By Donna Hoover
he application of Variable Fre-
quency Drives (VFDs) in turf irri-
gation systems is a hot topic. A
VFD is an electronic device thatchanges the frequency of the AC power
going to a motor, thereby varying the
motor speed. When attached to a
pump, the change in motor speed
affects the flow and pressure of the
pump discharge.
VFD Advantages
ENERGY SAVINGS
Any time the demand is lower thanthe design point of the system, VFDs
reduce the motor speed (and there-
fore horsepower), resulting in a reduc-
tion in energy. The amount saved
depends on the design of the system,
actual demand and other factors.
REDUCTION IN WATER HAMMER
& LIFE EXTENSION OF THEIRRIGATION PIPING
This occurs because VFDs can be con-
figured to ramp the motor up and
down in a controlled manner.
ELIMINATION OF THE PRESSURE
CONTROL VALVE
The valves historically have required
excessive maintenance (though there
has been improvement in recent
designs). Additionally, control valves
reduce the pump discharge pressure
5-10 PSI, perhaps resulting in the
need for a larger pump.
L
L
L
12 PIPELINE
-
8/7/2019 The Application of VFDS Provide Irrigation Solution
2/4
www.fisstate.org 13
VFD Disadvantages
ENVIRONMENTAL SENSITIVITIES
The forces of nature in certain geo-
graphic areas may be of concern when
considering the use of VFDs. In Flori-
da, for instance, heat, humidity andlightning are natural phenomena that
can affect the performance of VFDs.
Since most VFDs are rated to operate
in ambient temperatures up to 104
F, in Florida auxiliary cooling would
be necessary. For drives mounted in
an industrial enclosure, an air condi-
tioner or air/water heat exchanger
would suffice. There are also drives
that can be mounted outside. These
are produced by some VFD manufac-
turers in NEMA 4 packages. They
should include a fan to cool the drive
when running. It is necessary that
they be shielded from direct sunlight.
Surge / lightning protection presents
another potential challenge. Since
the printed circuit boards inside VFDs
can be sensitive to surges, intermit-
tent problems or catastrophic failurescan occur. Well-engineered VFD sys-
tems include a line reactor or other
device to guard against surges.
SERVICE ISSUES
Since many VFD problems can be dif-
ficult to trace, it is often necessary to
call in a highly trained drive specialistto make repairs. When a VFD fails, it
can take a week or more for the
problem to be diagnosed and a new
VFD ordered and installed. (Larger
VFD systems do come with a bypass
that enables the system to be run in
manual if the VFD fails).
L
L
-
8/7/2019 The Application of VFDS Provide Irrigation Solution
3/4
14 PIPELINE
Ideal VFD ApplicationsSome excellent situations for applying a
VFD in a turf irrigation pump system are:
Any pump station with dramaticallyvarying flow rates over a wide flow
range, the VFD can be a better regu-lating device than a control valve.Care must always be taken to achieveevenly balanced flow requirementsacross the irrigation zones.
Some conventional pump stations uti-lizing jockey or pressure maintenancepumps The pumps keep the mainline
pressurized, offsetting the weeping offield valves. Jockey pumps reduce thewear and tear on the main pumpwhen low flows are required. A VFDon the main pump in lieu of a jockeypump may enable the pump to bet-ter operate at low flows.
Booster pumps for potable water or irri-
gation. The incoming pressure and dis-charge demand can vary greatly basedon time of day and other variables.
Pump stations with higher horsepowerpumps. They are better candidates forenergy savings than smaller stations.
Specifying a VFDPump Station
Once it has been determined that aVFD is appropriate for the application, thedesigner should consider the following:
Is the system designed to maintainconstant pressure? The pump stationshould be designed to maintain aconstant discharge pressure. In a welldesigned VFD system, a pressuretransducer provides a control feed-back. The VFD, when properlytuned, maintains constant pressure, ineffect matching pump output to
actual demand in the field. If a feed-back signal from a pressure transduc-er is absent, most of the advantagesof a VFD are lost.
How is the temperature limitation ofthe VFD being handled? If the VFD isto be installed in an industrial enclo-sure, an air conditioner or air/water
heat exchanger should be specified.If the VFD comes in a self-containedNEMA 4 package, it can be mountedunder the pump enclosure or on anopen skid. In that case, the VFDshould include a cooling fan and alsobe shielded from direct sunlight.
What electrical protection is being
offered? The pump station manufac-turer must include a separate devicefor disconnect, ground-fault/short-cir-cuit protection, and surge / lightningprotection as required by the Nation-al Electrical Code, the VFD manufac-turer, and best design practices.
Does the pump station include a VFD
for each motor? For stations withmultiple pumps, there should be anindividual drive for each motor. Manymanufacturers include one VFD andtransfer the motor across the linewhen the next pump starts. This isdone to reduce cost, but will result inreduced energy savings and unbal-anced loads between the pumps.
L
L
L
L
L
L
L
L
-
8/7/2019 The Application of VFDS Provide Irrigation Solution
4/4
What's WrongWith ThisPicture?
What's WrongWith ThisPicture?There are at leastfour obviousproblems withthis pump inletconnection . . .Can you see them?
For the answersturn to page 32.
www.fisstate.org 15
What pump controllogic is provided?The pump stationshould be designedto not only maintaina constant discharge
pressure, but also toretire the pump on ano-flow signal.Without this logic thesystem will cyclebetween high andlow operating setpoints, and the life ofthe motor and piping
will be affected. To provide the no-flow retirement, as well as loss ofprime and low pressure shutdown sequences, the pump stationshould include a programmable logiccontroller (PLC) or an integrated logiccard within the VFD.
The benefits of using VFDs in many
turf irrigation applications are notewor-thy. Thoughtful consideration should begiven, however, to each individual situa-tion to warrant the use of a VFD. It is of
major importance to properly design thesystem to ensure optimum efficiency andto reap the rewards a VFD promises.Time spent is money saved!
H o o v e r P u m p i n g S y s t e m s h a s b e e n m a n u f a c t u r i n g i r r i g a t i o np u m p s t a t i o n s f o r t h e F l o r i d a m a r -k e t f o r 25 y ea r s . Fo r mo re i n f o rma-t ion, p lease contact George Newman
or Kev in Cava io l i a t Hoover PumpingSys tems , 954-971-7350. Em a i l :g e o r g e @ h o o v e r p u m p i n g . c o m o r k e v i n @ h o o v e r p u m p i n g . c o m .