  Fire-Resistance Rat ing Requi rements for Buil ding Element s, shows each of the types with their respe ctiv e fire- resis tance requ irements for bui ldin g elements. These buildi ng elem ents include the struc tura l frame (colu mns, beam s, girde rs, trus ses, and span drel s), bea ring wal ls (i.e . wall s that have impos ed loa ds on them), non bea ring wal ls, floor s, and roofs . The only exce pti on is for non be ari ng interior walls, which have no fire-resistance requirements unless they’re required to be fire-resistive by other sections of the co de. The nine types of constru ction are:  Types IA and IB  Types IIA and IIB  Types IIIA and IIIB  Type IV  Types VA and VB Construction Types IA and IB are considered noncombustible and fire-resistive, and are the direct descendents of the  Uniform Building Code’s  (UBC) Type I-F.R. and Type II-F.R. (F.R. refers to “fire- resistive”) constru ction types, respect ively. The most significant differenc e between the IA and IB types is the level of fire-resistance required for the building elements previously discussed, with IA having a higher fire-resistanc e. Since both types are noncombus tible, they only permit noncombu stible materials. Unlike the UBC, the IBC doesn’t specify what materials are considered noncombustible; that is left to testing per IBC Section 703.4. Noncombu stible materia ls are determined through ASTM E 136 for basic, or “elementary,” materials and ASTM E 84 for composite materials. Cons truc tion Types IIA and IIB are also nonc omb usti ble, but have little to no fire-res ista nce. Like Type I construction, Types IIA and IIB are comparable to the former UBC Types II 1-hour and II-N. Determination of whether or not a material is noncombustible is the same as that for Type I construction. Type IIA has a minimum of 1-hour fire resist ance throu ghou t. Type IIB, althoug h nonc omb ustib le, has no requirements for fire-resistance, unless required by other sections of the code. Cons truc tion Types IIIA and IIIB are conside red combu stible . Bei ng a combust ible constr ucti on typ e, Type III cons truct ion permits the use of wood fra mi ng. Typ e III cons tru cti on, like Type II construction, ha s little to no fire-resistanc e. Type IIIA requires 1-hour fire-resista nce throughout exc ept

Transcript of The Code Corner No. 15 - Building Classification Part 2 - Construction Types(1)

5/11/2018 The Code Corner No. 15 - Building Classification Part 2 - Construction Types(1) - slidepdf.com

http://slidepdf.com/reader/full/the-code-corner-no-15-building-classification-part-2-construction-types1 1/3

 

 ©2009 RLGA Technical Services LLC — www.specsandcodes.com No. 15 — Building Classification - Part 2: Construction Types —

 

No. 15 — February

RLGATechnical Se

Building Classification - Part 2: Construction Typ

 By Ronald L. Geren, AIA, CSI, CCS, CCCA, SC

In my last article, I discussed the first of two types of building classifications used in the build

code: Occupancies. The second, which is frequently misunderstood by new users of the building cod

the Construction Type classification. The Construction Type has little to nothing to do with

Occupancy classification. But, like the two towers of the Golden Gate suspension bridge, without b

the whole thing wouldn’t hold together.

A Construction Type, as the term clearly states, is based on how the building is constructed, and

requirements are found in Chapter 6 of the International Building Code (IBC). Most people will re

the Construction Type to the materials used for constructing a building. But, it’s a little more than t

The “little more” is called combustibility and fire-resistance.

There are a total of nine types of construction that span from noncombustible types to combustitypes of construction, with varying degrees of each in between that are based on fire resistance. Ta

601, Fire-Resistance Rating Requirements for Building Element s, shows each of the types with th

respective fire-resistance requirements for building elements. These building elements include

structural frame (columns, beams, girders, trusses, and spandrels), bearing walls (i.e. walls that h

imposed loads on them), nonbearing walls, floors, and roofs. The only exception is for nonbear

interior walls, which have no fire-resistance requirements unless they’re required to be fire-resistive

other sections of the code. The nine types of construction are:

Types IA and IB

Types IIA and IIB

Types IIIA and IIIB

Type IV

Types VA and VB

Construction Types IA and IB are considered noncombustible and fire-resistive, and are the dir

descendents of the Uniform Building Code’s (UBC) Type I-F.R. and Type II-F.R. (F.R. refers to “fresistive”) construction types, respectively. The most significant difference between the IA and IB ty

is the level of fire-resistance required for the building elements previously discussed, with IA havin

higher fire-resistance. Since both types are noncombustible, they only permit noncombustible materi

Unlike the UBC, the IBC doesn’t specify what materials are considered noncombustible; that is lef

testing per IBC Section 703.4. Noncombustible materials are determined through ASTM E 136 for baor “elementary,” materials and ASTM E 84 for composite materials.

Construction Types IIA and IIB are also noncombustible, but have little to no fire-resistance. LType I construction, Types IIA and IIB are comparable to the former UBC Types II 1-hour and II

Determination of whether or not a material is noncombustible is the same as that for Type I construct

Type IIA has a minimum of 1-hour fire resistance throughout. Type IIB, although noncombustible,

no requirements for fire-resistance, unless required by other sections of the code.

Construction Types IIIA and IIIB are considered combustible. Being a combustible construc

type, Type III construction permits the use of wood framing. Type III construction, like Typ

construction, has little to no fire-resistance. Type IIIA requires 1-hour fire-resistance throughout exc

5/11/2018 The Code Corner No. 15 - Building Classification Part 2 - Construction Types(1) - slidepdf.com

http://slidepdf.com/reader/full/the-code-corner-no-15-building-classification-part-2-construction-types1 2/3

 

 ©2009 RLGA Technical Services LLC — www.specsandcodes.com No. 15 — Building Classification - Part 2: Construction Types —

 

No. 15 — February

RLGATechnical Se

that exterior bearing walls require no less than 2-hour fire-resistive construction. Type IIIB has no f

resistance requirements, except for exterior bearing walls, which has the same requirement as Type IIIA

Construction Type IV is unique. It is a combustible construction type, but it is limited to hetimber construction. Although it is considered a combustible construction type, the exterior walls

required to be of noncombustible construction. Heavy timber construction includes columns not less t

8 inches thick, and floor and roof framing not less than 6 inches thick; all dimensions are nominal. Flo

and roofs have thicker than normal construction consisting of varying layers of materials that build up

deck of 3 to 4 inches thick, nominally.

Lastly, Types VA and VB are also combustible construction, but each is slightly less fire-resist

than the Type III construction types. For example, the exterior bearing wall fire resistance is reduce

1-hour for Type VA and no fire resistance for Type VB.

It is important to understand, that a noncombustible building could still be classified as a Type II

V building. This is clearly stated in Section 602.1.1:

  A building or portion thereof shall not be required to conform to the details of a type of 

construction higher than that type, which meets the minimum requirements based on

occupancy even though certain features of such a building actually conform to a higher type

of construction.

In other words, if an entire building, or part of it, is designed to the requirements of a Type

construction (concrete frame and masonry walls, for example), but the actual height, allowable area,

occupancy housed would only require the building to be classified as a Type IIIB, then the building wnot be required to meet all the detailed requirements for the Type IIA construction.

In addition to the fire-resistance ratings indicated in Table 601, nonbearing exterior walls are requito comply with the hourly fire-resistance requirements of Table 602, Fire-Resistance Ra

 Requirements for Exterior Walls Based on Fire Separation Distance. As the title states, the requireme

are based on the fire separation distance between the wall and the nearest lot line, street centerline, or

imaginary line between two buildings on the same lot. This table also begins to incorporate occupan

into the mix when determining the fire-resistance. For example, a Group M (Mercantile) occupancy w

a nonbearing wall that is 20 feet from the lot line, and using Type IIA construction, is required to havfire-resistance rating of not less than 1-hour. If it were Type IIB construction or more than 30 feet fr

the lot line, it would have no requirement for fire-resistance.

Like I’ve stated in a few of my previous code articles, you need to look closely at the footnotes in

tables. In Table 601, there’s a footnote that permits the substitution of the 1-hour fire-resis

construction (excluding exterior walls) with the installation of an automatic sprinkler system

Construction Types IIA, IIIA, and VA. There is a catch, though…if the sprinkler is required by anot

section of the code, then this substitution can not be used; nor can it be used if the sprinkler systemused for an area increase (a subject that will be covered in next month’s article).

Additionally, there’s a footnote that permits the use of fire-retardant-treated wood in Type I androof construction (including girders and trusses) as long as the building 1) is two stories or less in hei

2) is Type II construction over two stories, or 3) is Type I construction over two stories and the verti

distance from the upper floor to the roof is 20 feet or more.

5/11/2018 The Code Corner No. 15 - Building Classification Part 2 - Construction Types(1) - slidepdf.com

http://slidepdf.com/reader/full/the-code-corner-no-15-building-classification-part-2-construction-types1 3/3

 

 ©2009 RLGA Technical Services LLC — www.specsandcodes.com No. 15 — Building Classification - Part 2: Construction Types —

 

No. 15 — February

RLGATechnical Se

Construction Types and Occupancy Groups establish the foundation upon which the majority of

building code is built. Occupancy Groups drive egress, floor area, building height, among ot

requirements. Likewise, Construction Types also affect building materials, floor area, building hei

and many other requirements. As you’ve probably noticed, building area and height are tied to bConstruction Types and Occupancy Groups…like the suspension part of the Golden Gate Bri

mentioned at the beginning. In my next article, we’ll look at how the IBC has changed the method

determining allowable area and height…so get your calculators ready!

To comment on this article, suggest other topics, or submit a question regarding codes, contact the aut

at [email protected].

  About the Author: Ronald L. Geren, AIA, CSI, CCS, CCCA, SCIP, is an ICC Certified Building Pl

  Examiner, and is the principal of RLGA Technical Services located in Scottsdale, Arizona, w

  provides specifications and code consulting services to architects, engineers, owners, and prod

manufacturers. A 1984 graduate of the University of Arizona, Ron has over 23 years of experience w

military, public, and private agencies.