Textile Based Ventilation for a good indoor climate

download Textile Based Ventilation for a good indoor climate

of 146

Transcript of Textile Based Ventilation for a good indoor climate

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    1/146

    T e x T i l e b a s e d v e n T i l aT i o n

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    2/146

    Textile Based Ventilation

    2012, 1st edition

    All information in this catalogue belongs to KE Fibertec AS. It may

    not be copied or used for any other purpose without the written

    consent of KE Fibertec AS.

    Published by:

    KE Fibertec AS

    Industrivej Vest 21

    DK-6600 Vejen - Denmark

    www.ke-fbertec.com

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    3/146

    1 . T E X T I L E B A S E D V E N T I L AT I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2 . P R O DU C T R A N G E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3 . W H E R E O U R P R O D U C T S A R E U S E D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4 . F R O M D I A L O G U E T O V E N T I L AT I O N S O L U T I O N . . . . . . . . . . . . . . . . . . . . . . .

    5 . L O W I M P U L S E S Y S T E M S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6 . H I G H I M P U L S E S Y S T E M S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7 . H Y B R I D H I G H I M P U L S E S Y S T E M S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8 . D E S I G N C O N S U LTA N C Y. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9 . R O O M C AT E G O R I E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1 0 . T Y P I C A L L A Y O U T S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1 1 . S O U N D L E V E L A S P E C T S O F D E S I G N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1 2 . M AT E R I A L S A N D C O L O U R S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1 3 . DE S I G N P R O C E S S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1 4 . S U S P E N S I O N S Y S T E M S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1 5 . W A S H I N G A N D M A I N TE N A N C E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1 6 . D ATA S H E E T S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    TA B L E O F C O N T E N T S

    3

    7

    1 1

    2 3

    3 1

    4 3

    5 5

    6 1

    7 1

    7 5

    8 5

    9 1

    9 9

    1 0 7

    1 1 3

    1 2 1

    1

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    4/146

    2

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    5/146

    1 . T E X T I L E B A S E D V E N T I L AT I O N

    3

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    6/146

    Creating a good indoor climate involves more than just selling air distribution products. For

    us at KE Fibertec its all about dialogue, expertise, reliability and logistics. We dont stock

    nished products or have standard components. All our solutions are tailored to the task

    at hand. Our philosophy is to start with the requirements and, through dialogue, design a

    solution that meets the expectations specied or a good indoor climate. Just as people are

    dierent, indoor climate requirements are dierent too. What we have done is to specialise

    in meeting these requirements.

    A I R T H E W AY Y O U W A N T

    D I A L O G U E

    No matter how much eort we put in, a good solution requires dialogue about the expecta-tions o the end result. We oer our advice ree o charge, so the sooner we are involved in

    the project, the better the chance we have o achieving a good result. Textile based ventila-

    tion (TBV) can replace more conventional air distribution ttings in almost every situation, but

    only i the design is tailored to the particular task. I you are in doubt whether TBV products

    can do the job or you, our ventilation engineers are available to oer you advice. But you

    should expect us to ask you questions not only about the air volume and your heating/cool-

    ing requirements, but also about the end users expectations and needs. We see it as a

    process o providing reliable advice based on dialogue.

    E X P E R T I S E A N D D E V E L O P M E N T

    KE Fibertec is one o the worlds leading manuacturers o Textile Based Ventilation. A great

    deal has happened since the rst TBV system was supplied to a slaughterhouse in Denmark

    in the early 1970s. Many years o product development and collaboration with leading uni-

    versities in the eld o air distribution, such as Aalborg University, Denmark, provide you with

    the guarantee that our products have been thoroughly tested. However, additional proo

    may still be needed in complex projects. We have learned the lessons rom this, so that we

    now have a ully equipped, ull-scale laboratory, which we can use to visualise solutions with

    smoke and make measurements. We may also choose to set up a ull-scale model o the

    end users acility and simulate dierent load situations. Regardless o the scope o the task,

    our well-trained, committed development team is always willing to prove the solution. This is

    also the case in situations where measurements are taken on site at the end users acility.

    R E L I A B L E D E S I G N

    A reliable, well-proven design is also part o our solution. All projects are dimensioned online

    using our WinVent 3D program, which is always kept up to date with the latest technology

    and product documentation. We rmly believe that technical data must be reliable and

    measurable, irrespective o whether we are dealing with pressure loss, air velocities,

    temperature distribution or sound calculations. Why do you need to determine the textile

    abrics air permeability at a given static pressure when you only need to know the total

    pressure loss or the system? Or why do you need to determine the theoretical velocity

    through the textile surace when only the critical air velocity in the occupied zone is a

    unctional requirement? We design solutions or a given premises, based on the parameters

    which we have determined through dialogue. Solutions that work in practice too.

    I you require any urther proo we can also provide you with CFD simulations.

    4

    T E X T I L E B A S E D V E N T I L AT I O N

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    7/146

    F R O M F I B R E T O F I N I S H E D F A B R I C

    KE Fibertec is the only manuacturer in the world which weaves all abrics used or our ductsin our own weaving mill, KE Fibertec Vveri AS. This is the only way that we can ensure that

    the materials have been tested and meet the stringent quality requirements we set:

    the air must pass through properly (uniormly through the whole abric)

    the abrics structure must provide the largest surace area (large dust holding capacity)

    the shrinkage rate ater washing must be less than 0.5%

    the materials must stand up to repeated washing and tumble-drying

    the nished materials must be re-approved (not just the bre).

    KE Fibertec Vveri manuactures more than 40 dierent product varieties rom Trevira CS

    polyester materials woven in 10 dierent permeabilities and in dierent colours, to antistat-ic materials and Nomex special blends. All materials are heat-treated, transilluminated and

    tested at the weaving mill. When they have been approved a bar code is axed to them

    displaying inormation about the weaving machine, permeability and production date. All this

    inormation guarantees complete electronic traceability or all products rom bre to nished

    TBV system.

    T E C H N O L O G Y T H AT M A K E S A D I F F E R E N C E

    KE Fibertec has gone against the fow and decided to raise the technology level o its entire

    production process in Denmark by introducing new standards or using laser technology.

    All the laser parameters are generated in the dimensioning program WinVent 3D and are

    transerred electronically to our laser cutters. This has resulted not only in boosting productivity

    and enhancing the product nish, but has also enabled us to introduce an entirely new

    product group, known as hybrid products. These hybrid products combine the best rom our

    passive low impulse systems with our high impulse systems (read more about these systems

    in Chapters 5, 6 and 7). KE Fibertec is naturally certied under ISO 9001 (quality), ISO 14001

    (environment) and most recently under ISO 18001 (work environment).

    The expertise oered and willingness to change shown by our motivated production sta

    have enabled us to create a good working environment, while also guaranteeing our competi-

    tiveness without comprising on quality.

    L O G I S T I C S T H A T W O R K

    Time is money. So we understand the importance o rapid, accurate delivery to the construc-

    tion site. Good cooperation is based on trust and understanding. We are very proud o the

    act that we can justiy your trust and guarantee meeting 99% o just in time delivery times,

    even though all our products are manuactured to order. Our typical turnaround time rom

    order conrmation to delivery is 10-15 working days, depending on the time o year and the

    orders complexity. We can, o course, respond more quickly to rush orders or part deliveries

    to every destination in Western Europe and the United States. You just need to remember

    to ask or our express delivery service Fast Line. I you want to reorder a product rom a

    previously delivered order, remember that all KE products are tted with a label that can help

    us to identiy the order.

    Thanks to the experience gained rom handling over 5,000 deliveries every year, we hope that

    we can justiy your trust too.

    5

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    8/146

    6

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    9/146

    2 . P R O D U C T R A N G E

    7

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    10/146

    KE Fibertec develops and markets three main TBV product groups, which can all be suppliedin three different geometries. In passive low impulse systems the air diffuses through a

    permeable material. In high impulse systems air is distributed solely through holes (KE-

    Inject System) or nozzles (KE-DireJet System). The hybrid models are a combination of the

    passive low impulse systems and the lasered Inject holes or DireJet nozzles. You can read

    more about these products and how they work in Chapters 5, 6 and 7.

    P R O D U C T R A N G E

    KE-Interior System (D)KE-Interior System (D)KE-Low Impulse SystemP R O D U C T R A N G E : L O w

    i m P U L s E s Y s T E m s

    KE-Inject System (D)KE-Inject System (D)KE-Inject SystemP R O D U C T R A N G E : H i G H

    i m P U L s E s Y s T E m s

    KE-DireJet System (D)

    KE-Inject

    Hybrid System (D)

    KE-Inject

    Hybrid System (D)

    KE-Inject

    Hybrid System

    KE-DireJet

    Hybrid System (D)

    KE-DireJet

    Hybrid System (D)

    KE-DireJet

    Hybrid System

    KE-DireJet System (D)KE-DireJet System

    P R O D U C T R A N G E :

    H Y B R i D H i G H i m P U L s E

    s Y s T E m s

    m A i N P R O D U C T s

    8

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    11/146

    L O w i m P U L s E s Y s T E m s

    H i G H i m P U L s E s Y s T E m s

    H Y B R i D H i G H i m P U L s E s Y s T E m s

    9

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    12/146

    10

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    13/146

    3 . W H E R E O U R P R O D U C T S A R E U S E D

    11

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    14/146

    Textile ducting can be used in almost any type o installation and building, irrespective o

    whether the requirement is or heating, cooling, ventilation or a replacement air system. Over

    the years, KE Fibertec and its partners have accumulated a large database o reerences

    covering every possible installation. This is why we can saely guarantee that we have a

    solution to suit your enquiry too. You will nd a number o reerences at www.ke-bertec.

    com.

    R E F E R E N C E S

    Flexibility and tailored products are the hallmark o our TBV solutions. This allows you to

    reely choose the size that best suits your design rather than having to be tied to a par-

    ticular number o standard solutions. In addition to this, the options oered when it comes

    to selecting system layouts, colours, osets, elbows, sockets and materials are endless,not to mention that you can choose whether the TBV system will be passive (low impulse),

    semi-active (hybrid) or active (high impulse). In a nutshell, there could not be more options

    available or achieving optimum air distribution.

    E I G H T G O O D

    R E A S O N S F O R

    C H O O S I N G A T B V

    S Y S T E M F R O M

    K E F I B E R T E C

    D I A L O G U E

    Finding the ideal solution requires knowledge about the

    issues behind the desire to improve or install ventilation.

    It could be anything rom local authority requirements or

    wanting to maintain a particular temperature or production

    equipment and/or products to showing concern or sta

    welare. No matter the size o the project, KE Fibertec willalways sit down and talk with the customer in order to

    achieve the best possible result and value or money.

    D I M E N S I O N I N G A N D C O N S U L TA N C Y

    Every TBV solution is dimensioned by experienced

    engineers using our unique WinVent 3D sotware. We have

    acquired over 30 years experience within the textile based

    ventilation sector, but i urther proo is still required, we can

    also provide CFD simulations.

    U N I Q U E M A T E R I A L S

    Our textiles are produced at our own weaving mill with the

    sole purpose o oering the most suitable materials or air

    distribution in the market. The selection o bres, weight,

    weaving technology, dyed yarns and heat treatment

    are based on our desire to achieve totally uniorm air

    permeability, a large dust holding capacity, the lowest

    possible shrinkage ater washing and basic colours without

    any additional cost.

    A C O U S T I C B E N E F I T S

    Our low impulse systems in particular oer unrivalled

    eatures in terms o noise generation and can be used, with

    the right dimensioning, in sound studios or instance.

    P AT E N T E D P R O D U C T S

    We oer the widest range o TBV products in the market,

    which is your guarantee that we will always nd the best

    solution. We are the only manuacturer capable o oering

    passive low impulse systems (textiles), semi-active hybrid

    systems and pure high impulse systems. Our high impulse

    systems can be supplied in a variety o patented holedesigns (Inject) or with ve dierent nozzle sizes (DireJet),

    depending on their unction.

    N O C O N D E N S A T I O N P R O B L E M S

    Both low impulse and hybrid systems are made rom porous

    abrics. This prevents the kind o surace condensation

    problems that metal ducts are renowned or.

    E A S Y T O S H I P A N D I N S T A L L

    The materials only weigh 260-400 g/m, which means

    that a typical TBV system weighs much less than metal

    ducting, while the textile ducts are much easier to handle

    and transport as they are packaged in cartons and not in

    three- or six-metre lengths. KE Fibertecs suspension rails

    are supplied cut to size, which makes assembly easier and

    quicker than with similar systems.

    H Y G I E N I C A N D L I G H T W E I G H T

    All TBV systems can easily be taken down and washed

    in a washing machine. The specially treated Trevira CS

    materials absorb no more than 1% o water, even with

    a relative humidity o over 90%. This is why their use is

    approved in the ood industry. High impulse products are

    manuactured in a coated material which does not require

    any more maintenance than conventional spiro ducting.

    W H E R E O U R P R O D U C T S A R E U S E D

    12

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    15/146

    F I N A N C I A L C O N S I D E R AT I O N S

    What does a metre o textile ducting actually cost? This is a question that we are otenasked by our customers, probably so that they can make a quick price comparison with

    the product price or more conventional solutions. Our concept o supplying tailored solu-

    tions designed or a given unction makes it more complicated to set a price. This is why we

    cannot unortunately give a reliable price per metre when requested. This does not mean

    that we cannot provide exact prices when preparing quotations, tender bids etc. We are,

    o course, able to do this, but the prices are always project-based, worked out according

    to the wishes and inormation we have received rom our partners. At the same time, it is

    important to emphasise that you can only make a proper comparison with conventional

    solutions and competitor products i all the relevant parameters are actored in to give a

    true picture, such as the product price, installation cost and ongoing maintenance costs,

    including the expected depreciation period.

    KE Fibertec and many o our KE partners can oer a total service concept, which includes

    installation and an attractive maintenance package aterwards.

    P R O D U C T P R I C E

    The actual product price depends mainly on the size o the system, as well as the products

    and material chosen. The product price per metre o ducting will be much cheaper, the biggerthe project is. For instance, a TBV duct or distributing 1,000 m 3/h o air costs signicantly

    more per metre o ducting than a TBV system or distributing 10,000 m3/h o air.

    The most expensive products in our range are D and D-shaped systems, which should

    mainly be chosen i appearance and product nish are important requirements.

    The actual textile material used also plays an absolutely crucial role in the product price.

    KE Fibertec oers re-approved Trevira CS textiles as standard, which comply with all the

    general national re requirements. These specially treated materials also oer value or

    money thanks to their highly uniorm air permeability, which is benecial to pressure loss and

    energy consumption. Textile ducting must be able to stand up to being repeatedly washed

    without losing its shape, shrinking or losing its colour. We guarantee that our materials are

    manuactured or long-term use, even i they are washed regularly.

    13

    The total investment in a KE FibertecTBV system is based on product price,

    installation cost and maintenance

    costs.

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    16/146

    All ventilation ducts must becleaned inside and outside at

    some point. It is simply not true

    that all TBV systems get clogged

    up within a year. For example, high

    impulse systems do not require

    any more maintenance than spiro

    ducting.

    Air quality, including the pre-lters quality. In low impulse systems we recom-

    mend F7 pre-lters or supply air. Remember that there is a big dierence in

    pre-lter quality.

    The systems annual operating time in hours.

    The air volume per m 2 o textile surace. The greater the load per surace area,

    the more requently the system needs to be cleaned.

    The textiles dust holding capacity (DHC). An ordinary standard abric oten only

    has hal the DHC o a KE Fibertec abric and it costs a great deal in unnecessary

    maintenance. A hybrid system with laser cut holes or DireJet nozzles has longer

    wash intervals than a standard low impulse system.

    Hygiene requirements. There may be absolutely specic hygiene requirements

    determining how requently the system must be washed, or instance, in the

    ood industry. The usual requency or washing is calculated as once a year,

    regardless o how dirty the TBV ducting actually is.

    In the ollowing section we have created a product chart based on type o premises

    matched with the best product choice. The approach taken when the charts were built

    was how to generate added value or the best possible value or money. This means that

    other products can also be used or a particular installation i the assessment is based on

    other requirements.

    I N S T A L L AT I O N P R I C E

    Round ducts are generally cheaper to install than D or D-shaped ducts. We recommendusing a rail solution rather than wire, even though this adds to the product price. Rails are

    always supplied cut to size and clearly labelled as to where they need to be installed. This

    makes the installation process much quicker, and very oten considerable savings can be

    made with the installation o a KE Fibertec TBV system, compared with a conventional

    system. Handling the heavy metal ducts, which includes adjusting the lengths, assembling

    the ttings etc., at the construction site is extremely time-consuming. When a TBV system

    is selected, all the lengths, elbows, osets etc. are delivered ready to be joined together

    with a zipper. The only requirement is that accurate eld verication takes place beore the

    project is released or manuacture.

    M A I N T E N A N C E

    All ventilation ducts must be cleaned at some point, both inside and outside, with TBV sys-

    tems being no exception. However, the various systems have dierent requirements. Low

    impulse systems require better pre-lters and more maintenance than high impulse sys-

    tems where the air is distributed through holes or nozzles. On the other hand, airborne dust

    particles do not settle on the surace o a low impulse duct, which can otherwise present a

    problem or non-permeable ducts in the electronics industry, or instance.

    The key parameters which infuence how oten the systems are washed are as ollows:

    W H E R E O U R P R O D U C T S A R E U S E D

    14

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    17/146

    Type of premises KE-Low Impulse KE-Interior KE-Inject KE-DireJet

    1. Comort Lecture/conerence halls

    Individual oces - -

    Open-plan oces

    Concert halls

    Sound studios - -

    Canteens

    Schools

    Child care acilities

    2. Showrooms/ Showroom/exhibition - -/*1

    Public buildings Supermarkets - -/*1

    Department stores - -/*1

    Pavilions - -

    Museums - -/*1

    Atriums - -/*1

    3. Laboratories VAV ume cupboard extr. - -

    Pharma production

    CAV systems - -

    Clean room classied - -

    R&D laboratories - -

    4. Sport/Leisure Sports halls - -/*1

    Fitness studios /*1

    Shooting ranges -/*1

    Swimming pools - -/*1

    Ice rinks - -/*1

    5. Industry Light industry - -

    Heavy industry - -

    Printing works - -

    Extreme cooling*2 - -

    Vehicle workshops

    6. Food industry Equalising rooms

    Process cooling

    Warehouses/Terminals

    Cheese-ripening acilities

    High-bay warehouses - -

    G U I D E T O S E L E C T I N G T H E B E S T A I R D I S T R I B U T I O N S Y S T E M

    Notes on the table:

    *1 Not recommended in the Low impulse version (textile), only in the Hybrid or

    Coated version

    *2 Extreme cooling requirements cover every type o production premises with a

    cooling requirement > 150 W/m2

    KE-Low Impulse KE-Interior KE-Inject KE-DireJet

    Ventilation Yes Yes Yes Yes

    Cooling Yes Yes Yes Yes

    Displacement ventilation Yes Yes Active Active

    Heating No No Yes Yes

    Category Comment

    - Not recommended

    Usable Acceptable

    Good

    Best

    15

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    18/146

    W H E R E O U R P R O D U C T S A R E U S E D

    K E R E F E R E N C E S F O R C O M F O R T V E N T I L AT I O N

    O F F I C E S , C A N T E E N S , S C H O O L S , C H I L D C A R E F A C I L I T I E S , L E C T U R E H A L L S

    Open-plan ofce: Algida Unilever, TurkeyOpen-plan ofce: Dell Technical Support Centre, USA

    Canteen: Algida Unilever, TurkeyChild care acility: Billy Bubbles, England

    Lecture hall: KPMG, SwedenOpen-plan ofce: 60 working spaces, MediatheekRotterdam, Netherlands

    To see more reerences, visit www.ke-fbertec.com

    16

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    19/146

    K E R E F E R E N C E S F O R S H O W R O O M S / P U B L I C B U I L D I N G S

    S H O W R O O M S , S U P E R M A R K E T S , S T O R E S , R E S TA U R A N T S , A T R I U M S , E X H I B I T I O N C E N T R E S

    Exhibition centre: Stockholm International Fairs, Sweden Atrium: Millennium Plaza, Cardi, Wales

    Car show: Audi, Cardi, Wales

    Museum: Dover Air Base, USA Commercial: Dublin Zoo, Ireland

    Supermarket: Sainsburys, Stoke on Trent, England

    To see more reerences, visit www.ke-fbertec.com

    17

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    20/146

    W H E R E O U R P R O D U C T S A R E U S E D

    K E R E F E R E N C E S F O R L A B O R AT O R I E S

    P R O D U C T I O N , C L E A N R O O M L A B O R AT O R I E S

    Clean room: Alcon Ireland, IrelandLaboratory: Southampton University, England

    Laboratory: Bespack, EnglandLaboratory: Uniquema, Gouda, Netherlands

    Laboratory: Boots Pharmaceuticals (Strepsils), EnglandLaboratory: Pfzer, Sittingbourne Research Centre, England

    To see more reerences, visit www.ke-fbertec.com

    18

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    21/146

    K E R E F E R E N C E S F O R S P O R T / L E I S U R E

    S W I M M I N G P O O L S , S P O R T S A R E N A S , F I T N E S S S T U D I O S

    Swimming pool: YMCA, Newton, USA Swimming pool: Egmont, Netherlands

    Fitness Studio: Esporta, Glasgow, Scotland

    Speed skate arena: Thial Heerenveen, Netherlands Sports arena: Skjern Bank Arena, Denmark

    Ice hockey stadium: Gigantium, Aalborg, Denmark

    To see more reerences, visit www.ke-fbertec.com

    19

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    22/146

    W H E R E O U R P R O D U C T S A R E U S E D

    K E R E F E R E N C E S F O R I N D U S T R I A L V E N T I L A T I ON

    P R O D U C T I O N P R E M I S E S , S T O R A G E R O O M S , P R I N T I N G W O R K S , V E H I C L E W O R K S H O P S

    Industry: Cimbria Construction, Thisted, Denmark

    Printing works: Plantijn Casparie, Netherlands

    Industry: Hickey Freeman, USA

    Industry: McCormicks, England

    Vehicle workshop: Danish Emergency ManagementAgency, Denmark

    Printing works: Geostick, Uithoorn, Netherlands

    To see more reerences, visit www.ke-fbertec.com

    20

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    23/146

    K E R E F E R E N C E S F O R I N D U S T R I A L R E F R I G E R A T I ON

    E Q U A L I S I N G R O O M S , S L I C I N G R O O M S , W A R E H O U S E S , F O O D T E R M I N A L S

    Equalising room: Chalmar Bee, South Arica Process cooling: Danish Crown, Denmark

    Food terminal: Arla Foods, Sweden

    Cold storeroom: Unilever, Sweden Food production: Ordal Bronwater, Belgium

    Process cooling: Dalehead Foods, Bury St. Edmunds,England

    To see more reerences, visit www.ke-fbertec.com

    21

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    24/146

    22

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    25/146

    4 . F R O M D I A L O G U E T O S O L U T I O N

    23

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    26/146

    F R O M D I A L O G U E T O S O L U T I O N

    KE Fibertecs well-trained team o sales engineers have the tools available to oer an en-

    hanced design service, which can help you nd the perect ventilation solution. Even at the

    quotation stage we think it is very important to establish a good dialogue. Dialogue can

    help us to identiy and ormulate the task so that we can guarantee that the TBV solution

    provided will meet the end users requirements and your expectations o the end result.

    R E Q U I R E M E N T S A N D

    E X P E C T A T I O N S

    A L L S O L U T I O N S A R E TA I L O R E D E X A C T LY

    KE Fibertec has developed a number o tools and services which our customers can

    choose to use throughout the entire project process. Our services are graded so that

    customers can decide themselves which ones they do and dont want. Our opinion is thatno two jobs are the same and no solution is standard. Consequently, the documentation

    and level o detail need to be adapted to the requirement and each individual project. Our

    service can be split into two categories:

    1 . Q U O T AT I O N A N D D E S I G N

    2 . E X T E N D E D P R O J E C T D O C U M E N T AT I O N

    KE Fibertec designs solutions or

    a given installation, based on the

    parameters which we have determined

    through dialogue solutions that

    also work in practice. This is why you

    shouldnt be surprised when we ask an

    array o questions right at the quotation

    phase, both about the ventilation

    system and also about the end users

    needs and requirements.

    Company Stamp

    1. What kind of problem is to be solved? (e.g. cooling of people, of a specific area of a room, or of aproduction process). Please notice if there are any major heat sources in the room, like machinery orother room equipment that might have influence on the air distribution:

    2. Type of application and the main purpose: Ventilation / cooling / heating or a combination?

    3. Room Dimensions and Capacities:

    Room length: Room width: Room height:m m m

    Required room temperature: - tolerance :C C

    Supply temperature (heating mode): Supply temperature (cooling mode):C C

    Air quantity: Available external static pressure:m/h Pa

    Project name:

    Date:

    Ref.:

    Page of

    4. Level of activity

    A. Sitting still B. Standing/Periodically movingC. Slight motion / Vigorous motion D. No fixed working stations

    5. Duct mounting height

    Height: To centrem , bottom or top of duct

    6. Placement and type of air inlet?

    Type of inlet: Top inlet: End inlet:

    Placement from end of duct (top inlet) or floor (end inlet) to centre of inlet : mm

    Type of connecting branch: Round D-shaped Square or a hole

    Dimension of connection branch: mm

    Please read KE Fibertecs guideline

    to Technical Questionnaire first or

    check out www.KE-Fibertec.com

    t

    c

    G U I D E L I N E T O T E C H N I C A L Q U E S T I O N N A I R E

    - H E L P U S O F F E R I N G V A L U E F O R M O N E Y !

    Your customers problem? (e.g. cooling down theentire room or just zone cooling?)

    We need to identify the main reason for installing Textile Ba-

    sed Ventilation (TBV). End User expectations is very es-

    sential in order for us to suggest the right solution. Is the

    purpose to create a high degree of comfort for the emplo-

    yees, food or similar product related cooling / heating,

    or is it replacement of air. Please notice that information

    about big heat sources, like machinery is very important.

    Is the application going to be used for ventilation /cooling / heating or a combination?

    This allow us to select the best TBV-product solving your problem.

    Type of application / room - where are you going touse the ducts?

    The more specific information about the application the more

    solution orientated design we can provide. We can include

    reference photos from similar installations and we can use

    our long experience to make the most cost efficient system.

    Room dimensions, temperatures and air quantities:

    This information is essential to make a quotation. The most

    important piece of information is the air quantity as this for

    instance determines the duct diameter and material cha-

    racteristics. It is important that the supply temperature is

    the temperature after the air handler, and that the exter-

    nal static pressure available for the TBV-system is stated.

    Level of activity?

    We aim to keep the air velocity in the occupied zone (1,8 m over the

    floor) at an acceptable level corresponding to the level of activity.

    Mounting height and type of air supply?

    This helps us make an accurate calculation of air distribution

    and define a TBV-system tailored to the system of the customer

    A

    C

    B

    D

    KE Fibertec offer an extended

    design service by our com-

    mitted and experienced engine-

    ers. To be able to provide you

    with the best possible solution,

    we need your input. Please

    read the enclosed guideline

    and technical questionnaire ca-

    refully and send it back to us.

    Height

    LenghtWidth

    Deliverytemperature

    Room

    temperature

    Air quantity+

    Available staticpressure ESP Distances

    Mountiing

    height

    TopCenterBottom

    Mountiing

    height

    24

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    27/146

    Q U O T AT I O N A N D D E S I G N P R O C E S S E S

    KE Fibertec oers advice and support rom our experienced in-house sales engineers, whohave all undergone extensive training on ventilation products and particularly on our TBV

    products. All the calculations are proven using our unique sotware WinVent 3D, which is

    oered to all our customers, regardless o the size o their project and, o course, ree o charge.

    Our quotation and design processes are described in detail in our ISO 9001 quality assurance

    system. This ensures that we prepare the basis or the quotation and the quotation itsel

    according to the standardised guidelines, making sure that the customers requirements

    are specied and documented in sucient detail. KE Fibertec puts large emphasis on

    ensuring that the nal solution is designed correctly even at the quotation stage. Ater all, it

    is not only about ensuring that the textile based ventilation system works properly, but also,

    to just as large extent, that the customers indoor climate requirements have been met.

    This is why we ask about the systems unctional requirements and the requirements or the

    indoor climate at the quotation stage.

    Our quotation is based on the ollowing inormation:

    Air volumes (possibly partial air volumes per socket) [m 3/h]

    Temperature-set cooling and possibly heating [C]

    Pressure available rom the an [Pa]

    Dimensions o the room L x W x H [m 3]

    Location o the air inlet(s)

    Requirements in terms o number o ducts and maximum duct dimensions

    Requirements in terms o the rooms use (room category)

    Requirements in terms o the maximum permissible air velocity in the room [m/s]

    Requirements in terms o the temperature in the room [C]

    Requirements in terms o the maximum sound pressure level in the room [dB(A)]

    Selection o duct colours

    Selection o suspension type

    Given that an innite number o combinations o system solutions and layout eaturescan be designed or textile based ventilation, it is important that its unction is specied

    precisely at the quotation stage. In our role as consultants, we always endeavour to meet

    the relevant need with the solution that we have agreed with the customer to oer. We

    are highly innovative in our way o thinking, which is why you must not always expect just

    a plain solution which ultimately cannot meet the requirements you set in terms o the

    systems appearance and the indoor climate. Our solution is based on the concept AIR

    THE WAY YOU WANT or the same reason.

    KE Fibertec puts large emphasis

    on ensuring that the nal solution

    is designed correctly even at the

    quotation stage. Ater all, it is not only

    about ensuring that the textile based

    ventilation system works properly, but

    also, to just as large extent, that the

    customers indoor climate requirements

    have been met.

    25

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    28/146

    F R O M D I A L O G U E T O S O L U T I O N

    Rapid, easy component assembly in both 2D and 3D

    Online price calculation

    Automatic technical data update

    Complete sound calculations per room

    Production and customer drawings in 2D and 3D, as well as transer to AutoCAD

    Preparation o electronic order conrmations

    Direct transer o orders to laser cutters

    - and many, many more!

    D E S I G N I N W I N V E N T 3 D

    All projects are dimensioned online using our WinVent 3D program, which is always kept upto date with the latest technology and product documentation in textile based ventilation.

    WinVent 3D is an object-oriented CAD/CAM/CAE application developed by KE Fibertec

    AS. WinVent is currently used by all KE Fibertecs partners worldwide and all quotations

    and orders are transerred online via the Internet.

    WinVent 3D oers our sales engineers the ollowing eatures:

    KE Fibertec puts large emphasis on

    proving that our textile based ventilation

    systems will work, which is why we

    speciy all the relevant parameters. We

    also make sure that the end users

    requirements are always met!

    26

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    29/146

    A U T O C A D D R A W I N G S

    Depending on the complexity o the project, KE Fibertecproduces drawings or quotations and orders. Our

    drawings can be split into our categories according to their

    purpose:

    P R O J E C T D O C U M E N T AT I O N

    All our orders obviously include separate installation

    instructions, as well as washing and maintenance

    instructions.

    Fire permits and other certicates are included on request.

    Sketches

    Sales drawings

    Production drawings

    Installation drawings

    I there are existing drawings or a specic project we will

    use these as the basis or our design and layout.

    P R O D U C T D O C U M E N T AT I O N

    KE Fibertec AS puts large emphasis on being able to

    document all our products. KE Fibertec wants to be the

    preerred partner in textile based ventilation, which is why it

    is important or us to ensure that our documentation always

    meets your requirements. All our products have been

    tested and documented in our laboratory and all the data

    is accurately described in catalogues and in our calculation

    program WinVent. This oers all our customers the benet

    o our expertise.

    D AT ASHEET 1

    DET ER M IN IN G T H E M A XIM U M C OOL IN G LOAD P ER M ET R E

    A B C

    D istance d [m] No r mal Lo w F loo r N o rmal Lo w F loo r N o rmal Lo w F loo r

    1.0 0 .3 2 0 .2 3 0 .1 7 0 .4 4 0 .3 2 0 .2 3 0 .5 3 0 .3 8 0 .2 8

    1.5 0 .6 0 0 .4 4 0 .3 2 0 .6 9 0 .5 0 0 .3 6 0 .7 5 0 .5 4 0 .3 9

    2.0 0 .8 9 0 .6 5 0 .4 7 0 .9 2 0 .6 7 0 .4 8 0 .9 3 0 .6 8 0 .4 9

    2.5 1 .1 6 0 .8 5 0 .6 1 1 .1 1 0 .8 0 0 .5 8 1 .1 0 0 .8 0 0 .5 7

    3.0 1 .4 3 1 .0 4 0 .7 5 1 .3 1 0 .9 5 0 .6 9 1 .2 4 0 .9 0 0 .6 5

    3.5 1 .6 8 1 .2 2 0 .8 8 1 .4 8 1 .0 8 0 .7 8 1 .3 8 1 .0 0 0 .7 2

    4.0 1 .9 1 1 .3 9 1 .0 0 1 .6 5 1 .2 0 0 .8 6 1 .5 0 1 .0 9 0 .7 9

    4.5 2 .1 4 1 .5 6 1 .1 2 1 .8 0 1 .3 1 0 .9 4 1 .6 1 1 .1 7 0 .8 4

    5.0 2 .3 6 1 .7 2 1 .2 4 1 .9 4 1 .4 1 1 .0 2 1 .7 2 1 .2 5 0 .9 0

    5.5 2 .5 7 1 .8 7 1 .3 5 2 .0 8 1 .5 1 1 .0 9 1 .8 2 1 .3 2 0 .9 5

    6.0 2 .7 7 2 .0 2 1 .4 5 2 .2 1 1 .6 0 1 .1 6 1 .9 1 1 .3 9 1 .0 0

    6.5 2 .9 7 2 .1 6 1 .5 6 2 .3 3 1 .6 9 1 .2 2 2 .0 0 1 .4 5 1 .0 5

    7.0 3 .1 5 2 .2 9 1 .6 5 2 .4 5 1 .7 8 1 .2 8 2 .0 8 1 .5 1 1 .0 9

    DET ER M IN IN G T H E M A XIM U M C OOL IN G LOA D P ER M ET R E

    C OR R EC T ION , K , F OR D IS T A N C E F R OM DU C T A N D H EA T S OU R C E T Y P ES

    Cooling load per metre [W/m]

    0

    200

    400

    600

    800

    1000

    1200

    1400

    1600

    10 2 3 4 5 6 7 8 9[C]

    d

    1,8m

    Room category C

    Room category B

    Room category A

    max

    = x k

    DA T A S H E E T 13

    K E - D I R E J E T 1 8 M M L0 . 2 0

    A N D L0 . 3 0

    F O R F R E E J E T S

    1

    1

    1

    l,

    l,

    l,

    l,

    l,

    l,

    l,

    200

    P [Pa]s

    150

    100

    90

    40

    50

    60

    70

    80

    l = 30,30

    l = 40,30

    l = 50,30

    l = 60,30

    l = 70,30

    l = 80,30

    q [m/m/h]

    120

    d=

    2

    d=

    4

    d=

    6

    d=8

    d=

    10

    d=

    12

    d=1

    4

    4020 60 80 100 120 140 160 200 400300

    d=2

    d=

    4

    d=6

    d=

    8

    d=

    10

    d=

    12

    d=

    14

    P [Pa]s

    4020 60 80 100 120 140 160 200 400300

    q [m/m/h]

    150

    100

    90

    80

    70

    60

    50

    40

    120

    200

    l = 50,20

    l = 60,20

    l = 70,20

    l = 80,20

    l = 90,20

    l = 100,20

    l = 120,20

    l,

    l,

    l,

    l,

    l,

    l,

    1

    1

    1

    AIRTHE WAY YOUWANT

    100%

    13%

    50%

    Startingpointof dimensioning

    Alu-rails labelled with a saw symbol do not require

    further trimming.

    Please find Information on delivery and installa-

    tion in the box labelled INFO.

    Room reference

    Suspension type

    KE--------#Office1--------------------1std SafeTrack-bulb

    Delivery Note

    Clamp 60 mm

    60 mm max7

    50mm

    max2

    500mm

    Diame

    terB

    (outlet

    )DiameterA(plenum)

    60mm

    **

    20mm

    *

    100mm

    50mm

    130mm

    20mm

    46mm

    26 mm

    36 mm

    26 mm

    max2500 mm

    73%

    100%

    Zip

    **20 mmexternallybetweenendofSafeTrack andsideof outlet socket

    **60mm internallybetweenendofSafeTrack andsideof outlet socket

    Pleasenotethatsomerelevantinformationmaybeonthereverseside

    Seefurther sizingdetails onenclosedproject drawings, if any, andalso seedelivery note(packinglist) andread off positiondescription.

    Double Suspension2 std SafeTrack-bulb

    Washing and MaintenanceKE-Low Impulse/KE-Laser Inject System

    WASHINGAND

    MAINTENANCE

    1.Machineshouldonlybefilledtohalfcapacity.Wash at20-40Cwithordinarydetergentforapprox.5 - 15 m i n. a t a t i me u n ti l t h ewashingwateris totallyclean.

    2.Rinsinginseveralchangesofwaterthatis graduallycooledoff.

    3.In thesecond-lastchangeofr i ns i n g w a te r a d i si n fe c ta n t ( chlor ine), ifneeded,maybead-ded.

    Donotaddfabr icsoftenerasthismayleadtoshr inkageandodour nuisances.

    4.Dripping-normal spin-dryingorhangingonalinewhilest illmoist.

    Dr ippingis recommended, buttumbledrying atlow temperature(max.60Coutgoingair ) canbeeffected,however ,withr isk ofshrinkage.

    WASCHENUND

    WARTUNG

    1 . M a sc h in e n u r h a l b f ll e n.Waschenbei20-40Cmitherkmm-lichemWaschmittelfretwa5-15Min.proMal,bisdasWasserganzsauberist.

    2.Mehrmalssplenim Wasser,daslangsamabgekhltwird.

    3.Bei dervorletztenSplung kann,f a ll s e r fo r de r li c h, e i n D e s-infektionsmittel zugesetzt werden(Chlor).

    WegeneventuellesEinlaufenundGeruchsbelstigungendarfWei ch-splernichtverwendet werden.

    4 . A b tr o pf e n l a s s e n - n o rm a l zentrifugieren oder tropfnassaufhngen.

    TropfnassesAufhngenwird emp-fohlen,aberTrockenschleudernbeiniedrigerTemperatur (max. 60CAusgangsluft)ist zulssig, jedochaufdieGefahr desEinlaufenshin.

    LAVAGEET

    ENTRETIEN

    1.I l fautseulement remplir lamachine laverdemi.Laver20-40C a ve c u n d t er ge nt ordinairependantenv.5-15 min.lafois, jusqu'ce quel'eaudelavagesoit totalementpropre.

    2.Rinagedansplusieurseauxtrspropresqui serefroidissentprogressivement.

    3.Ajouter ,sincessaire,und-sinfectant(chlore) l'avant-der-nireeaude rinage.

    cause de risque dertrcissementet denuisancesolfactivesl'usage dedtergentestdconseill.

    4. Egouttage - centrifugationnormaleou accrochage l'tathumide.

    Leschagepargouttageestrecommander ,maisun schageautambourfaibletemprature(max.60Cdetemp.desor t iedel'air )peutse faire, maisavecrisquedertrcissement.

    March 2006

    0980001-GB/D/F

    GB D F

    070907-01-0

    KE Fibertec AS

    CJ/MS 070907

    KE-system

    90333

    Badminton center

    27

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    30/146

    F R O M D I A L O G U E T O S O L U T I O N

    F U L L - S C A L E T E S T I N G I N O U R L A B O R A T O R Y

    Full-scale measurements can provide a very attractive solution in more complex projects.

    I the end user has any doubt about how the system will work and look or i there are very

    specic room-related reservations, they can contact KE Fibertec and our sales sta will

    submit, in conjunction with the development department, a proposal as to how a particular

    problem can be resolved in the best way. Our ull-scale laboratory is ully equipped so that

    we can visualise dierent solutions with smoke or we can choose to set up a ull-scale

    model o the relevant premises to illustrate and document the air distribution and indoor

    climate. We also oer on-site measurements taken at the end-users premises, i this is

    required. We are able to oer the ollowing:

    E X T E N D E D P R O J E C T D O C U M E N TAT I O N

    KE Fibertec is the only company in textile based ventilation to oer extended project docu-mentation as part o major, complex projects.

    Our extended project documentation includes:

    Full-scale testing in our laboratory

    On-site measurements

    CFD simulations

    Pressure measurements in ducts

    Measurement and logging o air temperature

    Measurement and logging o air humidity

    Measurement o duct speeds using a thermal antenna anemometer

    Measurement o air velocities in rooms using a hot-sphere anemometer

    Volume fow measurements

    Visualisation with smoke

    KE Fibertecs development depart-

    ment is always available to provide

    ull-scale measurements which can

    illustrate air fows and indoor climate

    parameters or a specic project.

    28

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    31/146

    O N - S I T E M E A S U R E M E N T S

    As part o KE Fibertecs quotation, you can request assistance with measuring your ownpremises and advice about the choice o ventilation solution and layout. When the textile

    based ventilation system has been installed we can also give advice on how to set the

    systems parameters. I any unexpected problems arise or you are simply interested in

    having the indoor climate documented, our development department can also oer to take

    measurements on site. This also helps us to provide a better service!

    C F D S I M U L A T I O N S

    KE Fibertec can provide CFD simulations as a major supplement to both technical air

    calculations in WinVent 3D and ull-scale measurements. CFD stands or Computational

    Fluid Dynamics and is a method o computer simulation used or air fows and temperature

    and concentration distribution.

    CFD simulations enable us to create a computer-based model o premises with textile

    based ventilation and to simulate, optimise and evaluate the indoor climate or a specic

    process.

    CFD simulations make a practical, but also time and resource-consuming tool. CFD

    simulations require a vast amount o computer power, depending on the complexity and

    size o the task, to come up with a correct, reliable solution within a reasonable timescale.

    A great deal o expertise in how things unction and operate in textile based ventilation is

    also required. CFD is a very eective tool or determining fow-related phenomena, but it isimportant to bear in mind that CFD cannot replace ull-scale measurements and laboratory

    tests. And also remember:

    CFD simulations cannot replace general common sense and more than 30 years

    experience in air distribution.

    CFD simulations give KE Fibertec the opportunity to carry out a risk assessment and oer

    better advice about air distribution in your project, even at the design stage. This enables

    us to ensure that the systems unction the way they are supposed to, thereby preventing

    problems with penetration lengths in heating installations being too short or with the supply

    air being short circuited. The key thing or a CFD simulation is to document more accurately

    the air distribution and indoor climate.

    F A C T S A B O U T C F D S I M U L A T I O N S

    A CFD simulation is perormed by numerically solving the dierential equations governing the air fow, known as the

    Navier Stokes equations. As CFD simulations oten include complicated three-dimensional fows with heat transer,

    heat radiation and turbulence, the governing equations can only be solved in a very ew cases.

    To solve the fows dierential equations they must be rewritten as algebraic dierential equations. This is done by

    splitting the CFD model into a large number o control volumes (calculation grid), ater which each o the governingequations is solved numerically or each calculation cell. This will provide a complete picture o the pressure, velocity

    and temperature distributions.

    29

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    32/146

    30

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    33/146

    5 . L o w i m p u L s e s Y s T e m s

    31

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    34/146

    1,1m

    Nrzone

    OpholdszoneOccupied zone

    1.1m

    Near zone

    1,8m

    Nrzone

    OpholdszoneOccupied zone

    1.8m

    Near zone

    The air distribution principle used or a textile based ventilation system is undamentally

    dierent rom a conventional ventilation system equipped with steel ducting and conventional

    air distribution ttings. Most architects, consultants and tters in the ventilation industry are

    already amiliar with the general principles o textile based ventilation systems, but not all

    o them are amiliar with the latest product versions and design options. The ollowing

    three chapters provide a brie description o KE Fibertecs product versions, along with a

    description o the air distribution principles or all product types.

    T e X T i L e B A s e D

    V e N T i L AT i o N s Y s T e m s

    T e X T i L e B A s e D L o w i m p u L s e s Y s T e m s

    KE Fibertec markets two products or textile based low impulse ventilation: the KE-LowImpulse System and KE-Interior System. The KE-Low Impulse System is produced using

    round ducts (), while the KE-Interior System is produced using hal-round (D) or quarter-

    round (D) ducts. There is basically no dierence in the air distribution principle when using

    these product versions. For this reason, just one description o the air distribution principle

    will be given below or the systems.

    o C C u p i e D Z o N e F o R L o w i m p u L s e s Y s T e m s

    The occupied zone is the area in a room which people occupy or a long period

    o time and is dened as the area where eorts are made to maintain the indoor

    climate at a general level.

    The occupied zone is not a standardised area, but a zone which is dened rom

    one project to another in consultation with the architect and client. The occupiedzone is oten dened as the zone rom the foor up to a height o 1.8 m above

    people who are in a standing position doing their job, while this height is set to 1.1

    m or people who are seated.

    N e A R Z o N e F o R L o w i m p u L s e s Y s T e m s

    In the case o horizontal low impulse systems, the near zone is dened as the zone

    under the textile ducting where there is the biggest risk o a cold downdraught or

    o draughts in general. The width o the near zone can be reckoned to be no more

    than three times the duct diameter.

    In the case o vertical low impulse systems, the near zone is dened as the local

    zone around the duct where the air velocity is too high in relation to the rooms

    comort requirements (depending on the room category).

    32

    L o w i m p u L s e s Y s T e m s

    KE-Interior System (D)KE-Interior System (D)KE-Low Impulse Systemp R o D u C T R A N G e : L o w

    i m p u L s e s Y s T e m s

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    35/146

    ZONE 1

    ZONE 2

    ZONE 3

    1.8m

    Near zone

    H o R i Z o N TA L L o w i m p u L s e s Y s T e m s

    The air distribution principle or horizontal low impulse systems is based on passive thermaldisplacement where the air is supplied at a lower temperature in relation to the air in the

    room. Because o the dierence in density, with the cooled air being heavier than the

    warmer air in the room, the room air is displaced below the duct while the supply air

    continues moving towards the foor. The air fow in the room is then based on natural air

    movements where the air is driven by the dierence in density and convection fows rom

    heat-releasing activities and processes, hence the term passive thermal displacement. A

    high level o heat activity rom heat sources generates bigger convection currents, resulting

    in the air rising more strongly and greater entrainment o the air around the source. This

    results in stratication in the ventilated room where heat and pollution are drawn away rom

    the occupied zone and extracted under the ceiling.

    A low impulse system can only be used or cooling purposes or or distributing large

    volumes o isothermal air, as warm air will settle under the ceiling like a blanket. When this

    occurs, the supply air is short circuited, which means a waste o energy.

    KE Fibertecs textile based low impulse systems are woven rom Trevira CS polyester yarn,

    and the textile surace acts as a ne mesh, allowing the supply air to pass through

    the surace at a very low, uniorm discharge velocity, which is normally less

    than 0.1 m/s. I the air needs to be distributed according to the low

    impulse principle the discharge velocity should be maintained below

    roughly 0.40-0.50 m/s. This is the limit at which the room air will start

    to be entrained and mixed with the low impulse fow.

    Z O N E 1

    The airfow in zone 1 is particularly reliant upon the cooling load

    per running metre o duct (W/m). A large cooling load leads to a

    more powerul acceleration o the supply air into zone 1, which

    results in the air dropping down and mixing with the rest o the

    air.

    Z O N E 2

    In zone 2 the warmer room air is displaced by the cooled air

    rom the low impulse duct. In low impulse fows there is almost

    no entrainment o the surrounding room air, which can reduce

    the velocity level beore the fow reaches the occupied zone. This

    means that a higher starting level will result in a higher end velocity

    when the air enters the occupied zone.

    Z O N E 3

    The width o the near zone is also particularly reliant upon the

    cooling load per running metre o ducting. The larger the cooling

    load, the narrower the near zone. The width at the entrance to theoccupied zone can be reckoned to be no more than three times

    the diameter o the low impulse duct.

    The picture below illustrates the air distribution principle or horizontal low impulse

    systems.

    The textile surace o textile based low

    impulse systems is a ne mesh, which

    allows supply air to pass through the

    surace at a very low, uniorm velocity.

    33

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    36/146

    As has just been mentioned on the previous page, the cooling load per running meter o

    ducting is crucial to how the air fow will be under the ducting, but the location o the heat

    sources in the room also has a major infuence on the air fow. The ollowing parameters are

    crucial or air velocity and air temperature under the duct:

    Unlike the cooling load per running metre o ducting, the static pressure, which keeps the

    textile duct infated, does not have any particular infuence on the air fows distribution in

    the room. No matter how great the static pressure is in the duct, there is not sucient orce

    (momentum) in the jet to give the air a throw length which is typical o KE Fibertecs high

    impulse systems.

    Cooling load per running metre of ducting

    Large cooling demands result in higher discharge velocities and a greater temperature

    dierence between the room air and the supply air (DT). Both these parameters end

    up accelerating the supply airs velocity.

    Location of heat sources

    Measurements have shown that equally distributed foor heat accelerates the

    discharge velocity much more than heat sources located high up in the premises (1.5

    to 2 m above foor level).

    As mentioned above, it is important to clariy how the heat load is distributed in the premises

    as it makes a big dierence whether the heat loads come rom machines, people or lighting,

    or whether it mainly takes the orm o transmission heat rom surrounding premises. As

    low impulse fows are only controlled by thermal orces, the location o heat sources and

    heat-releasing processes in the room is a vitally important parameter when calculating low

    impulse fows. KE Fibertecs room classication (as also shown in datasheet 1) takes into

    account the heat distribution which normally occurs in dierent types o premises. You are

    recommended to use these dimensioning values. The room classication and inormation

    in datasheet 1 give clear guidelines on how large the cooling load can be with dierent

    comort level requirements.

    The static pressure, which keeps

    the textile duct infated, does not have

    sucient momentum to give the air

    a throw length which is typical o KE

    Fibertecs high impulse systems. Due

    to the dierence in density between

    the supply air and the room air, the

    supply air is displaced towards the foor

    immediately ater passing through the

    textile surace.

    34

    L o w i m p u L s e s Y s T e m s

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    37/146

    L O C A T I O N O F H E A T S O U R C E S

    At heat sources convection heat rises up and will, at a certain propagation

    angle, meet the downcoming air rom the ducting. This phenomenon is also

    encountered with large window panels where the convection heat rom

    radiators located under the windows counteracts the cold downdraught.

    I the heat sources are located at a height the resulting air velocity will be

    somewhat lower when the current arrives down in the occupied zone.

    In other words, i the downcoming air velocity is greater than that o the

    upcoming warm air, the current will continue downwards, but at a reduced

    velocity.

    I the premises mainly has large concentrated heat sources it is important or low impulse

    ducts to be placed lower in the room and distributed between the heat sources rather than

    above in order to achieve a good displacement eect and prevent unnecessary mixing with

    the polluted air rom the upper zone and buoyancy rom machines. This will help to fush

    the work zones under the textile ducting very eectively. It is extremely important that the

    number o textile ducts and their location precisely match that o the machines and that

    the ducting runs or the whole length o the heat source. I the heat sources are distributed

    more evenly, like in oce premises or instance, the low impulse ducts should be placed incorridor areas or along walls to avoid a drop o cold air at xed workplaces. I the upcoming

    convection heat blocks the low impulse current, undesirable stratication can occur, with

    cold air on top and hot air underneath. To avoid a sudden drop o cold air, known as a

    turbulence draught, it is important to create a balanced system so that the risk o a drop

    o cold air does not arise.

    The location o the exhaust grilles also aects the air distribution in the premises. Return

    fow towards an exhaust grille positioned at foor level can eel like a draught, especially in

    cold production acilities where even very low air velocities eel uncomortable. The usual

    recommendation is or extraction vents to be positioned at ceiling level, spread a certain

    distance apart. Large doors or windows which are opened regularly also have an impacton air distribution as the uneven pressure conditions can cause an infow o air rom outside

    and rom surrounding premises.

    In theory, you can calculate the convection velocities above almost every

    common heat source. I you also know the air velocity under the low

    impulse duct you can, in principle, calculate the resulting air velocity, but

    this procedure is denitely not to be recommended! In reality, you will come

    across countless instances where the cold current can spread out to the

    side and veer away rom the ducts centreline and continue at a greater

    velocity than expected, with the subsequent risk o draught problems.

    35

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    38/146

    D T < 0 C

    A delivery o heated air results in the supply air being short circuited where the air

    orms a blanket under the ceiling. Low impulse systems are thereore not suitable

    or heating.

    D T = 0 C

    A delivery o isothermal air produces a very diuse fow pattern. Downward air

    movements (in the direction o the occupied zone) are oten required, in which

    case the recommendation can be made to increase the discharge velocity to

    0.40-0.50 m/s, which is the limit i the air is going to be supplied according to the

    low impulse principle. At discharge velocities above 0.50 m/s you can expect the

    surrounding room air to start being entrained.

    D T < 3 C

    A delivery o supercooled air produces the typical downward fow pattern

    characteristic o low impulse ventilation using textile ducting. A delivery with a

    moderate cooling load does not, under normal circumstances, cause any

    discomort in the near zone, even or those people who are seated. The maximum

    cooling load obviously depends on the distance rom the low impulse ducting to

    the occupied zone. The maximum cooling loads per running metre o ducting as a

    unction o the rooms height can be consulted in datasheet 1.

    D T > 5 C

    As the cooling load per metre o ducting increases, the fow pattern under the

    low impulse duct changes and the near zone becomes narrower, which means

    that the air velocities and air temperatures vertically under the duct may cause

    discomort. A delivery o extremely supercooled air with a cooling load o more

    than 700 W/m o ducting should mainly only be used where comort is a minor

    consideration. However, it is possible to deliver very large volumes o cool air,

    bearing in mind though that the air distribution will not be 100% perect.

    A

    D

    C

    B

    The gures below illustrate the typical fow pattern under a horizontal KE-Low Impulse

    System in a heating scenario, ventilation scenario and two cooling scenarios with a dierent

    cooling load per running meter o ducting.

    36

    L o w i m p u L s e s Y s T e m s

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    39/146

    D T < 0 C

    D T < 3 C

    D T = 0 C

    D T > 5 C

    A B

    C D

    37

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    40/146

    Z O N E 1

    The airfow in zone 1 is particularly reliant upon the cooling load

    per running metre o duct. A large cooling load results in a greater

    downward acceleration or the supply air in zone 1.

    Z O N E 2

    The near zone, which should not be used as a permanentworkplace, is dened as the distance rom the duct beore the

    velocity is reduced to an acceptable level, depending on the

    comort requirement. The length o the near zone is particularly

    dependent on the cooling load.

    Z O N E 3

    It is very important that the volume o air rom the vertical low

    impulse system has been adapted to the cooling requirement and

    that the volume o air supplied is at least equivalent to or greater

    than the convection fows generated by the heat sources. This

    helps to achieve the best displacement eect and create a clean

    zone at the bottom and a polluted zone on top.

    ZONE 3

    ZONE 1

    ZONE 2 Near zone

    V e R T i C A L L o w i m p u L s e s Y s T e m s

    The air distribution principle or vertical low impulse systems is, as with horizontal low impulsesystems, also based on passive thermal displacement where the air is supplied at a lower

    temperature in relation to the room air. The air is supplied, as in conventional displacement

    ventilation, at foor level, directly in the occupied zone. This creates a stratied fow where

    the cooled supply air fows out into the room under the warmer room air.

    In the same way as with horizontal low impulse systems, the fow in the room is based on

    natural air movements where the air is driven by a dierence in density and by convection

    fows rom heat-releasing activities and processes. Convection fows at heat sources

    generate a vertical air fow in the room, thereby creating a clean zone on the bottom and

    a polluted zone on top. A high level o heat activity rom heat sources generates bigger

    convection fows, resulting in the air rising more strongly and greater entrainment o the airaround the source.

    As the cold supply air only mixes to a small extent, it is important the air is supplied at a low

    velocity and slight temperature dierence as otherwise there is a risk o a cold downdraught

    rom the ducting, entailing the risk o a draught at foor level. The systems can, like horizontal

    low impulse systems, only be used or cooling purposes or or distributing isothermal air, as

    warm air will settle under the ceiling like a blanket.

    Vertical low impulse systems are particularly well-suited to premises with high ceilings,

    excess heat and pollution as warm air and polluted particles are drawn up under the ceiling.

    As the fow generated in the premises is moving vertically upwards, the heat and pollution

    do not return to the occupied zone. The picture below illustrates the basic principle o

    vertical low impulse ventilation.

    38

    L o w i m p u L s e s Y s T e m s

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    41/146

    The vertical textile ducts supply resh air directly in the occupied zone, which will obviously

    result in stratication in the ventilated room. This will cause a temperature gradient

    through the room, with the coldest air at the bottom and the warmest on top. This can

    be used benecially to reduce the cooling load as the cooling load removed rom the

    room is directly proportional to the dierence in temperature between the supply air and

    extracted air. I the air is extracted rom the top o the room this will be warmer than the

    air in the rooms occupied zone, allowing the same cooling load to be removed rom the

    room with a higher supply temperature. This results in energy savings when the cooling

    coil in the air conditioning unit is operating. It also means that ree cooling can be used

    or longer periods o the year.

    The required cooling load, combined with any comort requirements, provides the basis

    or determining the volume o supply air and the supply temperature. To determine

    the necessary cooling load accurately, you need to calculate internal and external heat

    loads, while taking into account the heat accumulation in the building.

    In the case o displacement ventilation, comort requirements also include, apart rom air

    velocity and air temperature requirements, the requirement or the maximum permitted

    thermal gradient in the occupied zone. KE Fibertec recommends that the maximum

    thermal gradient in the occupied zone does not exceed 1-2C/m as any bigger dierence

    may eel like a draught. The vertical thermal gradient can be approximately calculated

    based on a so-called 50% rule, which states that hal o the temperature rise rom supply

    to extraction takes place at foor level, while the other hal takes place between the foor

    and ceiling. Contact KE Fibertecs development department or more inormation.

    Designing a ventilation system with vertical low impulse ducts requires considerable

    knowledge about the heat distribution in the premises. It is vitally important that the

    ventilation system is dimensioned correctly so that it takes into account the level o

    comort in the premises work zones and the heat and polluted air are carried upwards

    and out o the occupied zone. To displace the polluted air it is important that the

    volume o air supplied is at least equivalent to the total convection fow volume in the

    room. I this is not the case, the ront o the polluted air will be dragged down towards

    the occupied zone, thereby reducing the eectiveness. Many actors aect the size o

    convection fows in the room, such as the shape, area and surace temperature o theheat sources. But actors like the ambient temperature in the premises also have an

    impact. This is why it is oten dicult to determine accurately the convection currents

    and table values must be used instead.

    Displacement ventilation with textile

    ducting tends to be used a lot in

    industrial environments, but can also be

    used in environments where there are

    high demands or comort.

    39

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    42/146

    D T < 0 C

    Delivering heated air short circuits the supply air, which means that the system is

    not suitable or heating. However, the heated air has a certain penetration, which

    initiates air circulation in smaller premises. As a result, the system can be used, to

    a certain extent, to heat the room beore work begins or it is used.

    D T = 0 C

    Delivering isothermal air produces a very diuse fow pattern, which does not

    generate a powerul displacement eect. Systems are suitable, to some extent,

    or supplying replacement air.

    D T < 3 C

    I slightly supercooled air is supplied the air will slowly drop towards the foor and

    be distributed evenly around the duct. In the event o heat-releasing activities

    and processes, the convection fows will entrain the supply air, thereby creating

    stratication in the room where the heat and pollution are drawn away rom the

    occupied zone and extracted under the ceiling.

    D T > 5 C

    I extremely supercooled air is supplied the air will quickly move towards the foor,

    thereby causing a greater risk o draught problems around the duct as the length

    and width o the near zone around the duct are increased. In the event o heat-

    releasing activities and processes, the convection fows will entrain the supply air,

    thereby creating stratication in the room where the heat and pollution are drawn

    away rom the occupied zone and extracted under the ceiling.

    The gures below illustrate the typical fow pattern under a vertical KE-Low Impulse System

    in a heating scenario, ventilation scenario and two cooling scenarios with a dierent cooling

    load per running meter o ducting.

    A

    D

    C

    B

    40

    L o w i m p u L s e s Y s T e m s

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    43/146

    D T < 0 C

    D T < 3 C

    D T = 0 C

    D T > 5 C

    A B

    C D

    41

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    44/146

    42

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    45/146

    6 . H i g H i m p u l s e s Y s T e m s

    43

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    46/146

    1,8m

    Opholdszone

    Arbejdszone

    1,8m

    H i g H i m p u l s e s Y s T e m s

    KE-Injet System (D)KE-Injet System (D)KE-Injet Systemp R O D u C T R A N g e : H i g H

    i m p u l s e s Y s T e m s

    KE-DieJet System (D)KE-DieJet System (D)KE-DieJet System

    Occupied zone

    1.8

    m

    1.8m

    Working zone Occupied zone

    O C C u p i e D Z O N e F O R H i g H i m p u l s e s Y s T e m s

    As with low impulse ventilation, the occupied zone is not a standardised area,

    but a zone which is dened rom one project to another in consultation with the

    architect and client. The occupied zone is oten dened as the zone rom the foor

    up to a height o 1.8 m above people who are in a standing position doing their

    job, while this height is set to 1.1 m or people who are seated.

    W O R K i N g Z O N e F O R H i g H i m p u l s e s Y s T e m s

    In the case o industrial premises, it may also be appropriate or high impulse

    systems to divide the room up into a working zone as the state o the air may

    vary rom the general level as a result o industrial processes. Heat and pollution

    sources are oten present which require special measures to be able to maintain

    a satisactory indoor climate in the working zone. I processes are carried out

    which cause extreme pollution, textile based ventilation should thereore be

    supplemented with local extraction vents.

    T e X T i l e B A s e D H i g H i m p u l s e s Y s T e m s

    KE Fibertec markets two products or textile based high impulse ventilation: the KE-InjectSystem and KE-DireJet System. Both these systems can be produced in the orm o

    round (), hal-round (D) or quarter-round (D) ducts. The KE-Inject System comprises

    groups o small holes in the textile duct, while the KE-DireJet System comprises rows o

    conical nozzles specically or directional air distribution. From a ventilation technology

    perspective, both the KE-Inject System and KE-DireJet System can be regarded as high

    impulse systems or mixing ventilation. For this reason, one general air distribution principle

    will be described or these systems, while the specic product eatures will be described

    separately.

    44

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    47/146

    ZONE 1

    ZONE 2

    ZONE 3

    1.8m

    A i R D i s T R i B u T i O N p R i N C i p l e F O R H i g H i m p u l s e

    s Y s T e m sKE Fibertecs high impulse systems are based on mixing ventilation and are characterised

    by the act that air is delivered at a high velocity outside the occupied zone. The high air

    velocity rate in the air jet will generate excess pressure, resulting in an infow and entrainment

    o room air towards the air jet supplied. During the rst air fow cycle the air velocity will

    be high, but as the quantity o room air that becomes mixed increases, the air velocity

    will decrease. I the system has been dimensioned properly the delivered air volume will

    be completely mixed with the room air beore it reaches the occupied zone and the air

    velocity rate has dropped to the desired level, depending on the room category. In a mixing

    ventilated room air velocities, air temperatures and humidity will be distributed identically

    and in theory, the air quality will be the same everywhere in the room.

    A textile based high impulse system, unlike its low impulse counterpart, can be

    used or cooling, ventilation and heating. The reason or this is that KE Fibertecs high

    impulses systems, unlike its low impulse systems, are less dependent on external

    eects, such as convective heat currents in the room. The supply air is delivered with

    high initial energy in the orm o velocity (momentum) through holes or nozzles, with

    the eect that the air is discharged into the room instead o being distributed through

    a textile surace at low velocity. This means that KE Fibertecs high impulse systems

    have what are known in fow engineering as a throw length and penetration length.

    Compared with low impulse systems, the location o the exhaust grilles is only o minor

    signicance to the air fows in the room. In practice, they are oten positioned along the ceiling.The picture below illustrates the air distribution principle or high impulse ventilation.

    Z O N E 1

    The air is delivered at high velocity, oten up to 15-18 m/s, through

    the holes (KE-Inject System) or nozzles (KE-DireJet System). This

    generates excess pressure in the centre o the air jets, resulting

    in an infow and entrainment o the air in the room towards the air

    jet supplied.

    Z O N E 2

    As the volume o entrained air increases, the air velocity in the fow

    gradually decreases. The velocity decreases in inverse proportion

    to the distance rom the duct.

    Z O N E 3

    In premises where a certain comort level is required, the air

    velocity at the entrance to the occupied zone must be adapted to

    the conditions, which mainly depend on the level o activity o the

    people working there and what they are wearing (room category).

    To ensure that a suitable air velocity is achieved, the distance rom

    the duct to the occupied zone must be greater than the calculated

    throw length (see denition on page 47).

    45

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    48/146

    f r E E J E T

    I the air jet is directed outwards into the open room, this is what is

    known in fow engineering as a ree jet. The turbulent air jet entrains air

    rom its surroundings and the jets diameter increases in proportion to

    the distance rom the duct, while the velocity in the jet decreases.

    H i g H i m p u l s e s Y s T e m s

    s H O R T C i R C u i T i N g W A R N i N g

    It is important to be aware that mixing ventilation also entails a risk o the supply air beingshort circuited (accumulated under the ceiling). This problem may occur i overheated air

    is supplied combined with an excessively low discharge velocity, or i there are strong

    upward currents in the premises, preventing the air rom reaching the occupied zone. This

    problem becomes particularly apparent when the T is more than 7-12C. In the best

    case scenario, the poor heat distribution in the room can be compensated or by raising

    the supply temperature, but i the heating coil in the air conditioning unit does not have

    sucient capacity to do this, the temperature in the occupied zone will all. This situation

    is very inconvenient, both rom an energy and comort perspective. To make sure that

    short circuiting is prevented, heated air must only be delivered i the supply temperature

    and discharge velocity are adjusted. This means that the warmer the supply air, the higher

    the discharge velocity needs to be to ensure that the air reaches the occupied zone. I the

    ceiling is particularly high (h > 8-10 m) the ducts need to be dimensioned or a high static

    pressure to be able to push the air down into the occupied zone. I this is not possible, the

    ducts can be positioned at a height o 5 metres, or instance.

    F R e e J e T s A N D W A l l J e T s

    A crucial actor or the air distribution principle behind the KE-Inject System and KE-DireJet

    System is the main direction o the air jets. I the jet is directed outwards into the open

    room, this is what is known in fow engineering as a free jet and i the air jet is directed

    at a surace, this is a wall jet. The dierence between these two fow phenomena is their

    ability to entrain room air. I the jet is directed towards the ceiling surace it will try to stick

    to this surace because a negative pressure is generated between the jet and the ceiling as

    no replacement air can be supplied or the volume o room air entrained by the jet. This is

    known as the Coanda eect and it increases the throw length by a actor o in relation

    to the throw length or a ree jet, while the velocity rate in the jet decreases proportionally

    more slowly. The air velocity needs to be a minimum o 0.35 m/s to be able to utilise the

    Coanda eect.

    2

    W A L L J E T

    I the air jet is directed towards a surace, this is what is known in

    fow engineering as a wall jet. The fow can be regarded as a bisected

    open jet as the surace can be regarded as a plane o symmetry. The

    maximum velocity is achieved close to the surace and is greater

    than the equivalent velocity or an open jet at the same distance romthe duct.

    2

    Occupied zone

    46

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    49/146

    v = 0.20 m/siso

    l0.20

    l0.20

    v = 0.20 m/siso

    minimum 0.75 x L

    L

    minimum 0.75 x L

    T H e R m A l p e N e T R A T i O N l e N g T H

    The thermal penetration length is absolutely crucial in

    determining whether the air is actually distributed as

    expected. The theory underlying wall jets is actually based

    on the act that the jet will not become so heavy that it

    will leave the ceilings surace beore it is supposed to. I

    it does, the air velocity at the entrance o the occupied

    zone will be higher than calculated. This means that it

    will eel uncomortable or anyone located in the zone

    aected by the jet. To prevent any drop o cold air, the

    thermal penetration length must be checked to see that itis at least 75% o the horizontal distance along the ceiling,

    L, where the air is moving.

    T H R O W l e N g T H

    The throw length is dened as the largest distance

    rom the supply duct to a specic point in the premises

    where the air velocity is precisely equal to the desired

    nal velocity, e.g. viso

    = 0.20 m/s. It is important to

    note that the throw length, by its denition, is valid in

    isothermal conditions. As a result, the calculations or

    air velocities must be corrected i the supplied air is

    either colder or warmer than the surrounding room air.

    The throw length or a wall jet is longer than or an

    equivalent ree jet. The reason or this is because a wall

    jet sticks to the ceiling due to the Coanda eect and as

    a result, only hal the volume o room air contributes to

    reducing the velocity rate.

    2

    47

  • 8/22/2019 Textile Based Ventilation for a good indoor climate

    50/146

    f L O W M O D E L 1 f L O W M O D E L 2

    0

    30

    60

    90

    150

    180

    120

    -30

    -60

    -90

    -150

    -120

    u s i N g F l O W m O D e l s

    Both the KE-Inject System and KE-DireJet System are highly fexible systems and anydirection at all can be chosen or the air jets. It is obviously important or the air jets to

    point in the main direction o the air fow ollowing the desired air fow pattern in the room.

    As mentioned earlier, it is also important that the air fow is directed downwards towards

    the occupied zone when heating is required in order to prevent short circuiting. Apart rom

    choosing the main direction or the air jet, secondary nozzle positions can be used. For

    instance, i the ceiling needs to be coated locally to avoid the ormation o condensation or

    part o the area needs to be cooled down/heated, it is possible to direct individual nozzles

    or holes towards the relevant area. Nozzles can also be let out entirely in sections o the

    duct i no air needs to be supplied.

    KE Fibertec uses three dierent fow models or textile based mixing ventilation in its everydayactivities, which are fow models 1, 2 and 3 respectively. To be able to use KE Fibertecs

    datasheets properly, you need to know which fow model is involved as all the datasheets

    have been specied or fow models 2 and 3, i.e. ree jets. It is important thereore to clariy

    what the user wants and needs in terms o the system, as well as to become amiliarised

    with processes and activities beore starting to dimension the nal design or the high

    impulse system.

    Using fow model 1 (wall jet) can bring some benet, even though the throw length increases

    as a result o the Coanda eect. Air jets tend to become more stable when cooled air is

    delivered, while the risk o a drop o cold air or draughts in general in the occupied zone

    is kept to a minimum. The Coanda eect also makes the blanket o air stick to theceiling, which means that it will not be defected by local heat sources, obstacles etc.

    Consequently, there is a greater likelihood o achieving the desired fow pattern in reality

    than with delivering an ree jet.

    As was mentioned beore, it is recommended to use fow model 2 or 3 or both the KE-

    DireJet System and KE-Inject System i the system is going to be used to provide heating.