TeSys SK, K, DControl relays
TeSys SK, K Relays - For control of TeSys K contactor coils and other devicesType of product Pages
Mini relay - 2 contacts, simultaneous actionTeSys SK, SKE
B7/2
Relays - 4 contacts, simultaneous actionTeSys K B7/4
Auxiliary contact blocks, accessories B7/6
TeSys D Relays - For control of TeSys D contactor coils and other devices
Relays and auxiliary contact blocks 5 contacts, simultaneous action TeSys D
B7/8
Accessories B7/10
Chapter
B7
Technical Data for Designers B7/13
TeS
ys
B7/2
Con
trol
re
lays
Product references
Mini-control relaysb Width of mini-control relays 27 mm.b Mounting on 35 mm 7 rail.b Connection by connectors.
Control circuit supply Auxiliary contacts Basic reference, to be completed by adding the voltage code (1)
a.c. supply 2 – CA2SK20pp
1 1 CA2SK11pp
d.c. supply 2 – CA3SK20pp
1 1 CA3SK11pp
Mini-control relay with alternating contactsThis mini-control relay with alternating contacts (see function diagram page B7/17) makes it possible to automatically split the operating time between 2 circuits of a redundant system.By regularly energising the “safety circuits”, this device makes it possible to ensure that they are operating correctly.
b Width of mini-control relay 45 mm.b Fixing by Ø4 screws.b Connection by connectors.b Cannot be fitted with front-mounted auxiliary contact block.b Cannot be fitted with coil suppressor module.
Control circuit supply Auxiliary contacts Basic reference, to be completed by adding the voltage code (1)
a.c. supply 2 – CA2SKE20pp
(1) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office):Mini-control relays CA2SK and CA2SKEVolts a 50/60 Hz
24 48 110 120 220 230 240 380 400
Code B7 E7 F7 G7 M7 P7 U7 Q7 V7Mini-control relays CA3SKVolts c 12 24 36 48 72
Code JD BD CD ED SD
TeSys TeSys SK, SKE Mini-control relays
CA2SK11pp
PB12
1522
.tif
CA2SKE20pp
PB12
1523
.eps
Characteristics:pages B7/14 and B7/15
Dimensions:page B7/16
Schemes:page B7/17
B7/3
Con
trol
re
lays
Product references
Instantaneous auxiliary contact blocks Clip-on front mountingFor use on control relays
Maximum number of blocks per contactor
Composition Reference
CA2SK20 1 2 – LA1SK20
– 2 LA1SK02
1 1 LA1SK11
Suppressor modulesConnection without need for tools by clipping onto right-hand side of contactorFor use on control relays
Type For voltages
Sold in lots of
Unit reference
CA2SK and CA3SK Varistor(1)
a and c 24 V…48 V 10 LA4SKE1E
a and c 110 V…250 V 10 LA4SKE1U
Diode(2)
c 24 V…250 V 10 LA4SKC1U
(1) Protection provided by limiting the transient voltage to 2 Uc max. Maximum reduction of transient voltage peaks. Slight increase in drop-out time (1.1 to 1.5 times the normal time).
(2) No overvoltage or oscillating frequency. Slight increase in drop-out time (1.1 to 1.5 times the normal time).
TeSys TeSys SK, SKE Mini-control relays - Contact block - Suppressor
Characteristics:page B7/15
Dimensions:page B7/16
Schemes:page B7/17
LA1SKpp
PB11
1639
_R.e
ps
LA4SKp1p
PB11
1640
_R.e
ps
B7/4
Con
trol
re
lays
Product references
Control relays for a.c. control circuitb Mounting on 35 mm 7 rail or Ø4 screw fixing. b Screws in the open “ready-to-tighten” position.
Control circuitConsumption
Auxiliary contacts
Basic reference, to be completed by adding the voltage code (1)
Screw clamp connections4.5 VA 4 – CA2KN40pp
3 1 CA2KN31pp
2 2 CA2KN22pp
Spring terminal connections4.5 VA 4 – CA2KN403pp
3 1 CA2KN313pp
2 2 CA2KN223pp
Faston connectors, 1 x 6.35 or 2 x 2.84.5 VA 4 – CA2KN407pp
3 1 CA2KN317pp
2 2 CA2KN227pp
Solder pins for printed circuit boards4.5 VA 4 – CA2KN405pp
3 1 CA2KN315pp
2 2 CA2KN225pp
Control relays for d.c. control circuitb Mounting on 35 mm 7 rail or Ø4 screw fixing.b Screws in the open “ready-to-tighten” position.
Screw clamp connections3 W 4 – CA3KN40pp
3 1 CA3KN31pp
2 2 CA3KN22pp
Spring terminal connections3 W 4 – CA3KN403pp
3 1 CA3KN313pp
2 2 CA3KN223pp
Faston connectors, 1 x 6.35 or 2 x 2.83 W 4 – CA3KN407pp
3 1 CA3KN317pp
2 2 CA3KN227pp
Solder pins for printed circuit boards3 W 4 – CA3KN405pp
3 1 CA3KN315pp
2 2 CA3KN225pp
(1) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office):Control relays CA2K (0.8...1.15 Uc) (0.85...1.1 Uc)Volts a 12 20 24(2) 36 42 48 110 115 127 220/ 230 230/ 380/ 400 400/ 440 500 660/50/60 Hz 230 240 400 415 690
Code J7 Z7 B7 C7 D7 E7 F7 FE7 FC7 M7 P7 U7 Q7 V7 N7 R7 S7 Y7Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72Control relays CA3K (0.8...1.15 Uc)Volts c 12 20 24(2) 36 48 60 72 100 110 125 200 220 230 240 250
Code JD ZD BD CD ED ND SD KD FD GD LD MD MPD MUD UDCoil with integral suppression device available: add 3 to the code required. Example: JD3.(2) When connecting an electronic sensor or timer in series with the coil of the control relay, select a 20 V coil (a code Z7,
c code ZD) so as to compensate for the incurred voltage drop.
TeSys TeSys K Control relays
Characteristics:pages B7/18 and B7/19
Dimensions:page B7/20
Schemes:page B7/21
CA2KN22pp
PB12
1524
.eps
CA3KNpp3pp
PB12
1543
.eps
CA3KNpp7pp
PB12
1525
.eps
CA2KNpp5pp
PB12
1526
.eps
B7/5
Con
trol
re
lays
Characteristics:pages B7/18 and B7/19
Dimensions:page B7/20
Schemes:page B7/21
Product references
Low consumption control relays d.c. control circuitb Mounting on 35 mm 7 rail or Ø4 screw fixing. b Screws in the open “ready-to-tighten” position.
Control circuitConsumption
Auxiliary contacts
Basic reference, to be completed by adding the voltage code (1)
Screw clamp connections1.8 W 4 – CA4KN40pp
3 1 CA4KN31pp
2 2 CA4KN22pp
Spring terminal connections1.8 W 4 – CA4KN403pp
3 1 CA4KN313pp
2 2 CA4KN223pp
Faston connectors, 1 x 6.35 or 2 x 2.81.8 W 4 – CA4KN407pp
3 1 CA4KN317pp
2 2 CA4KN227pp
Solder pins for printed circuit boards1.8 W 4 – CA4KN405pp
3 1 CA4KN315pp
2 2 CA4KN225pp
(1) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office):Control relays CA4K (Wide range coil: 0.7...1.3 Uc)Volts c 12 20 24 48 72 110 120
Code JW3 ZW3 BW3 EW3 SW3 FW3 GW3Coil with integral suppression device fitted as standard, by bi-directional peak limiting diode.
TeSys TeSys K Control relays
Characteristics:pages B7/18 and B7/19
Dimensions:page B7/20
Schemes:page B7/21
CA4KN40ppp
PB12
1527
.eps
B7/6
Con
trol
re
lays
Product references
Instantaneous auxiliary contact blocksClip-on front mounting, 1 per control relayConnection Composition Reference
Screw clamp terminals 2 – LA1KN20 – 2 LA1KN021 1 LA1KN114 – LA1KN40 (1)
3 1 LA1KN31 (1)
2 2 LA1KN22 (1)
1 3 LA1KN13 (1)
– 4 LA1KN04 (1)
Spring terminals 2 – LA1KN203– 2 LA1KN0231 1 LA1KN1134 – LA1KN403 (1)
3 1 LA1KN313 (1)
2 2 LA1KN223 (1)
1 3 LA1KN133 (1)
– 4 LA1KN043 (1)
Faston connectors1 x 6.35 or 2 x 2.8
2 – LA1KN207– 2 LA1KN0271 1 LA1KN1174 – LA1KN407 (1)
3 1 LA1KN317 (1)
2 2 LA1KN227 (1)
1 3 LA1KN137 (1)
– 4 LA1KN047 (1)
Electronic time delay contact blocksb Relay output with common point changeover contact, a or c 240 V, 2 A maximumb Control voltage 0.85...1.1 Ucb Maximum switching capacity 250 VA or 150 Wb Operating temperature -10...+ 60 °Cb Reset time: 1.5 s during the time delay period 0.5 s after the time delay period
Clip-on front mounting, 1 per control relayVoltage Type Timing
rangeComposition Reference
V sa or c 24...48 On-delay 1...30 1 LA2KT2E
a 110...240 On-delay 1...30 1 LA2KT2U
Other versions Electronic timers type RE4.Please consult your Regional Sales Office.
(1) Block of 4 contacts for use on CA2K and CA3K.
TeSys TeSys K Control relays - Contact blocks - Time delays
Characteristics:page B7/19
Dimensions:page B7/20
Schemes:page B7/21
LA1KN22
PB12
1528
.eps
LA1KNpp3
PB11
1987
_R.e
ps
LA1KNpp7
PB11
1988
_R.e
ps
LA2KT2E
PB12
1529
.eps
B7/7
Con
trol
re
lays
Suppressor modules incorporating LED indicatorMounting and connection
Type For voltages
Sold in lots of
Unit reference
Clips onto front of relay with locating device.No tools required.
Varistor (1) a and c12...24 V
5 LA4KE1B
a and c32...48 V
5 LA4KE1E
a and c50...129 V
5 LA4KE1FC
a and c130...250 V
5 LA4KE1UG
Diode + Zener diode (2) c12...24 V
5 LA4KC1B
c32...48 V
5 LA4KC1E
RC (3) a220...250 V
5 LA4KA1U
Mounting accessoriesDescription Application Sold in
lots ofUnit reference
Mounting plates On 1 4 rail Clip-on 1 LA9D973
On 2 4 rails 110/120 mm fixing centres
10 DX1AP25
Marking accessoriesDescription Application Sold in
lots ofUnit reference
Marker holder Clip-on fixing on front face – 100 LA9D90
Clip-in markers 4 maximum per relay Strips of 10 identical numbers 0 to 9
25 AB1Rp (4)
Strips of 10 identical capital letters A to Z
25 AB1Gp (4)
(1) Protection provided by limiting the transient voltage to 2 Uc max. Maximum reduction of transient voltage peaks. Slight increase in drop-out time (1.1 to 1.5 times the normal time).
(2) No overvoltage or oscillating frequency. Polarised component. Slight increase in drop-out time (1.1 to 1.5 times the normal time).
(3) Protection by limiting the transient voltage to 3 Uc max. and limitation of the oscillating frequency. Slight increase in drop-out time (1.2 to 2 times the normal time).
(4) Complete the reference by replacing the dot with the required character.
Product references
TeSys TeSys K Control relays - Accessories
Dimensions:page B7/20
Schemes:page B7/21
LA4KC1B
PB11
1989
_R.e
ps
LA9D973
PB12
1533
.eps
LA9D90
PB12
1541
.eps
AB1R9
PB12
1534
.eps
DF5
3363
5.ep
sD
F533
636.
eps
B7/8
Con
trol
re
lays
See page opposite for mounting possibilitiesaccording to control relay type and rating
DF5
2646
1.ep
s
B7/9
Con
trol
re
lays
Control relays for connection by screw clamp terminalsType Number of
contactsComposition Basic reference, to be
completed by adding the control voltage code (1)
Instantaneous 5 5 – CAD50pp (3)
3 2 CAD32pp (3)
Control relays for connection by spring terminalsInstantaneous 5 5 – CAD503pp
3 2 CAD323pp
Instantaneous auxiliary contact blocks for connection by screw clamp terminalsFor use in normal operating environmentsNumber of contacts
Maximum number per relay Composition ReferenceClip-on mountingfront side
2 1 – 1 1 LADN11– 1 on LH side 1 1 LAD8N11 (6)
1 – 2 – LADN20– 1 on LH side 2 – LAD8N20 (6)
1 – – 2 LADN02– 1 on LH side – 2 LAD8N02 (6)
4 (4) 1 – 2 2 LADN22 LADN22S (7)
1 3 LADN134 – LADN40– 4 LADN043 1 LADN31
4 (4) 1 – 2 2 LADC22Including 1 N/O and 1 N/C make before break.With dust and damp protected contacts, for use in particularly harsh industrial environmentsNumber of contacts
Maximum number per relay
Composition Reference
Front mounting
protected (5) not protected2 1 2 – – – – LA1DX20
– 2 – – – LA1DX022 – 2 – – LA1DY20 (8)
4 (4) 1 2 – – 2 – LA1DZ402 – – 1 1 LA1DZ31
Instantaneous auxiliary contact blocks for connection by spring terminals This type of connection is not possible for contact blocks LAD 8 and blocks with dust and damp protected contacts. For all other instantaneous auxiliary contact blocks, add the digit 3 to the end of the references selected above. Example: LADN11 becomes LADN113. (1) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).a.c. supply
Volts a 24 42 48 110 115 220 230 240 380 400 415 44050/60 Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7d.c. supply (coils with integral suppression device fitted as standard)
Volts c 12 24 36 48 60 72 110 125 220 250 440U from 0.7 to 1.25 Uc JD BD CD ED ND SD FD GD MD UD RDLow consumption (coils with integral suppression device fitted as standard)
Volts c 5 12 20 24 48 110 220 250Code AL JL ZL BL EL FL ML UL(2) LC: low consumption.(3) To order control relays with connection by lugs, add the digit 6 to the end of the selected reference.
Example: CAD50pp becomes CAD506pp.(4) Blocks with 4 auxiliary contacts cannot be used on low consumption control relays.(5) Product fitted with 4 earth screen continuity terminals.(6) These contact blocks are allowed with AC coil control relay only.(7) With red front face - for safety chain indication.(8) With 2 earth screen continuity poles.
Product references
Characteristics:pages B7/22 to B7/24
Curves:page B7/25
Dimensions:page B7/26
Schemes:page B7/27
CAD50pp
PB11
4200
_R.e
ps
CAD503pp
PB11
4198
_R.e
ps
LADN22
PB12
1539
.eps
LA1DY20
PB12
1530
.eps
TeSys TeSys D Control relays
B7/10
Con
trol
re
lays
Time delay auxiliary contact blocks for connection by screw clamp terminals (1)
Number and type of contacts
Maximum number per relay
Time delay Reference
Front mounting Type Range1 N/C and 1 N/O 1 On-delay 0.1…3 s (2) LADT0
0.1…30 s LADT210…180 s LADT41…30 s (3) LADS2
Off-delay 0.1…3 s (2) LADR00.1…30 s LADR2
(Sealing cover: see page B8/28) 10…180 s LADR4
Time delay auxiliary contact blocks for connection by spring terminals Add the digit 3 to the references selected above. Example: LADT0 becomes LADT03.
Mechanical latch blocks (4)
Unlatching control
Maximum number per relay
Basic reference to be completed (5)Front mounting
Manual or electric 1 LAD6K10p
Suppressor modulesThese modules clip onto the top of the control relay and the electrical connection is instantly made. Fitting of an input module is still possible.RC circuits (Resistor-Capacitor)b Effective protection for circuits highly sensitive to “high frequency” interference. b Voltage limited to 3 Uc maximum and oscillating frequency limited to 400 Hz maximum.b Slight time delay on drop-out (1.2 to 2 times the normal time).For mounting on
Operational voltage
Reference
CAD a a 24…48 V LAD4RCEa 50…127 V LAD4RCGa 110…250 V LAD4RCU
Varistors (peak limiting) b Protection provided by limiting the transient voltage value to 2Uc maximum. b Maximum reduction of transient voltage peaks.b Slight time delay on drop-out (1.1 to 1.5 times the normal time).
CAD a a 24…48 V LAD4VEa 50…127 V LAD4VGa 110…250 V LAD4VU
Freewheel diodeb No overvoltage or oscillating frequency. b Increase in drop-out time (6 to 10 times the normal time).b Polarised component.
CAD c c 5…600 V LAD4DDL
Bidirectional peak limiting diode (6)
b Protection provided by limiting the transient overvoltage value to 2Uc maximum. b Maximum reduction of transient voltage peaks.
CAD a a 24 V LAD4TBa 72 V LAD4TS
CAD c c 24 V LAD4TBDLc 72 V LAD4TSDLc 125 V LAD4TGDLc 250 V LAD4TUDLc 600 V LAD4TXDL
(1) These contact blocks cannot be used on low consumption control relays.(2) With extended scale from 0.1 to 0.6 s.(3) With switching time of 40 ms ±15 ms between opening of the N/C contact and closing of the N/O contact.(4) Power should not be simultaneously applied or maintained to the mechanical latching block of the CAD N. The duration of
the control signal to the mechanical latching block and the CAD N should be u 100 ms.(5) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office):Volts a and c 24 32/36 42/48 60/72 100 110/127 220/240 256/277 380/415Code B C E EN K F M U Q(6) CADpp c and low consumption control relays are fitted with a built-in bi-directional peak limiting diode suppressor as
standard. On control relays produced after 15th July 2004, this diode is removable. It can therefore be replaced by the user (see references LAD4Tppp above). It can also be replaced by a freewheel diode LAD4DDL. If a d.c. or low consumption control replay is used without suppression, the standard suppressor should be replaced with a blanking plug LAD9DL.
Product references
Characteristics:pages B7/22 to B7/24
Illustrations:page B7/8
Curves:page B7/25
Dimensions:page B7/26
Schemes:page B7/27
LAD6K10
8105
31.e
ps
LAD4RCU
DF5
1038
4.ep
sD
F503
726.
eps
LAD4DDL
TeSysTeSys D Control relays - Accessories
PB12
1535
.eps
PB12
1536
.eps
PB12
1537
.eps
PB12
1538
.eps
LADT2
8105
33.e
ps
B7/11
Con
trol
re
lays
Accessories (to be ordered separately)Description For
mounting onSold in lots of
Unit reference
For markingSheet of 64 blank legends, self-adhesive, 8 x 33 mm
CAD, LAD (4 contacts) 10 LAD21
Sheet of 112 blank legends, self-adhesive, 8 x 12 mm
LAD (2 contacts),LADT
LAD22
Strips of blank, self-adhesive legends for printing by plotter (4 sets of 5 strips)
All products 35 LAD24
“SIS Label” labelling software for legends LAD 21 and LAD 22, supplied on CD-Rom
Multi-language version:English, French, German, Italian, Spanish
1 XBY2U
Legend holder, snap-in, 8 x 18 mm
LC1D09...38LC1DT20...40LADN (4 contacts)LADT, LAD R
100 LAD90
For protectionSealing cover LADT, LAD R 1 LA9D901Safety cover preventing access to the moving contact carrier
CAD LAD9ET11
Red cover (for safety chain indication)
CAD 1 LAD9ET1S
LAD9ET1S
PB11
3924
_R.e
ps Spare parts: coilsSpecificationsb Average consumption at 20 °C:
- inrush (cos φ = 0.75) 50/60 Hz: 70 VA at 50 Hz, - sealed (cos φ = 0.3) 50/60 Hz: 8 VA at 60 Hz,
b Operating range (θ < 60 °C): 0.85 to 1.1 UcControl circuit voltage Uc
Average resistance at 20 °C ±10 %
Inductance of closed circuit
Reference (1) 50/60 Hz
V V H
LXD1
PB12
1531
.eps 12 6.3 0.26 LXD1J7
21 (2) 5.6 0.24 LXD1Z724 6.19 0.26 LXD1B732 12.3 0.48 LXD1C736 – – LXD1CC742 19.15 0.77 LXD1D748 25 1 LXD1E760 – – LXD1EE7100 – – LXD1K7110 130 5.5 LXD1F7115 – – LXD1FE7120 159 6.7 LXD1G7127 192.5 7.5 LXD1FC7200 – – LXD1L7208 417 16 LXD1LE7220/230 539 22 LXD1M7 (3)
230 595 21 LXD1P7230/240 645 25 LXD1U7 (4)
277 781 30 LXD1W7380/400 1580 60 LXD1Q7400 1810 64 LXD1V7415 1938 74 LXD1N7440 2242 79 LXD1R7480 2300 85 LXD1T7500 2499 – LXD1S7575 3294 – LXD1SC7600 3600 135 LXD1X7690 5600 190 LXD1Y7(1) The last 2 digits in the reference represent the voltage code. (2) Voltage for special coils fitted in control relays with serial timer module with 24 V supply.(3) This coil can be used on 240 V at 60 Hz.(4) This coil can be used on 230/240 V at 50 Hz and on 240 V only at 60 Hz.
Product references
LA9D901
8105
35.e
ps
TeSys TeSys D Control relays - Accessories, spare coils
PB12
1532
.eps
B7/12
B7/13
Con
trol
re
lays
Technical Data for Designers
TeS
ys S
K, K
, D
ContentsTeSys SK: > characteristics ................... B7/14 and B7/15 > dimensions ..........................................B7/16 > schemes ..............................................B7/17TeSys K: > characteristics ................... B7/18 and B7/19 > dimensions ..........................................B7/20 > schemes ..............................................B7/21TeSys D: > characteristics ...................... B7/22 to B7/24 > curves .................................................B7/25 > dimensions ..........................................B7/26 > schemes ..............................................B7/27
B7/14
Con
trol
re
lays
EnvironmentRated insulation voltage (Ui) Conforming to IEC 60947,
CSA 22-2 n° 14, UL 508V 690
Conforming to standards IEC/EN 60947-5-1, UL 60947-5-1, CSA C22.2 n° 60947-5-1, GB/T 14048.5Approvals cULus, CCC, EAC, CB certificationDegree of protection Conforming to IEC 60529 Protection against direct finger contact IP2XAmbient air temperature around the device
Storage °C -50…+70Operation °C -20…+50
Maximum operating altitude Without derating m 2000
Operating position Vertical axis Horizontal axis
DF5
1102
8.ep
s
DF5
1102
9.ep
s
Without derating Without derating
Connection by connectors Min. Max.Solid cable mm2 1 x 1.5 or 2 x 1.5 1 x 6 or 2 x 4Flexible cable without cable end mm2 1 x 0.5 or 2 x 0.35 1 x 6 or 2 x 2.5Flexible cable with cable end mm2 1 x 0.35 or 2 x 0.35 1 x 6 or 2 x 1.5
Tightening torque Pozidriv n° 1 head N.m 0.8Terminal referencing Conforming to standards
EN 50005 and EN 50011Up to 4 contacts
Control circuit characteristicsControl relay CA2SK CA2SKE CA3SK
Rated control circuit voltage (Uc) V a 24…400 c 12…72Control voltage limits (y 50 °C)
For operation 0.85…1.1 Uc 0.85…1.1 UcFor drop-out y 0.20 Uc y 0.10 Uc
Average consumption at 20 °C and at Uc
Inrush 16 VA 23 VA 2.2 WSealed 4.2 VA 4.9 VA 2.2 W
Heat dissipation W 1.4 1.5 2.2Operating time at 20 °C and at Uc
Between coil energisation andopening of the N/C contacts ms 8…16 10…18closing of the N/O contacts ms 7…14 8…12
Between coil de-energisation andopening of the N/O contacts ms 6…8 4…6closing of the N/C contacts ms 8…10 6…8
Maximum operating rate In operating cycles per hour 1200 1200Mechanical durability at Ucin millions of operating cycles
50/60 Hz coil 10 –Standard c coil – 10
Characteristics
TeSys TeSys SK, SKE Mini-control relays
References:pages B7/2 and B7/3
Dimensions:page B7/16
Schemes:page B7/17
Ref.
B7/15
Con
trol
re
lays
Characteristics
Auxiliary contact characteristics of mini-control relays and instantaneous contact blocksRated operational voltage (Ue)
V Up to 690
Rated insulation voltage (Ui) Conforming to IEC 96047 V 690
Conventional rated thermal current (Ith)
For ambient temperature y 55 °C
A 10
Frequency of the operational current Hz Up to 400
Short-circuit protection Conforming to IEC 60947, gl fuse
A 10
Operational power of contacts conforming to IEC 60947a.c. supply, category AC-15 d.c. supply, category DC-13
Electrical durability (valid for up to 3600 operating cycles/hour) on an inductive load such as the coil of an electromagnet: making current (cos φ 0.7) = 10 times the power broken (cos φ 0.4).
Electrical durability (valid for up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the load.
V 24 48 110/ 127
220/ 230
380/ 400
440 V 24 48 110 220 440
1 million operating cycles VA 48 96 240 440 800 880 W 120 80 60 52 513 million operating cycles VA 17 34 86 158 288 317 W 55 38 30 28 2610 million operating cycles VA 7 14 36 66 120 132 W 15 11 9 8 7Occasional making capacity VA 1000 2050 5000 10000 14000 13 000 W 720 600 400 300 230
TeSys TeSys SK, SKE Mini-control relays
References:page B7/3
Dimensions:page B7/16
Schemes:page B7/17
Ref.
B7/16
Con
trol
re
lays
DimensionsMini-control relaysCA2SK and CA3SK
3,5LA4 SK
55,5
56
27
DF5
3366
8.ep
s
56
2755,5
84,55
3,5LA1 SK (1)
DF5
3366
9.ep
s
(1) Only on CA2SK20.
MountingMini-control relaysCA2SK and CA3SK
On mounting rail NSYDR200BD or NSYDR200 (7 35 mm)
56
55,5 27
DF5
3367
0.ep
s
DimensionsCA2SKE
4
68 45
58
DF5
3367
1.ep
s
MountingCA2SKEOn panel On mounting rail NSYDR200BD or NSYDR200 (7 35 mm)
34-35
48-5
0
DF5
3367
2.ep
s 4568
58
DF5
3367
3.ep
s
Dimensions and mounting
TeSys TeSys SK, SKE Mini-control relays
References:pages B7/2 and B7/3
Characteristics:pages B7/14 and B7/15
Schemes:page B7/17
Ref.
B7/17
Con
trol
re
lays
SchemesCA2SK20, CA3SK20 CA2SK11, CA3SK112 N/O 1 N/O + 1 N/C
A1
13/N
O14A
2
23/N
O24
DF5
3367
4.ep
s
A1
13/N
O14A
2
21/N
O22
DF5
3367
5.ep
s
CA2SKE CA2SKE2 N/O Function diagram
A1
13/N
O14A
2
23/N
O24
DF5
3367
6.ep
s
A2A1
1413
2423
De-energised
Close
Open
Close
Open
EnergisedD
F533
677.
eps
Instantaneous auxiliary contacts 2 N/O 2 N/C 1 N/O + 1 N/C
LA1SK20 LA1SK02 LA1SK11
33/N
O34 44
43/N
O
DF5
3367
8.ep
s
31/N
C32 42
41/N
C
DF5
3367
9.ep
s
33/N
O34 42
41/N
C
DF5
3368
0.ep
s
Schemes
TeSys TeSys SK, SKE Mini-control relays
References:pages B7/2 and B7/3
Characteristics:pages B7/14 and B7/15
Dimensions:page B7/16
Ref.
B7/18
Con
trol
re
lays
Characteristics
EnvironmentConforming to standards IEC/EN 60947-5-1, UL 60947-5-1, CSA C22.2 n° 60947-5-1, GB/T 14048.5Product certifications UL, CSA, CCC, EAC, CB certification Operating positions Vertical axis
DF5
3362
9.ep
s
Horizontal axis
DF5
1102
6.ep
s
DF5
3363
0.ep
s
Without derating Without derating Possible positions for CA2K only, with derating, please consult your Regional Sales Office.
Connection Min. Max. Max. to IEC 60947Screw clamp connections Solid cable mm2 1 x 1.5 2 x 4 1 x 4 + 1 x 2.5
Flexible cable without cable end mm2 1 x 0.75 2 x 4 2 x 2.5Flexible cable with cable end mm2 1 x 0.34 1 x 1.5 + 1 x 2.5 1 x 1.5 + 1 x 2.5
Spring terminals Solid cable mm2 1 x 0.75 1 x 1.5 2 x 1.5Flexible cable without cable end mm2 1 x 0.75 1 x 1.5 2 x 1.5
Faston connectors Clip mm 2 x 2.8 or 1 x 6.35Solder pins for printed circuit board
With locating device between power and control circuits
4 mm x 35 microns
Tightening torque Philips head n° 2 and Ø6 N.m 0.8Terminal referencing Conforming to standards
EN 50005 and EN 50011Up to 8 contacts
Degree of protection Conforming to IEC 60529 Protection against direct finger contact IP2x (devices with screw clamp terminals or pins for printed circuit board)
Ambient air temperaturearound the device
Storage °C -50...+80Operation °C -25...+50
Maximum operating altitude Without derating m 2000Vibration resistance Control relay open 2 gn5...300 Hz Control relay closed 4 gnFlame resistance Conforming to IEC 60695-2-11 850 °CShock resistance(1/2 sine wave, 11 ms)
Control relay open 10 gnControl relay closed 15 gn
Control circuit characteristicsControl relay type CA2K CA3K CA4K
Rated control circuit voltage (Uc) V a 12...690 c 12...250 c 12...120Control voltage limits (y 50 °C) single voltage coil
For operation 0.8...1.15 Uc 0.8...1.15 Uc 0.7...1.3 UcFor drop-out y 0.2 Uc y 0.1 Uc y 0.1 Uc
Mechanical durability at Uc In millions of operating cycles
50/60 Hz coil 10 – –Standard c coil – 20 –Wide range, low consumption c coil
– – 30
Maximum operating rate In operating cycles per hour 10 000 10 000 6000Average consumption at 20 °C and at Uc
Inrush 30 VA 3 W 1.8 W Sealed 4.5 VA 3 W 1.8 W
Heat dissipation W 1.3 3 1.8Operating time at 20 °C and at Uc
Between coil energisation andopening of the N/C contacts ms 5...15 25...35 25...35closing of the N/O contacts ms 10...20 30...40 30...40
Between coil de-energisation and opening of the N/O contacts ms 10...20 10 10...20closing of the N/C contacts ms 15...25 15 15...25
Maximum immunity to microbreaks ms 2 2 2
TeSys TeSys K Control relays
References:pages B7/4 to B7/7
Dimensions:page B7/20
Schemes:page B7/21
Ref.
B7/19
Con
trol
re
lays
Characteristics
Contact characteristics of control relays and instantaneous contact blocksNumber of auxiliary contacts On CApK 4
On LA1K 2 or 4 for CA2K and CA3K, 2 for CA4KRated operational voltage (Ue) Up to V 690Rated insulation voltage (Ui) Conforming to IEC 60947 V 690
Conforming to UL 60947-5-1, CSA C22.2 n° 60947-5-1
V 600
Conventional thermal current (Ith)
For ambient temperature y 50 °C A 10
Frequency of the operational current Hz Up to 400Minimum switching capacity U min V 17
I min mA 5Short-circuit protection Conforming to IEC 60947,
gG fuseA 10
Rated making capacity Conforming to IEC 60947I rms A 110
Short-time rating Permissible for 1 s A 80500 ms A 90100 ms A 110
Insulation resistance MΩ > 10Non-overlap distance CApK and LA1K: linked contacts
conforming to INRS, BIA and CNA specifications
mm 0.5 (see schemes page B7/21)
Operational power of contacts conforming to IEC 60947a.c. supply, category AC-15 d.c. supply, category DC-13
Electrical durability (valid for up to 3600 operating cycles/hour) on an inductive load such as the coil of an electromagnet: making current (cos φ 0.7) = 10 times the power broken (cos φ 0.4)
Electrical durability (valid for up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the load.
V 24 48 110/127
220/230
380/400
440 600/690
V 24 48 110 220 440 600
1 million operating cycles VA 48 96 240 440 800 880 1200 W 120 80 60 52 51 503 million operating cycles VA 17 34 86 158 288 317 500 W 55 38 30 28 26 2510 million operating cycles VA 7 14 36 66 120 132 200 W 15 11 9 8 7 6Occasional making capacity VA 1000 2050 5000 10000 14000 13000 9000 W 720 600 400 300 230 200
1 Breaking limit of contacts valid for: b maximum of 50 operating cycles at 10 s intervals (power broken = making current x cos φ 0.7).
2 Electrical durability of contacts for: b 1 million operating cycles (2a)b 3 million operating cycles (2b)b 10 million operating cycles (2c).
3 Breaking limit of contacts valid for:b maximum of 20 operating cycles at 10 s intervals with current passing for 0.5 s per operating cycle.
4 Thermal limit
10 000
5000
3000
2000
1000800600500400300
200
1008060
24 48 110 220440 690 V120
380 50040
16 000
80006000
4000
2c2b
4
1
2a
Power broken in VA
DF5
2330
5.ep
s
1000
700500
300
200
1008060504030
20
1086
12 24 48 110 220 440 600 V
250
200
140
100
50
20
2c
2a
3
4
2b
Power broken in W
Tim
e co
nsta
nt
in m
s
DF5
1056
1.ep
s
TeSys TeSys K Control relays & contact blocks
References:page B7/6
Dimensions:page B7/20
Schemes:page B7/21
Ref.
B7/20
Con
trol
re
lays
Dimensions and mounting
Control relaysCA2K, CA3K, CA4K On panel On printed circuit board
5735
LA1 K
58 50=
=
35
45
= =
DF5
3363
7.ep
s
49 51.5
45
58
8.65 = = = A1
A21.9
DB4
2584
0.ep
s
On mounting rail NSYDR200BD or NSYDR200 (7 35 mm)
57
58
45
DF5
3363
9.ep
s
LA9D973 DX1AP25 On asymmetrical rail with clip-on mounting plates On asymmetrical rail with clip-on mounting plates
57 21
45
35= =
505
5
DF5
3364
0.ep
s
110
45
120
57
57 27
DZ5 ME5
DF5
3364
1.ep
s
Electronic time delay contact blocksLA2KT
On control relay
38 38
27
DF5
3364
2.ep
s
57
LA2 KT
58
38
DF5
3364
4.ep
s
Suppressor modulesLA4K
On control relay
6
25
22DF5
3364
3.ep
s
5722
58
LA4 K
DF5
3364
5.ep
s
TeSys TeSys K Control relays
References:pages B7/4 to B7/7
Characteristics:pages B7/18 and B7/19
Schemes:page B7/21
Ref.
B7/21
Con
trol
re
lays
Schemes
Control relays With integral suppression deviceCA2K, CA3K, CA4K CA3K CA4K4 N/O 3 N/O + 1 N/C 2 N/O + 2 N/C
+A
1–A
2
DF5
3364
9.ep
s
_+ A1 A2
DD
4257
37.e
ps
A1
A2
14 24 34
13/N
O
23/N
O
33/N
O
43/N
O44
DF5
3364
6.ep
s
A1A2
13/N
O14
21/N
C22
33/N
O34
43/N
O44
DD
4257
35.e
ps
A1A2
13/N
O14
21/N
C22
31/N
C32
43/N
O44
DD
4257
36.e
ps
Instantaneous auxiliary contact blocks LA1KFor CA2K, CA3K, CA4K For CA2K, CA3K2 N/O 2 N/C 1 N/O + 1 N/C 4 N/O 3 N/O + 1 N/C 2 N/O + 2 N/C
LA1KN20, LA1 KN207 LA1KN02, LA1 KN027 LA1KN11, LA1 KN117
LA1KN40, LA1 KN407 LA1KN31, LA1 KN317 LA1KN22, LA1KN227
53/N
O54
63/N
O64
DF5
3365
1.ep
s
61/N
C62
51/N
C52
DF5
3365
2.ep
s
61/N
C62
53/N
O54
DD
4257
38.e
ps
54 64 74
53/N
O
63/N
O
73/N
O
83/N
O84
DF5
3365
4.ep
s
62 74
53/N
O54
61/N
C
73/N
O
83/N
O84
DD
4257
39.e
ps
53/N
O54
61/N
C62
71/N
C72
83/N
O84
DD
4257
40.e
ps
1 N/O + 3 N/C 4 N/CLA1KN13, LA1KN137 LA1KN04, LA1KN047
54 62 72 82
53/N
O
61/N
C
71/N
C
81/N
C
DD
4257
41.e
ps
51/N
C52
61/N
C62
71/N
C72
81/N
C82
DF5
3365
8.ep
s
Electronic time delay contact blocks LA2KT Suppressor modulesFor CA2K, CA3K, CA4K LA4KC LA4KE1 C/O
+ _
DF5
3366
0.ep
s
DF5
3366
1.ep
s
LA2KT2
A1
A2
1815
16
DF5
3365
9.ep
s
TeSys TeSys K Control relays
References:pages B7/4 to B7/7
Characteristics:pages B7/18 and B7/19
Dimensions:page B7/20
Ref.
B7/22
Con
trol
re
lays
TeSys TeSys D Control relays
EnvironmentControl relay type CAD a CAD c CAD c
low consumptionRated insulation voltage (Ui) Conforming to IEC 60947-5-1
Overvoltage category III and degree of pollution 3
V 690 690 690
Conforming to UL, CSA V 600 600 600
Rated impulse withstand voltage (Uimp)
Conforming to IEC 60947 kV 6 6 6
Separation of electrical circuits
Conforming to IEC 60536 Reinforced insulation up to 400 V
Conforming to standards IEC/EN 60947-5-1, UL 60947-5-1, CSA C22.2 n° 60947-5-1, GB/T 14048.5
Product certifications UL, CSA, CCC, EAC, CB certification, EU-MR-RO by DNV-GL
Degree of protection Conforming to IEC 60529 Front face protected against direct finger contact IP 2X Protection against direct finger contact IP 2X
Ambient air temperature around the device
Storage °C -60…+80
Operation (1) °C -40…+60
Allowed (1) °C +60...+70 at Uc to 1,●● x Uc
Maximum operating altitude Without derating m 3000 3000 3000
Operating positions Without derating in the following positions
30°
30°
DF5
1076
4.ep
s
DF5
1076
5.ep
s
90°90°
180°
DF5
1076
6.ep
s
180°
Positions that are not allowed
DF5
3781
4.ep
s
DF5
3781
5.ep
s
Shock resistance (2)
half sine wave for 11msControl relay open 10 gn 10 gn 10 gn
Control relay closed 15 gn 15 gn 15 gn
Vibration resistance (2)
5…300 HzControl relay open 2 gn 2 gn 2 gn
Control relay closed 4 gn 4 gn 4 gn
Screw clamp connections Flexible conductor without cable end
1 conductor mm2 1…4 1…4 1…4
2 conductors mm2 1…4 1…4 1…4
Flexible conductor with cable end
1 conductor mm2 1…4 1…4 1…4
2 conductors mm2 1…2.5 1…2.5 1…2.5
Solid conductor without cable end
1 conductor mm2 1…4 1…4 1…4
2 conductors mm2 1…4 1…4 1…4
Tightening torque N.m 1.7 1.7 1.7
Spring terminal connections 1 or 2 flexible or rigid conductors without cable end
mm2 1…2.5 1…2.5 1…2.5
(1) As per IEC60947-1, operating time and drop out voltage given and tested for -5...+40 °C.(2) In the least favourable direction, without change of contact state, with coil supplied at Uc.
Characteristics
References:pages B7/9 to B7/11
Curves:page B7/25
Dimensions:page B7/26
Schemes:page B7/27
Ref.
B7/23
Con
trol
re
lays
TeSys TeSys D Control relays
Control circuit characteristicsControl relay type CAD a CAD c CAD
low consumptionRated control circuit voltage (Uc) V 12…690 12…440 c 5…72Control voltage limits
Operation With coil 50/60 Hz 0.8…1.1 Uc at 50 Hz – –0.85…1.1 Uc at 60 Hz – –
With standard coil, wide range
– 0.7…1.25 Uc 0.7…1.25 Uc
Drop-out 0.3…0.6 Uc 0.1…0.25 Uc 0.1…0.25 Uc
Average consumption at 20 °C and at Uc
a 50/60 Hz (at 50 Hz) VA Inrush: 70 – –sealed: 8 – –
With standard coil W – Inrush or sealed: 5.4 Inrush or sealed: 2.4
Operating time(at rated control circuit voltage and at 20 °C)
Between coil energisation and- opening of the N/C contacts
ms 4…19 55 ± 15 % 67 ± 15 %
- closing of the N/O contacts ms 12…22 63 ± 15 % 77 ± 15 %
Between coil de-energisation and- opening of the N/O contacts
ms 4…12 20 ± 20 % 27 ± 20 %
- closing of the N/C contacts ms 6…17 25 ± 20 % 35 ± 20 %
Short supply failure Maximum duration without affecting hold-in of the device
ms 2 2 2
Maximum operating rate In operating cycles per second
3 3 3
Mechanical durabilityIn millions of operating cycles
With coil 50/60 Hz (at 50 Hz)
30 – –
With standard coil cwide range
– 30 30
Time constant L/R ms – 28 40
Characteristics
References:pages B7/9 to B7/11
Curves:page B7/25
Dimensions:page B7/26
Schemes:page B7/27
Ref.
B7/24
Con
trol
re
lays
Characteristics of instantaneous contacts incorporated in the control relayNumber of contacts 5
Rated operational voltage (Ue)
Up to V 690
Rated insulation voltage (Ui)
Conforming to IEC 60947-5-1 V 690Conforming to UL, CSA V 600
Conventional thermal current (Ith)
For ambient temperature ≤ 60 °C A 10
Frequency of the operational current
Hz 25...400
Minimum switching capacity U min V 17I min mA 5
Short-circuit protection Conforming to IEC 60947-5-1 gG fuse: 10 ARated making capacity Conforming to
IEC 60947-5-1I rms a 140, c 250
Short-time rating Permissible for 1 s A 100500 ms A 120100 ms A 140
Insulation resistance MΩ > 10
Non-overlap time Guaranteed between N/C and N/O contacts
ms 1.5 (on energisation and on de-energisation)
Tightening torque Philips head n° 2 and Ø6 N.m 1.7
Non-overlap distance Linked contacts in association with auxiliary contacts LADN
Mechanically linked contacts Conforming to IEC 60947-5-1 The 3 N/O contacts and the 2 N/C contacts of CAD N32 are linked mechanically by one mobile contact carrier.
Characteristics
References:pages B7/9 to B7/11
Curves:page B7/25
Dimensions:page B7/26
Schemes:page B7/27
TeSys TeSys D Control relays
Ref.
B7/25
Con
trol
re
lays
Rated operational power of contacts (conforming to IEC 60947-5-1)a.c. supply, categories AC-14 and AC-15
Electrical durability (valid for up to 3600 operating cycles/hour) on an inductive load such as the coil of an electromagnet:making current (cos φ 0.7) = 10 times the power broken (cos φ 0.4).
V 24 48 115 230 400 440 6001 million operating cycles VA 60 120 280 560 960 1050 14403 million operating cycles VA 16 32 80 160 280 300 42010 million operating cycles VA 4 8 20 40 70 80 100
d.c. supply, category DC-13Electrical durability (valid for up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the power.
Operating cycles V 24 48 125 250 4401 million W 96 76 76 76 443 million W 48 38 38 32 –10 million W 14 12 12 – –
Curves
0,1 0,2 0,3 0,40,5
0,60,7
0,80,9
1 2 3 45
67
8910
0,1
0,2
0,3
0,4
0,60,5
0,80,7
7
1
2
3
54
6
810
Milli
ons
of o
pera
ting
cycl
es
Current broken in A
DF5
1076
2.ep
s
0,1 0,2 0,3 0,40,5
0,60,7
0,80,9
1 2 3 45
67
8910
0,1
0,2
0,3
0,4
0,60,5
0,80,7
7
1
2
3
54
6
810
440 V
48 V
250 V
125 V
24 V
Milli
ons
of o
pera
ting
cycl
es
Current broken in A
DF5
1076
3.ep
s
References:pages B7/9 to B7/11
Characteristics:pages B7/22 to B7/24
Dimensions:page B7/26
Schemes:page B7/27
TeSys TeSys D Control relays
Ref.
B7/26
Con
trol
re
lays
DimensionsCAD a CAD c or LC (low consumption)
4512,5(LAD8)
b
cc1c2c3
DF5
1108
0.ep
s
b
cc1c2c3
45
DF5
1108
1.ep
s
CAD 3250
323503
CAD 3250
323503
b 77 99 b 77 99c without cover or add-on blocks 84 84 c without cover or add-on blocks 93 93
with cover, without add-on blocks 86 86 with cover, without add-on blocks 95 95c1 with LADN or C (2 or 4 contacts) 117 117 c1 with LADN or C (2 or 4 contacts) 126 126c2 with LAD6K10 129 129 c2 with LAD6K10 138 138c3 with LADT, R, S 137 137 c3 with LADT, R, S 146 146
with LADT, R, S and sealing cover 141 141 with LADT, R, S and sealing cover 150 150
Operating cycles V 24 48 125 250 4401 million W 120 90 75 68 613 million W 70 50 38 33 2810 million W 25 18 14 12 10
MountingCADPanel mounted Mounted on rail NSYDR200BD or NSYDR200
60/7
0=
=35 ==
(1)
c
DF5
1108
2.ep
s
78
==
45c
8107
11.e
ps
CAD a CAD c or LC CAD a CAD c or LC c with cover 86 95 c (NSYDR200BD) (2) 88 97
c (NSYDR200BD) (2) 96 105
(1) 2 elongated holes 4.5 x 9. (2) With cover.
Mounted on plate AM1P
c 35
60/7
0
AF1 EA4
DF5
2331
9.ep
s
CAD a CAD c or LC c with cover 86 95
Dimensions and mounting
References:pages B7/9 to B7/11
Illustration:page B7/8
Characteristics:pages B7/22 to B7/24
Curves:page B7/25
Schemes:page B7/27
TeSys TeSys D Control relays
Ref.
B7/27
Con
trol
re
lays
Instantaneous auxiliary contacts5 N/O 3 N/O + 2 N/C
CAD50 CAD32
A1
A2
03/N
O04
13/N
O14
23/N
O24
33/N
O34
43/N
O44
A1
A2
03/N
O04
13/N
O14
31/N
C32
21/N
C22
43/N
O44
DD
4257
42.e
ps
Instantaneous auxiliary contact blocks1 N/O + 1 N/C 2 N/O 2 N/C
LADN11 LAD8N11 (1) LADN20 LAD8N20 (1) LAD8N02 LADN02
53/N
O54
61/N
C62
DD
4257
43.e
ps
153/
NO
154
161/
NC
162
(184
)(1
83)
(172
)(1
71)
DD
4257
44.e
ps
53/N
O54
63/N
O64
DD
4257
45.e
ps
153/
NO
154
163/
NO
164
(184
)(1
83)
(174
)(1
73)
DD
4257
46.e
ps
261/
NC
262
(282
)(2
81)
251/
NC
252
(272
)(2
71)
DD
4257
53.e
ps
51/N
C52
61/N
C62
DD
4257
49.e
ps
(1) The figures in brackets are for the device mounted on the RH side of the control relay.
2 N/O + 2F N/C 1 N/O + 3 N/C 4 N/O 4 N/C 3 N/O + 1 N/CLADN22 LADN13 LADN40 LADN04 LADN31
53/N
O54
61/N
C62
71/N
C72
83/N
O84
DD
4257
48.e
ps
53/N
O54
61/N
C62
71/N
C72
83/N
O84
DD
4257
47.e
ps
53/N
O54
63/N
O64
73/N
O74
83/N
O84
DD
4257
50.e
ps
71/N
C72
81/N
C82
51/N
C52
61/N
C62
DD
4257
51.e
ps
53/N
O54
61/N
C62
73/N
O74
83/N
O84
DD
4257
52.e
ps
2 N/O + 2 N/C including1 N/O + 1 N/Cmake before break
With dust and damp protected contacts2 N/O protected 2 N/C protected 2 N/O protected (2)
with 2 cable screen terminals
2 N/O protected +2 N/O non protected
2 N/O protected +1 N/O + 1 N/Cnon protected
LADC22 LA1DX20 LA1DX02 LA1DY20 LA1DZ40 LA1DZ31
53/N
O54
61/N
C62
87/N
O88
75/N
C76
1273
36.e
ps
53/N
O54
63/N
O64
8107
27.e
ps
5251
/NC
6261
/NC
8107
34.e
ps
53/N
O54
63/N
O64
8107
26.e
ps
(2) Product fitted with 4 earth screen continuity terminals.
Time delay auxiliary contact blocks Mechanical latch blocksOn-delay 1 N/O + 1 N/C Off-delay
1 N/O + 1 N/CLADT LADS LADR LAD6K10
55/N
C56
67/N
O68
8107
16.e
ps
55/N
C56
67/N
O68
8107
19.e
ps
57/N
O58
65/N
C66
8107
21.e
ps
E2
E1
A2
A1
8107
32.e
ps
53/N
O54
83/N
O84
63/N
O64
73/N
O74 62
61/N
C
53/N
O54
83/N
O84
73/N
O74
Schemes
References:pages B7/9 to B7/11
Illustration:page B7/8
Characteristics:pages B7/22 to B7/24
Curves:page B7/25
Dimensions:page B7/26
TeSys TeSys D Control relays
Ref.
B7/28
Con
trol
re
lays